CASE STUDY

www.icecold2.com 855.EcoCOOL (326.2665)

Data Analysis for Unibrite AC Units

Page 2: Data Analysis for - IceCOLD Technology | IceCOLD ... · Data Analysis for Unibrite AC Units. Data Analysis for Unibrite AC Units SUMMARY of OBSERVATIONS Analysis is based on pre-

Data Analysis for Unibrite AC Units

SUMMARY of OBSERVATIONS

Analysis is based on pre-

and post-

measurements associated with introducing Iced Cold product

into refrigera�on compressors serving Unibrite Cooler and Freezer.

Measurement and monitoring include 1-min-interval

data collected

for the following parameters:

Ambient Dry Bulb Temperature, Condenser Water Temperature, Cooler Supply and Return

Temperatures, Freezer Supply and Return Temperatures, High Stage and Low Stage (Booster)

Compressors’ AC

Currents.

Dura�on of data monitoring was ~two weeks before and a�er -

on 9/18-10/3/2014

-

for pre-

treatment, and 12/10-12/25/2014 – for post-treatment.

Some observa�ons are discussed below.

Table presents single-value averages and totals for all measured parameters (please, refer to Excel

charts for detailed trend-logs, complemen�ng single-value summaries):

As Table indicates, and the corresponding trend-logs in Excel charts (not included here) confirm,

the Low Stage AC Current (Amps) was in average ~20.4% lower in post-treatment measurements

than in pre-treatment. Correspondingly, the total energy consumed (in Amp-hours, or –

propor�onally – in kilowa�-hours) was 20.4% lower

as well. Similar

comparison for High Stage AC

Current indicates smaller improvement on 2.7%.

It should be noted, that post-

measurements were performed in some colder (in average) outdoor

condi�ons. However, comparison of subsets of collected data with iden�cal outdoor air

temperatures, s�ll demonstrate improvement (savings) on ~20% for Low Stage compressor, as

shown above.

The air temperature difference between pre-

and post-treatment was minimal

(negligible) for both

cooler and freezer

supply and return air. Cooler Supply and Return Air deltaT was almost zero in

both pre-

and post-measurements, and Freezer Supply and Return Air deltaT was also very small

(1.55 and 1.79

degF respec�vely).

Comparison of Low-stage and High-stage AC Currents is shown below.

AC Current for Low-stage compressor on post-treatment is clearly lower than pre-treatment:

1www.icecold2.com 855.EcoCOOL (326.2665)

Page 3: Data Analysis for - IceCOLD Technology | IceCOLD ... · Data Analysis for Unibrite AC Units. Data Analysis for Unibrite AC Units SUMMARY of OBSERVATIONS Analysis is based on pre-

This Amps difference is translated in propor�onal difference ( 20.4% savings) in Amp-hrs, kWh and

dollars.

High-stage compressor operates with permanent cycling on two levels (between three Current

values) as it shown below:

While sufficient Amps and/or Amp-hours decrease wasn’t detected

for High-stage compressor, the

three Amps levels for current’s varia�ons became significantly different in post-treatment, than

they were in pre-treatment.

The

difference is presented below:

2www.icecold2.com 855.EcoCOOL (326.2665)

Page 4: Data Analysis for - IceCOLD Technology | IceCOLD ... · Data Analysis for Unibrite AC Units. Data Analysis for Unibrite AC Units SUMMARY of OBSERVATIONS Analysis is based on pre-

It’s clearly visible that in post-treatment measurements, the difference between maximal and

intermediate Amp-levels became smaller, and levels themselves – more consistent. While this Iced

Cold effect requires addi�onal analysis / inves�ga�on, it might be indica�on that high stage

compressor operates a�er Iced Cold treatment “not as hard as before” treatment , which could be

translated into extended equipment life�me.

It should be noted that chart above is plo�ed for case-specific (pre- and post-) outdoor air

condi�ons, which enables appropriate weather-independent comparison. Similarly Iced Cold effect

on Low Stage compressor amperage for “aligned” weather condi�ons is shown below, indica�ng

un-ques�onable improvements: