AIR CONDITIONING SYSTEM [ 50Hz ] 36 0 ° airflow!! RZR71LVVM RZR50LVVM RZR60LVVM RZR100LVVM RZR125LVVM All rights reserved 05/14 SS c 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor. Cautions on product corrosion Warning Ask a qualified installer or contractor to install this product. Do not try to install the product by yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion. Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings. If you have any enquiries, please contact your local importer, distributor and/or retailer. PCSSG0814 Specifications, designs and other content appearing in this brochure are current as of May 2014 but subject to change without notice. No. 10 Ang Mo Kio Industrial Park II Singapore 569501 Tel. +65-6-5838888 Fax. +65-6-3497310 / 311 www.daikin.com.sg DAIKIN AIRCONDITIONING (SINGAPORE) PTE. LTD.
26
Embed
DAIKIN AIRCONDITIONING (SINGAPORE) PTE. LTD. · floor standing type compact multi flow ceiling mounted cassette type ceiling mounted built-in type duct connection middle and high
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
AIR CONDITIONING SYSTEM [50Hz]
360° airflow!!
RZR71LVVMRZR50LVVM RZR60LVVM RZR100LVVM RZR125LVVM All rights reserved 05/14 SSc
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.
Cautions on product corrosion
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product by yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
PCSSG0814
Specifications, designs and other content appearing in this brochure are current as of May 2014 but subject to change without notice.
No. 10 Ang Mo Kio Industrial Park II Singapore 569501Tel. +65-6-5838888 Fax. +65-6-3497310 / 311www.daikin.com.sg
DAIKIN AIRCONDITIONING (SINGAPORE) PTE. LTD.
FLOOR STANDING TYPE
COMPACT MULTI FLOW CEILING MOUNTED CASSETTE TYPE
CEILING MOUNTED BUILT-IN TYPE
DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE
1 2
Daikin meets your needs with this full lineup of inverters for various types of indoor units and power supplies.
NEW RZR50LVVM NEW RZR60LVVM NEW RZR71LVVM NEW RZR100LVVM NEW RZR125LVVM NEW RZR140LVVM
5 6
Comfortable currents of air are sent to every corner of the room.
Simultaneous twin multi operationSimultaneous twin multi operation
Refrigerant branch piping kit for Twin Multi operation 2 sets of Twin Multi
For example, four indoor units are judiciously spaced in this wide
single-floor restaurant to deliver comfortable currents of air to every corner of the room.
Achieved higher COP with 4 Tick Energy LabelEnergy savingEnergy saving
New types of indoor unitsNew types of indoor units
COP is equal to capacity (kW) divided by power consumption (kW), and the larger the COP value, the higher the energy efficiency, enabling cooling and heating with less electricity and increasing the energy saving performance.
Note : *Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24.0°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
What is COP (Coefficient of Performance)
COP
2
3
4
5
FCQ50LUV1RZR50LVVM
Coo
ling*
FCQ140LUV1RZR140LVVM
2.85
Coo
ling*
FCQ125LUV1RZR125LVVM
3.40
Coo
ling*
FCQ100LUV1RZR100LVVM
3.60
Coo
ling*
FCQ71LUV1RZR71LVVM
3.57
Coo
ling*
FCQ60LUV1RZR60LVVM
4.874.30
Coo
ling*
CEILING MOUNTED CASSETTE TYPE
Round Flow
Non-inverter
Inverter Time
Running current
Starting current
Time
Running current
Cur
rent
Cur
rent
At startup, full power is used to achieve the set temperature quickly. Then, the capacity is adjusted according to the outdoor temperature changes and subtle indoor load changes to achieve fine capacity control resulting in a more stable room temperature.Non-inverter type air conditioners must be switched on and off repeatedly, causing large fluctuations of the room temperature.
Inverter performs variable control of frequency, which determines air conditioner’s power performance.
Enhanced comfort with Inverter
Small temp. differenceCools a room
in less time
Cooling operation
Inverter power controlNon-inverter type air conditioner
Time
Temp
Set temp
ComfortableComfortableAt startup, inverter raises frequency smoothly, eliminating the starting current spike.
26 new combinations added!
Wider lineup of invertersWider lineup of invertersDaikin meets your needs with this full lineup of inverters for various types of indoor units and power supplies.
CEILING MOUNTED CASSETTE TYPE
Round Flow
COMPACT MULTI FLOW CEILING MOUNTED CASSETTE TYPE
CEILING MOUNTED CASSETTE TYPERound Flow
CEILING SUSPENDED TYPE
WALL MOUNTED TYPE
DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE
CEILING MOUNTED BUILT-IN TYPE
FLOOR STANDING TYPE
DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE
• Condition after exposure to the smoke of 600 cigarettes in 1 m3 enclosed space.
Treated surface
Untreated surface
Grimy surface
Resists soiling
External panels are treated with a coating that repels dirt.
Mould-proof drain pan includes a silver ion antibacterial agent that assists in preventing the growth of slime, bacteria, and mould that cause smells and clogging.
Avoids uneven temperature and discomfort caused by drafts.
To prevent dirt sticking to the external panels, they have been coated with a surface treatment.
Because air flows out from corner outlets, comfort spreads more widely.
360° airflow Air movement is gentle with Round Flow
Condensation does not easily form on and dirt does not cling to non-flocking flaps. It is easy to clean.
Non-flocking flapsSilver ion anti-bacterial drain pan
Prevents mould and microorganisms growing out of the dust and moisture that adheres to the filters.
Filter has anti-mould and bactericidal treatment
Grime prevention and bactericidal coating: Make cleaning easier.
Adapts easily to the installation space.
Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing material (option) must be used to close each unused outlet.
3-way flow L-shaped 2-way flow
Opposite 2-way flow
(E.g., installed in a corner)
(E.g., installed in a long room)
(E.g., installed near a wall)
(E.g., installed in middle of ceiling)
4-way flow also possible.
All-round flow
360° airflow can maintain comfort even if air discharge speed is lower.
Typical flow patterns There are a total of 23 flow patterns.
If you raise the set temperature by 1 to 1.5°C,and velocity is decreased by 25%, you still obtain the same feeling temperature and comfort.
Operation sound increases when using 2-way or 3-way flow.
A signal receiver must be added to the indoor unit.
Wireless remote controller and signal receiver unit are sold as a set.
Wireless LCD remote controller
Signal receiver unit (Installed type)
Note: Remote controller cable not included. Cables must be procured locally.
Note: Remote controller cable not included. Cables must be procured locally.
Wired LCD remote controller
BRC1C61
7 8
Remote controller
*3 *3 *3 *3 *4
Setp
oint
rang
e se
t
Wee
kly
sche
dule
tim
er
Setp
oint
aut
o re
set
Off
timer
(pro
gram
med
)
On/
Off
timer
Cassette air conditioner with 360° uniform airflow sets the standardCassette air conditioner with 360° uniform airflow sets the standard
Options required for specific operating environments
High-efficiency filterAvailable in two types: 65% and 90% colorimetry.
Using this kit, a duct can be fitted to increase the intake of outdoor air.
*Connecting ducts, insect nets, fire dampers, air filters, and other parts should, as required, be procured locally.
**Outside Air fan interlocked with air conditioning unit is necessary. Optional PCB(KRP1C63)is required for interlocking.
***It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the operating sound and may also influence temperature sending.
Fresh air intake kit
Even in smoky environments where the air conditioning is on most of the time, the ultra long-life filter only has to be changed once a year.
Ultra long-life filter Panel spacerUse when only minimal space is available between drop ceilings and ceiling slabs.
Sealing material of air discharge outletSealing material block air discharge openings not used in 2-way or 3-way blow.
Branch duct (direct-connection round duct)Outside
Note: Use of options will increase operating sound.
The units can be installed in the following different ways.
Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing your unit.
Direct installation type
Flexible duct
T-joint pipe
Intake duct(procured locally)(duct length: 4 m max.)
Intake duct(procured locally)(duct length: 4 m max.)
With Ultra long-life filters (option), maintenance is not required in normal shops or offices for up to four years.
The condition of the drain pan anddrain water can be checked byremoving the drain plug andintake grille. Drain plug
Just open the
intake grille!
40mm
Panel spacer
A round duct can be attached without the need for a chamber.A flanged port for direct connection of a round duct is provided. An existing branch duct chamber can also be fitted (square slit hole).
Connectionchamber
Suctionchamber
Smoky atmosphere: annual filter change
Ordinary store or office: filter change every 4 years
*For dust concentration of 0.3 mg/m3 (Requires separately sold Air Cleaner.) 1 year (Approx. 5,000 hr) 15 hr/day x 28 day/month x 12 month/year
*For dust concentration of 0.15 mg/m3
4 years (Approx. 10,000 hr) 8 hr/day x 25 day/month x 4 years
Note:
Quick and easy to installJust 256 mm high. Installable in tight ceiling spaces (50LU-71LU)
Fine square panels Compact body and quiet operation
*Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room. **Wireless remote controller does not have a temperature-sensor.
Note : Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
Note: Air direction is set to the standard position when the unit is shipped from the factory. The position can be changed from the remote controller.
Panel size is same for all models, FCQ50-140LU.It is easy to maintain a neat appearance when multiple units are installed.
Optimal comfort and convenience assured by air discharge modes
Both indoor unit and wired remote controller (option) contain temperature- sensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control. This feature must be set during commissioning by the technicians.
Two selectable temperature-sensors
Even in spaces with high ceilings, a comfortable airflow is carried down to the floor level.
Suitable for high ceilings
Operation starts when the preset time of the ON timer elapses and stops when the preset time of the OFF timer elapses.
On/Off timer
Indoor unit High Low
125LU 44 34140LU 44 36
100LU 43 3271LU 35 2860LU 35 2850LU 35 28
dB(A)
Same for all models
Air direction
Auto air direction control
Settable to 5 different levels between 15° and 60°
Settable to 5 different levels between 25° and 60°
Auto-swing between15° and 60°
Auto-swing between25° and 60°
Recommended for shops with light coloured ceilings that
must be kept spotless.Standard position to
prevent draft.
Standard setting Setting to prevent soiling of ceiling*
The air direction is set automatically to the memorised position of the previous air direction.
Desired situation
Auto-swing
5-levelsair directionsetting
*Closing of the corner discharge outlets is recommended.
Number of air discharge outlets used
4-wayflow
3-wayflow
2-wayflow
4-wayflow
3-wayflow
2-wayflow
3.1 m3.4 m4.0 m
All round flow
2.7 m3.0 m3.5 m
3.0 m3.3 m3.5 m
3.5 m3.8 m-
3.4 m3.9 m4.5 m
All round flow
3.2 m3.6 m4.2 m
3.6 m4.0 m4.2 m
4.2 m4.2 m-
StandardCeiling height High ceiling
High ceiling
Criteria for ceiling height and number of air discharge outlets
950 mm 950 mm
Note: Factory settings are for standard ceiling height and all-round flow. High ceiling settings (1) and (2) are set with the remote controller by field setting.
256 mm *1 266 mm *2
*1 298 mm high with 100LU–140LU*2 308 mm high with 100LU–140LU
All models can be installed without using lifter because of the light weight.
Connection to a centralised control system is available without option
Low gas pressure detection
Drain pump is equipped as standard accessory with 850 mm lift.
Transparent drain socket
Each corner of the unit has an Adjuster Pocket that lets you easily adjust the unit's suspended height.
Since the orientation of the intake grill can be adjusted after installing,the direction of the intake grill lines can be unified when multiple unitsare installed.
Note: If the wireless remote control option is installed, a light receptor unit is housed in one of the adjuster pockets.
Easy height adjustment
Installable in any direction
Because the drain socket is transparent, after the drain piping has been installed, it is easy to check if the drain come out through the socket.High setting provides maximum reach while low
setting minimises drafts.
Switchable fan speed: High/Low
175 mm
850 mm
100LU–140LU50LU–71LU
9 10
CEILING MOUNTED CASSETTE TYPE Round Flow
(Ceiling height is reference value)
25B 29.5 24.535B 32 25
CompactSized to fit inside 600mm wide ceiling grids
Two selectable temperature-sensors
*Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room. **Wireless remote controller does not have a temperature-sensor.
Designed for low draft performance
Consistent comfort throughout
Quiet operation has been achieved even with a compact body and developed spiral hub cover that reduces the static pressure inside the indoor unit.
Both indoor unit and wired remote controller (option) contain temperature- sensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control. This feature requires initial setting by the installer.
High setting provides maximum reach while low setting minimises drafts.Switchable fan speed: High/Low
Drain pump is equipped as standard accessory with 750 mm lift.
Comfortable
QuietQuiet, small-diameter fan
Multi-Flow System Air direction can be selected according to installation.
1 pattern
4-way flow
4 patterns
3-way flow
1 pattern
2-way flow
" " denotes piping direction. Drain piping " " denotes sealing member for air discharge outlet (option) .Note: For 3-way or 2-way flow installation, the sealing
member for air discharge outlet (option) must be used to close off the unused outlet(s).
Note: Operation sound increases when using 2-way or 3-way flow.
Spiral hub cover
750 mm
Settable to 5 different levels between 0° and 35°
Settable to 5 different levels between 0° and 60°
Settable to 5 different levels between 25° and 60°
Auto-swing between 0° and 35°
Auto-swing between 0° and 60°
Auto-swing between 25° and 60°
Draft prevention setting(Set on site)
(Set on site)
Standard setting
Setting to prevent soiling of ceiling
Auto-swing operation distributes conditioned air more evenly.
Airfow angle can be adjusted in accordance with room conditions.
Auto-swing
0° 0°
0°
25°
60° 60°
0°
35°
25°
60°
35°
60°
5-levels air direction setting
Horizontal flow0° 0°
Less draftcan be felt
575 mm
575 mm
700 mm
700 mm
286 mm
High Low
Fits without the need to cut T-bar grid
T bar
600 mm600 mm
Decoration panel is also
compact.
Note: This angle above is provided as a guide. It may differ depending on the installation site.
Ceiling panel
Indoor unit
The switch box is built in to the unit, so maintenance is possible by simply removing the grill. An inspection opening is not required even for modules other than 600 x 600.
Note : Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
Note: Remote controller cable not included. Cables must be procured locally.
CleanlinessComfort Work & Servicing Control features OthersOption
Features
*1Applicable when wired remote controller is used*2Applicable when BRC1E62 is used*3Applicable when BRC1C61 is used*4 For the outdoor units
COMPACT MULTI FLOW CEILING MOUNTED CASSETTE TYPE
Quiet decor-blending form and easy installation in new or old buildings.Quiet decor-blending form and easy installation in new or old buildings.
Swin
g pa
ttern
sel
ectio
n
Switc
habl
e fa
n sp
eed
(2 s
tep)
Auto
sw
ing
Prog
ram
me
"Dry
"
Dra
in p
ump
mec
hani
sm
Pre
char
ged
for
up to
10
m
Long
-life
filte
r
Filte
r sig
n
Self-
diag
nosi
s fu
nctio
n
Fres
h ai
r int
ake
kit
Con
trol b
y 2
rem
ote
cont
rolle
rs
Auto
-rest
art
Gro
up c
ontro
l by
1 re
mot
e co
ntro
ller
Exte
rnal
com
man
d co
ntro
l
Cen
tral r
emot
e co
ntro
l
Inte
rlock
con
trol
Anti
corro
sion
trea
ted
heat
exc
hang
ers
Two
sele
ctab
le
tem
pera
ture
-sen
sors
• • • • *1 • *4 • •
Cei
ling
soilin
g pr
even
tion
• • • • • • • • • *4
BRC7E531WA signal receiver must be added to the indoor unit.
Wireless remote controller and signal receiver unit are sold as a set.
Wireless LCD remote controller
Signal receiver unit (Installed type)
Note: Remote controller cable not included. Cables must be procured locally.
Wired LCD remote controller
BRC1C61
•
Anti-
bact
eria
l air
filte
r
•
Mou
ld-p
roof
dra
in p
an
FFQ25/35B
11 12
Remote controller
*2 *2 *2 *2 *3
Setp
oint
rang
e se
t
Wee
kly
sche
dule
tim
er
Setp
oint
aut
o re
set
Off
timer
(pro
gram
med
)
On/
Off
timer
* For dust concentration of 0.15 mg/m3
Uses quiet stream fan and other quiet technologies.
Non-flocking flap
Turbulent flow is reduced
Straightening plate Quiet stream fan
Quiet operation
Easy maintenance
*Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room. **Wireless remote controller does not have a temperature-sensor.
Oil resistant grille
Note: Intended for use in salons, dining rooms, and ordinary sales floors, this specification is not suitable for kitchens or other harsh environments.
Oil-resistant plastic is used for the air suction grille. This satisfies durability in restaurants and other similar environments.
Two time settings (2500 hrs and 1250 hrs) are available to match the installation environment. Maintenance time warning is displayed on the remote controller (filter sign).
Easy-clean, flat surfaces
Long-life filter lasts about 1 year*
Comfortable
Both indoor unit and wired remote controller (option) contain temperature- sensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control. This feature requires initial setting by the installer.
Dehumidification is a microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.
Two selectable temperature-sensors
Programme "Dry"
3 fan speeds: High/Middle/Low
Installable on ceilings 4.3 m high
Flexible installation
*Water used in the test-run can now be drained from the air discharge opening rather than from the side as was formerly the case.
The unit fits more snugly into tight spaces.
Flap neatly closes when not in use.
Fresh white colour.
Drain pump kit (option) can be easily incorporatedDrain pipe connection can be done inside the unit. refrigerant and drain pipe outlets are at the same opening.
All wiring and internal servicing can be done from under the unit
Installation flexibility for freedom of design
New 140 model provides greater capacity for large spaces
Note : Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
Pipes more easily rigged
Low gas pressure detection
Condensation does not easily form on and dirt does not cling to non-flocking flap. It is easy to clean.
Non-flocking flap
(FHQ35-125BV)
The technology of the DC fan motor, wide sirocco fan, and large heat exchanger combine for greater airflow and quiet operation.
Sophisticated design
Connection to a centralised control system is available, without option.Drain pump kit (option) includes a silver ion antibacterial agent that assists in preventing the growth of slime, bacteria, and mould that cause smells and clogging.
Installable on ceilings 3.5 m high (FHQ35-125BV)
Auto swing (up and down) and louvers (left and right by hand) bring comfort to the room
Louver manually adjusts for straight or wide angle airflow
Switchable fan speed: High/Low (FHQ35-125BV)
30 mm or more
30 mm or more
High/Middle/Low : 46/42/38 dB(A)
50/60BVV1G 39 35
Indoor unit High Low35BVV1B 37 32
71BVV1B 39 35100BVV1B 42 37125BVV1B 44 39
140CA 46
---
Middle---
---------42 38
Sound operation has been reduced on the exposed ceiling suspended type unit. dB(A)
Note: Remote controller cable not included. Cables must be procured locally.
Note: Remote controller cable not included. Cables must be procured locally.
Wired LCD remote controller
BRC1C61
A signal receiver must be added to the indoor unit. Wireless LCD remote controller
CEILING SUSPENDED TYPE
Wireless remote controller and signal receiver unit are sold as a set.
Signal receiver unit (Installed type)
Comfortable airflow travels throughout the roomComfortable airflow travels throughout the room
FHQ71BV
FHQ140CANEW
35-125BV140CA
BRC7EA66BRC7GA56
CleanlinessComfort Work & Servicing Control features OthersOptions
Features
• *1 • *2 • *4 • • • • • • • *10*4*3 *7
*1FHQ35-125BV: 2 step, FHQ140CA: 3 step*2Installable on max. 3.5 m (35-125BV), 4.3 m (140CA) high ceiling *3Applicable when wired remote controller is used*4Applicable to RZR outdoor units
*5Applicable when BRC1E62 is used*6Applicable when BRC1C61 is used*7Option
*8Applicable to RKS outdoor units*9FHQ140CA only*10For the outdoor units
Maintenance possible from the front of the unitAll maintenance tasks can be carried out via front access. During service work, attachment and detachment of parts is easier.
Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.
Programme "Dry"
Two selectable temperature-sensors
Comfort even on the far side of the roomTo carry air to the far side of long rooms, extra-high airflow adds 10% more fan speed the "high" setting. Air discharge strength is selected from the remote controller by field setting.
Note: Remote controller cable not included. Cables must be procured locally.
15 16
CompactCompact design of built-in type helps blend with interior decor.
Work & Servicing
Comfortable
Height reduced to allow installation in confined spaces.
Flexibly adapts to shop interiors
L-shaped space U-shaped space Long space
To cope with the challenges of L-shaped or U-shaped spaces, it is possible to install the air discharge unit away from the main unit. At the same time, different types of architectural space can be kept comfortable.
The height of the unit is a mere 300 mm. It can be installed in a narrow ceiling space.(when access panel is used.)
Provided with condensate drain pump, waking drain piping easier in awkward spaces.
External static pressure can be set depending on duct length, presence of high-efficiency filter, and other installation conditions.
Access panel
250mm
Access panel
300mm300mm
Two selectable temperature-sensors
*Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room. **Wireless remote controller does not have a temperature-sensor.
Both indoor unit and wired remote controller (option) contain temperature-sensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control. This feature requires initial setting by the installer.
(mm)
71B 34 3060B 34 30
Indoor unit High Low50B 33 29
30060/71B
1,000800
Height
Indoor unit
WidthDepth
700
50B
Quiet operation
Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.
Programme "Dry"
Switchable fan speed: High/Low
dB(A)
Note : Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
High Standard88
Indoor unitExternal static pressure pattern
50B–71B 49 20Low
External static pressure is set to standard when the unit is shipped from the factory.
(Pa)
Control featuresWork & ServicingComfort Others
CEILING MOUNTED BUILT-IN TYPE
Clever and compact mini ducted unit provides comfort and flexibility.Clever and compact mini ducted unit provides comfort and flexibility.
Features
FBQ50/60/71B
*1Applicable when wired remote controller is used*2Applicable when BRC1E62 is used*3Applicable when BRC1C61 is used*4For the outdoor units
FBQ50BV1A
BRC4C62A signal receiver must be added to the indoor unit.
Wireless remote controller and signal receiver unit are sold as a set.
Wireless LCD remote controller
Signal receiver unit (Separate type)
• • *4*1 • • • • • • • *4•
Switc
habl
e fa
n sp
eed
(2 s
tep)
Prog
ram
me
"Dry
"
Pre
char
ged
for
up to
10
m
Filte
r sig
n
Self-
diag
nosi
s fu
nctio
n
Anti
corro
sion
trea
ted
heat
exc
hang
ers
Con
trol b
y 2
rem
ote
cont
rolle
rs
Auto
-rest
art
Gro
up c
ontro
l by
1 re
mot
e co
ntro
ller
Exte
rnal
com
man
d co
ntro
l
Cen
tral r
emot
e co
ntro
l
Inte
rlock
con
trol
Two
sele
ctab
le
tem
pera
ture
-sen
sors
•
Mou
ld-p
roof
dra
in p
an
•
Dra
in p
ump
mec
hani
sm
Note: Remote controller cable not included. Cables must be procured locally.
Note: Remote controller cable not included. Cables must be procured locally.
Increased freedom of design thanks to variable control over external static pressure
Comfort airflow achieved in accordance with conditions such as duct length.Using a DC fan motor, the external static pressure can be controlled within a range of 50 Pa to 200 Pa.
Thin, lightweight indoor unit makes delivery and installation easy.
With a height of only 300 mm, installation is possible even in buildings with narrow ceiling spaces.
Drain pump is equipped as standard accessory with 700 mm lift.
300100D 125D 140D
1,000
36
1,400700
HeightIndoor unit
WidthDepth
46Machine weight
50/60/71D
Freely control external static pressure
50 Pa 200 Pa
Set to high static pressure for advanced needs such as when using dampers and long ducts.
Set to low static pressure when ducts
are short.
Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening)
Ventilation grille
Door-installedventilation grille
Ventilation grille
Wall-installedventilation grille
Under-door cutout
Under-door cutoutWhen air conditioning two rooms simultaneously, the air discharged into each room must be circulated back to the air conditioner. To achieve this, a ventilation duct should be installed for each room or one of the indicated ventilation grilles should be installed on the partitioning wall or under the door between the rooms.
Ventilates air through the partitioning wall. (See right)
Partitioning wall
Note: The under-door cutout method should be used only when there is a small volume of airflow.
(mm)
(mm)
(mm)
(kg)
Quiet operation
When testing standard integrated ceiling units that employ duct work, much time used to be required to adjust airflow to the right level. Thanks to the ability provided by Daikin to automatically perform this troublesome adjustment using a remote controller, this step is now quick and easy. (Adjust by H tap .)1. Adjust to approximately ±10% of the rated H tap airflow. 2. Once actual operation has begun, adjustment of the rated airflow is not possible.
Reduced installation timeUse remote controller to adjust airflow
Mould-proof drain pan includes a silver ion antibacterial agent that assists in preventing the growth of slime, bacteria, and mould that cause smells and clogging.
Silver ion anti-bacterial drain pan
Maintenance is easy because the drain pan can be removed.
Easy maintenance
Clean
Both indoor unit and wired remote controller (option) contain temperature- sensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control.This feature requires initial setting by the installer. *Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room.
**Wireless remote controller does not have a temperature-sensor.
Two selectable temperature-sensors
Comfortable
dB(A)
100D 125/140DHighLow
38 4033 36
50/60/71D3732
700 mm
300mm
Easier connection with the centralised control system
Note : Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
Note: Remote controller cable not included. Cables must be procured locally.
Control featuresWork & ServicingComfort Cleanliness OthersOption
DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE
Features
*1Applicable when wired remote controller is used*2For the outdoor units*3Applicable when BRC1E62 is used*4Applicable when BRC1C61 is used*5Option
• *2• *1 *2 *2• • • • • • • *2• •
Switc
habl
e fa
n sp
eed
(2 s
tep)
Prog
ram
me
"Dry
"
Nig
ht q
uiet
ope
ratio
n
*5
Anti-
bact
eria
l air
filte
r
•
Silv
er io
n an
ti-ba
cter
ial
drai
n pa
n
Pre
char
ged
for
up to
30
m
Filte
r sig
n
Self-
diag
nosi
s fu
nctio
n
•
Emer
genc
y op
erat
ion
Low
gas
pre
ssur
e de
tect
ion
Anti
corro
sion
trea
ted
heat
exc
hang
ers
Hig
h ef
ficie
ncy
filte
r
Con
trol b
y 2
rem
ote
cont
rolle
rs
Auto
-rest
art
Gro
up c
ontro
l by
1 re
mot
e co
ntro
ller
Exte
rnal
com
man
d co
ntro
l
Cen
tral r
emot
e co
ntro
l
Inte
rlock
con
trol
•
DIII
-NET
com
mun
icat
ion
stan
dard
Two
sele
ctab
le
tem
pera
ture
-sen
sors
FBQ50/60/71/100/125/140D
BRC4C64A signal receiver must be added to the indoor unit.
Wireless remote controller and signal receiver unit are sold as a set.
Wireless LCD remote controller
Signal receiver unit (Separate type)
Note: Remote controller cable not included. Cables must be procured locally.
Wired LCD remote controller
BRC1C61
*5
Long
-life
filte
r
•
Dra
in p
ump
mec
hani
sm
19 20
Remote controller
*3 *3 *3 *3 *4
Setp
oint
rang
e se
t
Wee
kly
sche
dule
tim
er
Setp
oint
aut
o re
set
Off
timer
(pro
gram
med
)
On/
Off
timer
Enhance comfort using cleverly placed ductsEnhance comfort using cleverly placed ducts
Accessory required for indoor unit.Option
Note: Remote controller cable not included. Cables must be procured locally.
Wired LCD remote controller
BRC1C61
Floor Standing Type
New airflow control for more comfortNew airflow control for more comfort
21 22
Quiet operation
Quick and easy installation and maintenance
Lightweight indoor unit
Easier connection with the centralised control system.
Enables smooth transport and installation of the indoor unit.
The grill will not open even upon impact.
Long-life filter lasts about 1year * maintenance not requiredEnergy saving
A DC fan motor improves efficiency.
* For dust concentration of 0.15 mg/ m3
Employs a safety lock function of suction grill.
Note : Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
Long
-life
filte
r
100C 125C 140CHigh
Indoor unit 50/60/71C
50 51 5343Middle 47 48 5141Low 44 46 4838
dB(A)
39 47
100C 125C 140C
Weight
Indoor unit 50/60/71C(kg)
FVQ50/60/71/100/125/140CNEW
• • •*2 *5 • *4 •• • • • • • • • • *4
CleanlinessComfort Remote controller Work & Servicing Control features Others
Features
*3
*1Applicable when BRC1E62 is used*2Applicable for FVQ50-100*3Applicable when wired remote controller is used *4For the outdoor units
*5Applicable when BRC1C61 is used
Switc
habl
e fa
n sp
eed
(3 s
tep)
•
Inde
pend
ent u
p-an
d-do
wn
airfl
ow
*1
Auto
airf
low
rate
Auto
sw
ing
Prog
ram
me
"Dry
"
Hig
h fa
n sp
eed
mod
e
On/
Off
timer
*1
Off
timer
(pro
gram
med
)
*1
Wee
kly
sche
dule
tim
er
*1
Setp
oint
rang
e se
t
*1*4
Setp
oint
aut
o re
set
Pre
char
ged
for
up to
30
m
Anti-
bact
eria
l air
filte
r
Filte
r sig
n
Emer
genc
y op
erat
ion
Self-
diag
nosi
s fu
nctio
n
Con
trol b
y 2
rem
ote
cont
rolle
rs
Auto
-rest
art
Anti
corro
sion
trea
ted
heat
exc
hang
ers
•
DIII
-NET
com
mun
icat
ion
stan
dard
*4
Low
gas
pre
ssur
e de
tect
ion
Gro
up c
ontro
l by
1 re
mot
e co
ntro
ller
Exte
rnal
com
man
d co
ntro
l
Cen
tral r
emot
e co
ntro
l
Inte
rlock
con
trol
Two
sele
ctab
le
tem
pera
ture
-sen
sors
Nig
ht q
uiet
ope
ratio
n
Comfortable fan speed control
To carry airflow to the far side of the room, airflow rate can be increased 5% or 10% depending on the installation condition or customer's request. (Field setting by remote controller.)
High fan speed mode
Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.
Programme "Dry"
(applicable for FVQ50-100)
Airflow rate is automatically controlled in accordance with the difference between room temperature and set temperature.
Auto airflow rate is selectable.
Example applications
When cooling
Turning louvers and upward and leaving and horizontal will reduce uneven room temperature.
New comfortable airflow control1) Left and right directions
2) Up and down directions Independent up-and-down airflow directions facilitate even room temperature and help save energy.
New unit
(by remote controller)
(by hand)
Freely select both up and down airflow direction with 8-louver (horizontal blade) operation.
Each set of louvers to can be independently adjusted. (Manual adjustment)
Auto swing direction is selectable from 3 patterns to suit the layout of the room.
Pattern 1 Wide swing toward the front
When installed in the center of a wall. When installed in the corner of a room.
Pattern 2 Swing on the left side Pattern 3 Swing on the right side
Switchable fan speed: High/Middle/Low and Auto("Auto" is applicable when BRC1E62 is used.)
Accessory required for indoor unit.Option
BRC1E62 can be
incorporated into the
main unit.
(Wired Remote Controller)
Navigation Remote Controller
Note: Remote controller cable not included. Cables must be procured locally.
BRC1E62
(Applicable when BRC1E62 is used.)
These two features work to reduce noise. Guides are added to the bell mouth intake to reduce turbulence in the airflow generated by fan suction. The Aero Spiral Fan features fan blades with the bent blade edges, further reducing turbulence.
Smooth Air Inlet Bell Mouth and Aero Spiral Fan
Escaping eddies are sucked in by the bent blade edges, reducing overall turbulence.
The high efficiency compressor to achieve a high COP
2
1
DC fan motorEfficiency improved in all areas compared to AC motors, especially at low speeds.
Sine wave DC inverter
>> Smooth sine wave DC inverter Use of an optimised sine wave smoothes motor rotation, further improving operating efficiency.
Sucked gas is compressed in the scrolling part before the heated motor, so that the machine compress the non-expanded gas, resulting in high efficiency compression.
>> The structural scrollEnergy savings is realised, eliminating the friction and the leakage of refrigerant gas.
>> Swing compressor
Compressor equiped with Reluctance DC motor
3
DC fan motor structure
With the bent blade edge
Without the bent blade edge
ReluctanceDC motor
Scroll section
Suction
Discharge Motor section
RZR50/60/71/100LVVM
Technology for energy efficiency
Swing bushing Refrigerant gas
Piston by incorporated blade and roller.
500 30 60 90 120
60
70
80
90
Small load Large loadLow capacity High capacity
Reluctance DC Motor
Conventional DC motor
More than 20%
AC motor
Rotational speed (rps)
Mot
or e
ffici
ency
(%)
Daikin DC Inverter models are equipped with the Reluctance DC motor for compressor. The Reluctance DC motor uses 2 different types of torque, neodymium magnet*1 and reluctance torque*2. This motor can save energy because it generates more power with a smaller electric power than an AC or conventional DC motor.
*1. A neodymium magnet is approximately 10 times stronger than a standard ferrite magnet.
*2. The torque created by the change in power between the iron and magnet parts.
Note: Data are based on studies conducted under controlled conditions at a Daikin laboratory.
RZR125/140LVVM, RZR100/125/140LUY1
(RZR100-140 only)
3
1
2
OUTDOOR UNIT
Compact Outdoor unit
Easy installation and maintenancePre charged for up to 30 metres
Long piping length
4-direction piping offers greaterlayout freedom
Separation available
If refrigerant piping length does not exceed 30 m, there is no need for on-site gas charging.
A pump-down switch is provided to make it easier to collect refrigerant if the unit is to be moved or layout modified.
Facilitates pump down (Refrigerant recovery function)
Effective gas monitoring reduces the labor required for operation, maintenance, and repairs.
Low gas pressure detection function
The maximum capacity is maintained within a set level of power consumption, which makes it possible to keep comfort and effective demand control.
As the bottom frame is subject to corrosion, corrosion-proof galvarium steel plate is adopted to enhance the durability.Heat exchange fins provided with anti-corrosion treatment
Durability
Through use of a V-cut propeller fan that imitates the efficiency of the swan, a migratory bird, airflow becomes smooth and loss is reduced.
Energy saving
ConstructionNon-treated fin
Anti corrosion treated heat exchangers
Aluminium
AluminiumCorrosion resistantacrylic resin
Hydrophilic film
Allowed refrigerant piping length and level difference
Note : 1Additional refrigerant charging is required if the refrigerant pipe is longer than the length.
Demand Control Function
8:00 12:00 16:00 20:00
Pow
er
cons
umpt
ion
Time
Limitation
* Required for KRP58M51 (Option)
Max. length
Max. leveldifference
Pre charged1
ALL model
30 m
50 m(Equivalent length 70m)
30 m
The outer panel for the piping connection part of the front, right side and backside can be removed and is easier for post-installation piping work.
*Pump-down function is available for pre-charged refrigerant amount.
(RZR100-140 only)
Night time quiet operation functionThe Automatic night quiet mode will initiate 8 hours after the peak temperature is reached in the daytime, and normal operation will resume 10 hours after that.
4849
RZR71LVVM48RZR50/60LVVM
Sound level1 (dB(A))
RZR100LVVM/LUY150RZR125LVVM/LUY150
4445
44
4546RZR140LVVM/LUY1
Rated2 Night Quiet Mode
Note : 1Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions. 2Value when cooling. Value will differ when heating. Note : 3In case of RZR100
Reducing noise will reduce capacity slightly.
100
50
0
8:00
Peak in outdoor temperature
8 hours
Rated
10 hours
Quiet modeQuiet mode
12:00 16:00 20:00 0:00 4:00 8:00
45
49
Cap
acity
(%)
Load
(%)
Ope
ratio
n So
und3 (d
B(A)
)
Comparison of outdoor unitsRZR100KU RZR100LV
Height 1,170 mm 990 mmWeight 92 kg 78 kg
990mm
Reduced installation work thanks to light, compact outdoor unit.
Enables temperature sensing closer to target area for improved comfort. (When using remote control from another room, temperature-sensor in indoor unit's air inlet must be selected.)
Facilitates maintenance and repairAll initial settings can be set from the remote controller. After interior construction is complete, ceiling mounted cassette type can be remotely set without having to use stepladder access for manual setting.Setting contents: High ceiling use, air direction, filter type, address for centralised control (group control address is set automatically).
Remote controller is equipped with model name and failure display functions. This facilitates service in the unlikely event of a malfunction.
SkyAir shares common control with Heat Reclaim Ventilator and the other Daikin air-conditioning units, thus simplifying interlocking operations.
Easily adaptable to large-scale, high-function, centralised remote control systems.Installing and connecting control wiring between SkyAir and other Daikin air-conditioning equipment is easy.
LCD panel shows operating status in letters, numbers, and motion.Airflow / swing display Displays auto-swing operating status and setting position of air discharge angle.
Preset temperature / operation mode display Displays preset room temperature and operating status (fan, dry, cool).
Programming time display Operation start and stop time can be set for individual timers up to 72 hours. The LCD also shows when it is time to clean the filter, when changeover is under centralised control, and ventilation/cleaning.
Self-diagnosis function Monitors operating status within the system covering 40 items, and displays a message to indicate as soon as a malfunction occurs.
CEILING MOUNTED CASSETTE TYPECOMPACT MULTI FLOW TYPE
CEILING MOUNTED BUILT-IN TYPE
CEILING SUSPENDED TYPE 35-125BV140CA
BRC7E531WBRC7F633F
BRC4C62DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE BRC4C64
BRC7EA66BRC7GA56
WALL MOUNTED TYPE BRC7EB519
Wired remote controller has built-in temperature-sensor (Applies to wired remote controllers (BRC1C61/1E62))
- 5 actions per day can be scheduled for each day of the week.- The holiday function will disable schedule timer for the days that have been set as holiday.- 3 independent schedules can be set. (e.g. summer, winter, mid-season)
Display is available in 11 languages.
Dot matrix display Backlight display
ConvenienceWeekly schedule Multilingual display
Easy-to-read LCD remote controller allows various system control configurations and can control multiple indoor units. Remote controller options are shown on the page introducing each indoor unit model.
A combination of fine dots enables various icons.Large text display is easy to see.
This simple, modern designed remote controller with fresh white colour matches your interior design. Operation is much easier and smoother, just follow the indications on the navigation remote controller.
Energy savingNEW
- Sets and saves setting for an increment of time that automatically turns off air conditioner after a preset period of time for each time operation starts.- Period can be preset from 30 to 180 minutes in10-minute increments.
Off timer (programmed)
Setpoint range setNEW Setpoint auto reset
Restaurant sampleRestaurant opened
Temperature is set to 27ºC
27°C
- Saves energy by limiting the min. and max. set temperature.
- Avoids excessive heating or cooling.
- This function is convenient when the remote controller is installed at a place where any number of people may operate it.
- Even if the set temperature is changed, it returns to the preset temperature after apreset period of time.
- Period selectable from 30min/60min/90min/120min.
Full tables at lunchtimeThen is lowered to 24ºC for crowded room
24°C
After 30 minutes*Automatically returns to preset temperature (27ºC)
*Setting possible for after 30, 60, 90, and 120 minutes.
Returns to
27°Cautomatically
Signal receiver unit (For ceiling mounted cassette type)
Wireless remote controller for each indoor unit type
LCD wireless remote controller
Note: The signal receiver unit shown in the photograph is for mounting inside the decoration panel of the ceiling mounted cassette type.
Wireless remote controller
BRC7F633F
The wireless remote controller is supplied in a set with a signal receiver.Signal receiver unit is contained inside decoration panel or indoor unitShape of signal receiver unit differs according to the indoor unit.
The rubber switch and the oil-resistant plastic casing are adopted for durability.Only 17 mm thick. Can be installed either recessed or exposed.
Easy to read because of large LCD screen.Wired LCD remote controller
BRC1C61
LCD REMOTE CONTROLLER
Central remote controller
Interface adaptor for SkyAir series
Easily adaptable to large-scale, high-function, centralised remote control system.
Centralised control, with setting as simple as it is with a standardremote controller, of up to 64 groups (1,024 indoor units) is possible.
DCS302CA61 (Option)
DTA112BA51 (Option)
With its high functionality, the full colour “all-in-one” graphic controller facilitates management of SkyAir System in a variety of ways.
DCS601C51 (Option)
Unified on/off controller
Centralised control of on/off by group or all at once for up to 256 indoor units.
DCS301BA61 (Option)
Schedule timer
Unified control of weekly schedule for up to 1,024 indoor units.
DST301BA61 (Option)
Schedule timer sets on/off time in 1 minute units to be executed twice a day for a week at a time.
Simple system provides a diverse assortment of control modes.
Control by 1remote controller
Control pattern Wired remote controller Wireless remote controller
Control by 2remote controllers
Group control
Control by external command
Centralised remotecontrol
Interlock controlwith Heat Reclaim
Ventilator
(Basic system)
Link by remote controller group control.
Zone link control by centralised control.
For control from 2 locations such as in room and control room, exits, etc.
For simultaneous control of up to 16 indoor units.
Centralised control of up to 64 indoor groups from remote locationup to 1 kilometer away.
Control by 1 wireless remote controller and 1 wired remotecontroller (See note 2, 3)Signal receiver unit installed on indoor unit
Signal receiver unit installed on indoor unit
Heat Reclaim Ventilator for indoor units within a zone are operated by interlocking Can also be operated independently by remote controller.
Central remote controller (option)
Heat ReclaimVentilator
Can be operated simultaneously or independently by remote controller (set by ventilation mode)
Heat ReclaimVentilator
Central remote controller (option)
Non-polar, double-core (max. wiring length 500 m)
Connects 2 wired remote controllers (See note 1)
Automatic address setting function Automatic address setting functionSignal receiver unit installed on 1 indoor unit
Optional wiring adaptor for electrical appendices is necessary
Central remote controller (option)
Can be operated simultaneously by remote controller (set by ventilation mode)
Heat ReclaimVentilator
Heat Reclaim Ventilator for indoor units within a zone are operated by interlocking
Central remote controller (option)
Heat ReclaimVentilator
Operation and surveillance is carried out using the contact signal from the operation control box in the building surveillance (security) room.
Optional wiring adaptor for electrical appendices is necessary
Interface adapter for SkyAir series (option) is required (See note 4)
Interface adapter for SkyAir series (option) is required (See note 4)
Note: 1BRC1E62 can connect to BRC1E62 only. 2It is not possible to use two wireless remote controllers. 3BRC1E62 cannot connect to wireless remote controller. 4The ceiling mounted cassette type <Round Flow>, ceiling suspended type (140CA only), wall mounted type, duct connection middle and high static pressure type, and floor standing type come standard with an interface adaptor for SkyAir series.
Enables centralised control via connection to a high-speed, DIII-NET communication system, adopted for the Daikin VRV system.Necessary for interface adaptor for SkyAir series with the central remote control units shown at above.
The interface adaptor for the SkyAir series is optional except for the ceiling mounted cassette type <Round Flow>, ceiling suspended type (140CA only), wall mounted type, duct connection middle and high static pressure type, and floor standing type.
Simultaneous operation system
27 28
Twin Multi for comfort and economyLower installation cost than individual pair typeReduced outdoor unit installation spaceDistributed indoor units enhance comfort
Piping guidelineOutdoor unit
Max. piping length
One-way max. piping length(longest length of liquid piping or gas piping)
Max. branch piping lengthMax. difference of branch piping lengthMax. level difference between indoor units
Max. level difference between outdoor unit and indoor units
RZR125/140LVVMRZR125/140LUY1
Refrigerant branch piping kit for Twin Multi operation (option)
KHRP58P216T
2 sets of Twin Multi
For example, four indoor units are judiciously
spaced in this wide single-floor restaurant to deliver comfortable
currents of air to every corner of the room.
Twin Multi operation
Four new types of Multi series indoor units are now available!Four new types of Multi series indoor units are now available!
Branch piping kit
Branch piping kit
Branch piping kit
Main piping
Branch piping
L1
L2
L0
H
H1
Branch piping
Indoor unit
Indoor unit
Outdoor unit
Page 39
L0 L1 L2 60 m
L0 L1 50 m(In case of L1 L2)
L1, L2 20 m
L1 L2 10 m(In case of L1 L2)
H1 0.5 m
H 30 m
Branch piping kit
Page 31specificationsFCQ60/71LUV1 X2
Page 35specificationsFBQ60/71DV1 X2
Page 33specifications
FHQ60BVV1G X2FHQ71BVV1B X2
Page 36specifications
FVQ60CVE X2FVQ71CVEB X2
If there is a malfunction elsewhere in the system, the fan or compressor can still be operated.
Insufficient gas charging is normally hard to detect. During post-installation trials and regular inspection procedures, the refrigerant level is monitored by microprocessor to maintain proper gas pressure. Reliability is assured and maintenance and inspection can be carried out more quickly.
You can turn up to 16 indoor units on/off with a single remote controller. (When using connected indoor units, the settings must all be the same and on/off will be simultaneous.)
Note: Some features only available on selected models. See model pages for full list of features applicable to each unit.
Emergency operation
Low gas pressure detection
Group control by 1 remote controller
Operation and surveillance is carried out using the contact signal from the operation control box in the building surveillance (security) room.
External command control
Optional central remote controller enables centralised control of up to 1024 indoor units (64 groups) from up to 1 kilometer away.
Central remote control
Enables interlocking control with external equipment such as Heat Reclaim Ventilator.
Interlock control
The operating parameters of indoor and outdoor units, and sensor data at critical locations throughout the system, are constantly monitored using a microcomputer. To facilitate quick response in the event of a malfunction, a message appears on the LCD of the remote controller and an LED on the unit illuminates.
Self diagnosis function
Two types are available: 65% and 90% colorimetry. High-efficiency filter unit
You can provide air-conditioning with fresh air from outside. Convenient for places where a ventilation fan cannot be installed.
Fresh-air intake kit
Work and Servicing
Control features
Options
Steeper gradient realises more efficient condensate drainage. High-lift is especially useful for long lengths of drain piping.
Maintenance is not required for one year (two years when a ceiling mounted cassette type is used).
If refrigerant piping length does not exceed 30 m, there is no need for on-site gas charging.
The filter sign warns you when it is time to clean the filter. *When using a wired remote controller the sign is displayed in the LCD. When using a wireless remote controller the filter sign lamp illuminates on the signal receiver unit.
Drain pump mechanism
Long-life filter
Pre charged for up to 30 metres
Filter sign
Daikin's innovative air discharge mechanism keeps airflow away from the ceiling. Ceiling cleaning is less frequently required.
Ceiling soiling prevention function
If there is a power outage while the equipment is operating, operations will restart in the same mode as before the power cut when electricity is restored.
Ultra long-life filter
Auto-restart
Using 2 remote controllers you can operate the equipment locally or from a remote location.Note: When a wireless remote controller is used, remote control by two remote controllers is not possible.
Control by 2 remote controllers
RXS50FA/60F/71F,RKS25A/35A : 10 m*Applicable to RZR50-140.
Requires no maintenance for about 4 years* (10,000h) in stores and offices.*For dust concentration of 0.15 mg/m3
*Required for KRP58M51 (Option)
*Connecting ducts, insect nets, fire dampers, air filters, and other parts should, as required, be procured locally.
**Outside Air fan interlocked with air conditioning unit is necessary. Optional PCB(KRP1C63)is required for interlocking.
***It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the operating noise and may also influence temperature sending.
Note:
Others
To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, coated Anti corrosion treated heat exchangers (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit.In high corrosive areas, regular maintenance needs to be carried out.
Anti corrosion treated heat exchangers
Standardly equipped interface enables connection to centralised control system without need of an adaptor.
DIII-NET communication standard
29 30
Abundance of functions that provide comfortable air-conditioning in stores and offices. Note: Some features only available on selected models. See model pages for full list of features applicable to each unit.
Mould-proof drain pan prevents growth of mould in highly humid conditions.
Mould-proof drain pan
Cleanliness
Mould-proof drain pan includes a silver ion antibacterial agent that assists in preventing the growth of slime, bacteria, and mould that cause smells and clogging.
Silver ion anti-bacterial drain panThe Air filter has a anti-bacterial treatment to help prevent the growth of bacteria and mould on it.
Anti-bacterial air filter
Sanitary filter has mould-resistant treatment.Mould-proof air filter
Note: Wireless remote controllers have no temperature-sensor.
Use the temperature-sensor in the indoor unit when controlling air conditioning from another room.
Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature. Useful for reducing uncomfortable humidity without uncomfortable cooling of the room.
Delivers comfortable air-conditioning to all areas, near to and far from the air-conditioner.
High setting provides maximum reach while low setting minimises drafts.
Auto-swing Programme "Dry"
Switchable fan speed
(1) Air direction in standard setting
(2) Air direction in ceilingsoiling prevention setting
(standard, ceiling soiling prevention)
Note:When units are installed on high ceilings, depending on the model, various restrictions concerning maximum height, air discharge direction, and choice of options may apply.
You can freely set 2 air discharge setting by remote controller.
Swing pattern selectionDelivers air-conditioning comfort all the way down to the floor in air-conditioning zones with high ceilings.
High-ceiling application
Airflow rate is automatically controlled in accordance with the difference between room temperature and set temperature.
Auto airflow rate
Two selectable temperature-sensors
Comfort
The air flow direction can be fixed at your desited angle by the remote controller.
Temperature-sensors are included in the indoor unit and optional wired remote controller. Temperature sensing closer to target area is possible to further increase the comfort level.
Remote Controller
Sets and saves setting for an increment of time that automatically turns off air conditioner after a preset period of time for each time operation starts.
Off timer (programmed)
Operation starts when the preset time of the ON timer elapses and stops when the preset time of the OFF timer elapses.
On/Off timer
Up to five operation ON/OFF settings can be programmed per day for each day of the week. Not only can the time be set for the operation ON setting, but also the temperature.
Weekly schedule timer
Even if the set temperature is changed, it returns to the preset temperature after a preset period of time.
Saves energy by limiting the minimum and maximum set temperatures. Avoids excessive heating and cooling.
Setpoint auto reset
Setpoint range set
Applicable for wall mounted typeYou can increase fan speed approximately 10% higher than the "high" setting.
High fan speed mode The Automatic night quiet mode will initiate 8 hours after the peak temperature is reached in the daytime, and normal operation will resume 10 hours after that.
Night quiet operation
Independently adjust (manually) the eight horizontal blade louvers in both up and down directions to achieve an airflow that reduces uneven room temperature.
Independent up-and-down airflow
CEILING SUSPENDED TYPE
SPECIFICATIONS
W/WCOP
35
1 Phase, 220–240 V, 50 Hz
37/32195X960X680
24
3.4 (1.2-3.7)
1.053.24
White
VP20 (I.Do/ 20XO.Do/ 26)
10 to 46o/ 6.4
47550X765X285
34
1.0 (Charged for 10 m)0.6
Ivory white
2015
Hermetically sealed swing type
o/ 9.5
o/ 18.0 (Hole)
°CWB
kW
kWPower consumption
°CDBCertified operation range
Certified operation range
Motor outputCompressor
ModelName
Indoor unit
Outdoor unit
Dimensions (HXWXD)
Colour
mmdB(A)
kWRefrigerant charge (R-410A) kg
dB(A)Sound level2Dimensions (HXWXD) mmMachine weight kg
Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2Capacities are net, including a deduction for cooling for indoor fan motor heat.3Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2Capacities are net, including a deduction for cooling for indoor fan motor heat.3Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2Initial setting is standard.3Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
WALL MOUNTED TYPE
m3/min
100FAQ100CVEA
RZR100LVVM
100FAQ100CVEA
RZR100LUY1
49/45/41
17340X1,200X240
o/ 9.5
49
Ivory white
30Both liquid and gas piping
Fresh white
o/ 15.9
Hermetically sealed swing type Hermetically sealed scroll type
o/ 26.0 (Hole)
1.6 (Charged for 30 m) 3.35 (Charged for 30 m) 2.7 (Charged for 30 m)
Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2Capacities are net, including a deduction for cooling for indoor fan motor heat.3Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
Note : 1Rated cooling capacities are based on the following conditions: Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)2Capacities are net, including a deduction for cooling for indoor fan motor heat.3Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
Note : 1Rated cooling capacities are based on the following conditions: Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)2Capacities are net, including a deduction for cooling for indoor fan motor heat.3Initial setting is standard.4Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.5Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency(gravity method) 50% or more.
For each flow pattern – all round, 4-way, 3-way, 2-way, branch duct connection – the compatibility of each independently installed option (shown in the column on the left) to accessory options (listed across the top of each table) is shown in the cells where the relevant row and column intersect.A circle (o) indicates compatibility, and a cross (x) indicates incompatibility. Any options not shown below are not suitable for independent or accessory installation.
Round flow type: List of optional parts required to achieve different flow patterns
1In some cases, depending on how the unit is embedded in the ceiling, use of branch ducts and fresh air intake kits may not be possible. Before starting installation work make sure to check whether or not joint installation is possible. In particular, ensure that the lower fixing position caused by the addition of panel spacers is acceptable.
2Use a chamber connection kit if two different types of optional chamber are used together. In this case, the fresh air intake kit must be installed in the upper position.3It is not possible to use panel spacers in a 2-way flow installation. 4It is not possible to install a branch duct on the same side to which a fresh air intake kit (direct mount) is installed.
Panel/grille relatedIndependently installable optional parts
Operation control relatedAuxillary function related
Filter related
Optional accessory parts
Independently installable optional partsOptional accessory parts
Independently installable optional partsOptional accessory parts
Panel spacer1
Panel spacer1 o o ox oWireless remote controller o o oo o
Fresh air intake kit (direct mount) o o oo ox o o
xx
High-efficiency filter2
Filter related Ultra-long-life filter2
o o ox
xUltra-long-life filter2 o o o xx
High-humidity operation kit
Panel/grille relatedOperation control relatedAuxillary function related
Panel spacer1
Wireless remote controller
Fresh air intake kit (direct mount)High-humidity operation kit
All round flow 4-way flow
o3 o3 xx o3
o3 o
x
xxo o
o3 o xx
o ox o o x
o3 o o xx
3-way flow 2-way flow
1-way branch / unit 3-way flowBranch duct1(Chamber type)(Round duct type)
o o o4 xx o2-way branch / unit 2-way flow1-way branch / unit 2-way flow
x o o4 xx ox o o4 xx o
Branch duct connection
Wireless remote controller
Fresh air intake kit (direct mount)
High-efficiency filter2
High-humidity operation kit
Ultra-long-life filter2
Panel spacer1 Wireless remote controller
Fresh air intake kit (direct mount)
High-efficiency filter2
High-humidity operation kit
Ultra-long-life filter2
Panel spacer1 Wireless remote controller
Fresh air intake kit (direct mount)
Fresh air intake kit (Chamber type)1,2 o o ox o
Fresh air intake kit (Chamber type)1,2 o3 o xx o
oo
xoo
o3
o
x
x
x
o
o o o
Fresh air intake kit (Chamber type)1,2
Fresh air intake kit (Chamber type)1,2
Fresh air intake kit (Chamber type)1,2
High-efficiency filter2
High-humidity operation kit
Ultra-long-life filter2
Cooling only
OPTIONS
37 38
------------------------------
Touch Controller
Indoor unit
Kit nameName of option FHQ35BVV1B FHQ50BVV1G FHQ60BVV1G
Central remote controllerUnified ON/OFF controllerSchedule timer
Adaptor for wiringWiring adaptor for electrical appendices4
Interface adaptor for SkyAir seriesInstallation box for adaptor PCB
FFQ25BV1B FFQ35BV1BDecoration panel
Fresh air intake kit
Central remote controller3
Unified ON/OFF controller3
Schedule timer3
Adaptor for wiring2
Direct installation type
Wiring adaptor for electrical appendices2
Sealing material of air discharge outletPanel spacer
Interface adaptor for SkyAir series
Installation box for adaptor PCB
Replacement long-life filter
Remote sensor (for indoor temperature)
DCS302CA61DCS301BA61
DCS601C51DST301BA61
KRP1BA57KRP4AA53KRCS01-1B
BYFQ60B8W1/BYFQ60B3W1
BRC1C61
KDBH44BA60KDBQ44BA60A
KDDQ44XA60
DTA112BA51
KRP1BA101
KAFQ441BA60
Note: 1Wiring for wired remote controller to be procured locally.2Installation box for adaptor PCB (KRP1BA101) is necessary. 3This optional accessory requires DTA112BA51.
COMPACT MULTI FLOW CEILING MOUNTED CASSETTE TYPE
CEILING SUSPENDED TYPE
Note: 1Wiring for wired remote controller to be procured locally.2This optional accessory requires DTA112BA51.3FHQ140CA is equipped standardly with the interface adaptor for SkyAir series. DTA112BA51 is unnecessary.4Installation box for adaptor PCB is necessary.
Remote controller Wireless type Cooling only
Cooling only
FHQ71BVV1B FHQ100BVV1B FHQ125BVV1B FHQ140CAVEB
KRP1BA54DCS601C512
DCS302CA613
DCS301BA613
DST301BA613
DCS601C513
KRP4AA52DTA112BA51KRP1CA93
KHFP5MA160
KAF501DA112 KAF501DA160
KDU50N125VE
KRCS01-1BKJB311AAKJB212AA
Remote sensor (for indoor temperature)Electrical box with earth terminal (3 blocks)Electrical box with earth terminal (2 blocks)
Note: 1Wiring for wired remote controller to be procured locally.2The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.3Installation box for adaptor PCB (KRP4AA93) is necessary.
WALL MOUNTED TYPEName of option Remark
Central remote controller2
Remote controller
Unified ON/OFF controller2
Schedule timer2
Wiring adaptor for electrical appendices3
Electrical box with earth terminal (3 blocks)Electrical box with earth terminal (2 blocks)
Kit nameFAQ100CVEA
DCS302CA61DCS301BA61DST301BA61DCS601C51KRP4AA51
KJB311AAKJB212AA
Drain-up kit
Installation box for adaptor PCB
Noise filter ( For electromagnetic interface use only)
Note: 1Refer to page 10 for the details. 2Required for installing high-efficiency filter or ultra long-life filter. 3Wiring for wired remote controller to be procured locally.4The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary. 5Installation box for adaptor PCB (KRP1H98) is necessary.
DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE
Cooling only
DIMENSIONS (Unit: mm)
39 40
CEILING MOUNTED CASSETTE TYPE
Notes:1Sticking location for manufacture's label manufacture's label for indoor unit: Suction grille inner side's electric components box's lid surface manufacture's label for decoration panel : Decoration panel's corner decoration cover inner surface2In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.
3When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
4Though the installation is acceptable up to maximum of 910mm square ceiling opening, keep the clearance of 35mm or less between the indoor unit and the ceiling opening so that
the panel overlap allowance can be ensured.5Please do not place the thing been damp and troubled under an indoor unit. When the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall.
The necessary space is 500mm or more when the air-outlet is blocked with the accessory.Moreover when the corner areas are blocked (both right and left of the blocked air outlet), the necessary space is 200mm or more.
Wiring adaptor for electrical appendicesRemote sensorMounting plate for adaptor PCB.4
DCS301BA61DCS302CA61
DST301BA61
KRCS01-4BKRP4A96 5,6
KRP4AA51
Note: 1If installing a high efficiency filter on the unit, an assembly chamber for either bottom or rear suction is required. 2Wiring for wired remote controller to be procured locally. 3The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary. 4Mounting plate for adaptor PCB is necessary for each adaptor marked . 5Up to 2 adaptors can be fixed for each mounting plate.6Only one mounting plate can be installed for each indoor unit.
Wiring adaptor for electrical appendicesInstallation box for adaptor PCB
Note: 1Wiring for wired remote controller to be procured locally. 2The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.3Installation box for adaptor PCB (KRP4AA95) is necessary.
FVQ125CVEB FVQ140CVEB
KRP1BA57DCS601C51
KRP4AA52KRP4AA95
BRC1E62Wired type1Wired type1
62.5
Note)4.
210
(Direct connection)Outdoor air intake
Ceiling
4–M4 Hole
4–M8 to M10
2
25
62.5
285
Hanging bolt
172
arrow view
3
750
4
585–660 (Ceiling opening space)
320
For h
eight
instal
lation
21145 or less
183
1
295 o
r mor
e
1500
or m
ore55
300 or less
575
585–
660 (
Ceilin
g ope
ning s
pace
)
196
5
150
Adjus
table(
0–54
5)
45 or less
89
89
145
Note)2.
1500mm or more*
1500mm or more*
Required space
1500mm or more*
1500mm or more*575
6
700
62.5
260
533 (Hanging bolt pitch)
2500
or m
ore
From
the f
loor s
ide
100
62.5
205
(180
)
Drain connection side
Piping connection side
320
A
A
B
(Req
uired
spac
e)53
3 (H
angin
g bo
lt pitc
h)
7arrow view
700
B
30
8
*When the discharge grill is closeout, the required space is 200mm or more.
DIMENSIONS (Unit: mm)
41 42
6
φ80 hole
5
φ80 hole
894
Approx.475
52
105
104
98
Piping and Wiring intakeOutside line
14.5
44
Mounting location 460
44
Approx.390Approx.345
8
120 or less
For installation in high spaces
50 o
r mor
e
2500 or more
30 o
r mor
e(R
equi
red
spac
e)(R
equi
red
spac
e)
Piping direction
2 19
238
Approx.400
290
240
Dimensions for full open front panel
3
50 or moreName plate Note)2
50 or morePiping directionPiping direction
1050
7
(Requred space) (Requred space)
WALL MOUNTED TYPE
[FAQ71CVEA]
Front panelFront grillAir outletGas pipeLiquid pipeDrain hoseEarth terminalRight side pipe connection holeLeft side pipe connection hole
123456789
Notes:1
2
3
Location of unit's of Name Plate:Right side surface of casingIn case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote contorller in detail.Please do not place the thing been damp and troubled under an indoor unit. when the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall.
235
Hanging bolt1
30 or more1590(Service space)
4-M8~M10
(Service space)30 or more
11
131
197
6 57
o/ 45
91
4 5
14
83
156
6
268
42
221
Drain pipe connection VP20(For left piping)
763 5
(Note.2)Brand name plate
7
The Front
214268
105
195
156
189100
8
210
1550
260
57
210
163
2018
116
(Han
ging
bo
lt pi
tch)
(Hanging bolt pitch)
17
30
105
16
87
131 35
102
10
13
300 o
r mor
e
197
690
57
ObstacleFloor side
(Req
uire
d sp
ace)
(Requi
red sp
ace)
5Fo
r heig
ht ins
tallat
ionFro
m the
floor si
de 250
0 or m
ore
19 103
(Req
uire
d sp
ace)
5
220
15
175
Position : Hole of wall for taking out in piping back(View from the front)
40
59
115
63
Connection position of fresh air intake kit12090
51
90
φ100(Knock out hole) 9
15792
175
13412
63
60Position slit hole for taking out in piping back
(View from the front)
Notes:1
2
3
Location of unit's Name Plate: Bottom of fan housing inside the suction grille.In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.Please do not place the thing been damp and troubled under an indoor unit.When the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall.
CEILING SUSPENDED TYPE
[FHQ140CAVEB]
1234567891011121314151617181920
Air discharge grilleAir suction grilleAir filterGas pipe connectionLiquid pipe connection Drain pipe connectionEarth terminal (inside the control box) (M4)HangerRear piping penetration coverTop panel penetration coverRight side pipe connection Left back drain pipe connection Left side drain pipe connection Right side drain pipe connection Hole of wall for taking out in piping back Upward drain pipe connection Upward gas pipe connection Upward liquid pipe connectionPower supply wiring and a unit wiring back connectionPower supply wiring and a unit wiring upper connection
The Front
(Service space)30 or more
(Service space)30 or more
4-M8~M10Hanging bolt
(Note.2)Brand name plate
Position slit hole for taking out in piping back
(For left piping)Drain pipe connection VP20
80 80
225
275
170105
170
127
142 58
36
85 160
192102
185
10590
210
260
195
300
275
105
135
5
For h
eight
instal
lation
300 o
r mor
e(Re
quired
space
)
From t
he floo
r side
2500 o
r more
ObstacleFloor side
55
680
515
5
145 60
6511
560
65
135
40 50 60
912
13 15590
40
11
14
15
18 17 16
10
5
4
42
6
57
1
6
8
3
Position : Hole of wall for taking out in piping back(View from the front)
(View from the front)
o/ 45 55
80
(Hanging position)A
B
(Han
ging
p
ositi
on)
(Req
uire
d sp
ace)
(Req
uire
d sp
ace)
123456789101112131415161718
Air discharge grilleAir suction grilleAir filterGas pipe connectionLiquid pipe connection Drain pipe connectionEarth terminal (inside the electric components box)(M4)Suspension bracketBackward pipe and wiring connection opening lidUpward pipe and wiring connection opening lidRight side pipe connection Left back drain pipe connection Left side drain pipe connection Right side drain pipe connection Hole of wall for taking out in piping back Upward drain pipe connection Upward gas pipe connection Upward liquid pipe connection
Notes:1
2
3
Location of unit's Name Plate: Bottom of fan housing inside the suction grille.In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail. (Applies to FHQ35-71BV only)The remote control code is the standard <about 3 m outside the machine> attached.(0.5 mm2 2 wicks O.D. 5.4)(It is not attached to VRV.)
A92011201120112013601550
B96011601160116014001590
FHQ35BVV1B
FHQ71BVV1BFHQ100BVV1B
FHQ50BVV1GFHQ60BVV1G
FHQ125BVV1B
CEILING SUSPENDED TYPE
Liquid pipe connectionGas pipe connectionDrain pipe connectionPower supply connectionRemote control code and control wiring connectionAir discharge grilleSuction grilleDrain hose
12345
678
Notes: 1Sticking location for manufacture's label manufacture's label for indoor unit : on the bell mouth inside suction grille manufacture's label for decoration panel : on the inner frame inside suction grille2In case of using wireless remote controller, this position will be a signal receiver. refer to the drawing of wireless remote controller in detail.3When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.4Though the installation is acceptable up to maximum of 660mm square ceiling opening, keep the clearance of 45mm or less between the main unit and the ceiling opening so that the panel overlap allowance can be ensured.
COMPACT MULTI FLOW CEILING MOUNTED CASSETTE TYPE
[FHQ35-125BV]
DIMENSIONS (Unit: mm)
DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE
(SAME AS THE INDOOR UNIT SIZE OR MORE)
Fig.AAir outlet
Inspection hatch 1(450mmX450mm)
Air inletUnit base
Control box
200
or le
ss
CASE 1)
300
or m
ore
Inspection hatch
Control box
Ceiling
150
215
View
165 49
1160
245
(From the Air outlet)
7X150=1050
(All around)20-8X12 oblong hole635
1185
40
232
212
167
(467 or
less) 3
300
7169
1
(A ca
se w
ithou
t the
ceilin
g)
6
2X65
=130
290
(Not
e.4)
300 o
r mor
e
4
2
2814
4
700
11
700
or le
ss
5
3X65
=195
2500
or m
ore
Air outlet
Floor surface
Air inlet (Note.2)
Ceiling
Adjus
table
80
20-8X12 oblong hole
8X150=1200
1350
150
713300 or less
150 27
7
1325
12(All around)
247
(From the Air inlet)
(Ser
vice
spac
e)
27 63140- 4.7 Hole(All around)
48- 4.7 Hole
1438
(Han
ging
bol
t pitc
h)
700 or more
(Hanging bolt pitch)
9
16X6
5=10
40
(All around)8
10
19X6
5=12
35
450
or m
ore
200
or le
ss14
00
(Service space)
1205
65
Air inlet
Inspection hatch 450 or more
Air outlet
200
or less
Control box
Inspection hatch 1(450mmX450mm)
700 or more
(SAME AS THE INDOOR UNIT SIZE OR MORE)
Inspection hatch 2
1400
or more 170
0 or m
ore
Control box
(SAME AS THE INDOOR UNIT SIZE +300 OR MORE)
Inspection hatch 3
700 or more
View B-2
CASE 2),3)
CeilingInspection hatch
B
20
or m
ore
Control box
View B-1
According to any one of below 1)~3),secure a space for service works,such as,checking and maintenance of control box,etc.
1)One inspection hatch (450X450) on the control box side and a space of 300mm or more under the unit.(Fig.A)2)One inspection hatch (450X450) on the control box side and 2 (two) inspection hatches under the unit.(Arrow View B-1)3)3 (three) inspection hatches under the unit and the control box.(Arrow View B-2)
Notes: 1Location of MANUFACTURE'S LABEL: Control box surface2Mount the air filter at the suction side.(Select its colorimethod (gravity method) 50% or more.3Do not locate things should not be wet under the indoor unit.Dews may drop when humidity reaches over 80%,or a drain gets stuck,or air filters are not clean.4Space for Service Works
[FBQ100/125/140DV1]
43 44
Liquid pipe connectionGas pipe connectionDrain pipe connectionEarth terminal(Terminal in Control box)Control box(Inside)Remote control wiring connectionPower supply wiring and a transmission wiringAir discharge flangeAir suction flangeHangerSocket (for maintenance)Drain hose(Accessory)
1234
56
7
89101112
DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE
(From the Air inlet)
12
247
513
277
80
925
18-8X12 oblong hole
6X150=900
300 or less
950
150
(All around)
150
(Service space)
59
Air outlet Air inlet
Inspection hatch 450 or more
10
13X6
5=84
5
8
450
or m
ore 20
0 or
less
1038
(Han
ging
bol
t pitc
h)
9
65
631
805
1000
700 or more
27(Hanging bolt pitch)
11X6
5=71
5(S
ervi
ce s
pace
)
30- 4.7 Hole(All around) 30- 4.7 Hole
(All around)
16-8X12 oblong hole(All around)
(From the Air outlet)
760
435
View
245
150
785
165 5X150=750
215
49
Air inlet(Note.2)
Adjus
table
Floor surfaceCeiling
Air outlet
700
144
167
11
212
6
169290
(467 o
r less) 2
700
or le
ss
300
or m
ore
300
7 4
2500
or m
ore
3
3X65
=19540
(A c
ase
with
out
the
ceilin
g)
(Not
e.4)
1
28
5
232
2X65
=130
Ceiling
Control box
300
or m
ore
Inspection hatch
Inspection hatch 1 (450mmX450mm)
Control box
200
or le
ss
Fig.AAir outlet
Unit baseAir inlet
CASE 1)
View B-1
CASE 2),3)
Ceiling
20
or m
ore
Inspection hatch
Control box
B
Inspection hatch 2(SAME AS THE INDOOR UNIT SIZE OR MORE)
200
or le
ss10
00
or mo
re
Inspection hatch 1(450mmX450mm)
700 or more
Control box
View B-2
700 or more
1300
or
mor
e
(SAME AS THE INDOOR UNIT SIZE +300 OR MORE)
Inspection hatch 3
Control box
According to any one of below 1)~3),secure a space for service works,such as,checking and maintenance of control box,etc.
1)One inspection hatch (450X450) on the control box side and a space of 300mm or more under the unit.(Fig.A)2)One inspection hatch (450X450) on the control box side and 2 (two) inspection hatches under the unit.(Arrow View B-1)3)3 (three) inspection hatches under the unit and the control box.(Arrow View B-2)
Notes: 1Location of MANUFACTURE'S LABEL: Contro box surface2Mount the air filter at the suction side. (Select its colorimethod (gravity method) 50% or more.)3Do not locate things should not be wet under the indoor unit. Dews may drop when humidity reaches over 80%,or a drain gets stuck,or air filters are not clean.4Space for Service Works
[FBQ50/60/71DV1]
Liquid pipe connectionGas pipe connectionDrain pipe connectionEarth terminal(Terminal in Control box)Control box(Inside)Remote control wiring connectionPower supply wiring and a transmission wiringAir discharge flangeAir suction flangeHangerSocket (for maintenance)Drain hose(Accessory)
1234
56
7
89101112
630
A
D
57Service space300 or moreG
60
Suspension bolt50E
65
27
B
800
45 46
440315
25 25
145
600
Fresh sir intake position
160 P.C.D.
(Knock hole)
6-M5 Hole(Circumference)
19512
013
5
J
228
20015067
13515
021
524
530
030
0Se
rvice
spac
eNo
te)2
160
150
208
250
100
(Sus
pens
ion
posi
tion)
(Suspension position)7 8
10
26 4
13 5
9
2 6
5=13
0
3
65= 1
95
F
C
H
I
viewA
viewB
AB
125
Approx.4005
65
454
45
Piping and Wiring intake
79.5
Approx.465
6
Mounting location
φ80 hole
114
1085
14.5
φ80 hole
Outside line
Approx.46089
35.5
Piping direction
(Req
uire
d sp
ace)
(Req
uire
d sp
ace)
120 or less
8
2500 or moreFor installation in high spaces
50 o
r mor
e30
or m
ore
(Requred space) (Requred space)1200
7
50 or more 50 or morePiping directionName plate Note)2Piping direction3
9
Approx.440
Dimensions for full open front panel
242
340
2 1
240
WALL MOUNTED TYPE
[FAQ100CVEA]
Front panelFront grillAir outletGas pipeLiquid pipeDrain hoseEarth terminalRight side pipe connection holeLeft side pipe connection hole
123456789
Notes:1
2
3
Location of unit's of Name Plate:Right side surface of casingIn case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote contorller in detail.Please do not place the thing been damp and troubled under an indoor unit. when the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall.
Notes: 1Location of unit's Name Plate: Fan hosing surface.2If the ceiling is not removable, a 300 mm service space must be kept between the unit and the ceiling.3Mount the air filter at the suction side. (Select its colorimethod (Gravity method) 50 % or more)