8/10/2019 Cummins-Onan Power Topic White Papers - Alternator http://slidepdf.com/reader/full/cummins-onan-power-topic-white-papers-alternator 1/29 Our energy working for you. TM Power topic #5981 | Technical information from Cummins Power Generation ■White Paper Rich Scoggins — Applications Engineering Technical Specialist, Cummins Power Generation David Matuseski, PE — Technical Counsel / Critical Protection, Cummins Power Generation Alternator winding pitch and power system design Winding Pitch Considerations In this paper we will state three conclusions: ■ 2/3 pitch is recommended for all 4-wire distribution systems (i.e., distribution systems which include a neutral conductor) because 2/3 pitch alternators suppress third harmonic current which will circulate in the neutral. ■ 5/6 pitch alternators are acceptable in systems that do not include a neutral, including the majority of medium voltage/high voltage systems ■ Alternators of different pitches may be paralleled if measures are taken to eliminate or mitigate the risks of current circulating in the neutrals. Winding pitch is one of many parameters in an alternator design that must be chosen to optimize the product for its intended application. As with most design decisions, the best choice depends on the application. This paper will examine the key factors influencing the selection of alternator winding pitch and advantages and disadvantages of the two most commonly used winding pitches, 2/3 pitch and 5/6 pitch. We will also discuss concerns related to paralleling alternators of different winding pitches and how these concerns are mitigated.
29
Embed
Cummins-Onan Power Topic White Papers - Alternator
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
8/10/2019 Cummins-Onan Power Topic White Papers - Alternator
Power topic #5981 | Technical information from Cummins Power Generation
■ White Paper
Rich Scoggins — Applications Engineering Technical Specialist, Cummins Power Generation
David Matuseski, PE — Technical Counsel / Critical Protection, Cummins Power Generation
Alternator winding pitch andpower system design
Winding Pitch Considerations
In this paper we will state three conclusions:
■ 2/3 pitch is recommended for all 4-wire
distribution systems (i.e., distribution systemswhich include a neutral conductor) because2/3 pitch alternators suppress third harmoniccurrent which will circulate in the neutral.
■ 5/6 pitch alternators are acceptable in systemsthat do not include a neutral, including themajority of medium voltage/high voltage systems
■ Alternators of different pitches may be paralleledif measures are taken to eliminate or mitigate therisks of current circulating in the neutrals.
Winding pitch is one of many
parameters in an alternator design
that must be chosen to optimize the
product for its intended application.
As with most design decisions,
the best choice depends on the
application. This paper will examine
the key factors influencing the
selection of alternator winding pitch
and advantages and disadvantages
of the two most commonly used
winding pitches, 2/3 pitch and 5/6
pitch. We will also discuss concerns
related to paralleling alternators ofdifferent winding pitches and how
these concerns are mitigated.
8/10/2019 Cummins-Onan Power Topic White Papers - Alternator
Impact of leading powerfactor loads onsynchronous alternators
Power topic #6001 | Technical information from Cummins Power Generation
Many electrical loads incorporate elementsthat can impose a leading power factor on thepower source. While these loads are typicallynot a problem for utility power sources, leadingpower factor can cause generator set failures orthe failure of certain loads to operate properlyon a generator set. This paper briefly explainsthe phenomena, and what can be done toaddress problems when leading power factor
loads are present.
The problems seen when attempting to operate genera-
tor sets with leading power factor loads may seem
mysterious, but in reality, they are not too much different
from another energy absorption problem: the limited
ability of a generator set to absorb real kW power from
loads some elevator drives, and in crane applications.
A generator is physically unable to absorb more than a
very small amount of real (kW) or reactive (kVAR) power.
While the reverse kW power produced by a dropping
load in a crane application drove the engine into over-
speed conditions when it exceeded the ability of the
engine to absorb it, the reverse kVAR load presented by
leading power factor devices will drive the alternator into
over voltage conditions.
Over the past years, generator set manufacturers have
evolved their equipment designs to include use of
digital automatic voltage regulator (AVR) equipment,
separate excitation systems, and PWM-type control
architecture to enable the generator set to produce
and stable output voltage and successfully operate
non-linear loads. At the same time, manufacturers of
equipment that has non-linear load characteristics have
begun to commonly employ filters to limit harmonic
current distortion induced on the power supply.
Capacitive elements are also applied in facilities to
improve the power factor when operating on the utility
source to avoid higher energy charges. While filters
provide positive impacts on the overall power system,
they can be very disruptive to generator operation.
> White paper
By Gary Olson, Director, Power Systems Development
FIGURE 1 – In this example no load field required is 17 amps, while
full load is approximately 38 amps.
360
10 20 30 40 50 60
280
320
240
200
160
120
80
40
80
40
00
EXAMPLE
Field Current Amperes
Full Load Amperes
No LoadSaturation
1.0 P.F. 0.8 P.F.
Zero P.F.
Normal Volts
G e n e r a t o r V o l t s
G
0
250 kw – 312.5 kVa
240 Volts – 735 Amps
8/10/2019 Cummins-Onan Power Topic White Papers - Alternator
Alternator protection, part 1:Understanding code requirements
Power topic #6002 Part 1 of 3 | Technical information from Cummins Power Generation
This paper identifies requirements for protectionof alternators based on North American code.The paper also provides insight on how thecodes should be interpreted based on thecharacteristics of alternators used in emergencyand legally required generator set applications.
North American code requirementsfor alternator protection
It is nearly universal practice to protect electricaldistribution systems from the effects of electricaloverloads and short circuits, since these conditionscan cause major damage, loss of revenue, and mayeven cause loss of life. The use of overcurrent and shortcircuit protection are well-accepted and practiced forgrid-powered distribution systems, but special attentionis needed for alternator protection due to the char-acteristics of the generator sets themselves, and thedifferences in the objectives of protection on emergencysystems compared to systems served by normal power.
The design of power systems requires an appreciationof the balance between protection and reliability. Ingeneral, as protection is made more certain, reliabilityof electrical service is compromised. North Americancodes and standards recognize not only the technicaldifferences in protection needs between generatorequipment and systems, but also the need to strikethe right balance between protection and reliability inspecific applications.
Defining “alternator damage”
One of the major objectives of established codes andstandards is to prevent alternator damage, so it isimportant to understand what constitutes “alternator
damage.” Alternator windings, like other electricalconductors, will operate at increasingly higher tempera-ture as load level increases. Under overload conditionstemperatures will increase to sufficiently high levelsto cause thermal stress and ultimately insulation (andalternator) failure. Even if the alternator does not fail,even a single overload may cause the effective lifeof the alternator to be dramatically reduced withoutcausing an immediate failure.
In a simplistic sense, an alternator is damaged due to
the effects of an overcurrent condition whenever analternator fails to function, or its life is unacceptablyshortened. “Fails to function” is pretty clear—the alter-nator ceases to produce usable output, and perhapscauses damage to the facility around it. “Unacceptablyshortened life” is not a precise engineering definition foralternator damage. Alternator manufacturers typicallywill provide curves that describe the magnitude of3-phase current and duration of current flow that canbe carried by a specific alternator without causing analternator failure, or shortening of insulation systemlife to the point that the effective life of the machine isshortened too much.
Since we know that high alternator temperature is onesymptom of impending damage, it may be expectedthat one method that might be used to detect damagewould be to instrument the alternator with temperaturesensing devices (usually thermocouples) throughoutthe windings, and then define the damage point asany time that the temperature at any thermocouplereaches a predefined value. However, the responsecharacteristics of imbedded temperature detectors andtheir monitoring devices are not suitable for reportingdamage before it becomes severe, and even if theycould detect damage, the machine can be damaged
> White paper
By Gary Olson, Technical Counsel
8/10/2019 Cummins-Onan Power Topic White Papers - Alternator
The 2005 US National Electric Code® (NEC® ), NFPA 70®,makes the following references to generator protection:
240.21 Location in circuit: (G) Conductors from
Generator Terminals. Conductors from generator ter-minals that meet the size requirement in Section 445-13shall be permitted to be protected against overload bythe generator overload protective device(s) required bySection 445-12.
445.12 Overcurrent protection: (A) Constant Voltage
Generators. Constant voltage generators, except ACexciters, shall be protected from overloads by inherentdesign, circuit breakers, fuses, or other acceptableovercurrent protective means suitable for the conditionsof use. Exception to (A) through (E): Where deemed by the
Reprinted with permission from NFPA 70HB-2008, National Electric Code Handbook 2008, National Fire Protection Association, Quincy, MA 02169. This
reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety.
authority having jurisdiction, a generator is vital to the operationof an electrical system and the generator should operate tofailure to prevent a greater hazard to persons. The overload
sensing device(s) shall be permitted to be connected to an an- nunciator or alarm supervised by authorized personnel insteadof interrupting the generator circuit.
445.13 Ampacity of conductors: The ampacity ofthe conductors from the generator terminals to the firstdistribution device(s) containing overcurrent protectionshall not be less than 115 percent of the nameplatecurrent rating of the generator. It shall be permitted tosize the neutral conductors in accordance with Section220.61. Conductors that must carry ground faultcurrents shall not be smaller than required by Section250.24(C)… Exception: Where the design and operation of the
generator prevent overloading, the ampacity of the conductors shall not be less than 100 percent of the nameplate current rating.
Power topic #6002 Part 1 of 3 | Page 2
under other conditions, such as rotor (field) damagewhich can occur on unbalanced faults.
Consequently, alternator manufacturers define alterna-tor damage due to overloads based on a conservativeengineering estimate of the capability of the alternatorto resist damage on over current conditions. Theseestimates are based on testing of alternators undershort circuit conditions, measurement of current flowsand temperatures inside the machine, and an under-standing of the characteristics of the insulation systemused in a specific machine. (See FIGURE 1.) The curvesthat are drawn and provided to customers and consul-tants as a result of this testing and evaluation do notnecessarily define the exact failure point of a specificmachine. Rather, they provide an accepted guideline forwhen the life of the machine is unacceptably shortened.Use of the alternator manufacturer’s damage curve inconjunction with protective device operation curves willresult in optimum system protection while maintainingsystem reliability at acceptable levels.
The above references cite the need for overcurrentprotection both for the conductors connecting the
generator set to the first level of distribution devices(240.21) and the alternator itself (445.12). Several pointsare significant. Note that the authority having jurisdic-tion (AHJ) may allow an exception to the requirementfor protection, especially when the premature operationof the protection may cause hazards to people. Inother words, the code would allow the generator set tooperate without any protection at all, in some cases,
28-902 Protection of constant voltage generator sets
(1) Constant voltage generators, whether direct-currentor alternating-current, shall be protected from excesscurrent by overcurrent devices, except that:
(a) When the type of apparatus used and the nature ofthe system operated make protective devices inadvis-able or unnecessary, the protective device need not beprovided…
CSA C282-00 Emergency electrical power supply
for buildings, requires:
7.7.1 The overcurrent devices in the emergency distributionsystem shall be coordinated to maximize the selectivetripping of branch circuit breakers when a short circuitoccurs. Short circuit currents of sufficient magnitudeshall be made available from the generator to satisfythis coordination ability.
Power topic #6002 Part 1 of 3 | Page 3
if failure would cause a greater risk to people in thefacility served. This is a direct indication of the principalof balance noted earlier—protection of hardware shouldnot be done at expense of putting people at risk.
Note also that the code allows the alternator protectionto be used as the protective equipment for the feederconductors from the generator set to the first level ofdistribution as long as it is sized properly. Adding anotherprotective device for protection of a fully rated feederwould provide no better protection, increase the risk of
nuisance tripping, and make coordination more difficult.
This is a reasonable practice, as can be seen inFIGURE 1, which illustrates that the generator damagecurve for an alternator falls well to the left of thedamage curve for a fully rated feeder cable. So, anyprotective system that fully protects the alternator willalso protect the feeder cable.
Note also that if there is overload protection in thegenerator control system, feeder sizing can be limitedto 100% of the generator rating. (Section 445.13requires feeder protection to be 115% of the protectivedevice rating.)
The Canadian Electrical Code (22.1-1990) includesrequirements that are similar to the US NEC. Specificrequirements for generator protection are described inSection 28-902.
In addition to these requirements in both the US andCanadian codes, it is only reasonable that the system
be designed so that nuisance protective device opera-tions (i.e., circuit breaker tripping) are avoided. The lossof system operation is as disruptive and dangerouswhen on a generator set as the loss of normal facilitypower when generator set power is not available.
There is some specific recognition of this problem inthe NEC. In the exception at the end of section 445.12,it is noted that sometimes keeping the generator setrunning to protect human life is more important thanprotecting the generator set itself. NFPA 110-2002®,
which is particularly applicable to emergency andlegally required applications, states:
6.5.1 General. The overcurrent protective devices in theEPSS shall be coordinated to optimize selective trippingof the circuit overcurrent protective devices when ashort circuit occurs.
In summary, one can say that generator sets in criticalapplications can be protected in a less rigorous fashionthan other equipment, but effective protection isgenerally required; that effective protection depends oncoordinating the thermal damage curve of the alterna-tor with the protective device; and that electrical system
coordination (discrimination) is also required in mostcritical applications.
Protection for the generator set can come in manyforms. The NEC only requires that the generator setbe provided with appropriate protection. It specificallyallows overcurrent sensing devices, and inherentovercurrent protection.
8/10/2019 Cummins-Onan Power Topic White Papers - Alternator
That being said, it should be noted that the thermaldamage curve of an alternator generally follows anI2t characteristic, so circuit breakers that don’t haveoperating characteristics with that curve shape throughthe overload operating range of the alternator will bedifficult or impossible to apply in a way that adequately
protects an alternator. For example, in FIGURE 2 wesee an example situation where a 500 kW/480 VAC al-ternator is being “protected” by a typical 800A moldedcase circuit breaker with thermal magnetic trip unit.
Note that for this situation for nearly any overloadcondition the breaker operation curve lies to the rightof the thermal damage curve of the alternator, so itcan provide no protection at all. Obviously, protectionis not present even though a reasonably sized, typicalbreaker is provided.
System designers must verify that the protectionprovided is coordinated with the thermal damage
curve of the alternator, and verify that coordination withdownstream devices is provided. It cannot be assumedthat “any circuit breaker” will work—rather it is often
the case that breakers, especially thermal-magnetictrip breakers sized to the capability of the alternator willoften provide inadequate protection through all or partof the possible overload range. Better protection canbe provided by breakers with electronic trip units, ormicroprocessor-based protective relaying equipment.
Recommendations
Alternators must be protected from the effects ofovercurrent and short circuit conditions, but thisprotection must be carefully chosen with full knowledgeof the capabilities and limitations of the generator set.Protective devices that can provide proper protectioninclude:
• Circuit breakers with solid state trip units that
are fully coordinated with the alternator thermaldamage curve.
• Fuses also could be applied, but many owners
prefer not to use them because of the danger ofsingle phase operation and problems with fusereplacement in an emergency situation.
• Individual phase protective relaying properly
coordinated with the alternator thermal damagecurve.
Note that whatever protective device is chosen, itmust be specifically matched to the alternator thermaldamage curve so that potential nuisance tripping orincomplete protection is avoided. Protection should be3-phase sensing with I2t characteristic shape.
Whatever protective system is used, system designersshould review the capabilities of the protection systemand the thermal limits of the alternator to be certain thatthe machine is adequately protected. Circuit breakeroperation curves are commonly available, but alternatorthermal damage curves are generally not published andwidely distributed by alternator manufacturers. In anycase, they are needed to ascertain the viability of theprotection proposed by the supplier.
The protective system design should recognize thefact that single-phase faults are much more commonthan 3-phase faults, and provide proper protection for
the alternator under that condition. This may includeaccelerated tripping to compensate for the additionalheating effects of single-phase faults.
For additional technical support, please contact yourlocal Cummins Power Generation distributor. To locateyour distributor, visit www.cumminspower.com.
1000
100
10
1
0.1
0.01 1 0
2 0
5 0
1 0 0
2 0 0
5 0 0
1 0 0 0
2 0 0 0
5 0 0 0
1 0 0 0 0
2 0 0 0 0
5 0 0 0 0
1 0 0 0 0 0
ALTERNATOR THERMAL DAMAGE CURVE
AND MOLDED CASE BREAKER TRIP CURVE
Current in Amp Res at 480 Volts
T i m e i n S e c o n d s
GE 800A Molded Case
Circuit Breaker
Generator
FLA, 752A
MaximumInstantaneous
Trip Setting (8X)
Minimum
Instantaneous
Trip Setting (3X)
Generator
Damage
Curve
FIGURE 2 – Alternator thermal damage curve and molded casebreaker trip curve. At current levels less than 2000 amps the molded
case breaker cannot provide protection for the alternator.
8/10/2019 Cummins-Onan Power Topic White Papers - Alternator
Controls shall be provided to monitor the output current of the gen-erator set and initiate an alarm when load current exceeds 110% of
the rated current of the machine for more than 60 seconds. The con-
trols shall shut down and lock out the generator set when the outputcurrent level approaches the thermal damage point of the alternator.
Controls shall be provided to monitor the kW load on the generator
set, and initiate an alarm condition when the total load on the genera-
tor set exceeds the generator set rating for more than 5 seconds.
Control shall include a load shed control to operate a set of dry
contacts for use in shedding designated loads when the generator
set is overloaded.
An individual phase AC over voltage monitoring system monitoringall three phases of the alternator shall be provided to initiate shut-
down of the generator set when alternator output voltage exceeds
110% of the operator set voltage level for more than 10 seconds.
Shutdown shall occur with no intentional delay if alternator outputvoltage exceeds 130%. Under voltage shutdown shall occur when
the alternator output voltage is less than 85% of the operator set volt-
age for more than 10 seconds.
References
• ANSI/ NFPA 70, National Electrical Code, 2005.
• ANSI/ NFPA 99, Health Care Facilities.
• ANSI/ NFPA 110, Generator Sets for Emergency
and Standby Power Applications.
• ANSI/IEEE Std 242-1986, “IEEE Recommended Practice for
Protection and Coordination of Industrial and Commercial Power
Systems” (Buff Book), Section 11.4.
• Baker, David S., “Generator Backup Protection”,
IEEE Transactions on Industry Applications, Vol. 1A-18, No. 6,November-December 1982.
• Canadian Standards Association, C282,
“Emergency Electrical Power Supply for Buildings” 2000.
• Earley, Mark W., Murray, Richard H., and Caloggerro, John M.,
“National Electrical Code Handbook” National Fire Protection Association, Fifth Edition.
• R-1053, PowerCommand® AmpSentry™ Time Overcurrent
Characteristic Curve, Onan Corporation, 1994.
He has been employed by Cummins Power Generationfor more than 25 years in various engineering andmanagement roles. His current responsibilities includeresearch relating to on-site power applications, technicalproduct support for on-site power system equipment,and contributing to codes and standards groups.He also manages an engineering group dedicated todevelopment of next generation power system designs.
About the author
Gary Olson graduated from Iowa StateUniversity with a Bachelor of ScienceDegree in Mechanical Engineering in
1977, and graduated from the College ofSt. Thomas with a Master of Business
Power topic #6002 Part 2 of 3 | Technical information from Cummins Power Generation
Generators sets are commonly to be protectedfrom the effects of overload conditions byequipment that is required by local codes andstandards. The standards generally do notstipulate what type of protection device thatis required, so a system designer can selectprotective devices based on the needs of theapplication and the preferences of the user.This document provides an overview of over-
load protection alternatives that are availablefor generator sets.
Power topic #6002 Part 1 identified requirements for
protection of alternators based on North American codes.
Inherent overcurrent protection
The “US National Electrical Code® Handbook” (page606) notes that generator sets can be designed so thata short term overcurrent condition causes a collapseof the voltage on the output of an alternator. This limitsthe current and output kW of the alternator during an
overload or short circuit condition so that it can consid-ered inherently self-protected.
In practice, this can be achieved with a shunt-typeexcitation system design. In this type of generatorexcitation system, both the sensing and power leads ofthe voltage regulator are connected to the output of thealternator. When an overload or short circuit occurs, thecollapsing voltage on the power supply to the voltageregulator effectively limits the power available to thealternator excitation system, thus causing alternatoroutput voltage to collapse until the overload is removedfrom the system.
The weakness of this design is that shunt-type systemstypically utilize single phase sensing voltage regulators,so a single-phase fault or overload may not cause thesystem to collapse immediately. If a fault or overloadoccurred on a phase which is not used for sensing orregulation power, the overcurrent condition would bemaintained until the fault spread far enough to affectthe power supply to the voltage regulator. By that time,alternator damage may have occurred.
Shunt-type excitation systems have other weaknesses
related to motor starting and coordination (discrimina-tion) on generator sets, so they are not often specified,particularly for large or critical systems. However, theirhistorical acceptance without other overcurrent protec-tion is a precedent for acceptance of other types ofinherent protection for alternators.
Other inherent protection systems are available whichaddress the concerns stated here for shunt-type systems.
Circuit breaker protection
Molded case breakers with
thermal-magnetic trip units
Generator sets that are rated for operation at less than1000 volts, and 1200 amps and smaller are often pro-vided with a molded case circuit breaker for alternatorprotection. The molded case breaker is usually providedwith a thermal-magnetic trip unit. The “conventionalwisdom” is that this device will protect the alternatorand the feeder connecting it to the first level of distribu-tion, and these devices are often accepted for alternatorprotection by authorities. However, it is difficult (if notimpossible) to design an effective alternator protectionsystem using this equipment.
> White paper
By Gary Olson, Technical Counsel
8/10/2019 Cummins-Onan Power Topic White Papers - Alternator
In FIGURE 1 you can see an illustration of a typicalgenerator set thermal damage curve that has beenoverlaid on a time overcurrent characteristic curve fora molded case circuit breaker with thermal-magnetictrip unit. A problem is apparent from the first glance atthe chart: The thermal damage curve of the alternatoroverlaps the trip curve of the circuit breaker. For properprotection the damage curve must be entirely to theright of the trip curve of the breaker, illustrating that forany current level, for any time duration, the breaker will
positively trip before alternator damage will occur.
In general, a molded case breaker that is sized to carrythe full output of a generator set on a continuous basiswill overlap the alternator thermal damage curve. Use ofa larger breaker would make the situation even worse.
If the generator set is exposed to a bolted fault closeto the terminals of the generator set, the circuit breakermay trip in it’s instantaneous region as much as severalseconds before it needs to trip to protect the alternator.Tripping in the instantaneous region of the breakercurve can also occur due to surge currents from start-ing of large motors, or due to transformer magnetizing
current. In many cases, this would be considered anuisance trip, because there is no potential damageto any part of the system, but the breaker has clearedanyway. If this happens in the “real world”, the operatorwould probably re-adjust the trip curve of the gensetbreaker to delay tripping, thus making the trip curvemove further to the right, and providing even lessprotection to the alternator.
1000
100
10
1
0.1
0.01 1 0
2 0
5 0
1 0 0
2 0 0
5 0 0
1 0 0 0
2 0 0 0
5 0 0 0
1 0 0 0 0
2 0 0 0 0
5 0 0 0 0
1 0 0 0 0 0
ALTERNATOR THERMAL DAMAGE CURVE
AND MOLDED CASE BREAKER TRIP CURVE
Current in Amperes at 480 Volts
T i m e i n S e c o n d s
GE 800A Molded Case
Circuit Breaker
Generator
FLA, 752A
Maximum
Instantaneous
Trip Setting (8X)
Minimum
Instantaneous
Trip Setting (3X)
Generator
Damage
Curve
FIGURE 1 – At current levels less than 2000 amps the molded case
breaker cannot provide protection for the alternator.
North American requirements for generator
(alternator) protection
The 2005 US National Electric Code® (NEC® ), NFPA 70®,makes the following references to generator protection:
240.21 Location in circuit: (G) Conductors from
Generator Terminals. Conductors from generator ter-minals that meet the size requirement in Section 445-13shall be permitted to be protected against overload bythe generator overload protective device(s) required bySection 445-12.
445.12 Overcurrent protection: (A) Constant Voltage
Generators. Constant voltage generators, except ACexciters, shall be protected from overloads by inherentdesign, circuit breakers, fuses, or other acceptableovercurrent protective means suitable for the conditionsof use. Exception to (A) through (E): Where deemed by the
Reprinted with permission from NFPA 70HB-2008, National Electric Code Handbook 2008, National Fire Protection Association, Quincy, MA 02169. This
reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety.
authority having jurisdiction, a generator is vital to the operationof an electrical system and the generator should operate tofailure to prevent a greater hazard to persons. The overload
sensing device(s) shall be permitted to be connected to an an- nunciator or alarm supervised by authorized personnel insteadof interrupting the generator circuit.
445.13 Ampacity of conductors: The ampacity ofthe conductors from the generator terminals to the firstdistribution device(s) containing overcurrent protectionshall not be less than 115 percent of the nameplatecurrent rating of the generator. It shall be permitted tosize the neutral conductors in accordance with Section220.61. Conductors that must carry ground faultcurrents shall not be smaller than required by Section250.24(C)… Exception: Where the design and operation of the
generator prevent overloading, the ampacity of the conductors shall not be less than 100 percent of the nameplate current rating.
8/10/2019 Cummins-Onan Power Topic White Papers - Alternator
If a low level overcurrent condition occurs the alterna-tor will be damaged long before the breaker trips toprotect the alternator. For example (see FIGURE 1), witha 1000 amp load, the alternator will be damaged after300 seconds, but the breaker would not trip until thecondition had lasted at least 1000 seconds.
Clearly, a molded case breaker with a thermal-mag-netic trip, sized for the full output of the genset, doesnot provide effective alternator protection under allpotential failure modes and conditions. There is anotherfacet to the problem, and that is the reliability of serviceto loads when using molded case breakers.
Molded case breakers with thermal-magnetic trip unitsare generally not continuously rated devices. Unlessa breaker is specifically listed and labeled to carry a100% rating, it will carry only 80% of its nameplaterating on a continuous basis. Use of a breaker that isequal in rating to the generator output rating can limit
the ability of the generator set to operate at high currentlevels (which it is designed to do) for extended periods
of time (particularly at high ambient temperatures). Ifthe generator set is operating at a high load level, themolded case breaker can trip in the 80-100% currentrange, especially in high ambient conditions, causingan unnecessary interruption of service to critical loads.
Some designers attempt to address the derating
problem by application of oversized breakers or byuse of continuously rated breakers. Note that a largercapacity breaker would probably trip later, makingprotection less effective for the alternator. It also wouldrequire larger generator feeder conductors that addcost to the installation because the feeder conductorsize and the breaker must be coordinated to protectthe feeder. Any continuously rated breaker would stillneed to be matched to the thermal damage curve of thealternator in order to protect the alternator through alloverload conditions.
Another potential solution is to use multiple smaller
breakers to feed smaller transfer devices or systemloads. If a molded case breaker with thermal-magnetictrips is rated for approximately half the rating of thealternator, it will generally protect the machine throughall overcurrent levels and duration’s. (The designershould verify this for each application by comparison ofthe breaker trip curves and alternator thermal damagecurve.) This strategy can be used where the loads ona generator set can be split and fed to multiple circuitsdirectly from the generator set.
However, in general we can say that the most com-monly specified and applied protective system for low
voltage generator sets (molded case/thermal-magneticbreakers) will not provide necessary protection underall circumstances, and will subject the power systemto nuisance power failures due to unnecessary breakertripping.
An alternative that can be investigated is the use of“generator” type circuit breakers. These breakers areavailable from a few manufacturers, and allow bettercoordination of the genset thermal damage curve bymodifying the characteristic trip curve to be more likethe genset curve.
Molded case (and other) breakers
with solid state trip unitsBetter alternator protection can also be achieved by useof breakers with more capable trip units. In FIGURE 2an 800 amp insulated case breaker with solid state tripis overlaid on the alternator thermal damage curve. Inthis case the breaker characteristic curve shape moreclosely resembles the thermal damage curve of the
1
1000
100
10
0.1
0.01 1 0
2 0
5 0
1 0 0
2 0 0
5 0 0
1 0 0 0
2 0 0 0
5 0 0 0
1 0 0 0 0
2 0 0 0 0
5 0 0 0 0
1 0 0 0 0 0
ALTERNATOR PROTECTION
USING A MOLDED CASE BREAKER WITH SOLID STATE TRIP UNIT
Current in Amperes at 480 Volts
T i m e i n S e c o n d s
Potential
Problem Area
Generator
FLA, 752A
GE 800A RMS-9
Programmer
Generator
Damage
Curve
FIGURE 2 – This breaker provides better protection than one with a
thermal-magnetic trip unit.
8/10/2019 Cummins-Onan Power Topic White Papers - Alternator
alternator and it falls almost completely to the left of thealternator damage curve, so much better protection isprovided to the generator set. There is the potential fordamage due to a sustained low level overload conditionfor an extended period of time.
Insulated case breakers are not often applied on
generator sets since they are considerably moreexpensive than molded case breakers, and may be toolarge or fragile for direct mounting on many generatorsets. Most molded case breakers are available withsolid state trip units (usually higher ampacities). Theseallow the designer to more closely match the breakeroperation characteristic to the alternator provided.However, they do need to be adjusted for each alterna-tor, and they may not provide complete protection insome operating regions, or may be misadjusted inthe field due to what are perceived by an operator asnuisance trips.
All breakers that include instantaneous trips aresusceptible to nuisance tripping under some surge loadconditions on a generator set. (Tripping that occurs dueto peak inrush current which is less than the thermaldamage limit of the alternator, but higher than theinstantaneous pickup setting.)
A final point: The natural reaction to a breaker trip(and generator shutdown) by most operators wouldbe to reset the breaker and immediately restart themachine. If the fault were still present on the machine,the machine could be damaged on the second opera-tion. This is because the breaker would theoreticallytake the same time to clear as on initial trip, but sincethe machine is at higher internal temperatures at thestart of the fault, it would reach a higher than expectedtemperature, potentially damaging the machine. Thisproblem is present in all breakers, and most overcur-rent relays.
Overcurrent protective relaysSpecific overcurrent protective relays could be providedfor alternator protection. These are often used foralternators operating at over 1000 volts AC. Relaysare available in the marketplace that will provide goodprotection for the alternator, and may include overcur-rent, differential overcurrent, zero or negative sequencedevices. The drawback to these devices is cost, bothin terms of the design (device selection and settingsdecisions on the part of the system designer) andinstallation of the relay(s) selected. For small generatorsets the cost of a installed utility grade relay couldapproach the cost of the generator set! Installation cost
increases may be significant, since many protectivedevices are not designed for mounting or long termoperation on a generator set due to vibration or harshtemperature extremes that are common on a generatorset. Depending on the devices chosen, maintenancecosts may be increased due to the need for calibrationand other maintenance on the relays compared to otherprotective devices.
Another solution
Cummins PowerCommand® generator sets with AmpSentry™ protective relay provide the alternator
protection that is required by codes and standards andby facility owners desiring good alternator protection.Because AmpSentry protective relay is specificallydesigned for alternator protection, it can providenecessary protection without the compromises andlimitations that are necessary with other approaches.(FIGURE 3)
FIGURE 3 – PowerCommand generator sets include an overcurrentand short circuit protection algorithm that is designed specifically for
alternator protection. The I2t portion of the curve is matched to the
alternator provided on the genset.
1000
100
10
1
0.1
0.01
0
1
0.05
0
3
1
0
1 0
0
AMPSENTRY PROTECTIVE RELAY WITH
DECREMENT CURVE AND ALTERNATOR THERMAL DAMAGE CURVE
Current in Amp (Times Rated)
T i m e i n S e c o n d s
Molded Case Circuit Breaker
With Thermal-Magnetic Trip
Alternator Thermal
Damage Curve
Amsentry Protective Relay
8/10/2019 Cummins-Onan Power Topic White Papers - Alternator
PowerCommand generator set controls continuouslymonitor the output current and voltage on each phaseof the alternator. On sensing a current level of morethan 110% of the steady state rating of the generator
set for more than 60 seconds on any phase, an alarmcondition is initiated to alert the operator that an abnor-mal condition is present on the machine. The controlalso logs the time and nature of the fault condition.
If the overload continues, the control continuouslymonitors the current level and duration and performsI2t calculations to determine when the overload hasreached a point that it may damage the machine. Priorto reaching that point, the excitation system is switchedoff, thus protecting the alternator and system loadsfrom the affects of the condition. Depending on theversion of the PowerCommand control provided, the
machine may or may not operate for a short time (withexcitation switched off) to allow the engine and alterna-tor to cooldown prior to being shut down. This reducesthe risk of damage to the engine and presents nodanger to the installation since the alternator excitationsystem is switched off.
Short circuit conditions
Under 3-phase short circuit conditions, the operationof the control is slightly different than operation underovercurrent conditions. Again, the PowerCommandcontrol continuously monitors the output current andvoltage on all phases of the machine. If the control
senses current on any phase greater than 3 timesrated, it will switch to current regulation mode. Thecontrol will adjust the excitation system output to thefield of the alternator based on sensed current levelrather than sensed voltage level. The control, using apermanent magnet excitation support system providedwith the alternator, will regulate the output current to300% of the rated output current. The 300% currentlevel is intended to be sufficient to clear downstreamovercurrent protective devices. The generator set mayalso enter this state during starting of motors that arelarge relative to the size of the alternator. When the faultclears (or the motor starts), the control returns to voltage
regulation mode, and softly ramps the system voltageback to normal levels, without a voltage overshoot.
The overcurrent protective functions of an AmpSentryprotective relay does not completely reset after thefault is cleared. The control system “remembers” theovercurrent energy expended by the machine, and thetime since clearing. It will progressively move the trip
curve left to maintain protection for the alternator if it isnot fully cooled down after a fault.
AmpSentry protective relay protections in PowerCommandcontrols effectively eliminates the need for a main genera-tor set circuit breaker. AmpSentry provides both positivealternator protection and protection for the feeder con-
necting the generator set to the next level of downstreamprotective devices, as long as the feeder is sized tooperate under the full rated output of the generator set.
Throughout this document another significant assump-tion has been made: That the engine has sufficienthorsepower available to drive the alternator at rated speedduring the overload or short circuit condition. It is possiblethat under some fault conditions the horsepower load onthe engine will be sufficiently large to cause the enginespeed to drop or even collapse. PowerCommand gensetswith AmpSentry protective relay include a kW overloadfunction and under frequency protection to respond to
these conditions.
Medium voltage applications
There are no specific special protection requirementsfor medium voltage applications versus low voltageapplications. Medium voltage alternators must meet thesame general protection requirements as low voltagemachines—they must be protected.
Several IEEE documents provide recommendations forsystem design for medium voltage alternators. Theseusually incorporate many more protective functionsthan are commonly provided low voltage machines.
In addition, the IEEE recommendations often includeneutral grounding resistors for medium voltage genera-tor sets. The grounding resistor will limit line to groundfault magnitude and limit the magnitude of over voltagethat occurs on a ground fault, so that there is more timeto clear downstream faults before alternator damageand less probability of damage to the alternator due tothe over voltage condition.
Generally, system designs utilize Overcurrent and otherprotective relays to provide alternator protection ratherthan depending on a circuit breaker trip unit.
Cummins generator sets that incorporate AmpSentry
protective relay functions provide the necessary overcur-rent functions that are coordinated with the alternatorthermal damage curve, other protective functions, andfault current regulation capability that limits ground faultcurrent without impeding coordination and also preventthe over voltage condition that will occur on a groundfault due to overexcitation in the system.
Power topic #6002 Part 2 of 3 | Page 5
8/10/2019 Cummins-Onan Power Topic White Papers - Alternator
• ANSI/NFPA 110, Generator Sets for Emergency and Standby
Power Applications.
• ANSI/IEEE Std 242-2001, “IEEE Recommended Practice for
Protection and Coordination of Industrial and Commercial Power
Systems” (Buff Book), Section 12.
• Baker, David S., “Generator Backup Protection”,
IEEE Transactions on Industry Applications, Vol. 1A-18, No. 6,November-December 1982.
• Canadian Standards Association, C282,
“Emergency Electrical Power Supply for Buildings” 2000.
• Earley, Mark W., Murray, Richard H., and Caloggerro, John M.,
“National Electrical Code Handbook”, National Fire Protection Association, Fifth Edition.
• R-1053, PowerCommand AmpSentry Time Overcurrent
Characteristic Curve, Cummins Power Generation, 2007.
For additional technical support, please contact yourlocal Cummins Power Generation distributor. To locateyour distributor, visit www.cumminspower.com.
Suggested protection specifications:
Alternator shall be protected per the requirements of NFPA 70 section445.12. The protection provided shall be coordinated with the thermal
damage curve of the alternator. Damage curve and protection curve
shall be submitted to verify performance.
The protection shall allow operation of the generator set continuously
at its rated output.
The protection equipment provided shall be 3rd party certified to
verify performance.
Generator set shall be provided with individual phase line to neutral
over voltage protection that is adjustable and set to operate at morethat 110% of nominal voltage for more than 0.5 seconds.
He has been employed by Cummins Power Generationfor more than 25 years in various engineering andmanagement roles. His current responsibilities includeresearch relating to on-site power applications, technicalproduct support for on-site power system equipment,and contributing to codes and standards groups.He also manages an engineering group dedicated todevelopment of next generation power system designs.
About the author
Gary Olson graduated from Iowa StateUniversity with a Bachelor of ScienceDegree in Mechanical Engineering in1977, and graduated from the College ofSt. Thomas with a Master of Business
Alternator protection, part 3:Generator set disconnectrequirements
Power topic #6002 Part 3 of 3 | Technical information from Cummins Power Generation
In utility distribution systems protection equip-ment and disconnecting functions are oftenmerged together. However, because generatorsets can be prevented from operation, discon-necting means are often different. This paperprovides a discussion of disconnect require-ments in the USA.
Power topic #6002 Part 1 identified requirements for protection of alternators based on North American codes.
Power topic #6002 Part 2 provides an overview ofoverload protection alternatives that are available for generator sets.
Generator sets are required to have a disconnectingmeans so that the equipment can be quickly andeffectively shut down during an emergency situation(such as a fire in the facility) and to allow service tothe equipment or conductors. However, what the termdisconnect means in the context of the US National
Electrical Code® (NEC® ) does not necessarily mean aswitch or circuit breaker.
In most applications, a generator set is unlike a utilityservice, in that a generator set can be prevented from
energizing a circuit in a number of different ways. Theseinclude switching off the fuel supply, disconnectingthe starting batteries, operating a keyed auto/manualswitch, or engaging an emergency stop circuit. Thedisconnect means may also be a circuit breaker ordisconnect switch. While a disconnect switch or circuitbreaker is required to isolate a utility service from afacility distribution system, because you can’t switchoff the utility service, other means are allowed on agenerator set.
In Article 445.10 of the NEC it is clearly stated that agenerator set, unless it is in an installation where it can
be paralleled, can use any means that will prevent theengine of the generator set from operating. There arecompelling reasons to avoid use of a traditional dis-connect switch or circuit breaker as the “disconnectingmeans”:
• Addition of a molded case breaker with thermal-
magnetic trip unit can make the system less reliablebecause of the potential for nuisance tripping ofthe device due to surge loads from motor starting,or due to operation at more than the device’s
> White paper
By Gary Olson, Technical Counsel
An emergency stop switch fitted with lockout/tag-out provis ions.
8/10/2019 Cummins-Onan Power Topic White Papers - Alternator
continuous rating (usually 80% of nameplate tripsetting). A breaker would cause an extendedoutage in the system since the breaker cannot beautomatically reset. An operator must manuallyreset the breaker and re-close it to energize thesystem.
• When a breaker is opened for the purpose of
servicing a system, it may be inadvertently leftopen after service is completed. NFPA 110and NFPA 99 both require local and remote
indication that a generator set is disabled. Useof a control function integrated into the gensetcontrol system that automatically issues the “notin auto” remote indication provides an easy andeffective means to meet that requirement. A circuitbreaker or disconnect switch fitted with auxiliarycontacts that indicate the switch is open may beinterconnected to the control system to achieve therequired remote indication, but this adds cost andcomplexity to the design.
• When a breaker is used for the disconnecting
means, it may result in difficulty achieving selectivecoordination of the emergency electrical system, asis required by the NEC.
Whatever disconnecting means is used on a generatorset, it should have a lock-out/tag-out provision to allowtechnicians to prevent energization of the system untilthey have completed their work on it.
When generator sets are applied in paralleling applica-tions the paralleling breaker may be required to includea locking means to prevent energization of the feederfrom a generator set from the paralleling bus.
For additional technical support, please contact yourlocal Cummins Power Generation distributor. To locateyour distributor, visit www.cumminspower.com.
North American requirements for generator
(alternator) protection
The 2005 US National Electric Code® (NEC® ), NFPA 70®,makes the following references to generator protection:
445.10 Disconnecting means required for generators:
Generators shall be equipped with a disconnect bymeans of which the generator and all protective devicesand control apparatus are able to be disconnectedentirely from the circuits supplied by the generatorexcept where;
(1) The driving means for the generator can be readilyshut down; and
(2) The generator is not arranged to operate in parallelwith another generator or source of voltage.
100.A Service: The conductors and equipment fordelivering electric energy from the serving utility to thewiring system of the premises served.
Reprinted with permission from NFPA 70HB-2008, National Electric Code Handbook 2008, National Fire Protection Association, Quincy, MA 02169. Thisreprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety.
8/10/2019 Cummins-Onan Power Topic White Papers - Alternator
The generator set control shall include a lock-out/tag-out devicewhich is integrated with the control-mounted emergency stop
switch. The lock-out/tag-out device shall cause the generator set
to be in emergency stop mode whenever a padlock is installed onthe device, preventing the generator set from running, producing
power, or cranking.
References
• ANSI/ NFPA 70, National Electrical Code, 2005.
• ANSI/ NFPA 99, Health Care Facilities.
• ANSI/ NFPA 110, Generator Sets for Emergency
and Standby Power Applications.
• Earley, Mark W., Murray, Richard H., and Caloggerro, John M.,
“National Electrical Code Handbook” National Fire Protection
Association, Fifth Edition.
He has been employed by Cummins Power Generationfor more than 25 years in various engineering andmanagement roles. His current responsibilities includeresearch relating to on-site power applications, technicalproduct support for on-site power system equipment,and contributing to codes and standards groups.He also manages an engineering group dedicated todevelopment of next generation power system designs.
About the author
Gary Olson graduated from Iowa StateUniversity with a Bachelor of ScienceDegree in Mechanical Engineering in1977, and graduated from the College ofSt. Thomas with a Master of Business
Generator reactances are used for twodistinctly different purposes. One use is tocalculate the flow of symmetrical short circuitcurrent in coordination studies. A second usefor generator reactances are in specificationsthat limit the sub-transient reactance to 12%or less in order to limit the voltage distortioninduced by non-linear loads. For either shortcircuit or harmonic distortion analyses, the
stated reactances will need to be converted toa common base to make valid comparisons.Typically, generator reactances are publishedin per unit values on a specified base alterna-tor rating. Where the generator set ratingdiffers from the alternator base rating it will benecessary to convert the per unit values fromthe alternator base rating to the generatorset rating. For selecting circuit breakers withadequate AIC rating the maximum asymmetricalshort circuit current to flow in the first half
cycle may be approximated from the genera-tor sub-transient reactance (x"
d ) and a factor
to account for DC offset.
The flow of current in an AC circuit is controlled byimpedance. When a short circuit fault occurs in adistribution system the fault current that flows is afunction of:
1. the internal voltage of the connected machinesin the system (generators and motors),
2. the impedance of those machines,
3. the impedance to the point of the fault, mostlycable impedance,
4. and the impedance of the fault, if arcing.
The generator internal voltage and generator imped-ance determines the current that flows when theterminals of a generator are shorted. The effect ofarmature reaction on the generator air gap flux causesthe current to decay over time from an initial high value
to a steady state value dependant on the generatorreactances. Since the resistive component in genera-tors is negligible, for practical purposes it may beignored and only the reactances need be considered.Generator reactances, as determined by tests withfixed excitation, are:
> White paper
By Timothy A. Loehlein, Technical Specialist-Electrical
Calculating generator reactancesPower topic #6008 | Technical information from Cummins Power Generation
Name Symbol Range1 Effective Time
Importance
Sub-transient reactance X"d .09 – .17 0 to 6 cycles
Determines maximum instantaneous current and current at timemolded case circuit breakers usually open.
Transient reactance X'd .13 – .20 6 cycles to 5 sec.Determines current at short time delay of circuit breakers.
Synchronous reactance Xd 1.7 – 3.3 after 5 sec.
Determines steady state current without excitation support (PMG).
Zero sequence reactance Xo .06 – .09
A factor in L-N short circuit current.
Negative sequence reactance X2 .10 – .22
A factor in single-phase short circuit current.
1 Reactances shown are typical per unit values for generators ranging from 40 to 2000 kW.
8/10/2019 Cummins-Onan Power Topic White Papers - Alternator
Cummins Power Generation publishes generatorreactance values in Per-Unit (P.U.) to a base alternatorrating as specified on the alternator data sheet. Thegenerator sets however, have various base ratings, andso there is a need to convert from the alternator baseto the generator set base. This conversion is accom-plished using the following formula:
Power topic #6008 | Page 2
Sub-transient reactance
With a generator operating at full voltage, a symmetrical3-phase short circuit at its terminals will cause a largeamount of current to flow. This initial current is used todetermine the required interrupting rating of overcurrentdevices, circuit breakers and fuses, located at the
generator(s). The initial instantaneous current value(ISC
Sym ) is controlled by the sub-transient reactance
(X"d ) and is expressed by the voltage divided by the
sub-transient reactance, or:
ISCSym
= E AC
÷ X"d
In per unit, assuming a 0.10 sub-transient reactance,the initial symmetrical short circuit current expressed inmultiples of full load current:
ISCSym
= 1.0 ÷ 0.10 = 10 = 1000% of full load current
Reactances, including the sub-transient, are expressedwith a plus or minus tolerance of 10%, typically.Determination of the maximum current should use theworst case tolerance of minus 10%. The maximumsymmetrical current from the example above becomes:
ISCSym
= 1.0 ÷ (0.10 – 10%) = 11.1 = 1110% of full load current
The peak current in the first half cycle will also includea DC component, the magnitude of which depends onthe point in the cycle when the short circuit occurs.
A DC component offsets the symmetrical currentaround the zero axis resulting in asymmetry. If the shortoccurs at point where voltage is at its peak, the DCcomponent will be zero. If the short occurs at the point
where voltage is at zero, the DC component will be atits maximum, and the peak current will be almost twotimes the symmetrical current.
In practice the actual DC offset will likely range some-where between zero offset and the maximum offset.However, for the purpose of selecting the interruptingrating of circuit breakers the assumption that the DCoffset will be at maximum is a safe and conservativeassumption (ISC
Sym x 2). Generally, circuit breaker
interrupting ratings are expressed in RMS Symmetrical Amperes and are tested to achieve near maximumoffset at that symmetrical current magnitude. Select
breakers, then, based on the maximum allowablegenerator symmetrical short circuit current.
FIGURE 1 – Symmetrical current
FIGURE 2 – Asymmetrical current
P.U.Z.new = P.U.Z.given
base kV given
2
base kV new( )
base kVA new
base kVA given( )
8/10/2019 Cummins-Onan Power Topic White Papers - Alternator
related to the generator set sub-transient reactance.The higher the reactance is, the higher the voltagedistortion. Reducing the source impedance (reactance)reduces the voltage distortion. This calculation willneed to be used to check and compare suppliers’submittals against specifications. In the example, whilea 125°C rise alternator may have been specified, 105°Calternator would have to be supplied to meet a 0.12per-unit or less sub-transient reactance requirement.
Summary
The sub-transient reactance of a generator set is usedto calculate the maximum available short circuit currentfor selecting circuit breakers with adequate interruptingrating. Since nearly all of the generator impedance isreactance, addition of the DC component for the first fewcycles may almost double the symmetrical value of cur-rent. Specifications that limit the sub-transient reactance(x"
d ) to 12-per-unit or less limit the voltage distortion
caused by non-linear load currents. Calculation of theavailable short circuit current using per-unit values mayrequire converting from the alternator base rating to thegenerator set base rating using the formula provided.
For additional technical support, please contact yourlocal Cummins Power Generation distributor. To locateyour distributor, visit www.cumminspower.com.
For example, suppose you want to find the sub-transient reactance (X"
d ) in Per-Unit for the 105°C rise,
480 volt alternator on a 750 kW DFHA generator set.From the generator set specification sheet, S-1132,the alternator data sheet is ADS-311. ADS-311 showsa sub-transient reactance of 0.16 P.U. based on the125°C alternator base rating of 1300kVA. The base kVArating of the 750DFHA is 938 kVA. Using the formula,calculate X"
d on the generator set base as follows:
Limiting voltage distortion
It is becoming commonplace for consulting engineersto limit sub-transient reactance in specifications to 0.12per-unit or less to limit generator voltage distortioncaused by non-linear load induced harmonic currents.The alternator source voltage distortion induced bythe harmonic (sub-cyclic) current distortion is directly
Design Engineer, Technical Project Leader and ProjectManager. His current position is a Technical Specialist-Electrical in application engineering for CumminsEnergy Solutions Business, supporting combined heatand power (CHP) and peaking applications.
About the author
Timothy A. Loehlein is a graduate of theUniversity of Minnesota with a Bachelorof Electrical Engineering and a PE inMinnesota. Tim has been a CumminsPower Generation employee since 1976in positions as Application Engineer,