Top Banner
Features Ease of Installation 23" Cabinet Each system contains up to twenty four 50A rectifiers pro- viding 1200A. Rectifiers are mounted four across in six 4U shelves SNMP interface Battery Temperature Compensation Power Factor Corrected Rectifiers Flexible Output Distribution built in: 1-100 Amp Small Circuit Breakers 100-700 Amp Large Circuit Breakers 70-600 Amp Large Fuses Output Distribution Bays with: 100-700 Amp Large Circuit Breakers 70-600 Amp Large Fuses built in Current metering on large distribution bays Typical Applications Cellular and PCS Distributed Networks IXC (Inter Exchange Carrier) ISP Telehouse Broadband Wireless Fiber Industry Approvals Safety: UL 1950 EMC: Complies with FCC Part 15 Subpart J, Class A NEBS Pending Warranty The MX28B1200/4800 is under warranty against faulty manufac- ture and faulty components for a period of two years from the date of delivery. Please refer to condi- tions of sale for full details. We reserve the right to amend specifi- cations without prior notification. DC Series MX28B1200/4800 Modular, scalable DC power plant for large- sized wireless/cellular, co-location, cable and telecommunications applications APC’s MX28B1200/4800 system is an easily installed 23" compatible modular stand-alone power plant capable of supplying multiples of 1200A at -48V DC. Configurable options allow the user to tailor the system for specific high integrity power requirements. The system can be configured with up to 24 x 50A rectifiers per bay with up to 4 bays. A Low Voltage Disconnect (LVD) can be supplied on either battery or load side. No LVD is also an option. A single master control unit in the first power system provides control and monitoring for the entire system. The MX28B1200 can be expanded to 4800 amps with the addition of expansion bays. System Options 125 - 700 Amp circuit breaker Temperature Probe LVD 70 - 600 Amp fuse option NEW! Now available with 480V input
2

DC Series MX28B1200/4800 - Terms and Conditions - 700 Amp circuit breaker Temperature Probe LVD 70 - 600 Amp fuse option NEW! Now available with 480V input An optional 48 position

Mar 15, 2018

Download

Documents

trinhanh
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: DC Series MX28B1200/4800 - Terms and Conditions - 700 Amp circuit breaker Temperature Probe LVD 70 - 600 Amp fuse option NEW! Now available with 480V input An optional 48 position

Features� Ease of Installation

� 23" Cabinet

� Each system contains up totwenty four 50A rectifiers pro-viding 1200A. Rectifiers aremounted four across in six4U shelves

� SNMP interface

� Battery TemperatureCompensation

� Power Factor CorrectedRectifiers

� Flexible Output Distributionbuilt in:1-100 Amp Small CircuitBreakers100-700 Amp Large CircuitBreakers70-600 Amp Large Fuses

� Output Distribution Bays with:100-700 Amp Large CircuitBreakers70-600 Amp Large Fusesbuilt in

� Current metering on large

distribution bays

Typical Applications� Cellular and PCS

� Distributed Networks

� IXC (Inter Exchange Carrier)

� ISP

� Telehouse

� Broadband Wireless

� Fiber

Industry Approvals� Safety: UL 1950

� EMC: Complies with FCC Part

15 Subpart J, Class A

� NEBS Pending

Warranty

The MX28B1200/4800 is underwarranty against faulty manufac-ture and faulty components for aperiod of two years from the dateof delivery. Please refer to condi-tions of sale for full details. Wereserve the right to amend specifi-cations without prior notification.

DC SeriesMX28B1200/4800Modular, scalable DC power plant for large-sized wireless/cellular, co-location, cable andtelecommunications applications

APC’s MX28B1200/4800 system is an easily installed 23" compatible modular stand-alone power plantcapable of supplying multiples of 1200A at -48V DC. Configurableoptions allow the user to tailor thesystem for specific high integritypower requirements. The system canbe configured with up to 24 x 50Arectifiers per bay with up to 4 bays.

A Low Voltage Disconnect (LVD) canbe supplied on either battery or load side. No LVD is also an option.

A single master control unit in thefirst power system provides controland monitoring for the entire system.

The MX28B1200 can be expandedto 4800 amps with the addition ofexpansion bays.

System Options� 125 - 700 Amp circuit breaker

� Temperature Probe

� LVD

� 70 - 600 Amp fuse option

N E W !Now available with

480V input

Page 2: DC Series MX28B1200/4800 - Terms and Conditions - 700 Amp circuit breaker Temperature Probe LVD 70 - 600 Amp fuse option NEW! Now available with 480V input An optional 48 position

An optional 48 position plug-in breaker tier provides -48V distribution. Connections for -48 Vdc loads, requiring standard #10-32 two-hole lugs on 5/8"centers, are located directly above the corresponding breaker. Alternative option panels include mounted circuit breakers for 250A to 700A range and70-600 amp large fuse holders. Optional large fuse and large circuit breaker bays are available

Weight 775 lbs. (352 kg)

Mechanical

Color Dawn Gray

Dimensions 23" rack - 26" wide x 26" deep x 84" high (660mm wide x 660mm wide x 2134mm high)

Up to 10,000 ft. (3000m), OperatingUp to 32,000 ft. (10,000m), Storage

-29˚F to +149˚F (-20˚C to +65˚C) Operating-40˚F to +185˚F (-40˚C to +85˚C) Storage0% to 85% RH non-condensing, Operating0% to 95% RH non-condensing, StorageHumidity

Altitude

Up to twenty-four MRF28H54BV or MRF28H54BV50 (277V input) rectifiers can be fitted in the cabinet dependent on system configuration.Rectifiers are forced air cooled with front to rear airflow

Overvoltage 59.5Vdc

Power Factor 99% Typical, 98% Minimum

A rear located enclosure provides a terminal strip(s) for AC input power connectionAC Input Connection

Output voltage 54.0Vdc nominal

Output Current 1200A up to 4800A dependent on configuration

Polarity Positive Earth

3 Phase Input V (nominal) Connection Phase Loading* input current per rectifier Phase loading input current per rectifier*Rectifierat nominal input voltage at nominal input voltage -15%

277/480V 3 phase Wye, 4 wire 11.5A 13.6A 1MRF28H54BV50

400V 3 phase Wye, 4 wire 13.9A 16.3A 1MRF28H54BV

208V 3 phase Delta, 3 wire 15.5A 16.3A 1MRF28H54BV

Safety UL 1950, NEBS pending

DC Output Specifications

Overvoltage

Complies with FCC Part 15 Subpart J, Class A pending

EMC

Safety

AC Input Specifications

Rectifiers

Temperature Compensation The system is offered with or without battery voltage temperature compensation. Optional temperature probe required

System Monitor / Control

Temperature Compensation

Alarm outputs Eight (8) sets of independent Form C contacts. Two (2) are permanently allocated to Major and Minor the remaining 6 are user allocated

Number of Alarm Outputs

Environmental

MX28B/DM3000 microprocessor controlled and monitored

Alarm inputs The monitor can report up to four external alarm conditions. External alarms should be presented by a set of Form C dry contacts per alarm

External Alarm Inputs

EMC

Rectifiers

Ambient Temperature

©2002. All rights reserved. All APC trademarks are property of American Power Conversion. Other trademarks are property of their respective owners. Specifications are subject to change without notice. PART# 996-2166C

For more information call:Tel: 800 800 4APC - US & CanadaTel: 401 789 0204 - World wide

APC CorporateAPC North America132 Fairgrounds RoadWest Kingston RI 02892, USACall: 800 800 4APCFax: 401 789 3710

APC EuropeAPC IrelandBallybrit Business ParkGalway, IrelandCall: +35 391 702000Fax: +35 391 756909

APC Asia PacificAPC AustraliaLevel 1, 27 Northpoint100 Miller StreetNorth Sydney, NSW2060Call: +61 2 9955 9366Fax: +61 2 9955 2844

APC Latin America5301 Blue Lagoon Dr.Suite #610MiamiFL 33126, USACall: 305 266 5005Fax: 305 266 9695

Visit: www.apc.comE-mail: [email protected] Support: support.apcc.comPowerFax™: 800-347-FAXX

APC’s qualitysystem is certified byISO 9001 standards

APC Symmetra® Rack-MountPower Array™ (2-6 kVA)Symmetra RM provides all four components of theSymmetra Power Array: redundancy, scalability, manage-ability and self-serviceability in a rackmount form factor, toprovides high availability for mission critical servers, net-working and telecom equipment.

Also available from APC

N E W !

Output Distribution

*Maximum input current per rectifier will not exceed 16.3A

APC Symmetra® Power Array™ (4-16 kVA)Symmetra Power Array provides redundant power pro-tection with scalability, and manageability for multipleservers and business critical applications. It does forpower protection what RAID did for data storage.