Data sheet 5SU1653-1KK40 - Haitex Digital Strategy · — maximum 25 mm² Tightening torque / with screw-type terminals minimum 2.5 N·m maximum 3 N·m Position / of power supply
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Data sheet 5SU1653-1KK40RCBO, 4.5 kA, 1P+N, Type AC, 300 mA, C-Char, In: 40 A, Un AC:230 V
ModelProduct brand name SENTRONProduct designation RCBODesign of the product Instantaneous
General technical dataNumber of poles 2Number of poles / Note 1P+NNumber of poles / with protection 1Tripping characteristic class Ccircuit-breaker / Design 5SU1Mechanical service life (switching cycles) / typical 10 000Overvoltage category III
VoltageSurge current resistance / at (8/20) µs 1 kA
Protection classProtection class IP IP20, if the distribution board is installed, with connected
conductorsEnergy limiting class 3
Switching capacitySwitching capacity current
● acc. to EN 60898 / rated value 4.5 kA
● acc. to IEC 60947-2 / rated value 10 kA
DissipationPower loss [W]
● for rated value of the current / at AC / in hotoperating state / per pole
7.8 W
● maximum 15.6 W
ElectricityTripping residual current / rated value 300 mArated current In / IEC, DIN/VDE / at 40 Cel 37.6 AType of fault current ACCurrent / at AC / rated value 40 A