-
sBen-Ran Fu , Yuh-Ren Lee, Jui-Ching Hsieh
h i g h l i g h t s
A 250-kW ORC system using turbine expande The experimentally
maximal net power outpu The experimentally maximal system thermal
The turbine isentropic efciency was 63.7% w
the hea
Turbine expander219.5 kW with a uctuation of 5.5 kW during
prolonged operation. The maximal net power output andsystem thermal
efciency were 225 kW and 7.94%, respectively. Under this condition,
the isentropic
efcient methods for converting low-grade thermal energy, such
asthat derived from waste heat recovery, geothermal and solar
ther-mal sources, biomass combined heat and power (CHP), and
oceanthermal energy into electricity [2,3]. Previous studies on
ORCs have
ls, including con-[1,4], developinging application ofng waste
heat re-[8], and at data
control strategy models [11], quasi-dynamic models [12]. In
addi-tion, relevant studies have assessed the effect of the optimal
pinch-point temperature range of evaporators on system
performance[13], conducted prototype testing [14e16], and performed
statisti-cal analysis of ORC-related patent data [17] and
off-design perfor-mance analysis [18,19]. This section reviews
several previousexperimental studies on the ORC systems in detail.*
Corresponding author.
Contents lists available at ScienceDirect
Applied Therma
sev
Applied Thermal Engineering 80 (2015) 339e346E-mail address:
[email protected] (B.-R. Fu).sources [1]. ORC is considered to be
one of themost economical and centers [9], as well as proposing
proof-of-concepts [10], optimal1. Introduction
An organic Rankine cycle (ORC) is identical to a steam
Rankinecycle, except that it employs organic uids with a low
boiling pointas working uids to generate power from low-temperature
heat
applied various perspectives and research tooducting
technical-economic-market surveysmethods for selecting working uids
[5], reviewscroll expanders for ORC systems [6], evaluaticovery
from a power plant [7], onboard shipsobvious. 2015 Elsevier Ltd.
All rights reserved.Thermal efciencyWaste heat recovery efciency of
the turbine was 63.7% with a rotational speed of 12 386 rpm, and
the back-work ratio was
6.7%. In addition, the results of the dynamic testing
demonstrated that the present system respondedvery rapidly as the
heat source temperature changed. The experimental results also
demonstrated thatthe system thermal efciency and net power output
increased linearly with an increasing heat sourcetemperature.
However, the effect of the heat source temperature on the turbine
efciency was not The system responded very rapidly as
a r t i c l e i n f o
Article history:Received 3 December 2014Accepted 30 January
2015Available online 11 February 2015
Keywords:Organic Rankine cycle
(ORC)http://dx.doi.org/10.1016/j.applthermaleng.2015.01.071359-4311/
2015 Elsevier Ltd. All rights reserved.r was studied for waste heat
recovery.t was 219.5 5.5 kW.efciency was 7.94%.ith a rotational
speed of 12,386 rpm.t source temperature changed.
a b s t r a c t
This study involved designing and constructing a 250-kW organic
Rankine cycle system, consisting of apump, preheater, evaporator,
turbine, generator, condenser, as well as hot and cooling water
circulationsystems. Refrigerant R245fa was used as a working uid.
The design operating pressure levels of thepreheater/evaporator and
condenser was 1.265 MPa and 0.242 MPa, respectively. Under design
condi-tions, the net power output was 243 kW and the system thermal
efciency was 9.5%. The preliminaryexperimental results under
off-design conditions showed that the average net power output
wasGreen Energy and Environment Research Laboratories, Industrial
Technology Research Institute, Hsinchu 31040, TaiwanResearch
paper
Design, construction, and preliminary reRankine cycle system
*
journal homepage: www.el7ults of a 250-kW organic
l Engineering
ier .com/locate/apthermeng
-
l EnManolakos et al. [20] experimentally evaluated the
performanceof a low-temperature solar ORC system for reverse
osmosis (RO)desalination using R134a as the working uid and scroll
expander.In their experiments, the expander had amaximal efciency
of 65%,power output of 2.05 kW, and ORC efciency of 4%. In
addition,Manolakos et al. [21] presented on-site experimental
results of asolar ORC system combined with an RO system. However,
themaximal efciencies of the expander and the ORC system
wereapproximately 45% and 1.75%, respectively.
Lemort et al. [22] and Quoilin et al. [23] have
experimentallyinvestigated an ORC prototype with an open-drive
oil-free scrollexpander and R123 as the working uid. In their
experiments, themaximal isentropic effectiveness of the expander
was 68%, and theshaft work of the expander was between 0.4 and 1.82
kW. Themaximal system efciency was 7.4%. In addition, they
determinedthat the deviation between the experimental and predicted
resultsof the proposed model was only approximately 5%.
Wang et al. [24] reported on the experimental results of an
on-site micro-scale solar ORC system using R245fa and
R245fa/R152mixtures as theworking uids. Themaximal power output and
ORCefciency were 7.2 W and 5.59%, respectively. Their
resultsdemonstrated that the ORC efciency was considerably
improvedby using R245fa/R152 mixtures rather than using pure
R245fa.
Wang et al. [25] designed and constructed a low-temperaturesolar
ORC system using R245fa as the working uid and a rolling-piston
expander. In their experiments, the average shaft poweroutput and
isentropic efciency of the expander were 1.73 kW and45.2%,
respectively. They achieved a maximal ORC efciency of12.9%.
Pei et al. [26] experimentally examined a kW-scale ORC
systemusing a turbine and R123 as the working uid. The results
showedthat the isentropic efciency of the turbine was 62.5%; the
ORC
Nomenclature
Esys thermal efciency of the ORC system (%)Etur isentropic
efciency of the turbine (%)mW mass ow rate of the hot water (kg/s)s
mass specic entropy (kJ/kg K)T temperature (C)TC,in inlet
temperature of the cooling water (C)TC,out outlet temperature of
the cooling water (C)TW,in inlet temperature of the hot water
(C)TW,out outlet temperature of the hot water (C)Wnet net power
output of the system (kW)
B.-R. Fu et al. / Applied Therma340efciency was 6.8% at a
temperature difference of 70 C betweenthe heat source and heat
sink, and the power output was 1.36 kW.
Qui et al. [27] constructed and tested a micro-scale biomass-red
CHP system with an ORC. Their experimental results showedthat the
micro-CHP system with an ORC generated 0.861 kW and47.26 kW in
electricity and heat, respectively, and the corre-sponding
efciencies of the expander and ORC were 53.92% and3.78%,
respectively. Consequently, the overall biomass CHP ef-ciency was
78.69%.
Zheng et al. [28] proposed a kW-scale rolling-piston expanderfor
a low-temperature ORC system using R245fa as the workinguid and
conducted a running test of the proposed ORC system.
Theexperimental results showed that the expander operated at350e800
rpm with a maximal power output of 0.35 kW when theheat source
temperature was below 90 C. The maximal isentropicefciency of the
expander and cycle efciency were 43.3% and 5%,respectively.Declaye
et al. [29] experimentally investigated an ORC systemusing R245fa
as the working uid and a scroll expander. Theydemonstrated a
maximal isentropic efciency of the expander andshaft power of 75.7%
and 2.1 kW, respectively. A maximal cycleefciency of 8.5% was
reached at evaporating and condensingtemperatures of 97.5 and 26.6
C, respectively.
Twomey et al. [30] reported on the dynamic performance of
asmall-scale solar cogeneration system with an ORC using R134a
asthe working uid and a scroll expander. The results demonstrated
amaximal isentropic efciency of the expander of 59% with a
cor-responding ORC efciency of 3.47%. In addition, the maximal
poweroutput was 0.676 kW.
Hsu et al. [16] experimentally investigated the effect of
inletpressure and the pressure ratio in the expander on the
performanceof a 50-kW ORC system using a screw expander and R245fa
as theworking uid. The results showed that for a given pressure
ratio,higher inlet pressure resulted in both higher isentropic
efciency ofthe expander and higher system efciency under an
over-expansion condition, but resulted in lower isentropic efciency
ofthe expander and system efciency under an
under-expansioncondition. In their experiments, the maximal power
output was50 kW and the system thermal efciency was 10.5%.
Jradi and Riffat [31] experimentally examined a small-scale
tri-generation system, consisting of an ORC-based (using a
scrollexpander and HFE7100 as the working uid) CHP unit and a
com-bined dehumidication and cooling unit. They demonstrated
thatthis combined system provided approximately 9.6, 6.5, and 0.5
kWfor heating, cooling, and electric power, respectively. Under
amaximal electric power output condition, the isentropic efciencyof
the expander was 74.2% and the corresponding cycle efciencywas
5.64%.
Avadhanula and Lin [32] proposed empirical models for a
screwexpander based on the experimental data of a 50-kW ORC
systemusing R245fa as theworking uid. The experimental results
showedthat the pressure ratio, volume ratio, and power output of
the ORCsystem were 2.70e6.54, 2.54e6.20, and 10e51.5 kW,
respectively.In addition, their proposed models predicted the
system poweroutput accurately, namely within 10% and 7.5% of
experimentalvalues for the polytropic exponent model and isentropic
workoutput model, respectively. The maximal isentropic efciency
ofthe expander was nearly 70%, but no information of the ORC
ef-ciency was provided.
Klonowicz et al. [33] designed and constructed a
small-scaleturbine with a rotational speed of 3264 rpm for an ORC
system us-ing R227ea as the working uid. In addition, they
presented thenumerical and preliminary testing results of the
system. Theexperimental power output was 9.9 0.2 kW, and the
corre-sponding electrical efciency was 53 2%. However, the ORC
ef-ciencywasnotprovided. In addition, the predicted
systemefciencyexhibited a high consistency with the experimental
result.
Chang et al. [34] experimentally investigated an ORC systemwith
a scroll expander and R245fa as the working uid. Themaximal shaft
power output and electricity power output were 1.74and 1.375 kW,
respectively, at a temperature difference of 60.6 Cbetween the heat
source and heat sink. The maximal system ef-ciency of the ORC
system was 7.77%.
Zhang et al. [35] reported on the experimental results of an
ORCsystemwith a single-screw expander and R123 as the working
uidfor waste heat recovery from the exhaust of a diesel engine with
amaximal horsepower of 336 kW. The results demonstrated that
themaximal ORC power output was 10.38 kW. In addition, the
ORCefciency and overall system efciency were 6.48% and
43.8%,respectively, resulting in 250 kW of diesel engine output.
Using theORC improved the overall efciency of the diesel engine
by
gineering 80 (2015) 339e346approximately 1.53%.
-
More detailed experimental results of ORC systems from pre-vious
studies are summarized in Table 1. The cited studies
experi-mentally investigated ORC systems with a power output of
lessthan 50 kW. In addition, although numerous refrigerants
wereexamined in numerous studies (e.g., on the selection of
theworkinguid in an ORC system [5,36]), the typically used working
uids inthe experimental ORC systems were R123, R134a, and
R245fa.Table 1 indicates that scroll expanders were generally used
in low-kW-level ORC systems, which is due to the compact size, low
cost,high efciency, and low number of moving parts of scroll
expanders[30]; screw-type expanders were used in tens-of-kW-level
ORCsystems; the turbine expander type was generally used
inhundreds-of-kW-level ORC systems. However, based on
literaturereview, no studies have reported on experimental results
of largeORC systems (>100 kW) using turbine expanders. As shown
inTable 1, ORC thermal efciency was generally lower than 10%.
The present study constructed a 250-kW ORC system (usingR245fa
as the working uid), consisting of a pump, preheater,evaporator,
turbine, generator, condenser, as well as hot and cool-ing water
circulation systems. In addition, this paper presents
thepreliminary results of the present ORC system under
off-design
was 39 C), respectively. The design points of the heat source
(hotwater) temperature andmass ow rate were 133.9 C and 15.39 kg/s,
respectively. The details of mathematical model for eachcomponent
and system performance were described in the previ-ous studies
[18,19], which were preliminary analyses of the off-design
performance of the ORC system investigated in this study.Under
design conditions, the net power output and system thermalefciency
were 243 kW and 9.5%, respectively.
Table 1Some experimental results of the ORC system from
available literature (sorted byexpander type).
Authors Expander type(max. efciency, %)
Workinguid
Max.electricityor shaftpower (kW)
Max. ORCthermalefciency(%)
Wang et al. [24] e R245fa/R152a
0.0072 5.59
Qiu et al. [27] Multi-vane (53.92) HFE7000 0.861 3.78Peris et
al. [40] Volumetric (65.33) R245fa 15.93 10.88Wang et al. [25]
Rolling-piston (45.2) R245fa 1.73 12.9Zheng et al. [28]
Rolling-piston (43.3) R245fa 0.35 5Manolakos et al. [20] Scroll
(65) R134a 2.05 4Manolakos et al. [21] Scroll (45) R134a 1
1.75Lemort et al. [22] Scroll (68) R123 1.82 7.4Declaye et al. [29]
Scroll (75.7) R245fa 2.1 8.5Twomey et al. [30] Scroll (59) R134a
0.676 3.47Jradi and Riffat [31] Scroll (74.2) HFE7100 0.5 5.64Chang
et al. [34] Scroll (76) R245fa 1.375 7.77
B.-R. Fu et al. / Applied Thermal Engineering 80 (2015) 339e346
341Peterson et al. [41] Scroll (49.9) R123 0.256 7.2Wang et al.
[42] Scroll (77.5) R123 0.625 eMathias et al. [43] Scroll (83) R123
2.96 eLemort et al. [44] Scroll (71.03) R245fa 2.032 eBracco et al.
[45] Scroll (74) R245fa 1.5 8Liu et al. [46] Scroll (41) R123 0.76
2.9Zhou et al. [47] Scroll (57) R123 0.645 8.5Saitoh et al. [48]
Scroll (65) R113 0.35 11Tarique et al. [49] Scroll (64) R134a 0.92
8.5Li et al. [50] Scroll (83) R245fa/
R601a0.55 4.45
Miao et al. [51] Scroll (81) R123 3.25 6.39Gao et al. [52]
Scroll (55.3) R245fa 0.151 3.2Lee et al. [14,15] Screw (65) R245fa
50 8.05Hsu et al. [16] Screw (72.5) R245fa 50 10.5Avadhanula
and Lin [33]Screw (70) R245fa 51.5 e
Zhang et al. [35] Screw (57.88) R123 10.38 6.48Pei et al. [26]
Turbine (62.5) R123 1.36 6.8Klonowicz et al. [33] Turbine (59)
R227ea 9.9 eNguyen et al. [53] Turbine (49.8) n-Pentane 1.5 4.3Liu
et al. [54] Turbine () HFE7000,
HFE71000.284 e
Li et al. [55] Turbine (53) R123 6.57 eKang [56] Turbine (82.2)
R245fa 32.7 5.22Li et al. [57] Turbine (68) R123 6
7.98Borsukiewicz-Gozdur Turbine () R227ea 9.87 4.88[58]conditions.
The effect of the heat source temperature on systemperformance was
investigated.
2. System design and construction
This 250-kW ORC prototype, as shown in Fig. 1, was built at
theIndustrial Technology Research Institute, Taiwan. The ORC
unitmeasured 450 cm (length) 270 cm (width) 310 cm
(height),weighing approximately 11,000 kg. The working uid was
refrig-erant R245fa, one of the most appropriate uids for
low-gradewaste heat recovery of ORC systems [37]; the mass ow rate
was11.58 kg/s. The thermodynamic properties of R245fa were
evalu-ated using REFPROP 9.0 [38], which was developed by the
NationalInstitute of Standards and Technology (USA). The working
uidR245fa circulated on the shell side of the heat exchangers, and
thehot and cooling water circulated in the tube side. Fig. 2
depicts thedetailed scheme of the experimental test rig of the
system.
2.1. Design conditions
Fig. 3 shows the Tes diagram of the present ORC system.
Thedesign operating pressure levels in the preheater/evaporator
andcondenser were 1.265 MPa (the evaporation/saturation
tempera-ture was 100 C) and 0.242 MPa (the condensation
temperature
Fig. 1. Photograph of the 250-kW ORC prototype (pump is located
at back side). (1)Preheater, (2) evaporator, (3) turbine, (4)
generator, (5) condenser, (6) pump, (A)cooling water inlet, (B)
cooling water outlet, (C) hot water inlet, (D) hot water
outlet.Fig. 2. Detailed scheme of the experimental test rig.
-
Shell inside diameter 32.45 cmBundle hole diameter 1.61 cmBundle
diameter 31.66 cmSealing strips number 0Nozzle inside diameter 10
cmBafe plate diameter 31.95 cmBafe thickness 0.4 cmBafe spacing 20
cmBafe cut 30%Bafe plate number 17
(b) Evaporator
Tube inside/outside diameter 1.639/1.765 cmTube thickness 0.063
cmTube number 300Tube bundle 4 passTube inside type RiedTube
outside type Low-nnedFin height 0.06 cmFin thickness 0.02 cmTube
arrangement StaggeredTube pitch transverse 2.375 cmTube pitch
longitudinal 2.057 cmTube/Shell length 360 cmDistance upper
row/center 1.9 cmTube in upper row 28Number of tube rows 12Free
space above upper tube row 47%Shell inside diameter 69.59 cm
(c) Condenser
Tube outside diameter 1.905 cmTube number 480Tube bundle 2
passTube inside type RiedTube outside type Low-nnedTube arrangement
StaggeredTube pitch transverse 2.375 cmTube pitch longitudinal
2.090 cmTube/Shell length 360 cmDistance upper row/center 2.23
cmTube in upper row 23Number of tube rows 18
l En2.2. Heat exchangers
The present ORC system featured three heat exchangers, namelya
preheater, an evaporator, and a condenser. The preheater,comprising
200 heat transfer tubes, was of a one-pass shell-and-tube type, in
which the heat transfer tube was of a ried type in theinside and
low-nned type in the tube outside. The evaporator,consisting of 300
heat transfer tubes, was of a four-pass shell-and-tube ooded type.
The condenser, composed of 480 heat transfertubes, was of a
two-pass shell-and-tube ooded type. The detailedparameters of the
used preheater, evaporator, and condenser aresummarized in Table
2.
2.3. Pump, turbine, and generator
The pump used in the present system was manufactured byGrundfos
(model: CR 32-5, 60 Hz). The 250-kW turbine wasdesigned at the
Industrial Technology Research Institute (Taiwan)and by a SoftInWay
Inc. (USA) engineering team, and fabricated atthe Industrial
Technology Research Institute. Detailed informationon the turbine
performance was provided in a previous study [39].The manufactured
blade row is shown in Fig. 4a, and the rotorwheel mounted with a
stator ring and shaft is shown in Fig. 4b. Therotational speed of
the turbine was 12,000 10% rpm with anisentropic efciency of
approximately 80%. The shaft powergenerated by the turbinewas
transferred to the generator through agearbox at a rotational speed
of 3600 rpm; the generator efciencywas 90%. To prevent leakage of
the working uid, the turbine,gearbox, and generator were arranged
in a hermetic space. Thistype of hermetic turbogenerator was also
employed by Klonowiczet al. [33].
2
cooling water
hot water
5s
43
2s1T
empe
ratu
re (o
C)
Mass specific entropy (kJ/kgK)
5
Fig. 3. Tes diagram of the studied ORC system.
B.-R. Fu et al. / Applied Therma3422.4. Hot and cooling water
circulation systems
Hot water, considered the waste heat source, was supplied bythe
pressurized hot water boiler with a maximal capacity of3788 kW, as
shown in Fig. 5a. In the currently proposed system,natural gas was
used as a fuel for the boiler. Heated water wascollected in the
container, and owed into the ORC system throughthe piping. The
cooling water circulation system consisted of two500-RT cooling
towers and had a total maximal capacity of3860 kW, as shown in Fig.
5b.
2.5. Measurement and control
Pressure transducers with the full scale range of 2500
kPa,manufactured by WIKA (model A-10, Germany), and Pt100
(threewires) thermometers, designed by MorShine (Taiwan),
werelocated at each point of the system (i.e., Points 1 to 5 in
Fig. 3). TheTable 2Detailed parameters of the used heat
exchangers.
(a) Preheater
Tube inside/outside diameter 1.471/1.587 cmTube thickness 0.058
cmTube number 200Tube in window 83Tube bundle 1 passTube inside
type RiedTube outside type/Fin per inch (FPI) Low-nned/42Tube
arrangement StaggeredTube pitch transverse 1.984 cmTube pitch
longitudinal 1.718 cmTube/Shell length 360 cm
gineering 80 (2015) 339e346mass ow rate of the working uid was
measured at Point 2 using avortex ow meter made by BNC (model
1100/LRT-B/A, Taiwan). Inaddition, level meters were employed in
the evaporator andcondenser. The rotational speed of the turbine
was measured usinga tachometer sensor. Themass ow rate and
temperature of the hotand cooling water were measured using an
electromagnetic owmeter made by BNC (model BMS1000-A100, Taiwan) in
the hot andcooling water circulation systems. The electric power of
the in-duction generator was measured using a power analyzer made
byHIOKI (model 3169-20 with a 9661 clamp on sensor, Japan).
Theoverall system control (including the processes of startup,
shut-down, and emergency turn off) and data acquisition were
per-formed using an AB MicroLogix 1500 programmable logiccontroller
(USA). The measured data were then transmitted to a
Shell inside diameter 71.7 cm
-
personal computer for detailed system analysis. The
measurementuncertainties in temperature, pressure, mass ow rate of
theworking uid, mass ow rate of the water, heat transfer rate,
tur-bine efciency, system thermal efciency, and net power output
are0.25 C, 1.0%, 0.7%, 0.5%, 1.72%, 1.48%, 3.10%, and
2.36%,respectively.
3. Preliminary results and discussion
Fig. 6 shows the measured inlet and outlet temperatures of
thehot and cooling water and the system net power output (Wnet)
experiments, we increased themass ow rate of the hot water
from15.39 kg/s to 26.70 kg/s to enable the heat transfer rate to
meet therequirement. In addition, because of a lower heat source
temper-ature, a higher evaporation temperature (106 C) was applied
tomaintain the power output level as design value.
Fig. 6 also shows that the uctuations of the heat source andsink
temperatures were considerably low (1 C), indicating thatthe boiler
and cooling towers were functioning adequately; theaverage net
power output was 219.5 kW with a uctuation of5.5 kW (approximately
2.5% of the average net power output). Themaximal net power output
and system thermal efciency were
Fig. 4. (a) Manufactured rotor wheel and (b) rotor wheel mounted
with stator ring and shaft.
B.-R. Fu et al. / Applied Thermal Engineering 80 (2015) 339e346
343during prolonged operation. In this gure, TW,in and TW,out are
theinlet and outlet temperatures of the hot water, respectively;
andTC,in and TC,out are the inlet and outlet temperatures of the
coolingwater, respectively. The ORC system required approximately
30min(excluding the period for the boiler to warm up before the
exper-iments) to reach a steady-state condition and was longer than
that(approximately 15 min) required for the 50-kW ORC system in
ourprevious study [14]. When the system was under a
steady-statecondition, the average inlet temperature of hot water
was119.2 C; however, this was lower than it should have been
ac-cording to the design (i.e., 133.9 C). This was due to our
infra-structure limiting the supply of natural gas. Therefore,
during theFig. 5. Hot and cooling water circulation systems. (a)
H225 kW and 7.94%, respectively. Under the maximal net poweroutput
condition, the isentropic efciency of the turbine was 63.7%with a
rotational speed of 12,386 rpm. The pump and turbine ef-ciencies
were lower than the designed value; the generator ef-ciency reached
91.5%. In addition, the back-work ratio, dened asthe ratio between
the works consumed by the pump and producedby the expander, was
6.7%. The heat transfer rates in the preheaterand evaporator were
1161 and 1560 kW, respectively, close to thedesigned values. Heat
loss in the preheater and evaporator was113 kW, which was
approximately 4% of the heat input from the hotwater. The
temperatures of two particular cycle points, namely thesuperheat at
the evaporator outlet and the subcooling at theot water system, (b)
two 500-RT cooling towers.
-
condenser outlet, which were not considered in the
previousanalysis of the design condition, were 1.7 and 2.5 C,
respectively. Aslight degree of superheat was applied to ensure
that no liquid-phase working uid entered the turbine. The detailed
experi-mental results at themaximal power output and design
parameters
0 60 120 180 240 300 3600
50
100
150
200
250
Wnet
TC,outTC,in
TW,out
TW,in
T (
C)
Time (min)
0
50
100
150
200
250
Wne
t (kW
)
Fig. 6. Temperatures of hot and cooling water and system net
power output.
0 60 120 180 24080
90
100
110
120
(d)(c)(b)(a)
Wnet
TW,out
TW,in
T (
C)
Time (min)
100
150
200
250
Wne
t (kW
)
Fig. 7. Dynamic behavior of the system.
B.-R. Fu et al. / Applied Thermal Engineering 80 (2015)
339e346344are summarized in Table 3.After prolonged operation, a
dynamic testing was also con-
ducted. Fig. 7 shows the dynamic behavior of the system under
thecontinued change in the inlet temperature of the heat source,
i.e.,TW,in. During the dynamic testing, there were 4 periods, which
theoperation conditions were described as follows: (a) TW,in
decreasedrapidly from the steady-averaged value of 119.2 Ce102.7 C;
(b)TW,in increased rapidly from 102.7 C to 115.0 C; (c) TW,in
decreasedslowly from 115.0 C to 102.7 C; and (d) TW,in increased
slowly from102.7 C to 109.4 C. The corresponding dynamic responses
of thesystem net power output (Wnet) were described as follows:
(a)Wnetdecreased rapidly from 223.4 kW to 132.0 kW; (b) Wnet
increasedrapidly from 132.0 kW to 197.9 kW; (c)Wnet decreased
slowly from197.9 kW to 135.8 kW; and (d)Wnet increased slowly from
135.8 kWto 169.7 kW. In addition, the outlet temperature of the
heat source,i.e., TW,out, shows the same dynamic behavior with
Wnet. Mostimportantly, those dynamic results demonstrated that the
presentsystem responded very rapidly as the heat source
temperaturechanged.
Table 3Detailed experimental results at the maximum net power
output.Parameter Design Experiments
Mass ow rate of hot water (kg/s) 15.39 26.70Inlet temperature of
hot water (C) 133.9 119.8Outlet temperature of hot water (C) 94.4
94.7Mass ow rate of R245fa (kg/s) 11.58 11.85Evaporation
temperature (C) 100 106Evaporation pressure (MPa) 1.265
1.440Superheat at evaporator outlet (C) 0 1.7Total heat input from
hot water (kW) 2573 2834Heat transfer rate in the preheater (kW)
1016 1161Heat transfer rate in the evaporator (kW) 1557 1560Heat
loss in the preheater and evaporator (kW) 0 113Condensation
temperature (C) 39 40Condensation pressure (MPa) 0.242
0.251Subcooling at condensation outlet (C) 0 2.5Rotational speed of
turbine (rpm) 12,000 12386Back work ratio (%) 4.1 6.7Pump efciency
(%) 90 68.1Turbine efciency (%) 80 63.7Generator efciency (%) 90
91.5ORC thermal efciency (%) 9.5 7.94Net power output (kW) 243
225Furthermore, we studied the effect of the heat source
temper-ature (TW,in) on system performance, as shown in Fig. 8.
Theexperimental results show that as TW,in increased from 102.4
to119.8 C, the isentropic efciency of the turbine slightly
increasedfrom 58.8% to 63.7%; the net power output increased
linearly andsubstantially from 135 to 225 kW. We observed such a
linear in-crease of net power output in our previous off-design
analysis [18].Furthermore, the system thermal efciency increased
from 6.31% to7.94% for the studied range of TW,in, indicating that
the overallthermal efciency increased by 0.94%, as the heat source
temper-ature increased by 10 C. The increase in thermal efciency
wasconsistent with previous analytical results [18], which
demon-strated a 0.91% efciency increase for a 10 C of TW,in.
4. Conclusions
The present study involved designing and constructing a 250-kW
ORC system, consisting of a pump, preheater, evaporator, tur-bine,
generator, condenser, as well as hot and cooling water cir-culation
systems. The ORC unit measured 450 cm (length) 270 cm(width) 310 cm
(height), weighing approximately 11,000 kg.Refrigerant R245fa was
used as the working uid. The designoperating pressure levels of the
preheater/evaporator andcondenser were 1.265 MPa and 0.242 MPa,
respectively. Underdesign conditions, the net power output was 243
kW and the sys-tem thermal efciency was 9.5%.
The preliminary experimental results of the ORC system
underoff-design conditions showed that the average net power
outputwas 219.5 kW with a uctuation of 5.5 kW during prolonged100
105 110 115 120 1250
50
100
150
200
250
Etur
Esys
Wnet
Wne
t (kW
) or E
tur (
%)
TW,in ( C)
5
6
7
8
9
E sys
(%)
Fig. 8. Net power output, turbine and system efciencies as a
function of heat sourcetemperature.
-
al Enoperation. The maximal net power output and system thermal
ef-ciency were 225 kW and 7.94%, respectively, at evaporation
andcondensation temperatures of 106 and 40 C. Under this
condition,the isentropic efciency of the turbine was 63.7% with a
rotationalspeed of 12,386 rpm, and the back-work ratio was 6.7%. In
addition,the dynamic behavior of the system under the continued
change inthe inlet temperature of the heat source was also studied.
The re-sults of the dynamic testing demonstrated that the present
systemresponded very rapidly as the heat source temperature
changed.The experimental results also demonstrated that the system
ther-mal efciency and net power output increased linearly and
sub-stantially with an increase of the heat source
temperature.However, the effect of the heat source temperature on
the turbineefciency was not obvious.
Future study will focus on obtaining more experimental
resultsand constructing a map of system performance under
off-designheat source conditions. Such research could provide
operationalguidelines and indicate an optimal control strategy for
off-designoperation. In addition, we will also develop an
articial-intelligence feedback control system for the ORC unit.
Acknowledgements
The authors express their gratitude for the Energy R&D
foun-dation funding from the Bureau of Energy of the Ministry of
Eco-nomic Affairs, Taiwan, under the grant number of 104-E0207.
References
[1] S. Quoilin, M.V.D. Broek, S. Declaye, P. Dewallef, V.
Lemort, Techno-economicsurvey of organic Rankine cycle (ORC)
systems, Renew. Sustain. Energy Rev.22 (2013) 168e186.
[2] B.F. Tchanche, Gr Lambrinos, A. Frangoudakis, G. Papadakis,
Low-grade heatconversion into power using organic Rankine cycles e
a review of variousapplications, Renew. Sustain. Energy Rev. 15
(2011) 3963e3979.
[3] J. Wang, Z. Yan, M. Wang, S. Maa, Y. Dai, Thermodynamic
analysis and opti-mization of an (organic Rankine cycle) ORC using
low grade heat source,Energy 49 (2013) 356e365.
[4] F. Velez, J.J. Segovia, M.C. Martn, G. Antoln, F. Chejne, A.
Quijano, A technical,economical and market review of organic
Rankine cycles for the conversion oflow-grade heat for power
generation, Renew. Sustain. Energy Rev. 16 (2012)4175e4189.
[5] J. Bao, L. Zhao, A review of working uid and expander
selections for organicRankine cycle, Renew. Sustain. Energy Rev. 24
(2013) 325e342.
[6] P. Song, M. Wei, L. Shi, S.N. Danish, C. Ma, A review of
scroll expanders fororganic Rankine cycle systems, Appl. Therm.
Eng. 75 (2015) 54e64.
[7] D. Gewald, K. Siokos, S. Karellas, H. Spliethoff, Waste heat
recovery from alandll gas-red power plant, Renew. Sustain. Energy
Rev. 16 (2012)1779e1789.
[8] G. Shu, Y. Liang, H. Wei, H. Tian, J. Zhao, L. Liu, A review
of waste heat recoveryon two-stroke IC engine aboard ships, Renew.
Sustain. Energy Rev. 19 (2013)385e401.
[9] K. Ebrahimi, G.F. Jones, A.S. Fleischer, A review of data
center cooling tech-nology, operating conditions and the
corresponding low-grade waste heatrecovery opportunities, Renew.
Sustain. Energy Rev. 31 (2014) 622e638.
[10] S. Aghahosseini, I. Dincer, Comparative performance
analysis of low-temperature organic Rankine cycle (ORC) using pure
and zeotropic workinguids, Appl. Therm. Eng. 54 (2013) 35e42.
[11] G. Manente, A. Toffolo, A. Lazzaretto, M. Paci, An organic
Rankine cycle off-design model for the search of the optimal
control strategy, Energy 58(2013) 97e106.
[12] M.O. Bamgbopa, E. Uzgoren, Quasi-dynamic model for an
organic Rankinecycle, Energy Convers. Manag. 72 (2013) 117e124.
[13] Y.R. Li, J.N. Wang, M.T. Du, S.Y. Wu, C. Liu, J.L. Xu,
Effect of pinch point tem-perature difference on cost-effective
performance of organic Rankine cycle,Int. J. Energy Res. 39 (2013)
1952e1962.
[14] Y.R. Lee, C.R. Kuo, C.C. Wang, Transient response of a 50
kW organic Rankinecycle system, Energy 48 (2012) 532e538.
[15] Y.R. Lee, C.R. Kuo, C.H. Liu, B.R. Fu, J.C. Hsieh, C.C.
Wang, Dynamic response of a50 kW organic Rankine cycle system in
association with evaporators, Energies7 (2014) 2436e2448.
[16] S.W. Hsu, H.W.D. Chiang, C.W. Yen, Experimental
investigation of the per-formance of a hermetic screw-expander
organic Rankine cycle, Energies 7(2014) 6172e6185.
B.-R. Fu et al. / Applied Therm[17] B.R. Fu, S.W. Hsu, C.H. Liu,
Y.C. Liu, Statistical analysis of patent data relating tothe
organic Rankine cycle, Renew. Sustain. Energy Rev. 39 (2014)
986e994.[18] B.R. Fu, S.W. Hsu, Y.R. Lee, J.C. Hsieh, C.M. Chang,
C.H. Liu, Effect of off-designheat source temperature on heat
transfer characteristics and system perfor-mance of a 250-kW
organic Rankine cycle system, Appl. Therm. Eng. 70(2014) 7e12.
[19] B.R. Fu, S.W. Hsu, Y.R. Lee, J.C. Hsieh, C.M. Chang, C.H.
Liu, Performance of a250 kW organic Rankine cycle system for
off-design heat source conditions,Energies 7 (2014) 3684e3694.
[20] D. Manolakos, G. Papadakis, S. Kyritsis, K. Bouzianas,
Experimental evaluationof an autonomous low-temperature solar
Rankine cycle system for reverseosmosis desalination, Desalination
203 (2007) 366e374.
[21] D. Manolakos, G. Kosmadakis, S. Kyritsis, G. Papadakis, On
site experimentalevaluation of a low-temperature solar organic
Rankine cycle system for ROdesalination, Sol. Energy 83 (2009)
646e656.
[22] V. Lemort, S. Quoilin, C. Cuevas, J. Lebrun, Testing and
modeling a scrollexpander integrated into an organic Rankine cycle,
Appl. Therm. Eng. 29(2009) 3094e3102.
[23] S. Quoilin, V. Lemort, J. Lebrun, Experimental study and
modeling of anorganic Rankine cycle using scroll expander, Appl.
Energy 87 (2010)1260e1268.
[24] J.L. Wang, L. Zhao, X.D. Wang, A comparative study of pure
and zeotropicmixtures in low-temperature solar Rankine cycle, Appl.
Energy 87 (2010)3366e3373.
[25] X.D. Wang, L. Zhao, J.L. Wang, W.Z. Zhang, X.Z. Zhao, W.
Wu, Performanceevaluation of a low-temperature solar Rankine cycle
system utilizing R245fa,Sol. Energy 84 (2010) 353e364.
[26] G. Pei, J. Li, Y. Li, J. Ji, Construction and dynamic test
of a small scale organicRankine cycle, Energy 36 (2011)
3215e3223.
[27] G. Qiu, Y. Shao, J. Li, H. Liu, S.B. Riffat, Experimental
investigation of a biomass-red ORC-based micro-CHP for domestic
applications, Fuel 96 (2012)374e382.
[28] N. Zheng, L. Zhao, X.D. Wang, Y.T. Tan, Experimental
verication of a rolling-piston expander that applied for
low-temperature organic Rankine cycle,Appl. Energy 112 (2013)
1265e1274.
[29] S. Declaye, S. Quoilin, L. Guillaume, V. Lemort,
Experimental study on an open-drive scroll expander integrated into
an ORC (organic Rankine cycle) systemwith R245fa as working uid,
Energy 55 (2013) 179e183.
[30] B. Twomey, P.A. Jacobs, H. Gurgenci, Dynamic performance
estimation ofsmall-scale solar cogeneration with an organic Rankine
cycle using a scrollexpander, Appl. Therm. Eng. 51 (2013)
1307e1316.
[31] M. Jradi, S. Riffat, Experimental investigation of a
biomass-fuelled micro-scaletri-generation system with an organic
Rankine cycle and liquid desiccantcooling unit, Energy 71 (2014)
80e93.
[32] V.K. Avadhanula, C.S. Lin, Empirical models for a screw
expander based onexperimental data from organic Rankine cycle
system testing, J. Eng. GasTurbines Power Trans. ASME 136 (2014)
062601.
[33] P. Klonowicz, A. Borsukiewicz-Gozdur, P. Hanausek, W.
Kryowicz,D. Brggemann, Design and performance measurements of an
organic vapourturbine, Appl. Therm. Eng. 63 (2014) 297e303.
[34] J.C. Chang, C.W. Chang, T.C. Hung, J.R. Lin, K.C. Huang,
Experimental study andCFD approach for scroll type expander used in
low-temperature organicRankine cycle, Appl. Therm. Eng. 73 (2014)
1444e1452.
[35] Y.Q. Zhang, Y.T. Wu, G.D. Xia, C.F. Ma, W.N. Ji, S.W. Liu,
K. Yang, F.B. Yang,Development and experimental study on organic
Rankine cycle system withsingle-screw expander for waste heat
recovery from exhaust of diesel engine,Energy 77 (2014)
499e508.
[36] Z.Q. Wang, N.J. Zhou, J. Guo, X.Y. Wang, Fluid selection
and parametric opti-mization of organic Rankine cycle using low
temperature waste heat, Energy40 (2012) 107e115.
[37] E.H. Wang, H.G. Zhang, B.Y. Fan, M.G. Ouyang, Y. Zhao, Q.H.
Mu, Study ofworking uid selection of organic Rankine cycle (ORC)
for engine waste heatrecovery, Energy 36 (2011) 3406e3418.
[38] E.W. Lemmon, M.L. Huber, M.O. McLinden, NIST Standard
Reference Database23: Reference Fluid Thermodynamic and Transport
PropertieseREFPROP,Version 9.0, National Institute of Standards and
Technology, Standard Refer-ence Data Program, Gaithersburg, USA,
2010.
[39] L. Moroz, C.R. Kuo, O. Guriev, Y.C. Li, B. Frolov, Axial
turbine ow path designfor an organic Rankine cycle using R-245fa,
in: Proceedings of ASME TurboExpo 2013: Turbine Technical
Conference and Exposition, Paper No.GT2013e94078, pp. V05AT23A004,
San Antonio, Texas, USA, June 3e7, 2013.
[40] B. Peris, J. Navarro-Esbr, F. Moles, R. Collado, A.
Mota-Babiloni, Performanceevaluation of an organic Rankine cycle
(ORC) for power applications from lowgrade heat sources, Appl.
Therm. Eng. 75 (2015) 763e769.
[41] R.B. Peterson, H. Wang, T. Herron, Performance of a
small-scale regenerativeRankine power cycle employing a scroll
expander, Proc. Ins. Mech. Eng. Part AJ. Power Energy 222 (2008)
271e282.
[42] H. Wang, R.B. Peterson, T. Herron, Experimental performance
of a compliantscroll expander for an organic Rankine cycle, Proc.
Ins. Mech. Eng. Part A J.Power Energy 223 (2009) 863e872.
[43] J.A. Mathias, J.J.R. Johnston, J. Cao, D.K. Priedeman, R.N.
Christensen, Experi-mental testing of gerotor and scroll expanders
used in, and energetic andexergetic modeling of, an organic Rankine
cycle, J. Energy Resour. Technol.Trans. ASME 131 (2009) 012201.
[44] V. Lemort, S. Declaye, S. Quoilin, Experimental
characterization of a hermetic
gineering 80 (2015) 339e346 345scroll expander for use in a
micro-scale Rankine cycle, Proc. Inst. Mech. Eng.Part A J. Power
Energy 226 (2012) 126e136.
-
[45] R. Bracco, S. Clemente, D.Micheli,M. Reini, Experimental
tests andmodelizationof a domestic-scale ORC (organic Rankine
cycle), Energy 58 (2013) 107e116.
[46] G. Liu, Y. Zhao, Q. Yang, L. Wang, B. Tang, L. Li,
Theoretical and experimentalresearch on scroll expander used in
small scale organic Rankine cycle System,Proc. Inst. Mech. Eng.
Part E J. Process Mech. Eng. 229 (2015) 25e35.
[47] N. Zhou, X. Wang, Z. Chen, Z. Wang, Experimental study on
organic Rankinecycle for waste heat recovery from low-temperature
ue gas, Energy 55(2013) 216e225.
[48] T. Saitoh, N. Yamada, S. Wakashima, Solar Rankine cycle
system using scrollexpander, J. Environ. Eng. 2 (2007) 708e719.
[49] M.A. Tarique, I. Dincer, C. Zamrescu, Experimental
investigation of a scrollexpander for an organic Rankine cycle,
Int. J. Energy Res. 38 (2014) 1825e1834.
[50] T. Li, J. Zhu, W. Fu, K. Hu, Experimental comparison of
R245fa and R245fa/R601a for organic Rankine cycle using scroll
expander, Int. J. Energy Res. 39(2015) 202e214.
[51] Z. Miao, J. Xu, X. Yang, J. Zou, Operation and performance
of a low temperatureorganic Rankine cycle, Appl. Therm. Eng. 75
(2015) 1065e1075.
[52] P. Gao, L. Jiang, L.W. Wang, R.Z. Wang, F.P. Song,
Simulation and experimentson an ORC system with different scroll
expanders based on energy and exergyanalysis, Appl. Therm. Eng. 75
(2015) 880e888.
[53] V.M. Nguyen, P.S. Doherty, S.B. Riffat, Development of a
prototype low tem-perature Rankine cycle electricity generation
system, Appl. Therm. Eng. 21(2001) 169e181.
[54] H. Liu, G. Qiu, Y. Shao, F. Daminabo, S.B. Riffat,
Preliminary experimental in-vestigations of a biomass-red
micro-scale CHP with organic Rankine cycle,Int. J. Low-Carbon
Technol. 5 (2010) 81e87.
[55] M. Li, J. Wang, L. Gao, X. Niu, Y. Dai, Performance
evaluation of a turbine usedin a regenerative organic Rankine
cycle, in: Proceedings of ASME Turbo Expo2012: Turbine Technical
Conference and Exposition, Paper No. GT2012-68441,June 11e15, 2012,
pp. 425e432. Copenhagen, Denmark.
[56] S.H. Kang, Design and experimental study of ORC (organic
Rankine cycle) andradial turbine using R245fa working uid, Energy
41 (2012) 514e524.
[57] M. Li, J. Wang, W. He, L. Gao, B. Wang, S. Ma, Y. Dai,
Construction and pre-liminary test of a low-temperature
regenerative organic Rankine cycle (ORC)using R123, Renew. Energy
57 (2013) 216e222.
[58] A. Borsukiewicz-Gozdur, Experimental investigation of
R227ea applied asworking uid in the ORC power plant with hermetic
turbogenerator, Appl.Therm. Eng. 56 (2013) 126e133.
B.-R. Fu et al. / Applied Thermal Engineering 80 (2015)
339e346346
Design, construction, and preliminary results of a 250-kW
organic Rankine cycle system1. Introduction2. System design and
construction2.1. Design conditions2.2. Heat exchangers2.3. Pump,
turbine, and generator2.4. Hot and cooling water circulation
systems2.5. Measurement and control
3. Preliminary results and discussion4.
ConclusionsAcknowledgementsReferences