TB2 E/S 630 Max In (A) of Frame 630 Model Number of Poles Type S400 3, 4 GE Nominal current ratings I n (A) 50°C 250 400 Electrical characteristics Rated operational voltage Rated insulation voltage Rated impulse withstand voltage Ultimate breaking capacity (IEC, JIS, AS/NZS) Service breaking capacity (IEC, JIS, AS/NZS) Rated breaking capacity (NEMA) Rated short-time withstand current U e (V) AC 50/60 Hz 690 DC - U i (V) 800 U imp (kV) 8 I cu (kA) 690V AC 20 525V AC 30 440V AC 65 415V AC 70 400V AC 70 220/240V AC 100 250V DC - I cs (kA) 690V AC 15 525V AC 30 440V AC 50 415V AC 50 400V AC 60 220/240V AC 85 250V DC - (kA) 480V AC 30 240V AC 100 I cw (kA) 0.3 Seconds 5 Protection Adjustable thermal, adjustable magnetic Fixed thermal, fixed magnetic Microprocessor Utilisation category B Installation Front connection (FC) Extension bar (FB) Cable clamp (FW) Rear connection (RC) Plug-in (PM) DIN rail mounting (DA) Dimensions Weight • • • • - height (mm) 260 width (mm) 3 pole 140 (mm) 4 pole 185 depth (mm) 103 weight (kg) 3 pole 4.3 4 pole 5.7 Operation Direct Opening Action Toggle operation Door mounted (HS) / Breaker mounted handle (HB) Motor operation (MC) Endurance Electrical cycles 415V AC Mechanical cycles 4,500 15,000 • • Standard • Optional - Not Available DATA SHEET: TEMBREAK 2 S400-GE MCCB Electrical Characteristics to IEC 60947-2, EN 60947-2, JIS C 8201-2-1 ANN.1, AS/NZS 3947-2, NEMA AB-1 TemBreak2 S400-GE MCCB March 2018 Page 1 of 4
4
Embed
DATA SHEET: TEMBREAK 2 S400-GE - Terasaki · 2018-05-02 · 250V DC - Ics (kA) 690V AC 15 525V AC 30 440V AC 50 415V AC 50 400V AC 60 220/240V AC 85 250V DC - (kA) 480V AC 30 240V
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
TB2 E/S 630Max In (A) of Frame 630ModelNumber of PolesType
S4003, 4GE
Nominal current ratingsIn (A) 50°C 250
400
Electrical characteristicsRated operational voltage
Rated insulation voltage Rated impulse withstand voltage
Ultimate breaking capacity (IEC, JIS, AS/NZS)
Service breaking capacity (IEC, JIS, AS/NZS)
Rated breaking capacity (NEMA)
Rated short-time withstand current
Ue (V) AC 50/60 Hz 690DC -
Ui (V) 800Uimp (kV) 8
Icu (kA) 690V AC 20525V AC 30440V AC 65415V AC 70400V AC 70220/240V AC 100250V DC -
Ics (kA) 690V AC 15525V AC 30440V AC 50415V AC 50400V AC 60220/240V AC 85250V DC -
(kA) 480V AC 30240V AC 100
Icw (kA) 0.3 Seconds 5
Protection Adjustable thermal, adjustable magneticFixed thermal, fixed magneticMicroprocessorUtilisation category B
Operation Direct Opening ActionToggle operationDoor mounted (HS) / Breaker mounted handle (HB)Motor operation (MC)Endurance Electrical cycles 415V AC
Mechanical cycles 4,50015,000
••
Standard • Optional - Not Available
DATA SHEET: TEMBREAK 2 S400-GE
MCCB Electrical Characteristics to IEC 60947-2, EN 60947-2, JIS C 8201-2-1 ANN.1, AS/NZS 3947-2, NEMA AB-1
TemBreak2 S400-GE MCCB March 2018Page 1 of 4
With extension bars (optional)
With extension bars (optional)
30
30
Front connected
Rear connected
Front connected with Motor Operator
Rear connected with Motor Operator
DATA SHEET: TEMBREAK 2 S400-GE MCCB
Outline Dimensions S400-GE
ASL: Arrangement Standard Line HL: Handle Frame Centre Line
Page 2 of 4
11
8 (max.)
20 (max.)
Preperation of conductor
30 (max.)
Support or rail
Support or rail
Mounting screwM10x30 max.
Mounting screw M5 x 20
Mounting plate
90102
260
97
4
102113
48
138142
180
6t6t
198
258
65
276
90102
260
971
4
32
6t32
204208
246
12
1
Insulating plate
Mounting plate
Mounting M6 NUT
Insulating plate
Mounting screw M6x70
Mounting on a support or rails (shown with optional connection bars oriented for rear access)
Mounting through the backplate (shown with optional connection bars oriented for rear access)
Mounting on the backplate (optional connection bars must be oriented for front access)
Outline Dimensions Termination of Busbar
DATA SHEET: TEMBREAK 2 S400-GE MCCB
Outline Dimensions S400-GE Plug-in VersionASL: Arrangement Standard Line HL: Handle Frame Centre Line
Page 3 of 4
Percent Rated Current IRPercent Rated Current In
LT
ST
PTA
NP
Option
Standard
IR (A)LTD Pick-up current IR xIn 0.4 0.5 0.63 0.8 0.9 0.95 1.0
1Characteristics
Note(1) gF is not available when In is 250A. (2) Ii max. = 13 x In. (3) 1.0 x IR or 0.5 x IR can be selected. Characteristic of neutral protection (tN vs. IN) isidentical to characteristic of phase protection (tR vs. IR). (4) When you specify gF on MCCBs with 3 poles the terminal block is automatically fitted toconnect with the external neutral CT for 3 phases 4 wires system. See terminal blocks in section 4.