Data sheet 5SY4663-7 · Protection class Protection class IP IP20, with connected conductors Energy limiting class 3 Switching capacity Switching capacity current acc. to EN 60898
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Data sheet 5SY4663-7CIRCUIT BREAKER 400V 10KA, 3+N-POLE, C, 63A, D=70MM
General technical dataNumber of poles 4Number of poles / Note 3P+NTripping characteristic class Ccircuit-breaker / Design 5SY4Mechanical service life (switching cycles) / typical 20 000Overvoltage category 3
VoltageType of voltage AC/DCInsulation voltage
● with multi-phase operation / at AC / rated value 440 V
Supply voltageSupply voltage / at AC / rated value 400 VSupply voltage frequency
AWG number / as coded connectable conductorcross section
● minimum 14
● maximum 4
Tightening torque [lbf·in] / with screw-type terminals
● minimum 22 lbf·in
● maximum 26 lbf·in
Tightening torque / with screw-type terminals
● minimum 2.5 N·m
● maximum 3 N·m
Position / of power supply cord Any
Mechanical DesignHeight 90 mmWidth 72 mmDepth 76 mmMounting position anyInstallation depth 70 mmNumber of width units 4Mounting type Quick assembly systemNet weight 666 g
Environmental conditionsInfluence of the surrounding temperature Max. 95% humidityVibration resistance / acc. to IEC 60068-2-6 50m/s² at 25 to 150Hz and 60m/s² at 35Hz (4sec)Ambient temperature
● minimum -25 °C
● maximum 55 °C
● during storage / minimum -40 °C
● during storage / maximum 75 °C
CertificatesEquipment marking / acc. to DIN EN 61346-2 F