Staggs and Fisher Consulting Engineers, Inc 3264 Loch Ness Drive Lexington, Kentucky 40517 Phone 859-271-3246 Fax 859-271-3246 Email [email protected]The following comments are in response to Staggs and Fisher’s review of the attached shop drawing submittal. Description of Submittal: Job Name: Job No: Date: Reviewed By: Gregory G. Carter, P.E. Daniel H. Bransom, P.E. $7DJJDUW)RVWHU3( Christopher C. Keath,P.E. John R. Mason, P.E. William P. Wilson, P.E. Greg W. Kraeszig, P.E. :D\QH$7KRPDV3( -HQQ\//HLWFK3( Member of the Consulting Engineers Council Remarks (if applicable): X REVIEWED FURNISH AS CORRECTED REJECTED REVISE AND RESUBMIT DATE: Checking is only for general conformance with the design concept of the project and general compliance with the information given in the contract documents. Any action shown is subject to the requirements of the drawings and specification. Contractor is responsible for : Quantities, dimensions which shall be confirmed and correlated at the job site, and fabrication processes and techniques of construction. BY: _______________________________________________ Medium Voltage Cables UK Chemistry Physics - Replace Existing Switchgear 13522 May 19, 2017 Bill Wilson May 19, 2017
16
Embed
Description of Submittal: Job Name: Job No: Date: May19,2017
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
The following comments are in response to Staggs and Fisher’s review of the attached shop drawing submittal.
Description of Submittal:
Job Name:
Job No:
Date:
Reviewed By:
Gregory G. Carter, P.E. Daniel H. Bransom, P.E.
Christopher C. Keath, P.E.John R. Mason, P.E. William P. Wilson, P.E. Greg W. Kraeszig, P.E.
Member of the Consulting Engineers Council
Remarks (if applicable):
X REVIEWED FURNISH AS CORRECTED
REJECTED REVISE AND RESUBMIT
DATE:
Checking is only for general conformance with the design concept of the project and general compliance with the information given in the contract documents. Any action shown is subject to the requirements of the drawings and specification. Contractor is responsible for : Quantities, dimensions which shall be confirmed and correlated at the job site, and fabrication processes and techniques of construction.
Metallic Shield:• 5 mil annealed copper tape with an
overlap of 25%
Jacket:• Flame-retardant, moisture- and sunlight-resistant
Chlorinated Polyethylene (CPE)
Print:• GENERAL CABLE® (PLANT OF MFG) (MO/YR
OF MANUFACTURE) LIGHTNING BOLT SYMBOL 1/C SIZE (AWG OR KCMIL) COMPACT CU UNIBLEND® XLF CPE JKT (INSULATION
Print (cont’d.): THICKNESS) EPR TYPE MV-105 (VOLTAGE) KV%
INSULATION LEVEL SUN RES FOR CT USE (UL) SEQUENTIAL FOOTAGE MARK
* Sizes smaller than 1/0 AWG do not include “FOR CT USE”.
Options:• STRANDFILL® – blocked conductor. Tested in
accordance with ICEA T-31-610
Applications:• Superior performance in petrochemical plants,
pulp and paper mills, sewage and water treatment plants, environmental protection systems, railroads, mines, utility power generating stations, steel mills, textile plants and other industrial three-phase applications
• For use in wet or dry locations when installed in accordance with NEC
• For use in aerial, conduit, open tray and underground duct installations
• For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4(A)(5)
Features:• Rated at 105˚C• Excellent heat and moisture resistance• Excellent flame resistance• Outstanding corona resistance
Features (cont’d.):• Flexibility for easy handling• Low friction for easy pulling• High dielectric strength• Low moisture absorption• Electrical stability under stress• Low dielectric loss• Chemical-resistant• Meets cold bend test at -35˚C• 105°C rating for continuous operation• 140°C rating for emergency overload conditions• 250°C rating for short circuit conditions
Compliances:• National Electrical Code (NEC)• UL 1072• ICEA S-93-639/NEMA WC74 • ICEA S-97-682• AEIC CS8• UL listed as Type MV-105 for use in accordance
with NEC, UL File # E90501• UL 1685 (Sizes 1/0 AWG and larger) UL Flame
Exposure Test• Sizes 1/0 AWG and larger are listed and marked
“Sunlight-Resistant FOR CT USE” in accordance with NEC
• IEEE 1202 (70,000 BTU/hr)/CSA FT4• EPA 40 CFR, Part 261 for leachable lead content
per TCLP method• OSHA Acceptable• RoHS Compliant
Packaging:• Material cut to length and shipped on non-
returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit
• Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing
SPEC 6375September, 2015
Uniblend® CPE High SpeedEPR/Copper Tape Shield/CPE, Medium-Voltage Power, Shielded 15 kV, UL Type MV-105, 133% Ins. Level, 220 Mils
CATALOG NUMBER
COND. SIZE
(AWG/ kcmil)
NOMINAL CONDUCTOR DIAMETER
INSULATION DIAMETER
INCHESNOMINAL JACKET
THICKNESS
NOMINAL CABLE
COPPER WEIGHT
AMPACITY
CONDUIT SIZING (4) (INCHES)
DIAMETER WEIGHTCONDUITIN AIR (1)
UNDERGROUND DUCT (2) TRAY (3)
INCHES MIN. MAX. INCHES mm INCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km 90˚C 105˚C 90˚C 105˚C 90˚C 105˚C
Dimensions and weights are nominal. Subject to industry tolerances.* Non-stock item; minimum runs apply. Please consult Customer Service for price and delivery.(1) Ampacities are in accordance with Table 310.60(C)(73) of the NEC for triplexed or three single conductor copper cables in isolated conduit in air based on a conductor temperature of 90˚C (194˚F) or 105˚C (221˚F), temperature denoted in column header, and an ambient air temperature of 40˚C (104˚F).(2) Ampacities are in accordance with Table 310.60(C)(77) of the NEC for triplexed or three single conductor copper cables in underground ducts (three conductors per duct), based on a conductor temperature of 90˚C (194˚F) or 105˚C (221˚F), temperature denoted in column header, and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90.(3) Ampacities are based on single conductor Type MV-105 sizes #1/0 AWG and larger in an uncovered tray in accordance with Section 392.80(B)(2) of the NEC at an ambient air temperature of 40˚C (104˚F) the ampacities are based on 75% of the values per Table 310.60(C)(69), operating temperature denoted in column header. For cable trays with unventilated covers for more than 6 feet, the ampacities shall not exceed 70% of the values per Table 310.60(C)(69).(4) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio has been considered but should be checked for individual installations.¥ 100% insulation level is available upon request.Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE”.
b) The NESC Lightning bolt symbol is on all Uniblend® constructions.
HIGH VOLTAGE TERMINATION (HVT-Z)FOR SHIELDED CABLES
• Co-extruded one-piece termination
* Built-in stress control
• As an option, the HVT-Z can also be ordered with TE’s new line of Aluminum ShearBolt Terminals.
• These are range taking mechanical connectors that will accommodate a conductor range from #2 compact to 1000 kcmil stranded, Class B.
KEY FEATURES TE Connectivity’s (TE) Raychem HVT-Z high voltage termination system features a new, co-extruded one-piece termination. The main termination component consists of the proven Raychem non-tracking tube together with a co-extruded stress control grading layer.
This stress control layer is based on ceramic semi-conductor technology (ZnO) and provides superior discharge and impulse performance. When the tubing is shrunk down, the coating softens and sticks to irregular surfaces, providing moisture seals as well as electrical stress control.
HVT-Z high-voltage terminations are fully qualified per IEEE-48 as Class I terminations to provide a long, trouble-free service life.
ENERGY /// HIGH VOLTAGE TERMINATION (HVT-Z)
Customers can count on consistent, high quality products, driven by TE’s proven innovation and backed by our extraordinary customer support.
Raychem, TE Connectivity and TE connectivity (logo) are trademarks. Other logos, product and/or company names might be trademarks of their respective owners. While TE has made every reasonable effort to ensure the accuracy of the information in this brochure, TE does not guarantee that it is error-free, nor does TE make any other representation, warranty or guarantee that the information is accurate, correct, reliable or current. TE reserves the right to make any adjustments to the information contained herein at any time without notice. TE expressly disclaims all implied warranties regarding the information contained herein, including, but not limited to, any implied warranties of merchantability or fitness for a particular purpose. The dimensions in this catalog are for reference purposes only and are subject to change without notice. Specifications are subject to change without notice. Consult TE for the latest dimensions and design specifications.
Tyco Electronics introduces a new one-piece 15 kV splice for use with solid dielectric cables, including copper tape shielded, wire shielded, UniShield shielded, and lead sheath power cables.
The requirements on today’s splicing technologies are high. Reliability, simple installations and cost effectiveness are the key requirements to achieving a dependable network. Cable accessories using Rayfit components are an excellent solution to fulfill these requirements.
The base HVS-C-1520S series • accepts both copper and aluminum compression connectors.
HVS-C-152xS–M1 and M2 kits • include a range taking copper ShearBolt connector for use with copper conductor.
HVS-S-152xS-M (4-9) kits include • a range taking aluminum ShearBolt connector for use with aluminum or copper conductor. HVS-S-152x- M (4-9) kits are supplied with stress control shim tubes to increase the insulation diameter.
TestingAll HVS-C-1520S and HVS-S-1520 •
splices have been qualified to IEEE-404-2006 at 105˚C. (140˚C emergency operation) with the outer wraparound jacket removed for underwater load cycling.
Wraparound sleeve
Rayfit tube
FeaturesThis series of splices utilizes the new • triple-extrusion Rayfit splice sleeve.
This new sleeve provides high recovery forces resulting in superior interfacial pressure, reduced shrink and installation time, and a slimmer space saving profile.
Each kit contains all of the components • required for the complete joint assembly, excluding connectors, unless a –M kit
is ordered.
The installed length of the kit is greatly • reduced with the use of the Rayfit sleeve and a wraparound re-jacketing system.
Jacket Kit Required Conductor Insulation O.D. Connector Dimensions Installed InstallationCatalog Size Diameter (Max) Length O.D. Length SpaceNumber (AWG/kcmil) (Min-Max) A B C L M
Jacket Maximum Kit Required Conductor Insulation O.D. Connector Dimensions Installed InstallationCatalog Size Diameter (Max) Length O.D. Length SpaceNumber (AWG/kcmil) (Min-Max) A B C L M
Jacket Kit Required Conductor Insulation O.D. Connector Dimensions Installed InstallationCatalog Size Diameter (Max) Length O.D. Length SpaceNumber (AWG/kcmil) (Min-Max) A B C L M
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale. ShearBolt, Rayfit, Raychem, TE logo, and Tyco Electronics are trademarks. UniShield is a trademark of BICC General Cable Industries, Inc.
Energy Division – a pioneer in the development of economical solutions for the electrical power industry. Our product range includes: Cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters.
Ordering Information1. Select the appropriate catalog number. All selections are based on the typical dimensions for both 100 and 133% insulated cables, nominal insulation thickness 0.175-0.220".2. Use the insulation OD, and jacket OD range as the final ordering criteria.3. Kits can be installed with either aluminum or copper compression connectors (connectors not included with kit).4. If external grounding, order an HVS-EG kit.5. Standard package: 1 kit/box6. Related test reports EDR-5440 for HVS-C and test report EDR-5444 for HVS-S, IEEE 404-2006 and IEEE-48 draft 2008 for 105˚C of Splice and Terminations.7. For AL Mechanical ShearBolt connector information request datasheet 9-1773440-4 and for CU request 165972.
ELB-15/28-600 Series600/900 Amp 15/28 kV Class T-Body Elbow Connector
The Raychem ELB-15/28-600 and ELB-15/28-610 elbows are designed to terminate underground cables to high-voltage apparatus such as transformers and switchgear . They are fully shielded and fully submersible and meet the requirements of IEEE Standard 386 . They are interchangeable with other manufacturers products that conform with this industry standard .
They are designed for use on extruded (XLPE or EPR) solid dielectric cable. The conductor range is from 1/0 AWG to 1250 kcmil for aluminum or copper conductors with insulation diameters from .640" to 1 .965" . The ELB-15/28-610 elbow has a capacitive test point molded into the elbow body which provides a means of sensing voltage and provides an attachment point for test point fault indicators . 900A ratings can be achieved by ordering the kit with a copper shearbolt terminal .
As an option, the elbow can also be ordered with TE’s Aluminum or Copper ShearBolt Terminals . These are range taking mechanical connectors that will accommodate a conductor range from #2 compact to 1250 kcmil stranded, Class B .
The ShearBolt terminal design incorporates shear head bolts, which ensures that the correct torque is applied to each bolt and consequently the optimal contact force is generated to minimize connection resistance . Eliminating the need for crimp tooling and dies, they are therefore ideal when installation space is confined .
• Peroxide cured EPDM rubber ensures low tension set and high dielectric strength• 100% factory production tested for partial discharge and AC Hipot per IEEE 386 • Optional capacitive test point provided on elbow • Fits 15/28 kV cables up to 1250 kcmil• Molded semiconducting shield provides ground shield continuity per the requirements of IEEE 592• Meets IEEE 386-2006 specification requirements• 900A capability is available
Selection InformationThe part number for a 35 kV Elbow, 600 A with test point, an insulation OD of 1 .755”, and 750 kcmil stranded cable is ELB-35-610R750 . (Or with AL ShearBolt ELB-15/28-610K-A3)