4 3 “Optional Manual One-Button” Push and “Hold” a Button to operate Strike Open Push Button Strike Open Push Button 24 Volts DC 24 Volts DC Fire Dept Key Switch Fire Dept Key Switch M/S Link M/S Link Class 2 Supply Class 2 Supply Center Loop Center Loop Safety Loop Safety Loop Radio Receiver Radio Receiver Exit Loop Exit Loop G B A + OmniControl Surge Suppressor P/N Q410 Patent Pending P/N Q410 Patent Pending CENTER SAFETY EXIT CENTER SAFETY EXIT FIRE DEPT. 1 3 STRIKE OPEN RADIO RECEIVER TIMER SYSTEM ON EXIT LOOP ALARM SENSOR REVERSE SENSOR OPEN STOP CLOSE SAFETY LOOP CENTER LOOP GATE LOCKED 60 POWER OVERLOAD OFF W4 OPEN LEFT DC-BACKUP ALARM SENSOR OPEN RIGHT 3 SENSORS RESET MOTOR 1 3 1 3 COMMAND PROCESSED ON G B MS LINK A MADE IN USA OFF ON CHASSIS GROUND 12 13 11 CAUTION Black 120 Vac White Neutral Green Ground If the DC2000 is automatically opening the gate due to a power failure, any manual command such as “Manual One-Button”, “Three Push Button”, “Key Switch”, “Photocell” or “Edge Sensor” will cancel the automatic mode of the DC2000. After such cancellation, the DC2000 will continue to operate in manual mode until 115 Vac power is restored. “Manual” setting: The DC2000 will respond to the input devices wired to the J 20 socket. This mode can also be used as an emergency override. If 115 Vac power is on, but the system has an electronic malfunction, the gate can be operated using the DC2000 system with input devices wired to J 20 socket. “Auto” setting: The DC2000 opens the gate automatically upon 115 Vac power failure and stays open. When 115 Vac power is restored, the gate operator will return to normal operation. (The gate can be closed by manual command) System Setup Manual Mode Auto Mode Push and Hold to operate gate 115 Vac Power Failure 115 Vac Power On, OmniControl™ Board Malfunction 115 Vac Power On, Emergency Override Gate automatically opens Turn the 115 Vac power off then push and Hold to operate gate Push and Hold to override the OmniControl™ board Push and Hold to override the OmniControl™ board Turn the 115 Vac power off then gate opens automatically DO NOT wire 115 Vac power to the DC2000 DC2000 Harness W4 OFF ON DC2000 Back-Up Wiring for the OmniControl™ Board with Optional Equipment DC2000 Back-Up Wiring for the OmniControl™ Board with Optional Equipment 1 3 2 7 6 5 4 “Optional Radio Receiver” “Optional Key Switch” OmniControl™ Board Sensor Connection Push and “Hold” to Open Push again and “Hold” to Close Turn and “Hold” to Open Turn again and “Hold” to Close POWER OVERLOAD DC-BACKUP ALARM SENSOR 1 3 2 4 5 N.O. N.O. N.O. USE ONLY 12 VDC FAILSAFE PHOTO ELECTRIC SENSORS FOR THIS SAFETY OPTION Failsafe Photo Electric Sensor: If a photo electric sensor is not working, loses power or the beam is blocked, then the photo electric sensor will stop all gate operation. “Optional Photo Electric Sensor” 12 VDC “Optional Edge Sensor” 6 4 Com Com Com 4 5 SAFETY OPTIONS Factory Installed Stop/Reset Button Power +12 VDC Power Ground Part # AEXITP AEXITP Part # A1KX A1KX Part # 312HM 312HM Part # 02-103 02-103 Part # 373LM 373LM Part # AOMRON12V AOMRON12V Part #s G65MGO20 G65MGR20 G65MGS20 G65MGO20 G65MGR20 G65MGS20 4 4 4 If 115 Vac power is on, but the system has an electronic malfunction, the gate can be operated using the DC2000 system with ANY of these optional devices shown. EMERGENCY OVERRIDE J5 POWER OVERLOAD DC-BACKUP ALARM SENSOR DC2000 Harness Red Wire White Wire J5 Green and Purple wires wrap behind board to the limit switches Audio Alarm Wires DO NOT remove existing wires from the audio alarm or secondary protection sensor. OPEN CLOSE Jumper P3: to 12 Volt Jumper P2: to Constant (C) Refer to Receiver Manual for Further Details about settings. Button One: Normal Gate Operation Only (OmniControl™ Board) Button One: Normal Gate Operation Only (OmniControl™ Board) Button Two: Back-Up Operation ONLY (DC2000) Button Three: Optional Accessories Push and “Hold” DC2000 Transmitter Button to Open Push again and “Hold” DC2000 Transmitter Button to Close Radio Receiver + Factory installed Stop/Reset Button Wires to J20 Socket Stop/Reset Button Wire Cut and Discard Plug To Limit Switches Radio Receiver - 13 11 11 1 2 3 11 11 13 12 4 12 For Technical Support and Ordering Parts: 1-800-528-2806 CAUTION Black 120 Vac White Neutral Green Ground 3 4 “Optional Three-Button” 6 4 5 1 2 3 4 4 Socket All devices wired to the DC2000 MUST be dedicated to it alone. Normal operation will be controlled by separate devices wired to the OmniControl™ board. Important: Separate 12 VDC DC2000 Radio Receiver 24 VDC Factory Installed Radio Receiver WARNING: This product can expose you to chemicals including lead, which are known to the State of California to cause cancer or birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
2
Embed
DC20000 LiftMaster Back-Up Wiring for the OmniControl ... · DC2000 Back-Up Installation for CSW200UL™ modelsfor CSW200UL™ models STEP 1 STEP 2 STEP 3 STEP 4 Single Motor Step-by-Step
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
43
“Optional Manual One-Button”
Push and “Hold” a Button to operate
Strike OpenPush ButtonStrike OpenPush Button 24 Volts DC24 Volts DC
If the DC2000 is automatically opening the gate due to a power failure, any manual command such as “Manual One-Button”, “Three Push Button”, “Key Switch”, “Photocell” or “Edge Sensor” will cancel the automatic mode of the DC2000. After such cancellation, the DC2000 will continue to operate in manual mode until 115 Vac power is restored.
“Manual” setting: The DC2000 will respond to the input devices wired to the J 20 socket.
This mode can also be used as an emergency override. If 115 Vac power is on, but the system has an electronic malfunction, the gate can be operated using the DC2000 system with input devices wired to J 20 socket.
“Auto” setting: The DC2000 opens the gate automatically upon 115 Vac power failure and stays open. When 115 Vac power is restored, the gate operator will return to normal operation. (The gate can be closed by manual command)
System Setup
Manual Mode Auto Mode
Push and Hold to operate gate
115 Vac Power Failure
115 Vac Power On, OmniControl™ Board Malfunction
115 Vac Power On, Emergency Override
Gate automatically opens
Turn the 115 Vac power off then push and Hold to operate gate
Push and Hold to override the OmniControl™ board
Push and Hold to override the OmniControl™ board
Turn the 115 Vac power off then gate opens automatically
DO NOT wire 115 Vac power to the DC2000
DC2000 Harness
W4
OFF ON
DC2000 Back-Up Wiring for the OmniControl™ Board with Optional EquipmentDC2000 Back-Up Wiring for the OmniControl™ Board with Optional Equipment
1 327654
“Optional Radio Receiver”
“Optional Key Switch”
OmniControl™ Board Sensor Connection
Push and “Hold” to OpenPush again and “Hold” to Close
Turn and “Hold” to Open
Turn again and “Hold” to Close
POWEROVERLOAD
DC-BACKUP
ALAR
MSEN
SOR
1
3
2
4 5
N.O.
N.O.
N.O.
USE ONLY 12 VDC FAILSAFE PHOTO ELECTRIC SENSORS FOR THIS SAFETY
OPTION
Failsafe Photo Electric Sensor: If a photo electric sensor is not working, loses power or the beam is blocked, then the photo electric sensor will stop all gate operation.
“Optional Photo Electric Sensor” 12 VDC
“Optional Edge Sensor”
64
Com
Com
Com
45
SAFETY OPTIONS
Factory InstalledStop/Reset Button
Power +12 VDC
Power Ground
Part # AEXITPAEXITP
Part # A1KXA1KX
Part # 312HM312HM
Part # 02-10302-103
Part # 373LM373LM
Part # AOMRON12VAOMRON12V
Part #s G65MGO20G65MGR20G65MGS20
G65MGO20G65MGR20G65MGS20
4
4
4
If 115 Vac power is on, but the system has an electronic malfunction, the gate can be operated using the DC2000 system with ANY of these optional devices shown.
EMERGENCYOVERRIDE
J5
POWEROVERLOAD
DC-BACKUP
ALARM
SENSO
R
DC2000 Harness
Red Wire
White WireJ5
Green and Purple wires wrap behind board to the limit switches
Audio AlarmWires
DO NOT remove existing wires from the audio alarm or secondary protection sensor.
OPEN CLOSE
Jumper P3:to 12 Volt
Jumper P2:to Constant (C)
Refer to ReceiverManual for FurtherDetails about settings.
Button One:Normal Gate
Operation Only(OmniControl™ Board)
Button One:Normal Gate Operation Only
(OmniControl™ Board)
Button Two:Back-Up Operation
ONLY (DC2000)
Button Three:Optional
Accessories
Push and “Hold” DC2000 Transmitter Button to Open
Push again and “Hold” DC2000 Transmitter Button to Close
Radio Receiver +
Factory installedStop/Reset ButtonWires to J20 Socket
Stop/Reset Button Wire
Cut and Discard Plug
To Limit Switches
Radio Receiver -
13
11
11
123
11
11 13
12
412
For Technical Supportand Ordering Parts:1-800-528-2806
CA
UT
ION
Bla
ck 1
20 V
ac
Wh
ite N
eu
tral
Gre
en
Gro
un
d
3 4
“Optional Three-Button”
64 5
123
4
4
Socket
All devices wired to the DC2000 MUST be dedicated to it alone. Normal operation will be controlled by separate devices wired to the OmniControl™ board.
Important:
Separate 12 VDC
DC2000 Radio Receiver
24 VDC
Factory Installed
Radio Receiver
WARNING: This product can expose you to chemicals including lead, which are known to the State of California to cause cancer or birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
DC2000 Back-Up Installation for CSW200UL™ modelsDC2000 Back-Up Installation for CSW200UL™ models
STEP 1 STEP 2 STEP 3 STEP 4
Single Motor Step-by-Step DC2000 Installation
Remove existing belt.
Bolt the DC2000 plate securely to the lower gearbox.
W4
OFF ON
STEP 7
Bolt the DC motor to the plate but do not tighten it.
Install the 4L 240 belt provided. Make sure that all the pulleys are aligned.
Pull the DC motor to adjust the belt tension and tighten the bolts to secure the motor.
Connect the DC motor wires to the DC2000 control unit wires.
Remove the OmniControl™ board from the electrical box.
Feed DC2000 harness down behind electrical box. Then feed harness up through hole in bottom of electrical box.
Feed green, purple and Stop/Reset button wires through the top back hole of electrical box.
OFF ON
W4
STEP 6STEP 5
W4
OFF ON
W4
OFF ON
Top View of Limit Switches
PurpleOrange
Yellow
GreenRed
Brown
NC12
3NOCOM
NC1 2
3 NO
COM
Reinstall the OmniControl™ board and make sure that the green,purple and Stop/Reset button wires do not get pinched by the board.
Cut plug off and strip wires from Stop/Reset Button wire. Insert Red wire in J20 socket 3 and Black wire into socket 4.
Plug in the DC2000 harness in the DC-BackUp J5 slot on the OmniControl™ board.
Connect the red wire from the DC2000 harness into the top slot of the audio alarm plug. (DO NOT remove audio alarm wires)
Connect the white wire from the DC2000 harness into the bottom slot of the sensor plug.
Connect the purple and green wires to limit switches as shown.
Make sure the brown wire is in the “Common” connector on the limit switch.
Do not over tighten belt
Disconnect POWER!
B
C
A
B
A
B
A
A
B
C
A
B
C
D
E
A
A
B
C
D
D
A
A
B
C
Plug the 12 pin connector into the DC2000 control unit. Make sure the “System ON” and “Charge OK” LEDs are lit. If the “Battery Low” led comes on, the battery needs to charge before it can be used.
Set the gate direction switch the same as the gate operator is set. (Open left or Open right)
Select your mode of operation for the DC2000 unit. (Automatic open or Manual open, see back page.)
Permanently wire optional controls according to label on control unit. (See back page)
Adjust the sensitivity for the reverse sensor.
E
C
B C
B
BA
A
B
C
D
E
B
A A
Use 4L 240 Belt
D
1 327654
B
DiscardPlug
Place and secure the DC2000 control unit as shown.
Insert the plastic “snap bushing” provided into chassis hole.
Feed the black and red wires from the DC2000 through plastic bushing.
Reconnect POWER!
J5
POWEROVERLOAD
DC-BACKUP
ALAR
MSEN
SOR
D
E
A
C
B
CDC2000
Mounting HoleUse ONLY
WARNING!
Battery
Longer bolt WILL result in DC2000 battery damage!
long bolt ( x 20)12"/ 1
4"/
Red to Red and Black to Black
Caution!
STEP 3 STEP 4STEP 2STEP 1
W4
OFF ON
STEP 7
Place and secure the DC2000 control unit as shown
Feed the black and red wires from the DC2000 behind the electrical box and through the lower chassis hole with the plastic bushing in it.
STEP 6STEP 5
Twin Motors Step-by-Step DC2000 Installation
Disconnect POWER!
Remove existing belt.
Bolt the DC2000 plate to the operator. Do not
tighten bolts. Adjustment is required in Step 3.
Insert the plastic “snap b u s h i n g ” provided into chassis hole.
Bolt the DC motor to the plate.
Install the 4L 300 belt provided. Make sure that all the pulleys are aligned.
Pull the DC motor plate to adjust the belt tension and tighten the bolts to secure the plate.
Connect the DC motor wires to the DC2000 control unit wires.
Remove the OmniControl™ board from the electrical box.
Feed DC2000 harness down behind electrical box. Then feed harness up through hole in bottom of electrical box.
Feed green, purple and Stop/Reset button wires through the top back hole of electrical box.
OFF ON
W4
A
A
B
C
B C
B
W4
OFF ON
W4
OFF ON
Top View of Limit Switches
PurpleOrange
Yellow
GreenRed
Brown
NC12
3NOCOM
NC1 2
3 NO
COM
Reinstall the OmniControl™ board and make sure that the green,purple and Stop/Reset button wires do not get pinched by the board.
Cut plug off and strip wires from Stop/Reset Button wire. Insert Red wire in J20 socket 3 and Black wire into socket 4.
Plug in the DC2000 harness in the DC-BackUp J5 slot on the OmniControl™ board.
Connect the red wire from the DC2000 harness into the top slot of the audio alarm plug. (DO NOT remove audio alarm wires)
Connect the white wire from the DC2000 harness into the bottom slot of the sensor plug.
Connect the purple and green wires to limit switches as shown.
Make sure the brown wire is in the “Common” connector on the limit switch.
A
B
A
B
C
D
E
Plug the 12 pin connector into the DC2000 control unit. Make sure the “System ON” and “Charge OK” LEDs are lit. If the “Battery Low” led comes on, the battery needs to charge before it can be used.
Set the gate direction switch the same as the gate operator is set. (Open left or Open right)
Select your mode of operation for the DC2000 unit. (Automatic open or Manual open, see back page.)
Permanently wire optional controls according to label on control unit. (See back page)
Adjust the sensitivity for the reverse sensor.
E
C
BA
A
B
C
D
E
B
A A
D
1 327654
B
DiscardPlug
Reconnect POWER!
Caution!
J5
POWEROVERLOAD
DC-BACKUP
ALAR
MSEN
SOR
D
E
A
C
Red to Black and Black to Red
Mot
or
Mot
or
A
Mot
or
B
300 Windsor Dr, Oak Brook, IL 60523www.liftmaster.com