y The valves are pressure-relieved, i.e. the degree of opening is not affected by differential pressure Δp (pressure drop).
y The regulation range is defined for the point at which the valve begins to open.
y Cooling media temperature range: -25 – 130 °C
y Ethylene glycol as a cooling media up to 40%
AVTA SS for aggressive media. A valve body in stainless steel means that the valve can be used for aggressive media in such applications as the marine sector and the chemical industry.
Thermo. operated water valves are used for proportional regulation of flow quantity, depending on the setting and the sensor temperature.
The Danfoss range of thermo. operated water valves includes a series of products for both refrigeration and heating regulation. The valves are self-acting, i.e. they operate without the supply of auxiliary energy such as electricity or compressed air.
The required temperature is maintained constant without unnecessary use of:
y cooling water in cooling systems, y hot water or steam in heating systems.
The operating economy and-efficiency are maximized.
Data sheet Thermo. operated water valve, type AVTA
2 IC.PD.500.A7.02 / 520B6738
How it works
Thermo. operated water valves consist of three main elements:
1. Setting section with knob, reference spring and setting scale.
2. Valve body with orifice, closing cone and sealing elements.
3. Hermetically sealed thermostatic element with sensor, bellows and charge.
When the three elements have been assembled together, the valve installed and the sensor located at the point where the temperature is to be regulated, the function sequence is as follows:
1. The pressure changes in the sensor as a result of a change in temperature - builds up in the sensor.
2. This pressure is transferred to the valve via the capillary tube and bellows and acts as an opening or closing force.
3. The knob on the setting section and the spring exert a force that acts counter to the bellows.
4. When balance is created between the two opposing forces, the valve spindle remains in its position.
5. If the sensor temperature changes – or if the settings are changed – the point of balance becomes displaced and the valve spindle moves until balance is re-established, or the valve is fully open or closed.
6. The flow quantity change is approximately proportional to sensor temperature change.
The illustrations show an AVTA cooling water valve, but the function principle applies to all types of thermostatic valves.
AVTA applications AVTA thermo. operated water valves are widely used for temperature regulation in many different machines and installations where cooling is required. AVTA cooling water valves always open to admit flow on rising sensor temperature.
The valve can be installed in either the cooling water flow line or the return line.
The standard version of the ATVA thermo. operated water valve can be used with fresh water or neutral brine.
Typical application areas:
y Injection moulding machines y Compressors y Vacuum pumps y Dry cleaning machines y Distillation plants y Printing machines y Hydraulic systems y Roller mills y Biomass boilers y Industrial lasers y Steam sterilizers y Medical equipment y Food processing
For immersion pockets, see “Spare parts and accessories”, page 10.
1) ISO 228-1 2) Code no. covers complete valve incl. capillary tube gland.3) A ø2 mm bypass is drilled in the valve body.
Ordering AVTA with universal charge
Sensor installation Valve body with bypass
The charge is a mix of liquid and gas where the liquid surface (regulating point) is always inside the sensor. Which charge medium is used depends on the regulation range.
y Sensor dimensions ø18 × 210 mm y Sensor can be installed in a place where it is
either colder or warmer than the valve y Sensors must be orientated as shown in the
The charge is a mix of liquid and gas. Due to the mixture of liquid and gas the sensor must be installed in an area or environment that is warmer than the valve.
y Small sensor dimensions – ø9.5 × 180 mm y Short time constant y Max. pressure on sensor 25 bar
Data sheet Thermo. operated water valve, type AVTA
Installation AVTA with mounting bracket
The valves can be installed in any position. An arrow on the valve body indicates the direction of flow.AVTA valves are marked so that the letters RA are the right way up when the valve is held as shown. The installation of an FV filter ahead of the valve is recommended.Capillary tube Install the capillary tube without sharp bends (no ”kinks”). Make sure that there is no strain on the capillary tube at the ends. Relief is important where vibration might occur.Note: When an AVTA valve is used, the sensor must be able to react to variations in cooling water temperature on system start. Therefore a bypass line with a shut-off valve might be necessary to ensure flow at the sensor during start-up. If a mounting bracket is used – see “Spare parts and accessories”, page 10 – it must always be positioned between the valve body and the setting section (see illustration).
Data sheet Thermo. operated water valve, type AVTA
When sizing and selecting thermo. operated water valves, it is most important to ensure that the valve is able to give the necessary quantity of cooling water at any time, irrespective of the load. Therefore, to select a suitable size of valve it is necessary to know the precise amount of cooling required. On the other hand, to avoid the risk of unstable regulation (hunting), the valve should not be oversized.
The type of charge must be selected on the basis of the temperature to be maintained, and on an assessment of the characteristics of each type, as described in the foregoing.
In general the aim should be to select the smallest valve capable of giving the required flow.
It is also recommended that the temperature range be chosen so that the required sensor temperature lies in the middle of the regulation range.
To help fine-setting the valve, a thermometer should be installed near the sensor.
Valve size The following data are used when selecting the valve size:
y Required cooling water flow, Q [m3/h] y Temperature rise in cooling water, Δt [°C] y Differential pressure across valve, Δp [bar].
With fully open valve, the differential pressure should be around 50% of the total pressure drop across the cooling system.
The charts on page 12 are intended to make valve sizing easier.
Fig. 1 – Relation between heat quantity [kW] and cooling water quantity
Fig. 2 – Graphs of kv values
Fig. 3 – Valve operating range
Fig. 4 – Flow quantities as a function of pressure drop Δp
Example A cooling water valve must be selected for the temperature regulation of a vacuum pump.
Since direct regulation of the oil temperature is required, an AVTA valve is suitable. The sensor position is horizontal – and small dimensions are desired.
Given data: y Necessary cooling at full load 10 kW. y Oil temperature to be maintained constant at
45 °C y Cooling water p1 = 3 bar y Outlet p3 = 0 bar
y p2 =
p1+p3
2 (guess) y Cooling water temperature t1 = 20 °C y Outlet temperature t2 = 30 °C
1. The graphs in fig. 1 can be used to find the necessary cooling water quantity at Δt = 10 °C (30 °C – 20 °C) to 0.85 m3/h.
The graphs in fig. 2 show the necessary kv value for 0.85 m3/h with Δp = p1- p2 = 3 - 1.5 = 1.5 bar for 0.7 m3/h.
The columns in fig. 3 show that all four AVTA valves can be used, but in practice an AVTA 10 or 15 shall be selected, so the necessary water flow is in the middle of the regulating range.
The above considerations apply to both AVTA and FJVA types.
Operating conditions and other product requirements in this example mean that a valve with adsorption charge is the correct choice. The temperature range 10 °C – 80 °C is in order.
The table at the bottom of page 6 shows AVTA 10, code no. 003N1144, or AVTA 15, code no. 003N0107. Both fulfil the requirements named.
In many applications, installation conditions make the use of sensor pockets advisable.
“Accessories” on page 10 gives the code nos. for sensor pockets for ø9.5 mm sensors in brass and stainless steel: 017-436766 and 003N0196, respectively.
Data sheet Thermo. operated water valve, type AVTA
Kv values are always given for water flow in [m3/h] with a pressure drop ∆ p of 1 bar. The valve should be selected so that the necessary kv value lies in the middle of the regulation range.
Example: AVTA 10 and 15 are the most suitable for a kv value of 0.7.
Fig. 3 Nomogram showing the valve kv range.
Sizing (continued)
Options y DZR brass y Outer thread connecting y Other lengths of capillary tubes y Armouring of capillary tubes y Other combinations of sizes, materials and ranges y NPT – connection, see separate datasheet for USA / Canada
[m3/h]
Fig. 4 Valve flow quantity in fully open position, as a function of pressure drop Δp.