DESCRIPTION OF INTERIM CAPITAL PROJECT FOR CONSIDERATION June 7,
2018
USC COLUMBIA PROJECT NAME: South Caroliniana Library Renovation
REQUESTED ACTION: Establish Construction Budget (Phase II)
REQUESTED ACTION AMOUNT: $3,950,000
Internal Projected Cost: $8,950,000 BOARD APPROVAL RECEIVED:
April 2018 PREVIOUS CHE ACTIONS: Staff – Legislatively Authorized
Funds – Established February 2016
Project Budget Previous Change Revised Professional Service Fees
$1,000,000 $240,000 $1,240,000 Equipment/Materials $0 $112,098
$112,098 Site Development $0 $477,672 $477,672 Renovations –
Building Interior $3,500,000 $2,104,921 $5,604,921 Other:
Furniture, Fixtures, Hazmat Abatement $0 $266,098 $266,098
Contingency $500,000 $749,211 $1,249,211 Total $5,000,000
$3,950,000 $8,950,000
Source of Funds Previous Change Revised 2015-16 Capital Reserve
Funds $5,000,000 $0 $5,000,000 Private Gifts $0 $3,950,000
$3,950,000 Total $5,000,000 $3,950,000 $8,950,000
DESCRIPTION: The University of South Carolina requests to
proceed the construction phase to renovate the entire 22,843 SQ
footprint of the Library, constructed in 1840. The scope of the
project includes increasing security for the archives from fire and
inadequate environmental controls. A sprinkler system and fire
suppression system appropriate for archival storage will be
installed. The HVAC system will be replaced, and the archival
stacks will be separated from the main library rooms in a secure
wing with fire rated walls and access points. Operational
efficiencies and public accessibility to the elevator will be
improved. Architectural features will undergo a historic renovation
and the structural roof framing will be reinforced. All of the
items to be addressed will protect the published and unpublished
materials relating to history, literature and culture of South
Carolina which value is irreplaceable. The Library is available to
the entire student body, faculty, and history researchers. The
number of annual users is expected to be in the tens of
thousands.
The project was included on the 2017 CPIP as priority 3 of 9 for
2018. The source of funds for this project is a combination of
State Appropriated funds through the Capital Reserve fund, which
$5m was appropriated for this specific purpose in the 2015-16
budget, and $5m in private donations. The University received an
anonymous donation in January 2017, which is being used in part for
the renovation and the funds remaining will be used to create and
upfit an exhibition space. Execution of the construction contract
is estimated for April 2019 and completion is projected for August
2020.
Agenda Item 8.04.A.4.a
1
-
E&G MAINTENANCE NEEDS:
The current building score for South Caroliniana Library based
on the 2017 Building Condition Survey is a 35. Future maintenance
of the renovated space will be funded from the Education and
General Maintenance Reserve, which is replenished annually to
address planned capital renewal projects. Maintenance of this
facility is covered by the annual $80 per full-time student
fee.
ADDITIONAL ANNUAL OPERATING COSTS/SAVINGS:
This project is not expected to impact the operating budget.
2
-
Institution Name: Respondent:
Building Number:
Building Name: Telephone:
Location: E-Mail:
Gross Square Feet:
Year Const / Renov:
Replacement Cost:
Comments:
Multiplier
Foundation 3.750 0.275 x 0.13 = 0.0358
Exterior Walls 3.250 0.425 x 0.13 = 0.0553
Floor 4.000 0.200 x 0.07 = 0.0140
Roof 1.000 1.000 x 0.07 = 0.0700
Interior Walls 3.000 0.500 x 0.03 = 0.0150
Windows 3.000 0.500 x 0.02 = 0.0100
Doors 4.000 0.200 x 0.01 = 0.0020
Ceiling 2.750 0.575 x 0.03 = 0.0173
Heating 4.250 0.150 x 0.10 = 0.0150
Cooling 3.750 0.275 x 0.10 = 0.0275
Plumbing 3.667 0.300 x 0.08 = 0.0240
Electrical 3.750 0.275 x 0.08 = 0.0220
Elevators 1.000 1.000 x 0.01 = 0.0100
Safety 4.667 0.067 x 0.05 = 0.0033
Design Standards 3.667 0.300 x 0.09 = 0.0270
Agency Rating: 1.00 0.348
Bldg. Avg. Grade
Condition Code
Condition Multiplier Difference
Replacement Cost: $5,202,050 1 Satisfactory 1.00Building
Condition: 35 2 Remodel A 0.8 -0.2
3 Remodel B 0.5 -0.3Maintenance NeedOver 20 Years: $3,381,333 4
Remodel C 0.2 -0.3
5 Replace 0.00 -0.2
1978
Current % Value Bldg.
System % of Building
Please do not enter data in the cells below this line. Begin
data entry on Page 2.
System Avg. Score
DON GIBSON
803-777-1083
[email protected]
Owned Fee Simple
Roof replaced 2013 Renovation Planned for 2018
Name
Main Campus
22,843
$5,202,050
1840
USC Campus
4
South Caroliniana Library
3
-
Foundation Exterior Wall System Floor System1 - 2 - 3 - 4 - 5 1
- 2 - 3 - 4 - 5 1 - 2 - 3 - 4 - 5
Cracked Walls 4 Physical Condition 3 Structural Condition
4Foundation Settlement 4 Waterproofing 3 Maintainability
4Foundation Deterioration 4 Caulking 3 Floor Finish 4Design Load 3
Pointing 3 Vibration 4 Average 3.75 Code Compliance 3 Fire Rating
4
Insulation 4 Design Load 4Maintainability 4 Average 4Painting 3
Average 3.25
Roof System Interior Wall System Window System1 - 2 - 3 - 4 - 5
1 - 2 - 3 - 4 - 5 1 - 2 - 3 - 4 - 5
Physical Condition 1 Physical Condition 3 Physical Condition
3Leaks 1 Strength & Stability 3 Appearance 3Drainage 1
Acoustical Quality 3 Functional Ability 3Insulation 1 Appearance 3
Infiltration 3Fire Rating 1 Adaptability 3 Maintainability 3Design
Load 1 Maintainability 3 Average 3 Average 1 Average 3
Age of Roof Cover: 3Type of Roof Cover: ElastFlat: XPitched:
X
Door System Ceiling System Heating System1 - 2 - 3 - 4 - 5 1 - 2
- 3 - 4 - 5 1 - 2 - 3 - 4 - 5
Door Leaf 4 Structural Condition 3 Heating Capacity 3Frame 4
Accoustical 3 Temperature Control 4Hardware 4 Accessability 3 Noise
Level 3Security 4 Appearance 2 Air Circulation & Vent 5Fire
Rating 4 Average 2.75 Reliability 4 Average 4
Filtration 5Humidity 5 Average 4.25
Age of System:Heating Capacity-BTUs:
Cooling System Plumbing System Electrical System1 - 2 - 3 - 4 -
5 1 - 2 - 3 - 4 - 5 1 - 2 - 3 - 4 - 5
Cooling Capacity 3 Safety Conditions 3
Service Capacity 3Panel Capacity 5
Temperature 3 Convenience Outlets 5Noise Level 4 Drain &
Waste Function 3 Light Levels 4Air Circulation & Vent 5 Fixture
Quantities 3 Fixtures 4Reliability 3 Fixture Types & Cond. 5
Emergency Power 3Filtration 3 Wheel Chair Fixtures 4 Exit Lighting
3Humidity 5 Restroom Facilities 4 Average 3.75 Average 3.75 Roof
Drainage 4
Site Drainage 4Age of System: Average 3.6667Cooling
Capacity-Tons:
Elevator System Safety Standards Design Standards1 - 2 - 3 - 4 -
5 1 - 2 - 3 - 4 - 5 1 - 2 - 3 - 4 - 5
Size & Number 1 Means of Egress 4 Flexible Design
4Maintainability 1 Fire Ratings 4 Suitable for Present Use 3Code
Compliance 1 Extinguishing Systems 5 Gross to Assignable Area 4
Average 1 Detection & Alarm Sys. 5 Average 3.6667
Lighting Systems 5Handicap Access 5 Average 4.6667
Building Number: 4
Reasonable Energy Consumption 4
3
Building Name: South Caroliniana Library
Rating Rating
Rating Rating
Rating Rating Rating
Rating
Rating
Rating Rating Rating
Reasonable Energy Consumption 5
Water Pressure & Supply QuantitiesSanitation Hazards or
Cross Functions 3
Rating Rating Rating
4
-
5
-
6
-
7
-
8
-
9
-
10
-
11
-
12
-
20
20
UP
UP
UP
UP
UP
7
A
G
1 132 3 4 5 6 8 9 10 11 12
4.1 6.1 7.1 9.1
B
C
D
E
F
H
3' - 9 7/16"
4' -
0"
X1
01
01
01 0101
01
01
01
01
01
01
01
0101
01
01
01
01
01
01
02
02
02
02
02
02
04 04
04 04
0404
04
04
06
06
06
06
06
06
07
07
07
07
07
07
07
06
07
06
07
06
07
06
07
06
07
06
0706
07
06
07
08 09
10
11
11
9' -
2"
1' -
4 1
/8"
8' -
4 3
/8"
18' -
3 3
/4"
8' -
5 1
/2"
13' -
2 1
/4"
10' -
9 1
/8"
13' - 7 1/2" 14' - 5" 13' - 8"
20' - 7" 8' - 0 3/8" 9' - 11 3/8" 9' - 10 3/4" 10' - 2 3/8" 9' -
2" 9' - 2 1/2" 10' - 2 3/8" 10' - 2" 9' - 10" 7' - 10 1/4" 20' -
7"
08
08
08
08
08
08
2Sim
A200 D101
SLAB TO BE REMOVED
7' - 1 3/8"
LUMPKINFOYER
100
EXHIBITS
101 BOOKSTORAGE
119
14
14
14
14
01
DEMOLITION NOTES
01
02
04
06
07
REMOVE INTERIOR PARTITIONS & DOORS COMPLETE
REMOVE CASEWORK COMPLETE INCLUDING ASSOCIATED FIXTURES
REMOVE PLUMBING FIXTURES
REMOVE CEILING SYSTEM COMPLETE. INCLUDES ALL MEP DEVICES.
REMOVE DUMBWAITER COMPLETE & PREPARE TO RECIEVE
NEWDUMBWAITER
09
REMOVE ELECTRICAL MOUDLING & PREP FOR PAINT08
10REMOVE ELEVATOR COMPLETE & PREPARE TO RECIEVE
NEWELEVATOR
REMOVE FLOOR FINISH COMPLETE TO CONCRETE SLAB OR WOOD
SUBSTRATE.INCLUDES CARPET, VCT, ADHESIVES ETC. FIELD VERIFY
CONDITIONS
11 REMOVE EXISTING MASONRY WALL & PREP FOR NEW DOOR
14 REMOVE INTERIOR STUCCO TO MASONRY COMPLETE
PARTITIONSEXISTING CONSTRUCTION TOREMAIN
EXISTING CONSTRUCTION TOBE DEMOLISHED
DEMOLITION PLAN LEGENDGENERAL DEMOLITION NOTES
A. REFER TO STRUCTURAL DRAWINGS FOR INFORMATION REGARDINGSHORING
PRIOR TO REMOVING ANY STRUCTURAL ELEMENTS
B. REFER TO OWNERS HAZMAT REPORT PRIOR TO DEMOLITION
76 8
B
C
D
E
F
DEMOLISH CEILING ONLYWITHIN HATCHED REGION.
DO NOT DAMAGEPLASTER MOULDING
PROTECT PLASTERMOULDING FROM DAMAGE
B
C
D
E
F
6 7 8
North
Checked By:
Drawn By:
Date:
Project Number:
C Copyright 2018. All Rights Reserved. Reproduction, copying, or
use of this drawing and designs shown thereon without written
consent of Liollio Architecture, Inc. is prohibited and any
infringement is subject to legal action.
Revision Date Description
Scale:
NOT FORCONSTRUCTION
State Project Number:
SCALE:
147 Wappoo Creek DriveSuite 400Charleston, SC 29412
www.liollio.com
843.762.2222843.762.2300
H27-6119-LC
910 SUMTER STREETCOLUMBIA, SC 29208
1/8" = 1'-0"
1/8" = 1'-0"
UNIVERSITY OF SOUTH CAROLINA
17700
JMW
DRC
1/15/2018
FIRST FLOORDEMOLITION PLAN
D101
SOUTHCAROLINIANALIBRARYRENOVATION
SCALE:D101 1/8" = 1'-0"
1 FIRST FLOOR DEMOLITION PLAN
SCALE:D101 1/8" = 1'-0"
2 FIRST FLOOR DEMO REFLECTED CEILING PLAN 2 40 168
1/15/2018 DD-OSE PHASE ONE SUBMITTAL
13
-
UP
UP
UP
UPUP
UPUP UPUP UPUP
7
A
G
1 132 3 4 5 6 8 9 10 11 12
4.1 6.1 7.1 9.1
B
C
D
E
F
H
18' - 11"
22' - 0"
1' - 4 1/4" 18' - 11" 2' - 4 1/4" 91' - 4 1/16" 2' - 5"
91' - 6 1/16"
02 02 02 02 02020202 0202
0202020202 02 02 0202 02
02
06
0608
04
09
10
08
08
02
02
02
BULFINCHREADING
ROOM
201
KENDALLROOM
202
BOOKSTORAGE
213
14
14
14
14
14
PARTITIONSEXISTING CONSTRUCTION TOREMAIN
EXISTING CONSTRUCTION TOBE DEMOLISHED
DEMOLITION PLAN LEGENDGENERAL DEMOLITION NOTES
A. REFER TO STRUCTURAL DRAWINGS FOR INFORMATION REGARDINGSHORING
PRIOR TO REMOVING ANY STRUCTURAL ELEMENTS
B. REFER TO OWNERS HAZMAT REPORT PRIOR TO DEMOLITION
DEMOLITION NOTES
REMOVE INTERIOR PARTITIONS & DOORS COMPLETE
REMOVE CASEWORK COMPLETE INCLUDING ASSOCIATED FIXTURES
01
02
REMOVE ALL PLUMBING FIXTURES & ACCESSORIES COMPLETE04
07
08
REMOVE DUMBWAITER COMPLETE & PREPARETO RECIEVE NEW
DUMBWAITER
09
10REMOVE ELEVATOR COMPLETE & PREPARE TORECIEVE NEW
ELEVATOR
REMOVE FLOOR FINISH COMPLETE TO CONCRETE SLAB OR WOODSUBSTRATE.
INCLUDES CARPET, VCT, ADHESIVES ETC. FIELD VERIFYCONDITIONS
REMOVE ELECTRICAL MOUDLING & PREP FOR PAINT
14 REMOVE INTERIOR STUCCO TO MASONRY COMPLETE
A
G
1312
B
C
D
E
F
08
09
BOOKSTORAGE
214
14
14
14
14
A
G
1312
B
C
D
E
F
08
09
1139 SF
BOOKSTORAGE
215
14
14
14
North
Checked By:
Drawn By:
Date:
Project Number:
C Copyright 2018. All Rights Reserved. Reproduction, copying, or
use of this drawing and designs shown thereon without written
consent of Liollio Architecture, Inc. is prohibited and any
infringement is subject to legal action.
Revision Date Description
Scale:
NOT FORCONSTRUCTION
State Project Number:
SCALE:
147 Wappoo Creek DriveSuite 400Charleston, SC 29412
www.liollio.com
843.762.2222843.762.2300
H27-6119-LC
910 SUMTER STREETCOLUMBIA, SC 29208
1/8" = 1'-0"
1/8" = 1'-0"
UNIVERSITY OF SOUTH CAROLINA
17700
JMW
DRC
1/15/2018
SECOND FLOORDEMOLITION PLAN
D102
SOUTHCAROLINIANALIBRARYRENOVATION
SCALE:D102 1/8" = 1'-0"
1 SECOND FLOOR DEMOLITION PLAN
2 40 168
1/15/2018 DD-OSE PHASE ONE SUBMITTAL
SCALE:D102 1/8" = 1'-0"
2 2.5 FLOOR DEMOLITION PLAN - STACKSSCALE:D102 1/8" = 1'-0"
3 2.75 FLOOR DEMOLITION PLAN - STACKS
14
-
UPUP
UP
UP
7
A
G
1 132 3 4 5 6 8 9 10 11 12
B
C
D
E
F
OPEN TO BELOW
01
01
01
01
01
01
01
01 01 01
HALF WALL W/ DUCTWORK AND ELECTRICAL FIXTURES
DESKS
020202 02
02 02
0101
HALF WALL W/ DUCTWORK ANDELECTRICAL FIXTURES
01
06
07
08
06
07
06
07
06
07
06
07
07
07
07
07
09
10
05
MONITOR ABOVESEE D500
01
08
08
08
08
BOOKSTORAGE
314
MEZZA. A
310
MEZZAN. B
315B2
UP UP
01
01
14
14
14
14
REMOVE INTERIOR PARTITIONS & DOORS COMPLETE
DEMOLITION NOTES
REMOVE CASEWORK COMPLETE INCLUDING ASSOCIATED FIXTURES
01
02
REMOVE STAIR & RAILING COMPLETE TO FLOOR & ADJACENT
WALL05
REMOVE CEILING SYSTEM COMPLETE. INCLUDES ALL MEP DEVICES.06
REMOVE FLOOR FINISH COMPLETE TO CONCRETE SLAB OR WOOD
FLOOR.INCLUDES CARPET, VCT, ADHESIVES ETC. FIELD VERIFY
CONDITIONS
07
08
REMOVE DUMBWAITER COMPLETE & PREPARE TO RECIEVE
NEWDUMBWAITER
09
10REMOVE ELEVATOR COMPLETE & PREPARE TO RECIEVE
NEWELEVATOR
REMOVE ELECTRICAL MOUDLING & PREP FOR PAINT
14 REMOVE INTERIOR STUCCO TO MASONRY COMPLETE
PARTITIONSEXISTING CONSTRUCTION TOREMAIN
EXISTING CONSTRUCTION TOBE DEMOLISHED
DEMOLITION PLAN LEGENDGENERAL DEMOLITION NOTES
A. REFER TO STRUCTURAL DRAWINGS FOR INFORMATION REGARDINGSHORING
PRIOR TO REMOVING ANY STRUCTURAL ELEMENTS
B. REFER TO OWNERS HAZMAT REPORT PRIOR TO DEMOLITION
North
Checked By:
Drawn By:
Date:
Project Number:
C Copyright 2018. All Rights Reserved. Reproduction, copying, or
use of this drawing and designs shown thereon without written
consent of Liollio Architecture, Inc. is prohibited and any
infringement is subject to legal action.
Revision Date Description
Scale:
NOT FORCONSTRUCTION
State Project Number:
SCALE:
147 Wappoo Creek DriveSuite 400Charleston, SC 29412
www.liollio.com
843.762.2222843.762.2300
H27-6119-LC
910 SUMTER STREETCOLUMBIA, SC 29208
1/8" = 1'-0"
1/8" = 1'-0"
UNIVERSITY OF SOUTH CAROLINA
17700
JMW
DRC
1/15/2018
THIRD FLOORDEMOLITION PLAN
D103
SOUTHCAROLINIANALIBRARYRENOVATION
SCALE:D103 1/8" = 1'-0"
1 THIRD FLOOR DEMOLITION PLAN
2 40 168
1/15/2018 DD-OSE PHASE ONE SUBMITTAL
15
-
7
A
G
1 132 3 4 5 6 8 9 10 11 12
B
C
D
E
F
2"
/ 12"
2"
/ 12"
1/2
" / 12"
1/2
" / 12"
2"
/ 12"
2"
/ 12"
REMOVE EXISTING ROOF HATCH
THROUGH WALLSCUPPER
THROUGH WALLSCUPPER
SLOPEEXISTING 16" ROOFVENT, TYP
SLOPE
EXISTING 16" ROOFVENT, TYP
SLO
PE
SLO
PE
SLO
PE
SLO
PE RIDGE RIDGE
THROUGH WALL SCUPPER
EXISTING ROOF DRAINS
THROUGH WALL SCUPPER
EXISTING ROOF DRAINS
VALLEY
VALLEY
SLOPE
6' - 6 5/8"6' - 4 1/2"
11' -
4 1
/4"
12
13
12
13
12
13
12
13
1
D150 D500
ROOFMONITOR
TYP
TYP
1
D150 A500
4
D150 A500
12
13
REMOVE PVC ROOFING FOR ATTIC ACCESS DURINGCONSTRUCTION AND NEW
ROOF HATCH
DEMOLITION NOTES
REMOVE ROOF SHEATHING & PREPARE FOR NEW
12
13
GENERAL DEMOLITION NOTES
A. REFER TO STRUCTURAL DRAWINGS FOR INFORMATION REGARDINGSHORING
PRIOR TO REMOVING ANY STRUCTURAL ELEMENTS
B. REFER TO OWNERS HAZMAT REPORT PRIOR TO DEMOLITION
North
Checked By:
Drawn By:
Date:
Project Number:
C Copyright 2018. All Rights Reserved. Reproduction, copying, or
use of this drawing and designs shown thereon without written
consent of Liollio Architecture, Inc. is prohibited and any
infringement is subject to legal action.
Revision Date Description
Scale:
NOT FORCONSTRUCTION
State Project Number:
SCALE:
147 Wappoo Creek DriveSuite 400Charleston, SC 29412
www.liollio.com
843.762.2222843.762.2300
H27-6119-LC
910 SUMTER STREETCOLUMBIA, SC 29208
1/8" = 1'-0"
1/8" = 1'-0"
UNIVERSITY OF SOUTH CAROLINA
17700
ABB
DRC
1/15/2018
ROOF DEMOLITIONPLAN
D150
SOUTHCAROLINIANALIBRARYRENOVATION
SCALE:D150 1/8" = 1'-0"
1 ROOF DEMOLITION PLAN
2 40 168
1/15/2018 DD-OSE PHASE ONE SUBMITTAL
16
-
UP
UP
UP
UP
UP
7
A
G
1 132 3 4 5 6 8 9 10 11 12
4.1 6.1 7.1 9.1
B
C
D
E
F
H
A3011
A301
2
A300
1
A300 2
286 SF
ANTE/CONFERENCE
104
370 SF
ARCHIVALVAULT
105
346 SF
MECHANICALROOM
108
1058 SF
EXHIBITS
101
693 SF
LUMPKINFOYER
100
150 SF
DIRECTORCONFERENCE
ROOM
122 234 SF
LIBRARYDIRECTOR
121
44 SF
ELECTRICAL
116
259 SF
ADMINSTRATOR
115
223 SF
MECHANICALROOM
118
112 SF
CORRIDOR
112
112 SF
STAIR
117
61 SF
ELEVATOR
109
120 SF
CORRIDOR
106
112 SF
MENS
113
115 SF
WOMENS
114
51 SF
STORAGE
103
E101
E100
E102
E121
E119
E124
E126E100C
105
107
109
123
116
121
120
104
114 115
45 SF
STAIR
102
1139 SF
BOOKSTORAGE
119
70 SF
CORRID.
107
17' - 11"
20' -
8"
1
A401A101A7012
3
4
A1
A1
A1
A1
B
A1
A1
A701
1
90 SF
STORAGE
120
A1
A1
99 SF
IT CLOSET
110
23' -
1 7
/8"
5' - 1 3/8"
ELEVATOR
DUMB WAITER
1
A101 A200
2
A401A101
2
A400A101
1
A400A101
1
A101 A201
2
A101 A707
3
A101 A600
A7041
2
A101 A202
1
A101 A202
A1
A1
111
110
106A
108
112
113
117
15 SF
STORAGE
100A
PANEL INFILL, TYP.FOR EACH WINDOWIN STACKS
100A
A5A5
A5
A5
A5
GENERAL NOTES
A CONTRACTOR TO FIELD VERIFY ALL EXISTING BUILDING
DIMENSIONS
B DIMENSIONS TAKEN FROM FACE OF EXISTING WALLS & CENTERLINE
OF NEW WALLS
FLOOR PLAN LEGEND
X
WALL TAG
PARTITIONSEXISTING CONSTRUCTION TOREMAIN
NEW PARTITION
DASHED FURNITURE - N.I.C.
MILLWORK
SYMBOLS XXX DOOR TAG
XXX EXISTING DOOR TAGEXXX
1
24
3
ROOM FINISH WALL LOCATIONS
3 HOUR RATED WALL
ROOM TAG# # #
ROOM NAME
AXXX
EXISTING CAST IRON SHELVING
North
Checked By:
Drawn By:
Date:
Project Number:
C Copyright 2018. All Rights Reserved. Reproduction, copying, or
use of this drawing and designs shown thereon without written
consent of Liollio Architecture, Inc. is prohibited and any
infringement is subject to legal action.
Revision Date Description
Scale:
NOT FORCONSTRUCTION
State Project Number:
SCALE:
147 Wappoo Creek DriveSuite 400Charleston, SC 29412
www.liollio.com
843.762.2222843.762.2300
H27-6119-LC
910 SUMTER STREETCOLUMBIA, SC 29208
1/8" = 1'-0"
1/8" = 1'-0"
UNIVERSITY OF SOUTH CAROLINA
17700
JMW
DRC
1/15/2018
FIRST FLOORRENOVATION PLAN
A101
SOUTHCAROLINIANALIBRARYRENOVATION
SCALE:A101 1/8" = 1'-0"
1 FIRST FLOOR RENOVATION PLAN
2 40 168
1/15/2018 DD-OSE PHASE ONE SUBMITTAL
17
-
UP
UP
UPUP UPUP UPUP
7
A
G
1 132 3 4 5 6 8 9 10 11 12
4.1 6.1 7.1 9.1
B
C
D
E
F
H
A3011
A301
2
A300
1
A300 2
1138 SF
KENDALLROOM
202
2742 SF
BULFINCHREADING
ROOM
201
168 SF
STAIR
200 231 SF
STAIR
211
116 SF
MECH
212
1139 SF
BOOKSTORAGE
213
38 SF
STORAGE
209
38 SF
FOYER
210
40 SF
FOYER
203
180 SF
STAIR
205
26 SF
STORAGE
206
61 SF
ELEVATOR
207
39 SF
STAIR
208
E200
E203B
E207
E211
E212
E205
E212B
E203
E208
E202 E209
1
A401A101
A703
2
A7031 A702 2
A702
1
WOOD LOCKERS
WOOD BOOKSHELVES;TYP.
SERVICE DESK
2
A401A101
2
A400A101
1
A400A101
A7041
A704
5
A704 4
6
DUMBWAITER
E201 E210
ELEVATOR
PROJECTOR SCREENABOVE
PROJECTOR SCREENABOVE
DN
PANEL INFILL, TYP.FOR EACH WINDOWIN STACKS
A5 A5
A5
A5
A5A5
FLOOR PLAN LEGEND
X
WALL TAG
PARTITIONSEXISTING CONSTRUCTION TOREMAIN
NEW PARTITION
DASHED FURNITURE - N.I.C.
MILLWORK
SYMBOLS XXX DOOR TAG
XXX EXISTING DOOR TAGEXXX
1
24
3
ROOM FINISH WALL LOCATIONS
3 HOUR RATED WALL
ROOM TAG# # #
ROOM NAME
AXXX
EXISTING CAST IRON SHELVING
GENERAL NOTES
A CONTRACTOR TO FIELD VERIFY ALL EXISTING BUILDING
DIMENSIONS
B DIMENSIONS TAKEN FROM FACE OF EXISTING WALLS & CENTERLINE
OF NEW WALLS
A
G
1312
B
C
D
E
F
DUMBWAITER
1139 SF
BOOKSTORAGE
214
2
A400A101
PANEL INFILL, TYP. FOREACH WINDOW IN STACKS
A5
A5
A5
A5
A
G
1312
B
C
D
E
F
DUMBWAITER
1139 SF
BOOKSTORAGE
215
2
A400A101
PANEL INFILL, TYP.FOR EACH WINDOWIN STACKS
A5
A5
A5
A5
North
Checked By:
Drawn By:
Date:
Project Number:
C Copyright 2018. All Rights Reserved. Reproduction, copying, or
use of this drawing and designs shown thereon without written
consent of Liollio Architecture, Inc. is prohibited and any
infringement is subject to legal action.
Revision Date Description
Scale:
NOT FORCONSTRUCTION
State Project Number:
SCALE:
147 Wappoo Creek DriveSuite 400Charleston, SC 29412
www.liollio.com
843.762.2222843.762.2300
H27-6119-LC
910 SUMTER STREETCOLUMBIA, SC 29208
1/8" = 1'-0"
1/8" = 1'-0"
UNIVERSITY OF SOUTH CAROLINA
17700
JMW
DRC
1/15/2018
SECOND FLOORRENOVATION PLAN
A102
SOUTHCAROLINIANALIBRARYRENOVATION
SCALE:A102 1/8" = 1'-0"
1 SECOND FLOOR RENOVATION PLAN
2 40 168
1/15/2018 DD-OSE PHASE ONE SUBMITTAL
SCALE:A102 1/8" = 1'-0"
2 2.5 FLOOR PLAN - STACKSSCALE:A102 1/8" = 1'-0"
3 2.75 FLOOR PLAN -STACKS
18
-
UP
UP
7
A
G
1 132 3 4 5 6 8 9 10 11 12
B
C
D
E
F
A3011
A301
2
A300
1
A300 2
680 SF
COLLABSTAFF
307
159 SF
HEADUSER
SERVICE
306
179 SF
STAFFLOUNGE
305
1139 SF
BOOKSTORAGE
314
24 SF
CLOSET
304
61 SF
ELEV
302
26 SF
STORAGE
303
180 SF
STAIR
300
168 SF
ROOFACCESS
311 231 SF
STAIR
312
116 SF
MECH
313
653 SF
MEZZA. A
310
389 SF
MEZZAN. B
315B2
56 SF
FOYER
301
E304
E302
E309
E313
E310
E315
306
66 SF
HALLWAYA
316
305
1
A401A101
OPEN TO BELOW
A703
2
A7031 A702 2
A702
1
A1
A1
140 SF
GRADUATESWORKAREA
315A
E312
ELEVATOR
DUMBWAITER
2
A401A101
2
A400A101
1
A400A101
A704
2
A704
3
E301311
307
LADDER FORROOF ACCESS
PANEL INFILL, TYP.FOR EACH WINDOWIN STACKS
A1
A5
A5
A5
A5
A5
GENERAL NOTES
A CONTRACTOR TO FIELD VERIFY ALL EXISTING BUILDING
DIMENSIONS
B DIMENSIONS TAKEN FROM FACE OF EXISTING WALLS & CENTERLINE
OF NEW WALLS
FLOOR PLAN LEGEND
X
WALL TAG
PARTITIONSEXISTING CONSTRUCTION TOREMAIN
NEW PARTITION
DASHED FURNITURE - N.I.C.
MILLWORK
SYMBOLS XXX DOOR TAG
XXX EXISTING DOOR TAGEXXX
1
24
3
ROOM FINISH WALL LOCATIONS
3 HOUR RATED WALL
ROOM TAG# # #
ROOM NAME
AXXX
EXISTING CAST IRON SHELVING
North
Checked By:
Drawn By:
Date:
Project Number:
C Copyright 2018. All Rights Reserved. Reproduction, copying, or
use of this drawing and designs shown thereon without written
consent of Liollio Architecture, Inc. is prohibited and any
infringement is subject to legal action.
Revision Date Description
Scale:
NOT FORCONSTRUCTION
State Project Number:
SCALE:
147 Wappoo Creek DriveSuite 400Charleston, SC 29412
www.liollio.com
843.762.2222843.762.2300
H27-6119-LC
910 SUMTER STREETCOLUMBIA, SC 29208
1/8" = 1'-0"
1/8" = 1'-0"
UNIVERSITY OF SOUTH CAROLINA
17700
JMW
DRC
1/15/2018
THIRD FLOORRENOVATION PLAN
A103
SOUTHCAROLINIANALIBRARYRENOVATION
SCALE:A103 1/8" = 1'-0"
1 THIRD FLOOR RENOVATION PLAN
2 40 168
1/15/2018 DD-OSE PHASE ONE SUBMITTAL
19
-
TYPE 1 CEILING:2' x 2' SUSPENDEDACOUSTICAL TILE
TYPE 3 CEILING:GYPSUM BOARD
2' x 2' LEDLIGHT FIXTURE
TYPE 4 CEILING:EXPOSED TOSTRUCTURE
AIR HANDLER
RECESSED CAN LIGHT
1t
1'-0"
101
CEILING TAG WITHHEIGHT
ROOM NUMBER
EXHAUST FAN
EXIT LIGHT
LINEAR LED LIGHTFIXTURE
CEILING UNIT HEATER
P PROJECTOR CEILINGMOUNT LOCATIONSOLID WALL INDICATES
WALL EXTENDS TO DECK
REFLECTED CEILING PLAN LEGEND
RECESSED DIRECTIONAL CAN LIGHT
RECESSED EMERGENCY CAN LIGHT
STRIP LIGHT
EXTERIOR LIGHT
TYPE 2 CEILING:PLASTER
PENDANT
SPRINKLER HEAD
1. THE INTENT OF THE RCP IS TO FAMILIARIZE THE CONTRACTOR WITH
THETOTAL CONCEPT. THE CONTRACTOR SHALL NOT USE THE RCP FOR
ESTIMATINGELECTRICAL AND MECHANICAL WORK. MECHANICAL-ELECTRICAL
DOCUMENTSTAKE PRECEDENCE OVER THE RCP.
2. ALL CEILING-MOUNTED DEVICES MAY NOT BE SHOWN. COORDINATE
THEWORK SHOWN ON THIS DRAWING WITH THE WORK OF ALL OTHER TRADES
ANDDISCIPLINES.
3. ROOMS WITH NO CEILINGS SHALL HAVE WALLS THAT EXTEND TO THE
DECK.ALL RATED WALLS SHALL TERMINATE AT BOTTOM OF DECK ABOVE. REFER
TOTHE LIFE SAFETY PLAN FOR RATED WALL CONDITIONS.
GENERAL NOTES - RCP
7
A
G
1 132 3 4 5 6 8 9 10 11 12
4.1 6.1 7.1 9.1
B
C
D
E
F
H
1
A401A101
ACT
8' - 0"
GWB
8' - 0"
MECHANICALROOM
108
ARCHIVALVAULT
105
ANTE/CONFERENCE
104
EXHIBITS
101
STORAGE
103
IT CLOSET
110
ACT
8' - 0"ACT
8' - 0"
ACT
8' - 0"
ACT
8' - 0"
ACT
8' - 0"
ACT
8' - 0"
GWB
8' - 0"
ACT
8' - 0"
ACT
8' - 0"
ACT
8' - 0"
OPEN TO ABOVE
OPEN TO STRUCTURE ABOVE
MENS
113
WOMENS
114
LIBRARYDIRECTOR
121
DIRECTORCONFERENCE
ROOM
122
STORAGE
120
ADMINSTRATOR
115
ELECTRICAL
116
MECHANICALROOM
118
STAIR
117
OPEN TO ABOVE
2
A401A101
2
A400A101
1
A400A101
CEILING AND LIGHTINGBY ARCHIVAL VAULT
MANUFACTUER
LUMPKINFOYER
100
CORRIDOR
112
BOOKSTORAGE
119
CORRID.
107
GWB7' - 111/4"
ACT
8' - 0"
North
Checked By:
Drawn By:
Date:
Project Number:
C Copyright 2018. All Rights Reserved. Reproduction, copying, or
use of this drawing and designs shown thereon without written
consent of Liollio Architecture, Inc. is prohibited and any
infringement is subject to legal action.
Revision Date Description
Scale:
NOT FORCONSTRUCTION
State Project Number:
SCALE:
147 Wappoo Creek DriveSuite 400Charleston, SC 29412
www.liollio.com
843.762.2222843.762.2300
H27-6119-LC
910 SUMTER STREETCOLUMBIA, SC 29208
1/8" = 1'-0"
1/8" = 1'-0"
UNIVERSITY OF SOUTH CAROLINA
17700
ABB
DRC
1/15/2018
FIRST FLOORREFLECTED CEILINGPLAN
A131
SOUTHCAROLINIANALIBRARYRENOVATION
SCALE:A131 1/8" = 1'-0"
1 FIRST FLOOR REFLECTED CEILING PLAN
2 40 168
1/15/2018 DD-OSE PHASE ONE SUBMITTAL
20
-
7
A
G
1 132 3 4 5 6 8 9 10 11 12
4.1 6.1 7.1 9.1
B
C
D
E
F
H
OS GOS I
1
A401A101
KENDALLROOM
202
BULFINCHREADING
ROOM
201
FOYER
203
FOYER
210
BOOKSTORAGE
213
STORAGE
209
EXISTING
17' - 8"
2
A401A101
2
A400A101
1
A400A101
EXISTING CEILING - ABOVE
EXISTINGCEILING
OPEN TO ABOVE OPEN TO ABOVE
STAIR
205
STAIR
211
MECH
212
STAIR
200EXISTING PLASTERCEILING
EXISTING BARRELVAULT CEILING, TYP
EXISTING BARRELVAULT CEILING, TYP
OPEN TO STRUCTURE
EXISTING
16' - 8"
EXISTING
16' - 8"
PROJECTOR SCREEN
PROJECTOR SCREEN
GWB
17' - 0"
1. THE INTENT OF THE RCP IS TO FAMILIARIZE THE CONTRACTOR WITH
THETOTAL CONCEPT. THE CONTRACTOR SHALL NOT USE THE RCP FOR
ESTIMATINGELECTRICAL AND MECHANICAL WORK. MECHANICAL-ELECTRICAL
DOCUMENTSTAKE PRECEDENCE OVER THE RCP.
2. ALL CEILING-MOUNTED DEVICES MAY NOT BE SHOWN. COORDINATE
THEWORK SHOWN ON THIS DRAWING WITH THE WORK OF ALL OTHER TRADES
ANDDISCIPLINES.
3. ROOMS WITH NO CEILINGS SHALL HAVE WALLS THAT EXTEND TO THE
DECK.ALL RATED WALLS SHALL TERMINATE AT BOTTOM OF DECK ABOVE. REFER
TOTHE LIFE SAFETY PLAN FOR RATED WALL CONDITIONS.
GENERAL NOTES - RCP
TYPE 1 CEILING:2' x 2' SUSPENDEDACOUSTICAL TILE
TYPE 3 CEILING:GYPSUM BOARD
2' x 2' LEDLIGHT FIXTURE
TYPE 4 CEILING:EXPOSED TOSTRUCTURE
AIR HANDLER
RECESSED CAN LIGHT
1t
1'-0"
101
CEILING TAG WITHHEIGHT
ROOM NUMBER
EXHAUST FAN
EXIT LIGHT
LINEAR LED LIGHTFIXTURE
CEILING UNIT HEATER
P PROJECTOR CEILINGMOUNT LOCATIONSOLID WALL INDICATES
WALL EXTENDS TO DECK
REFLECTED CEILING PLAN LEGEND
RECESSED DIRECTIONAL CAN LIGHT
RECESSED EMERGENCY CAN LIGHT
STRIP LIGHT
EXTERIOR LIGHT
TYPE 2 CEILING:PLASTER
PENDANT
SPRINKLER HEAD
A
G
1312
B
C
D
E
F
2
A400A101
BOOKSTORAGE
214
OPEN TOSTRUCTURE
A
G
1312
B
C
D
E
F
2
A400A101
BOOKSTORAGE
215
OPEN TOSTRUCTURE
North
Checked By:
Drawn By:
Date:
Project Number:
C Copyright 2018. All Rights Reserved. Reproduction, copying, or
use of this drawing and designs shown thereon without written
consent of Liollio Architecture, Inc. is prohibited and any
infringement is subject to legal action.
Revision Date Description
Scale:
NOT FORCONSTRUCTION
State Project Number:
SCALE:
147 Wappoo Creek DriveSuite 400Charleston, SC 29412
www.liollio.com
843.762.2222843.762.2300
H27-6119-LC
910 SUMTER STREETCOLUMBIA, SC 29208
1/8" = 1'-0"
1/8" = 1'-0"
UNIVERSITY OF SOUTH CAROLINA
17700
JMW
DRC
1/15/2018
SECOND FLOORREFLECTED CEILINGPLAN
A132
SOUTHCAROLINIANALIBRARYRENOVATION
SCALE:A132 1/8" = 1'-0"
1 SECOND FLOOR REFLECTED CEILING PLAN
2 40 168
1/15/2018 DD-OSE PHASE ONE SUBMITTAL
SCALE:A132 1/8" = 1'-0"
2 2.5 STACKS RCPSCALE:A132 1/8" = 1'-0"
3 2.75 STACKS RCP
21
-
7
A
G
1 132 3 4 5 6 8 9 10 11 12
B
C
D
E
F
H
1
A401A101
STAFFLOUNGE
305
HEADUSER
SERVICE
306
COLLABSTAFF
307
HALLWAYA
316
STAIR
300
STORAGE
303
FOYER
301
ACT
9' - 6"
ACT
9' - 6"
ACT
9' - 0"
MEZZA. A
310
GRADUATESWORKAREA
315A
MEZZAN. B
315B2
ROOFACCESS
311
STAIR
312
MECH
313
BOOKSTORAGE
314
CLOSET
304ACT
8' - 0"
OPEN TO ABOVE
OPEN TO STRUCTURE
OPEN TO ABOVE
OPEN TO STRUCTURE
OPEN TOSTRUCTURE
2
A401A101
2
A400A101
1
A400A101
EXISTING CEILING
REPAIR PLASTER
TYPE 1 CEILING:2' x 2' SUSPENDEDACOUSTICAL TILE
TYPE 3 CEILING:GYPSUM BOARD
2' x 2' LEDLIGHT FIXTURE
TYPE 4 CEILING:EXPOSED TOSTRUCTURE
AIR HANDLER
RECESSED CAN LIGHT
1t
1'-0"
101
CEILING TAG WITHHEIGHT
ROOM NUMBER
EXHAUST FAN
EXIT LIGHT
LINEAR LED LIGHTFIXTURE
CEILING UNIT HEATER
P PROJECTOR CEILINGMOUNT LOCATIONSOLID WALL INDICATES
WALL EXTENDS TO DECK
REFLECTED CEILING PLAN LEGEND
RECESSED DIRECTIONAL CAN LIGHT
RECESSED EMERGENCY CAN LIGHT
STRIP LIGHT
EXTERIOR LIGHT
TYPE 2 CEILING:PLASTER
PENDANT
SPRINKLER HEAD
1. THE INTENT OF THE RCP IS TO FAMILIARIZE THE CONTRACTOR WITH
THETOTAL CONCEPT. THE CONTRACTOR SHALL NOT USE THE RCP FOR
ESTIMATINGELECTRICAL AND MECHANICAL WORK. MECHANICAL-ELECTRICAL
DOCUMENTSTAKE PRECEDENCE OVER THE RCP.
2. ALL CEILING-MOUNTED DEVICES MAY NOT BE SHOWN. COORDINATE
THEWORK SHOWN ON THIS DRAWING WITH THE WORK OF ALL OTHER TRADES
ANDDISCIPLINES.
3. ROOMS WITH NO CEILINGS SHALL HAVE WALLS THAT EXTEND TO THE
DECK.ALL RATED WALLS SHALL TERMINATE AT BOTTOM OF DECK ABOVE. REFER
TOTHE LIFE SAFETY PLAN FOR RATED WALL CONDITIONS.
GENERAL NOTES - RCP
North
Checked By:
Drawn By:
Date:
Project Number:
C Copyright 2018. All Rights Reserved. Reproduction, copying, or
use of this drawing and designs shown thereon without written
consent of Liollio Architecture, Inc. is prohibited and any
infringement is subject to legal action.
Revision Date Description
Scale:
NOT FORCONSTRUCTION
State Project Number:
SCALE:
147 Wappoo Creek DriveSuite 400Charleston, SC 29412
www.liollio.com
843.762.2222843.762.2300
H27-6119-LC
910 SUMTER STREETCOLUMBIA, SC 29208
1/8" = 1'-0"
1/8" = 1'-0"
UNIVERSITY OF SOUTH CAROLINA
17700
JMW
DRC
1/15/2018
THIRD FLOORREFLECTED CEILINGPLAN
A133
SOUTHCAROLINIANALIBRARYRENOVATION
SCALE:A133 1/8" = 1'-0"
1 THIRD FLOOR REFLECTED CEILING PLAN
2 40 168
1/15/2018 DD-OSE PHASE ONE SUBMITTAL
22
-
1 Floor0' - 0"
2 Floor9' - 3 1/2"
2.5 Floor - Stacks17' - 3 1/2"
Existing Roof42' - 0 1/2"
Top of Parapet43' - 6 1/2"
2.75 Floor - Stacks24' - 8 1/2"
3.5 Floor - Stacks32' - 1 1/2"
GRADE-0' - 6"
01 02 0202 01 01
01
05
04 04
04
A A A AAAA
B B
BB B B B
B B
B
3TYP
A300 A500
MECHANICAL EQUIPMENT,SEE MECH DRAWINGS (TYP)
GENERATOR, SEEELECTRICAL
DRAWINGS (TYP)
1 Floor0' - 0"
2 Floor9' - 3 1/2"
3 Floor29' - 3 1/2"
Existing Roof42' - 0 1/2"
Top of Parapet43' - 6 1/2"
3 Floor - Balcony28' - 3 1/2"
GRADE-0' - 6"
04 04
01 02
B B B B B
AAA
BBB
MECHANICAL EQUIPMENT,SEE MECH DRAWINGS (TYP)
CRACKING AT GRANITE WINDOW SILL.
SHEET NOTES
CRACKING AT STUCCO WATER TABLE.
01
02
STEEL CORROSION03
CRAKCING AT STUCCO CORNICE.04
SPALLING BRICKS05
GENERAL NOTES
REFER TO D101 THRU D104 FOR ADDITIONAL DEMOLITION NOTESA
ALL WINDOWS TO RECEIVE UV WINDOW FILM ON #2 SUBSURFACE.B
SIGNIFIGANT CRACKING OCCURS AT THE STUCCO CORNICES AND WATER
TABLECOURSE ON ALL ELEVATIONS. PERFORM SOUNDING STUDY AND REMOVE
STUCCOWHERE THERE IS LOSS OF BOND OR OTHER SIGNS OF FAILURE.
PREPARESUBSTRATE BEYOND PRIOR TO PATCHING. LAB ANALYSIS WILL BE
REQUIRED TOIDENTIFY AND MATCH COMPOSITION OF EXISTING HISTORIC
STUCCO. MORE THANONE STUCCO MIX IS ANTICIPATED.
C
MASONRY SUBSTRATES TO BE THOROUGHLY WETTED BEFORE APPLICATION
OFSTUCCO PATCHES.
D
APPLY MINERAL COATING TO STUCCO AS COLOR COAT. COLORS TO BE
SELECTEDBY ARCHITECT.
E
EXTERIOR WOOD CORNICES AND OTHER TRIM SHOULD BE PREPPED
ANDPAINTED. ALL PREP TO BE PERFORMED WITH HAND TOOLS. NO
MOTORIZEDSANDERS OR SCRAPERS TO BE USED WHICH MIGHT DAMAGE THE
HISTORICMATERIALS.
G
WHERE CRACKING OCCURS AT GRANITE WINDOW SILLS, REPAIR USING
SPECIALTYJAHN MORTAR FORMULATION THAT MATCHES THE CHARACTERISTICS
OF STONE.
F
EXTERIOR WOOD DOORS AND FRAMES TO BE CLEANED, REPAIRED &
REPAINTED.SEE ADDITIONAL NOTES AND DETAILS ON SHEET A600.
H
ALL EXTERIOR STEEL WINDOWS TO BE CLEANED, REPAIRED, PRIMED
&REPAINTED. STEEL TO BE SCRAPED AND BRUSHED BY HAND AND
ALLSURFACE CORROSION TO BE REMOVED. REPAIR AREAS WHERE
SIGNIFIGANTCORROSION OCCURS OR HAS RUSTED ALL THE WAY THROUGH
WITHEPOXIES TO RECONSTITUTE THE ORIGINAL PROFILES. SEALANTS TO
BESTRIPPED OUT AND WINDOWS RESEALED WITH HIGH QUALITY
ELASTOMERICSEALANT. SEE ADDITIONAL NOTES AND DETAILS ON SHEET
A601.
I
REPOINT MASONRY FOR ENTIRE BUILDING. LAB ANALYSIS WILL BE
REQUIRED TOIDENTIFY AND MATCH COMPOSISTION OF EXISTING MORTAR. MORE
THAN ONEMORTAR TYPE IN ANTICIPATED. ALL PREP TO BE DONE MY HAND.
POWERTOOLS WHICH MAY DAMAGE THE HISTORIC MASONRY IS NOT
PERMITTED.
J
CRACK OCCURING
ELEVATION LEGEND
DAMAGE OVER LARGE AREA
Checked By:
Drawn By:
Date:
Project Number:
C Copyright 2018. All Rights Reserved. Reproduction, copying, or
use of this drawing and designs shown thereon without written
consent of Liollio Architecture, Inc. is prohibited and any
infringement is subject to legal action.
Revision Date Description
Scale:
NOT FORCONSTRUCTION
State Project Number:
SCALE:
147 Wappoo Creek DriveSuite 400Charleston, SC 29412
www.liollio.com
843.762.2222843.762.2300
H27-6119-LC
910 SUMTER STREETCOLUMBIA, SC 29208
1/8" = 1'-0"
1/8" = 1'-0"
UNIVERSITY OF SOUTH CAROLINA
17700
JMW
ACD
1/15/2018
BUILDINGELEVATIONS
A300
SOUTHCAROLINIANALIBRARYRENOVATION
SCALE:A300 1/8" = 1'-0"
1 BUILDING ELEVATION - SOUTH
SCALE:A300 1/8" = 1'-0"
2 BUILDING ELEVATION - WEST2 40 168
1/15/2018 DD-OSE PHASE ONE SUBMITTAL
23
-
1 Floor0' - 0"
2 Floor9' - 3 1/2"
2.5 Floor - Stacks17' - 3 1/2"
Existing Roof42' - 0 1/2"
Top of Parapet43' - 6 1/2"
2.75 Floor - Stacks24' - 8 1/2"
3.5 Floor - Stacks32' - 1 1/2"
GRADE-0' - 6"
0404
E E E E E E E EF
E E E E F E E E E
E E E E F E E E E
EEEEFEEEE
E E E E E E E EF
MECHANICAL EQUIPMENT, SEEMECH DRAWINGS (TYP)
1 Floor0' - 0"
2 Floor9' - 3 1/2"
3 Floor29' - 3 1/2"
Existing Roof42' - 0 1/2"
Top of Parapet43' - 6 1/2"
3 Floor - Balcony28' - 3 1/2"
GRADE-0' - 6"
04
04 04
05
01
0202
01
02
BB BBB B
AA
D
AA
BBBB
C
2
A301 A500
TYPMECHANICAL EQUIPMENT,SEE MECH DRAWINGS (TYP)
ROOF HATCH (TYP)
GENERATOR, SEEELECTRICAL DRAWINGS (TYP)
CRACK OCCURING
ELEVATION LEGEND
DAMAGE OVER LARGE AREA
GENERAL NOTES
REFER TO D101 THRU D104 FOR ADDITIONAL DEMOLITION NOTESA
ALL WINDOWS TO RECEIVE UV WINDOW FILM ON #2 SUBSURFACE.B
SIGNIFIGANT CRACKING OCCURS AT THE STUCCO CORNICES AND WATER
TABLECOURSE ON ALL ELEVATIONS. PERFORM SOUNDING STUDY AND REMOVE
STUCCOWHERE THERE IS LOSS OF BOND OR OTHER SIGNS OF FAILURE.
PREPARESUBSTRATE BEYOND PRIOR TO PATCHING. LAB ANALYSIS WILL BE
REQUIRED TOIDENTIFY AND MATCH COMPOSITION OF EXISTING HISTORIC
STUCCO. MORE THANONE STUCCO MIX IS ANTICIPATED.
C
MASONRY SUBSTRATES TO BE THOROUGHLY WETTED BEFORE APPLICATION
OFSTUCCO PATCHES.
D
APPLY MINERAL COATING TO STUCCO AS COLOR COAT. COLORS TO BE
SELECTEDBY ARCHITECT.
E
EXTERIOR WOOD CORNICES AND OTHER TRIM SHOULD BE PREPPED
ANDPAINTED. ALL PREP TO BE PERFORMED WITH HAND TOOLS. NO
MOTORIZEDSANDERS OR SCRAPERS TO BE USED WHICH MIGHT DAMAGE THE
HISTORICMATERIALS.
G
WHERE CRACKING OCCURS AT GRANITE WINDOW SILLS, REPAIR USING
SPECIALTYJAHN MORTAR FORMULATION THAT MATCHES THE CHARACTERISTICS
OF STONE.
F
EXTERIOR WOOD DOORS AND FRAMES TO BE CLEANED, REPAIRED &
REPAINTED.SEE ADDITIONAL NOTES AND DETAILS ON SHEET A600.
H
ALL EXTERIOR STEEL WINDOWS TO BE CLEANED, REPAIRED, PRIMED
&REPAINTED. STEEL TO BE SCRAPED AND BRUSHED BY HAND AND
ALLSURFACE CORROSION TO BE REMOVED. REPAIR AREAS WHERE
SIGNIFIGANTCORROSION OCCURS OR HAS RUSTED ALL THE WAY THROUGH
WITHEPOXIES TO RECONSTITUTE THE ORIGINAL PROFILES. SEALANTS TO
BESTRIPPED OUT AND WINDOWS RESEALED WITH HIGH QUALITY
ELASTOMERICSEALANT. SEE ADDITIONAL NOTES AND DETAILS ON SHEET
A601.
I
REPOINT MASONRY FOR ENTIRE BUILDING. LAB ANALYSIS WILL BE
REQUIRED TOIDENTIFY AND MATCH COMPOSISTION OF EXISTING MORTAR. MORE
THAN ONEMORTAR TYPE IN ANTICIPATED. ALL PREP TO BE DONE MY HAND.
POWERTOOLS WHICH MAY DAMAGE THE HISTORIC MASONRY IS NOT
PERMITTED.
J
CRACKING AT GRANITE WINDOW SILL.
SHEET NOTES
CRACKING AT STUCCO WATER TABLE.
01
02
STEEL CORROSION03
CRAKCING AT STUCCO CORNICE.04
SPALLING BRICKS05
Checked By:
Drawn By:
Date:
Project Number:
C Copyright 2018. All Rights Reserved. Reproduction, copying, or
use of this drawing and designs shown thereon without written
consent of Liollio Architecture, Inc. is prohibited and any
infringement is subject to legal action.
Revision Date Description
Scale:
NOT FORCONSTRUCTION
State Project Number:
SCALE:
147 Wappoo Creek DriveSuite 400Charleston, SC 29412
www.liollio.com
843.762.2222843.762.2300
H27-6119-LC
910 SUMTER STREETCOLUMBIA, SC 29208
1/8" = 1'-0"
1/8" = 1'-0"
UNIVERSITY OF SOUTH CAROLINA
17700
JMW
DRC / ACD
1/15/2018
BUILDINGELEVATIONS
A301
SOUTHCAROLINIANALIBRARYRENOVATION
SCALE:A301 1/8" = 1'-0"
1 BUILDING ELEVATION - EAST
SCALE:A301 1/8" = 1'-0"
2 BUILDING ELEVATION - NORTH
2 40 168
1/15/2018 DD-OSE PHASE ONE SUBMITTAL
24
-
1S301
TEMPORARY SHORING TO THEGROUND AS REQUIRED FORTRUSS SUPPORT AND
ACCESS
NEW FRAMING FOR EXISTING MONITORS, 2LAYERS OF 1/4 INCH PLYWOOD
SHEETS 4FEET BY 8 FEET, WARPED AROUND EXISTINGMONITOR FRAMING,
ATTACH WITH SCREWS AT6 INCHES E.W. SUPPORTED ON 2 - 2 X 10SPANNING
BETWEEN TRUSSES
NEW LVL SISTERS ON EXISTINGPURLINS, MATCH DEPTH ANDSUPPORT ON
JOIST HANGERSFABRICATED FROM 3/16 INCH PLATES.
LIFT EXISTING TRUSSES AND MONITORS, 2TRUSSES AT A TIME. SISTER
TRUSSES AND
SUPPORT MONITORS ON NEW FRAMING.THEN LOWER TRUSSES.
NEW LVL SISTERS FOREVERY MEMBER, 1.75 X 12
ON BOTH SIDES.
NEW STRAPS AT EXISTINGMEMBER ENDS
3S501
PL 1/4 X 8, HOT-DIPPED GALVANIZED, TYPICAL,PREPUNCHED WITH 3/8
INCH DIAMETER HOLES
AT 3 INCHES O/C BOTH WAYS.
Checked By:Drawn By:Date:
Project Number:
C Copyright 2017. All Rights Reserved. Reproduction, copying, or
use of this drawing and designs shown thereon without written
consent of Liollio Architecture, Inc. is prohibited and any
infringement is subject to legal action.
Revision Date Description
Scale:
SHEET NOTES
NOT FORCONSTRUCTION
State Project Number:
SCALE:
147 Wappoo Creek DriveSuite 400Charleston, SC 29412
www.liollio.com
843.762.2222843.762.2300
H27-6119-LC
As indicated
As indicated
UNIVERSITY OF SOUTH CAROLINA
910 SUMTER STREETCOLUMBIA, SC 29208
16-029CMBTFC, JSB1/15/2018
TRUSS FRAMINGS301
SOUTHCAROLINIANALIBRARYRENOVATION
1/16" = 1'-0"KEYPLAN ROOF
1/2" = 1'-0"1TYPICAL TRUSS ELEVATION
1/15/2018 DD-OSE PHASE ONE SUBMITTAL
25
-
7
A
G
1 132 3 4 5 6 8 9 10 11 12
4.1 6.1 7.1 9.1
B
C
D
E
F
H
ANTE/CONFERENCE
104
ARCHIVALVAULT
105
MECHANICALROOM
108
EXHIBITS
101
LUMPKINFOYER
100
DIRECTORCONFERENCE
ROOM
122
LIBRARYDIRECTOR
121
ELECTRICAL
116
ADMINSTRATOR
115
MECHANICALROOM
118
CORRIDOR
112
STAIR
117
ELEVATOR
109
CORRIDOR
106
MENS
113
WOMENS
114
STORAGE
103
STAIR
102
BOOKSTORAGE
119
CORRID.
107
STORAGE
120
IT CLOSET
110
STAIR
111
PROTECTED BY
CLEAN AGENT
SYSTEM
FS001
3
2 1/2" DRAIN RISER UP4" SPRINKLER RISER UP WITH SPRINKLERFLOW
CONTROL STATION
4" SUPPLY RISER UP
PREACTION VALVE ANDRISER WITH SUPERVISED
CONTROL VALVE
SIDEWALL SPRINKLER IN ELEVATOR PIT
PEDESTAL FIREDEPARTMENTCONNECTION
North
Checked By:
Drawn By:
Date:
Project Number:
C Copyright 2017. All Rights Reserved. Reproduction, copying, or
use of this drawing and designs shown thereon without written
consent of Liollio Architecture, Inc. is prohibited and any
infringement is subject to legal action.
Revision Date Description
Scale:
SHEET NOTES
NOT FORCONSTRUCTION
State Project Number:
147 Wappoo Creek DriveSuite 400Charleston, SC 29412
www.liollio.com
843.762.2222843.762.2300
H27-6119-LC
UNIVERSITY OF SOUTH CAROLINA
Enter address here
17700
JOB
SRB
1/15/2018
FIRST FLOORSPRINKLER PLAN
FS101
SOUTHCAROLINIANALIBRARYRENOVATION
0' 4' 8' 16' 32'
SCALE:FS101 1/8" = 1'-0"
1 FIRST FLOOR SPRINKLER PLAN
SPRINKLER LEGEND - LEVEL 1
COUNT SYSMBOL MANUFACTURER & MODEL DESCRIPTION SIZE K-FACTOR
TEMPERATURE COVERAGE COLOR
30 TYCO TY313 (OR EQUAL) Q.R. UPRIGHT 1/2" 5.6 155 °F Standard
BRASS
1 TYCO TY331 (OR EQUAL) RECESS Q.R. SIDEWALL 1/2" 5.6 155 °F
Standard WHITE
39 TYCO TY3531 (OR EQUAL) CONCEALED PENDENT 1/2" 5.6 155 °F
Standard WHITE
TOTAL HEADS: 70
1 1/15/2018 DD-OSE PHASE ONE SUBMITTAL
26
-
7
A
G
1 132 3 4 5 6 8 9 10 11 12
4.1 6.1 7.1 9.1
B
C
D
E
F
H
KENDALLROOM
202
BULFINCHREADING
ROOM
201
STAIR
200
STAIR
211 MECH
212
BOOKSTORAGE
213
STORAGE
209
FOYER
210
FOYER
203
CORRIDOR
204
STAIR
205
STORAGE
206
ELEVATOR
207
STAIR
208
OPEN TO ABOVE
2 1/2" DRAIN RISER UP&DN4" SPRINKLER RISER UP&DN WITH
SPRINKLERFLOW CONTROL STATION
4" SUPPLY RISER UP&DN
PREACTION RISER
A/S RISER UP TOTHIRD LEVEL
North
Checked By:
Drawn By:
Date:
Project Number:
C Copyright 2017. All Rights Reserved. Reproduction, copying, or
use of this drawing and designs shown thereon without written
consent of Liollio Architecture, Inc. is prohibited and any
infringement is subject to legal action.
Revision Date Description
Scale:
SHEET NOTES
NOT FORCONSTRUCTION
State Project Number:
147 Wappoo Creek DriveSuite 400Charleston, SC 29412
www.liollio.com
843.762.2222843.762.2300
H27-6119-LC
UNIVERSITY OF SOUTH CAROLINA
Enter address here
17700
JOB
SRB
1/15/2018
SECOND FLOORSPRINKLER PLAN
FS102
SOUTHCAROLINIANALIBRARYRENOVATION
0' 4' 8' 16' 32'
SCALE:FS102 1/8" = 1'-0"
1 SECOND FLOOR SPRINKLER PLAN
SPRINKLER LEGEND - LEVEL 2
COUNT SYSMBOL MANUFACTURER & MODEL DESCRIPTION SIZE K-FACTOR
TEMPERATURE COVERAGE COLOR
30 TYCO TY313 (OR EQUAL) Q.R. UPRIGHT 1/2" 5.6 155 °F Standard
BRASS
25 TYCO TY3531 (OR EQUAL) CONCEALED PENDENT 1/2" 5.6 155 °F
Standard WHITE
TOTAL HEADS: 55
1 1/15/2018 DD-OSE PHASE ONE SUBMITTAL
27
-
7
A
G
1 132 3 4 5 6 8 9 10 11 12
4.1 6.1 7.1 9.1
B
C
D
E
F
H
COLLABSTAFF
307
HEADUSER
SERVICE
306
STAFFLOUNGE
305
BOOKSTORAGE
314
CLOSET
304
ELEV
302
STORAGE
303
STAIR
300
ROOFACCESS
311
STAIR
312
MECH
313
MEZZA. A
310
MEZZAN. B
315B2
FOYER
301
HALLWAYA
316
GRADUATESWORKAREA
315A
MEZZANINE
315B1
OPEN TO BELOW
SEE SHEET FS104
DETAIL 3 FOR
SPRINKLER LAYOUT
2 1/2" DRAIN RISER DN4" SPRINKLER RISER DN
4" SUPPLY RISER DN
PREACTION RISER
A/S RISER DN TOSECOND LEVEL
North
Checked By:
Drawn By:
Date:
Project Number:
C Copyright 2017. All Rights Reserved. Reproduction, copying, or
use of this drawing and designs shown thereon without written
consent of Liollio Architecture, Inc. is prohibited and any
infringement is subject to legal action.
Revision Date Description
Scale:
SHEET NOTES
NOT FORCONSTRUCTION
State Project Number:
147 Wappoo Creek DriveSuite 400Charleston, SC 29412
www.liollio.com
843.762.2222843.762.2300
H27-6119-LC
UNIVERSITY OF SOUTH CAROLINA
Enter address here
17700
JOB
SRB
1/15/2018
THIRD FLOORSPRINKLER PLAN
FS103
SOUTHCAROLINIANALIBRARYRENOVATION
0' 4' 8' 16' 32'
SCALE:FS103 1/8" = 1'-0"
1 THIRD FLOOR SPRINKLER PLAN
SPRINKLER LEGEND - LEVEL 3
COUNT SYSMBOL MANUFACTURER & MODEL DESCRIPTION SIZE K-FACTOR
TEMPERATURE COVERAGE COLOR
10 TYCO TY313 (OR EQUAL) Q.R. UPRIGHT 1/2" 5.6 155 °F Standard
BRASS
3 TYCO TY331 (OR EQUAL) RECESS Q.R. SIDEWALL 1/2" 5.6 155 °F
Standard WHITE
57 TYCO TY3531 (OR EQUAL) CONCEALED PENDENT 1/2" 5.6 155 °F
Standard WHITE
TOTAL HEADS: 70
1 1/15/2018 DD-OSE PHASE ONE SUBMITTAL
28