This nozzle is used for automatic systems (wet pipe, dry pipe and pre-action). Itrequires no additional detection system (except pre – action system). In stand-by mode,the water is blocked by a piston inside the nozzle. As result of heat, the glass bulbbursts and the piston is pushed downwards by a spring. This opens the water way andwater is discharged.Optional protective Teflon caps prevent passing contamination inside the nozzle.
General Properties
K – Factor : 1,200
Flow rate (at 100 bar): 12,00 l/min
Glass bulb: Fast Response 57°C
Material nozzle body and cage: Stainless steel
Material mic ro – nozzles: Stainless steel with brass swirling device
Material micro – filter: Stainless steel with copper seal
Material O – ring: NBR*
Material piston : Brass
Material spring: Stainless SteelMaterial protecti ve cap: Teflon
Weight: 0,200 kg
* O – ring is recommended to be changed every 10 years
This nozzle is used for deluge systems. It requires a system with manual, electric orpneumatic activation. As soon as the system is activated, water mist is discharged.Optional protective Teflon caps prevent passing contamination inside the nozzle.
General Properties
K – Factor : 0,290
Flow rate (at 100 bar): 2,90 l/min
Material nozzle body: Stainless steel
Material mic ro – nozzles: Stainless steel with brass swirling device
Material micro – filter: Stainless steel with copper seal
Material O – ring: NBR*
Material protecti ve cap: Teflon
Weight: 0,200 kg
* O – ring is recommended to be changed every 10 years
Socket is to be used only with FOGTEC nozzles. Socket has one pipe connection inaddition to nozzle inlet. Cutting ring and nut are included to socket assembly.
Socket is to be used only with FOGTEC nozzles. Socket has two pipe connections inaddition to nozzle inlet. Cutting rings and nuts are included to socket assembly.
The FOGGUN wall cabinet system is designed for manual fire fighting. It can be eitherstand-alone or be part of a FOGTEC fixed installation with automatic or open nozzles. TheFOGGUN wall cabinet system includes the wall cabinet and the FOGGUN 2 fire fighting gun.The FOGGUN 2 has two different spray pattern settings which can be chosen. The first set-ting creates a very effective fine droplet water mist, so even fluid or dust fires normally canbe put out without splashing. The fine mist can be used in conjunction with a centrally locat-ed jet that creates a coarse mist. The central jet is used to achieve greater reach or to ena-ble the use of mist on deep seated fires by using higher momentum of the droplets. TheFOGGUN also produces lateral jets which protect the fire fighter from radiated heat.
General Properties
Material of box: Carbon steel and corrosion resistant painting
Colour: Red (RAL3000)
Fire fighting gun: FOGGUN 2:- Flow 25l/min @ 100 bar
- Maximum pressure 120 bar- 12 side nozzles and 1 center nozzle
Hose: DN12, 35 or 70 meters, stainless steel fittings
Connection to the system: Stainless steel fitting for pipe L15 (DIN2391)
The section valve is meant to be used with deluge system and open nozzles. The pressure range ofvalve is designed for pump systems.
The section valve is a 2/2 – way solenoid valve that is controlled by an external fire detection system.They can be installed in different locations or they can be centralized in a valve station with a separatesupply pipe to each section, or decentralized at each distribution point from the main high pressure sup-ply pipe to the individual sections.
The test connection is used for air/water bleeding and testing the function of the solenoid section valve.
General Properties
Materials (contact to water): Stainless Steel
Connections: BSP - ISO 1719-1
Valve operation : Normally Closed
Maximum operating pressure: 150 barSolenoids: 24V(1,9A), 110V(0,42A), 230V(0,2A)
Valve is meant for automatic systems where the main pipes are wet until automatic nozzles. Thesection valve is especially design for Ordinary Hazard Group 1 applications. The section valvegroups nozzles to separate zones. The section valve has several functions which are following:
A. Detection of activated zone and giving an alarm signalB. Closing section manuallyC. Test connection for regular operation tests without activating nozzleD. Check valve function allowing drainage of main pipes without draining section pipingE. Pressure gauge for visual pressure level check
The section valve can be equipped on request with limit switch to control the portion of manualclosing valve. The section valve will be delivered without fittings.
General Properties
Materials (contact to water): Stainless Steel / Brass
Connections: ISO 1719-1
Maximum operating pressure: 140 bar
Pressure loss: 3.5bar @ 150l/min
Flow switch: Max 200V, 1A, 20VA
Pressure gauge: 0-250bar
Part Number Descrip tion Part Number
SECTION V ALVE – OH G1 (140bar) Standard 35000255
SECTION V ALVE – OH G1 (140bar) with limit switch on request
Fogtec Brandschutz GmbH & Co. KG Schanzenstr. 19 A D–51063 Köln (Cologne)Tel: +49-221-96223-0 Fax: +49-221-96223-30 [email protected] www.fogtec.com
FOGTEC reserves the right to improve and revise the products and recommended system configurations without notification. The document is protected under copyright law. Allrights with regard to the contents are reserved. These documents are to be treated confidentially. They may not be copied and third parties may not be allowed access to themwithout written consent. They are to be returned to us on request. These documents may not be translated, microfilmed nor stored or further processed in electronic systemswithout written consent. In the case of contravention of our rights legal action will be taken. Any rights to claim compensation are reserved
Description
This valve is meant for deluge systems where the main pipes are wet until section valves. Sectionpiping is dry and only open nozzles are used.The valve combines following parts. A. Manual service valve, B. Testing connection and C. pneumatic driven main valve.
General Properties
Materials: Stainless Steel
Connections: BSP - ISO 1719-1Valve operation: Normally Closed
This valve is to be used in water mist systems with automatic nozzles and wet pipe work until thesection valve, where the pipework after section valve shall be under pressurized air in stand-bysituation.The valve combines following parts. A. Manual service valve, B. Two pressure gauges, C. Pressure sensor, D. Testing connection andE. Pneumatic driven main valve.
General Properties
Materials: Stainless Steel
Connections: BSP - ISO 1719-1Valve operation: Normally Closed
The activation is triggered by an electric signal. The nitrogen cylinder valve is a solenoid op-erated valve with manual override for safety reasons in case of electric failure. After activa-tion the nitrogen is released to the slave module which will pressurize the pipe work and thenozzles starts the extinguishing. A pressure switch in the water manifold of the slave modulegives a message of activated system.
General Properties
Nitrogen cy linder : 1 x 80 litre (pressure 200 bar at 20°C)
Release method: Solenoid valve (electric signal or manual override)
The activation is triggered by pressure increase caused by activation of the master cylinder. After activation the nitrogen is released to the water cylinder which will pressurize the pipework and the nozzles starts the extinguishing. A pressure switch in the water manifold givesa message of activated system. This module shall only used in combination with dry pipesystem master modules.
General Properties
Water cylinder: 4 x 80 litre
Nitrogen cylinder: 1 x 80 litre (pressure 200 bar at 20°C)
Release method: Activated by Dry Pipe System Master Module
Compatible Master Modules: 31100311, 31100316
Connections:
Water port Stainless steel fitting for pipe L12 (DIN2391)
N2 filling port W21,8x1/14” (DIN477)
Part Number
Descrip tion Part Number
Dry Pipe Slave Cylinder Module 4 x 80l H20 + 1 x 80l N2 31100382
This 2x120 l/min pump unit is designed to be used in automatic systems. The pump unit is built modularand with reduced number of components. The jockey pump is meant to keep the pre-pressure of approx.20bar in wet pipes. The high-pressure pump type used is a triplex plunger high-pressure pump with themaximum flow rate of 120l/min at maximum pressure of 120bar. Both pumps in the pump unit assemblyhave individual electric motors, couplings and safety valves. Other main components are connected tothe suction and high-pressure manifolds that are shown in the dimension drawing.
Dimensions and main components
Specifications
Materials (contact to water): Stainless Steel / Brass
The pump unit is available in two versions. The standard version has all pipe connections to the rightside of the pump unit. The mirrored version has all pipe connections to the left side.
2x120 l/min Automatic, Standard (30100835) 2x120 l/min Automatic, Mirro red (30100857)
Descript ion Version Part number
2 x 120l/min Automatic Standard 30100835
2 x 120l/min Automatic Mirrored 30100857
Compatibility
Pump unit can be connected to the following tank, suction line / filling units and return line. (See technicaldata sheets of tank units in order to see the different layout possibilities with different tank and pump unitcombinations)
2x120 l/min Automatic, Standard (30100835):
2x120 l/min Automatic, Mirrored (30100857):
Tank unit / Suction line Part Number Return line (optional) Compressor (optional)
500L, DN80Standard30000729
DN5030000716
All suitable
1000L, DN80Standard30000735
DN5030000716
All suitable
3000L, DN80Standard30000745
DN5030000716
All suitable
4000L (On request) - - -
Tank unit / Suction line Part Number Return line (optional) Compressor (optional)
This 2x120 l/min pump unit is designed to be used in deluge systems. The pump unit is built modular andwith reduced number of components. The pump type used is a triplex plunger high-pressure pump withthe maximum flow rate of 120l/min at maximum pressure of 120bar. Both pumps in the pump unit as-sembly have individual electric motors, couplings and safety valves. Other main components are con-nected to the suction and high-pressure manifolds that are shown in the dimension drawing.
Dimensions and main components
Specifications
Materials (contact to water): Stainless Steel / Brass
The pump unit is available in two versions. The standard version has all pipe connections to the rightside of the pump unit. The mirrored version has all pipe connections to the left side.
2x120 l/min Deluge, Standard (30100856) 2x120 l/min Deluge, Mirrored (30100858)
Descript ion Version Part number
2 x 120l/min Deluge Standard 30100856
2 x 120l/min Deluge Mirrored 30100858
Compatibility
Pump unit can be connected to the following tank, suction line / filling units and return line. (See technicaldata sheets of tank units in order to see the different layout possibilities with different tank and pump unitcombinations)
2x120 l/min Deluge, Standard (30100856):
2x120 l/min Deluge, Mirro red (30100858):
Tank unit / Suction line Pump unit Return line (optional) Compressor (optional)
500L, DN80Standard30000729
DN5030000716
All suitable
1000L, DN80Standard30000735
DN5030000716
All suitable
3000L, DN80Standard
30000745
DN50
30000716 All suitable
4000L (On request) - - -
Tank unit / Suction line Pump unit Return line (optional) Compressor (optional)
The compressor produces compressed air that is needed in pre-action and dry pipe systems for filling thepipes or using pneumatic operated valves in deluge systems. The compressor for all systems is thesame, but there are two different mounting versions. The compressor with wall mounting kit can be usedwith all pump units. The compressor with pump unit mounting kit is available only with 2 and 3 x 120l/min pump systems.
The 1000 litre tank unit can be used with all standard pump units. The tank unit can work as total volumestorage or as break tank where water is supplied from a tank to the pumps. The tank is simultaneouslyfilled with fresh water from an external water supply in brake tank arrangement. The main water supplymust assure the minimum flow rate of the pump system within a pressure range of 1,5 to 6 bar to tankfilling. Tanks should be placed generally close to the pump unit, but the tank pump orientation can bechanged to different layouts.
The standard tank is made of black polyethylene*. The tank frame is galvanized carbon steel. The fillingunit and suction line assemblies are part of the tank unit, but depended on the used pump configuration.The available suction line and filling unit assemblies are available in different sizes. The return line as-sembly can optionally be installed. The tank overflow is used to protect the tank against overfilling. Thetank overflow should always be connected to water drain.
A level measurement is mounted to the side wall of the tank. This level measurement optically indicatesthe water level in the tank. It also includes switches, giving opening signals via the PLC control to thetank filling valve as well as a minimum alarm if the water level in the tank reaches the lowest level.
Dimensions and main components**
* 1000 litre stainless steel tank unit is also available on request, please contact FOGTEC Fire Protection.** Notice! Dimensions might change slightly depending on chosen filling unit and suction line assembly
Suction line size: DN40, DN50, DN80, DN100 and DN125
Filling unit assemblies: DN25, DN40 and DN50
Overflow connection: DN80
Return l ine assembly (optional): DN25 and DN50
Filtration rate (water): 100µm (abs.)
Filtration rate (air): 10 µm (abs.)
VersionsPump unit is available in two versions, standard and mirrored. The standard version has always all pipeconnections to the left side of the tank unit, which means that it can be connected to standard pump unitversions. The mirrored version means connections to the right side and only mirrored pump units. Themain dimensions of standard and mirrored pump units are exactly same.
1000 Lit re Tank Unit Standard 1000 Lit re Tank Unit Mirrored
The connections between tank unit and pump units are flexible, which enables changing of the layouteasily. The following drawing shows approximate areas where tank unit can be positioned. The drawingshows standard pump and tank units, but this can be mirrored with mirrored pump and tank units.
Possible tank unit installation areawith standard supply components
There is minimum distance between tank and pump unit that varies depending on the pump unit configu-ration. The normal minimum distance is 1.5 metre. This can be reduced to 0.7 metre if the pump unitconfigurations of 1-2 times 50l/min pumps or 1 time 120l/min pump units are used.
Part numbers and compatibility
The part numbers of different pump unit configurations are shown in the following table. The tank unitincludes always the suction line and filling unit assembly. These have to be dimensioned according topump unit configuration. All compatibilities between different pump units and 1000 litre tank unit are ex-plained in the table. The return line assembly is an optional selection with the different part number.
Notice! 1x50l/min and 1x120l/min standard pump units can be used with both tank designs.
The control cabinet controls and monitors all electrical components in the pump system according theFOGTEC software that is installed to the PLC. Control cabinet controls both tank unit and pump unit. Theelectrical connections to tank unit are standard independent which tank unit is used, but they differ de-pending on the pump concept. All pump units will have a different control cabinet depending on the num-ber of pumps and used system type (deluge/automatic). Control cabinets are available with two possiblemounting possibilities depending on the size. Smaller systems with 1 to 2 pumps use cabinets with wallmounting. Larger pump systems are built to self standing cabinets.
Notice! Control cabinets have different sizes depending on mounting method and number of controlledpumps.
All control cabinets have several self-diagnostic functions and failures are detected automatically. Controlcabinets have different programs for service runs. Pumps can also be manually operated and tested with