1 10/02/2012 Slide 1 Current Transformers: Ratio and Burden Testing Prepared by Rob Reese,TESCO For the Heartland Metermans Conference - March 31, 2014
28

Current Transformers: Ratio & Burden Testing

Jun 08, 2015

Download

Technology

This presentation will give you an understanding of self contained and transformer rated current transformers. You will also discuss meter testing, CT testing, ratio & burden testing.
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Current Transformers: Ratio & Burden Testing

110/02/2012 Slide 1

Current Transformers:

Ratio and Burden Testing

Prepared by Rob Reese,TESCOFor the Heartland Metermans Conference - March 31, 2014

Page 2: Current Transformers: Ratio & Burden Testing

2

Self Contained vs. Transformer Rated

1S, 2S, 3S, 4S, 9S, 12S, 16S, 45S, etc., etc.

What’s the Difference?

Different Forms for Different Services and Applications

Page 3: Current Transformers: Ratio & Burden Testing

3

Self Contained vs. Transformer Rated

Self Contained

(direct)

Transformer Rated

(indirect)

Page 4: Current Transformers: Ratio & Burden Testing

4

Self Contained

Primarily Residential

(1S, 2S, 12S)

Relatively Low Current

Example: 100A

Page 5: Current Transformers: Ratio & Burden Testing

5

Transformer Rated

Primarily Commercial/Industrial

(9S, 16S)Relatively High Current

Example: 400A

Page 6: Current Transformers: Ratio & Burden Testing

6

Transformer Rated

Primarily Commercial/Industrial

(9S, 16S)Relatively High Current

Example: 400A

400:5

5A

Page 7: Current Transformers: Ratio & Burden Testing

7

CT’s – Functions and Terminology

Ratio

Equivalent Circuit w/ losses

Conceptual Picture of a CT

As current is applied in the primary, it produces a magnetic flux in the core. This flux flows through the core and induces a current in the secondary

windings and circuit that is proportional to the number of turns.

Page 8: Current Transformers: Ratio & Burden Testing

8

CT’s – Functions and Terminology

Ratio

For instance, a CT with a 400:5 ratio will produce 5A on the secondary, when 400A are applied to

the primary.

Page 9: Current Transformers: Ratio & Burden Testing

9

CT’s – Functions and Terminology

Thermal Rating factor

A value representing the amount by which the primary current can be increased without exceeding the allowable temperature rise.

For instance, a RF of 4.0 at 30° ambient on a 400:5 ratio CT would allow for a primary current

up to 1600A.

Page 10: Current Transformers: Ratio & Burden Testing

10

CT’s – Functions and Terminology

Accuracy Classifications and Burden

All CT’s fall within an accuracy class.

IEEE Standards have defined accuracy classes.

Page 11: Current Transformers: Ratio & Burden Testing

11

CT’s – Functions and Terminology

Accuracy Classifications and Burden

Example: 0.3% @ B0.1, B0.2, B0.5

Page 12: Current Transformers: Ratio & Burden Testing

12

CT’s – Functions and Terminology

Faceplate

Page 13: Current Transformers: Ratio & Burden Testing

13

Transformer Rated

9S Meter Installation

5A

PHASE A

SOURCE

PHASE C

PHASE B

LOAD

400A

400A

400A

5A5A

Page 14: Current Transformers: Ratio & Burden Testing

14

Transformer Rated

9S Meter Installation

5A

PHASE A

SOURCE

PHASE C

PHASE B

LOAD

400A

400A

400A

5A5A

Page 15: Current Transformers: Ratio & Burden Testing

15

Meter Testing

9S Meter Installation

5A

PHASE A

SOURCE

PHASE C

PHASE B

LOAD

400A

400A

400A

5A5A

Isolate the Meter

from the Service

Page 16: Current Transformers: Ratio & Burden Testing

16

Meter Testing

9S Meter Installation

5A

PHASE A

SOURCE

PHASE C

PHASE B

LOAD

400A

400A

400A

5A5A

? ? ?

Page 17: Current Transformers: Ratio & Burden Testing

17

Meter Testing

9S Meter Installation

5A

PHASE A

SOURCE

PHASE C

PHASE B

LOAD

400A

400A

400A

5A5A

What if?

355:5

405:5

200:5

Shorted

etc.

Page 18: Current Transformers: Ratio & Burden Testing

18

CT Testing

CT Testing is Important!

1) Test for correct ratio

2) Test for functionality at rated burdens

Page 19: Current Transformers: Ratio & Burden Testing

19

Ratio Testing

Ratio of Primary Current to Secondary Current

5A

PHASE A

SOURCE LOAD

400A

400A

400A

5A5A

Calculate Ratio

Page 20: Current Transformers: Ratio & Burden Testing

20

Burden Testing

Functionality with Burden Present on the Secondary Loop

PHASE A

Some burden will always be present – junctions, meter coils,

test switches, cables, etc.

CT’s must be able to maintain an accurate ratio with burden on

the secondary.

Page 21: Current Transformers: Ratio & Burden Testing

21

Burden Testing

Functionality with Burden Present on the Secondary Loop

PHASE A

Some burden will always be present – junctions, meter coils,

test switches, cables, etc.

CT’s must be able to maintain an accurate ratio with burden on

the secondary.

Page 22: Current Transformers: Ratio & Burden Testing

22

Burden Testing

Functionality with Burden Present on the Secondary Loop

Example Burden Spec:

0.3% @ B0.1, B0.2, B0.5or

There should be less than the 0.3% change in secondary current from initial

(“0” burden) reading, when up to 0.5Ohms of burden is applied

Page 23: Current Transformers: Ratio & Burden Testing

23

Burden Testing

Functionality with Burden Present on the Secondary Loop

ANSI Burden Values0.1 Ohms

0.2 Ohms

0.5 Ohms

1 Ohms

2 Ohms

4 Ohms

8 Ohms

Page 24: Current Transformers: Ratio & Burden Testing

24

Burden Testing

0.0000

1.0000

2.0000

3.0000

4.0000

5.0000

6.0000

0 2 4 6 8

0.3% @ B0.1, B0.2, B0.5Initial Reading = 5Amps

0.3% x 5A = 0.015A

5A – 0.015 = 4.985A

Burden Reading

0 5.0000

0.1 4.9999

0.2 4.9950

0.5 4.9900

1 4.9800

2 4.9500

4 4.0000

8 0.8000

Page 25: Current Transformers: Ratio & Burden Testing

25

Burden Testing

4.9500

4.9600

4.9700

4.9800

4.9900

5.0000

5.0100

5.0200

5.0300

5.0400

5.0500

0 0.2 0.4 0.6 0.8 1

0.3% @ B0.1, B0.2, B0.5Initial Reading = 5Amps

0.3% x 5A = 0.015A

5A – 0.015 = 4.985AAt 0.5Ohms of Burden

the secondary current is still at 4.990A – Less than 0.3% change –

Good CT!Burden Reading

0 5.0000

0.1 4.9999

0.2 4.9950

0.5 4.9900

1 4.9800

2 4.9500

4 4.0000

8 0.8000

Page 26: Current Transformers: Ratio & Burden Testing

26

Analog Testing

Application of Burden and Calculation

Manual reading of initial and post-burden secondary currents

Page 27: Current Transformers: Ratio & Burden Testing

27

Digital Testing

Application of Burden and Calculation

Reads the initial current immediately prior to applying the selected burden

Applies the selected burden to the secondary

Reads the current immediately following current application

Calculates the percentages change

Page 28: Current Transformers: Ratio & Burden Testing

28

Questions?

Please feel free to call or e-mail any questions

Rob [email protected] 215-310-8809 (cell)