SS-340D 3/04 PRODUCT SPECIFICATIONS www.goodmanmfg.com High-Efficiency Split System Heat Pump The CPLJ outdoor split system heat pump is designed for ground-level or rooftop mount. Accessories • Standard room thermostat with 1-stage cool/1-stage heat (CHT18-60) • Digital room thermostat with 1-stage cool/1-stage heat (CHTD18-60) • Outdoor thermostats for stage/multi-stage indoor heating units (OT/EHR18-60) CPLJ SERIES 12 SEER Cabinet Construction • Polyester powder paint provides premium durability and improved UV protection • Heavy gauge, zinc-clad, G90 galvanized steel • When properly anchored, meets the 2001 Florida Building Code unit integrity requirements for hurricane-type winds 1 to 5 Ton [5.28 kW to 17.56 kW] Air Handler and Coil Compatibilities • CA and CH indoor coils • U, UC, H and HT fan-less indoor coils for heat pump or cooling applications • AEPT, ARPF, ARPT and ARUF multi-position electric heat air handlers • AWB vertical wall-mounted electric heat air handler • AH vertical wall-mounted hydronic heat air handler • AC ceiling-mounted electric heat air handler • ACHP ceiling-mounted hydronic heat air handler Standard Features • Louvered guard protects coil from damage and adds strength to unit • Copper tube, aluminum fin coil construction • Brass suction and liquid shut-off valves with sweat connections • Quiet operating top discharge • Totally enclosed, permanently lubricated condenser motor • Fully charged for 15’ [4.57m] of tubing length • Discharge line muffler • Low-pressure control for loss of charge protection • Factory-installed bi-flow liquid line filter drier • Suction line accumulator • Check-flowrater expansion device • Time-initiated, temperature terminate defrost • Bottom pan rails elevate unit above slab • Crankcase heater (where indicated) • High-efficiency compressor with internal high- pressure relief
8
Embed
CPLJ SERIES - Air Conditioning and Heating - · PDF fileCPLJ SERIES 12 SEER Cabinet Construction •Polyester powder paint provides premium durability and improved UV protection •Heavy
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
SS-340D 3/04
PRODUCT SPECIFICATIONS
www.goodmanmfg.com
High-EfficiencySplit System Heat Pump
The CPLJ outdoor split system heat pump is designed for ground-level or rooftop mount.
Accessories• Standard room thermostat with 1-stage cool/1-stage
heat (CHT18-60)• Digital room thermostat with 1-stage cool/1-stage
heat (CHTD18-60)• Outdoor thermostats for stage/multi-stage indoor
and improved UV protection• Heavy gauge, zinc-clad, G90 galvanized steel• When properly anchored, meets the 2001 Florida
Building Code unit integrity requirements for hurricane-type winds
11⁄2 to 5 Ton[5.28 kW to 17.56 kW]
Air Handler and Coil Compatibilities• CA and CH indoor coils• U, UC, H and HT fan-less indoor coils for heat pump
or cooling applications• AEPT, ARPF, ARPT and ARUF multi-position
electric heat air handlers• AWB vertical wall-mounted electric heat air handler• AH vertical wall-mounted hydronic heat air handler• AC ceiling-mounted electric heat air handler• ACHP ceiling-mounted hydronic heat air handler
Standard Features• Louvered guard protects coil from damage and adds
strength to unit• Copper tube, aluminum fin coil construction• Brass suction and liquid shut-off valves with
sweat connections• Quiet operating top discharge• Totally enclosed, permanently lubricated
condenser motor• Fully charged for 15’ [4.57m] of tubing length• Discharge line muffler• Low-pressure control for loss of charge protection• Factory-installed bi-flow liquid line filter drier• Suction line accumulator• Check-flowrater expansion device• Time-initiated, temperature terminate defrost• Bottom pan rails elevate unit above slab• Crankcase heater (where indicated)• High-efficiency compressor with internal high-
XX designates electric heat quantity.HSPF = heating seasonal performance factor.When mix matching outdoor and indoor units, the indoor unit check-flowrator must match the outdoor unit size.See “AR” unit for coil instructions.EEP - Order from service dept. part No. B13707-38 or new Solid State Board B13707-35S. Part No. B13707-38 is not interchangeable with B13707-35S.(1) Certified per ARI 240 @ 80 ºF/67 ºF/95 ºF(2) TVA Rating(3) Energy Efficiency Ratio @ 80 ºF/67 ºF/95 ºF(4) Seasonal Energy Efficiency Ratio
3
PRODUCT SPECIFICATIONS
MODEL OUTDOOR SECTION
MODEL INDOOR SECTIONTOTAL
COOLING BTUH (1)
SENSIBLE COOLING
BTUH
(2) BTUH @75ºF/63ºF-95ºF COOLING
SEER(4)COOLING EER (3)
HEATING BTUH47°F
HEATING COP47ºF
HEATING BTUH17ºF
HEATING COP17ºF
HEATING HSPF DECIBELS
TOTAL SENS.
CPLJ36-1A
AC36-XXAWB36-XX/ARPT036/ARUF036
U/UC42+EEPHT4248/H49F+EEPARPT042/ARUF042
AEPT036ARPF048
CA*F042*2A+EEPCHPF042B2A+EEP
320003300034000340003400035000350003400034000
230002380024500245002450025900259002450024500
302003115032100321003210034000340003210032100
240002490023300233002330024600246002330023300
11.0011.3012.0012.0012.0013.0012.0012.0012.00
10.0010.3011.0011.0011.0012.0011.0011.0011.00
310003300035000350003500035000350003500035000
2.803.203.503.503.503.503.503.503.50
170001900020000200002000020000200002000020000
2.002.102.302.302.302.302.302.302.30
7.007.507.807.807.808.007.807.807.80
80
CPLJ42-1A
ARPT042/ARUF042U/UC60+EEP
HT61/H61F+EEPARPF048/ARPT049/ARUF049
AEPT060-00A-1CA*F060*2A+EEPCHPF060D2A+EEP
38500400004000040000410004000040000
27600304003040030400310003040030400
36200378003780037800378003780037800
29300293002900029300299002930029300
11.3012.0012.0012.0013.0012.0012.00
10.3011.0011.0011.0012.0011.0011.00
38500400004000040000400004000040000
3.303.503.503.503.503.503.50
21000224002240022400230002240022400
2.102.302.302.302.302.302.30
7.508.008.008.008.308.008.00
80
CPLJ48-1A
ARUF048ARPT049/ARUF049
U/UC60+EEPHT61/H61F+EEP
AEPT060ARPF060/ARPT061/ARUF061
CA*F060*2A+EEPCHPF060D2A+EEP
4400044000440004400046000460004400044000
3250032500325003250035000350003250032500
4150041500415004150043400434004150041500
3100031000310003100033600336003100031000
11.5012.0012.0012.0012.5012.0012.0012.00
10.5011.0011.0011.0011.5011.0011.0011.00
4400045000450004500046000460004500045000
3.303.503.503.503.603.603.503.50
2400025000250002500027000270002500025000
2.202.302.302.302.402.402.302.30
7.508.008.008.008.508.008.008.00
80
CPLJ60-1A
ARUF060U/UC62+EEP
ARPF060/ARPT061/ARUF061HT61/U/UC61+EEP
H61F+EEPAEPT060
CA*F061*2A+EEPCHPF060D2A+EEP
5500055000560005600056000560005600056000
3960039600403004030040300403004030040300
5190051900526005260052600526005260052600
3700037000377003770037700377003770037700
11.3011.5012.0012.0012.0012.0012.0012.00
10.3010.5011.0011.0011.0011.0011.0011.00
5500055000560005600056000560005600056000
3.203.203.303.303.303.303.303.30
3000030000310003100031000310003100031000
2.102.102.302.302.302.302.302.30
7.507.508.008.008.008.508.008.00
80
Cooling and Heating Performance Data (cont.)
XX designates electric heat quantity.HSPF = heating seasonal performance factor.When mix matching outdoor and indoor units, the indoor unit check-flowrator must match the outdoor unit size.See “AR” unit for coil instructions.EEP - Order from service dept. part No. B13707-38 or new Solid State Board B13707-35S. Part No. B13707-38 is not interchangeable with B13707-35S.(1) Certified per ARI 240 @ 80 ºF/67 ºF/95 ºF(2) TVA Rating(3) Energy Efficiency Ratio @ 80 ºF/67 ºF/95 ºF(4) Seasonal Energy Efficiency Ratio
XX designates electric heat quantity. HSPF = heating seasonal performance factor.When mix matching outdoor and indoor units, the indoor unit check-flowrator must match the outdoor unit size. See “A” unit for coil instructions.EEP - Order from service dept. part No. B13707-38 or new Solid State Board B13707-35S. Part No. B13707-38 is not interchangeable with B13707-35S. (1) Certified per ARI 210/240 @ 26.6 ºC/19.4 ºC/35 ºC(2) TVA Rating(3) Energy Efficiency Ratio @ 26.6 ºC/19.4 ºC/35 ºC(4) Seasonal Energy Efficiency Ratio
5
PRODUCT SPECIFICATIONS
Electrical Data
† With Crankcase Heat* May use fuses or HACR type Circuit Breakers of the same size as noted+ Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes**With Scroll Compressor