This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
General Purpose Relays RSLRefer to Catalog DIA3ED2090304EN-US
Zelio™ Interface RelaysZelio RSL slim interface relays save valuable panel space with a 6 mm width and have a 6 Amp general purpose load rating. Features include:• Pre-assembled option: relay and socket are combined into one catalog number.• Universal AC/DC sockets have built-in protection from transients and reverse polarity voltages (see catalog
DIA3ED2090304EN-US for more detailed information).• Accessories, which include isolators, ID tags, and bus jumper save valuable installation time.
a Relays are mounted on sockets equipped with LED and protection circuit.
Approvals for RSL relays:
Approvals for RSLZ sockets:
Table 23.1: Zelio RSL Slim Interface: Pre-assembled Relay + Socket (sold in lots of 10)
Table 23.4: Socket AccessoriesDescription Compatibility Catalog Number $ Price ea.
ID tags (2 sheets of 64 tags) With all sockets RSLZ5 4.60Bus jumper (10 x 20-pole jumpers) With all sockets RSLZ2 3.80Butterfly isolator (10 isolators) With all sockets RSLZ3 3.70
General Purpose Relays RSBRefer to Catalog DIA3ED2090304EN-US
Zelio™ Plug-In Interface RelaysZelio RSB interface relays and sockets provide the optimum combination of robust performance and space saving for the most demanding applications. Relays are rated at 8 A, 12 A, and 16 A (250 Vac / 28 Vdc). Features include:• Optional protection modules for protection against electrical spikes• Optional plastic hold-down ejector clips• Socket or printed circuit board installation options
a To order a relay complete with socket (sold in lots of 20): add suffix S to the catalog numbers selected above.Example: RSB 2A080RD + RSZ E1S48M becomes RSB 2A080RDS.
b When using the relay with socket RSZ E1S48M, terminals must be jumpered.
Approvals for RSB relays:
Approvals for RSB sockets:
RZM modules are RoHS compliant as of date code 0610.
For mounting track, see page 24-16.
Table 23.5: Relays (sold in lots of 10)
Coil Voltage
Number and type of contacts - Thermal current (Ith)
General Purpose Relays RXMRefer to Catalog DIA3ED2090304EN-US
Zelio™ Plug-In RelaysZelio RXM miniature plug-in relays and sockets provide a complete system solution in response to the most demanding applications ranging from 3A to 12A. Some of the features include:• Test button with removable lock-down door for testing
the contacts (depending on model)
• Green LED indication of relay status (depending on model)
• Mechanical indication of relay status (standard)• Optional protection modules to protect against
electrical spikes• Bus jumpers for connecting multiple terminals reduce
installation timeIO
For sockets and accessories, see page 23-5.Approvals for Relays:
a When used with the appropriate socket.
RXM2AB2F7
RXM4GB2F7
Table 23.9: Miniature relays without LED, with Test Button and Lock-Down Door (sold in lots of 10)
Number and type of contacts - Thermal current (Ith)
2 C/O -12 A Res. 3 C/O - 10 A Res. 4 C/O - 8 A Res.
Coil Voltage Catalog Number $ Price ea. Catalog Number $ Price ea. Catalog Number $ Price ea.
Separate Box lug connectorRXM2••••• RXZE2S108Mc 5.00RXM3••••• RXZE2S111Mb 5.00RXM4••••• RXZE2S114Mb 5.00
Table 23.18: Protection modules (sold in lots of 10)
Description Voltage For use with Catalog Number $ Price ea.
Diode 6–250 Vdc All sockets RXM040W 1.90
RC circuit24–60 Vac All sockets RXM041BN7 1.90110–240 Vac All sockets RXM041FU7 1.90
Varistor6–24 Vac/Vdc All sockets RXM021RB 1.9024–60 Vac/Vdc All sockets RXM021BN 1.90110–240 Vac/Vdc All sockets RXM021FP 1.90
Table 23.19: Accessories (sold in lots of 10)
Description For use with Catalog Number $ Price ea.
Metal hold-down clip All sockets RXZ400 .50Plastic hold-down ejector clip All sockets RXZR335 .50Bus jumper, 2-pole (Ith: 5 A) All sockets with separate contacts RXZS2 .70DIN rail mounting adapter All relays RXZE2DA .70Panel mounting adapter All relays RXZE2FA .50
ID tagsAll relays (sheet of 108 tags) RXZL520 .10All sockets except RXZE2M114 RXZL420 .10
General Purpose Relays RPMRefer to Catalog DIA3ED2090304EN-US
Zelio™ Plug-In RelaysZelio RPM plug-in relays and sockets provide a complete system solution in response to the most demanding applications up to 15 A. Some of the features include:• Test button with removable lock-down door for testing the contacts (depending on model)• Green LED indication of relay status (depending on model)• Mechanical indication of relay status (standard)• Optional modules to protect against electrical spikes
Approvals for relays:
Approvals for Sockets:
Table 23.20: Power relays without LED, with Test Button and Lock-Down Door (sold in lots of 10)
Number and type of contacts - Thermal current (Ith)
1 C/O - 15 A Res. 2 C/O - 15 A Res. 3 C/O - 15 A Res. 4 C/O - 15 A Res.
Coil Voltage Catalog Number $ Price ea. Catalog Number $ Price ea. Catalog Number $ Price ea. Catalog Number $ Price ea.
General Purpose Relays RUMRefer to Catalog DIA3ED2090304EN-US
Zelio™ Plug-In RelaysZelio RUM plug-in relays and sockets provide a complete system solution in response to the most demanding applications up to 16 A. Some of the features include:• Test button with lock-down door for testing the contacts (depending on model)• Green LED indication of relay status (depending on model)• Mechanical indication of relay status (standard)• Optional protection modules to protect against electrical spikes• Bus jumpers for connecting multiple terminals reduce installation time
Approvals for Relays:
Table 23.27: Relays for standard applications without LED, with Test Button and Lock-Down Door(sold in lots of 10)
Pins Coil Voltage
Number and type of contacts - Thermal current (Ith)
2 C/O -16 A Res. 3 C/O -16 A Res.
Catalog Number $ Price ea. Catalog Number $ Price ea.
General Purpose Relays RUMRefer to Catalog DIA3ED2090304EN-US
a The inputs are mixed with the relay coil terminals, with the outputs located on the opposite side of the socket.b The inputs and outputs are separated from the relay coil terminals.
c See timer module description (selection of functions and time delays) in catalog 8501CT0601.
Approvals for Sockets:
Zelio™ RPF Power RelaysRPF Zelio power relays respond to the most demanding applications up to 30 A. Features include:• UL Listed• Sealed construction• Motor load ratings: 1hp @ 120 Vac / 3hp @ 240 Vac (N/O contacts only)• Dual DIN rail and panel mounting capability• Short circuit rating of 5,000 A @ 240 Vac (N/O contacts only)
a 30 A when mounted with 13 mm gap between two relays.25 A when mounted side by side without a gap.
Approvals for Relays:
For mounting track, see page 24-16
Table 23.30: Sockets (sold in lots of 10)
Contact terminal arrangement Connection Relay type Catalog Number $ Price ea.
Square D™ Plug-In Relays8501K relays are designed for multipole switching applications at 240 Vac or lower. These relays have industry standard wiring and pin terminal arrangements which allow for their use as replacements for many competitive relays without wiring or hardware modifications.
Note: S = Stocked. Factory order items require a minimum order quantity of 25 and have a lead time of 12 weeks.
Pilot Light Option—Available on Types KP and KU. Internal pilot lights are available in both AC and DC versions for positive indication of power to the coil. The pilot light is a green LED.Manual Operator Option—Available on Type KU only. To facilitate speed circuit testing, a manual operator (test button) can be provided. Coil VAC—3.0 VACoil VDC—1.4 Watts
Note: All 8501 K relays have a B300 rating.
a Socket is not required with Type KF relays.b 3 pole devices have a 20 A max. total (sum of currents in all 3 poles), continuous rating.c 3 pole devices have a 30 A max. total (sum of currents in all 3 poles), continuous rating.d Voltage code must be specified to order this product. Refer to standard voltage codes
listed in Table 23.37 and insert as shown in Table 23.41: How to Order.
For sockets and accessories, see page 23-14.For track, see page 24-16.
• 12 A relays• DPDT or 3PDT• Manual operator/
green pilot light options
• Motor load (hp) ratings• DPDT latching models
available• AC or DC operation• RoHS Compliant
Table 23.35: Type KF —Flange Mounted—Spade TerminalsInput
VoltageContact
Arrangement Options Type $ Price
AC50/60 Hz
DPDTNone Available
KF12d 24.60
3PDT KF13d 26.70
DCDPDT
None AvailableKFD12d 24.60
3PDT KFD13d 26.70
Table 23.36: Type KL—Latching Relay—Spade TerminalsInput
VoltageContact
Arrangement Options Type $ Price
AC50/60 Hz DPDT None Available KL12d 45.00
DC DPDT None Available KLD12d 45.00
Table 23.37: Voltage Codes and Stocked Relays
TypeAC Voltage 50/60 Hz
TypeDC Voltage
6 12 24 120 240 6 12 24 48 110 125
Voltage Codes V35 V36 V14 V20 V24 Voltage Codes V50 V51 V53 V56 V60 V63
KP12 S S S S S KPD12 S S S S S
KP12P14 S S S S KPD12P14 S S S S
KP13 S S S S KPD13 S S S S S
KP13P14 S S S KPD13P14 S
KU12 S S S S KUD12 S
KU12M1 KUD12M1 S
KU12P14 S S KUD12P14 S
KU12M1P14 S S KUD12M1P14 S
KU13 S S S S KUD13 S S S
KU13M1 KUD13M1
KU13P14 S S KUD13P14
KU13M1P14 S S S KUD13M1P14 S S
KF12 S S S KFD12 S S
KF13 S S KFD13 S
KL12 S S KLD12 S S
For 8501 KP, KU, and KF:
FileCCN
E78351NLDX2NLDX8
FileClass
2112693211 04
For 8501 KP, KU, and KL:
FileCCN
E78351NLDXNLDX7
When used with the appropriate 8501NR socket.
For 8501 KL:
FileCCN
E78351NLDX2NLDX8
FileClass
2112683211 04
Table 23.38: Type KP—Tubular TerminalsInput
VoltageContact
Arrangement Options Type $ Price
AC50/60
Hz
DPDT None KP12d 39.00DPDT Pilot Light KP12P14d 45.003PDT None KP13d 47.303PDT Pilot Light KP13P14d 53.30
DC
DPDT None KPD12d 39.00DPDT Pilot Light KPD12P14d 45.003PDT None KPD13d 47.303PDT Pilot Light KPD13P14d 53.30
Table 23.39: Type KU—Spade TerminalsInput
VoltageContact
Arrangement Options Type $ Price
AC50/60 Hz
DPDT None KU12d 22.70
DPDT Manual Operator KU12M1d 26.70
DPDT Pilot Light KU12P14d 28.70
DPDTManual Operator and Pilot Light
KU12M1P14d 30.80
3PDT None KU13d 24.60
3PDT Manual Operator KU13M1d 28.70
3PDT Pilot Light KU13P14d 30.80
3PDTManual Operator and Pilot Light
KU13M1P14d 35.00
DC
DPDT None KUD12d 22.70
DPDT Manual Operator KUD12M1d 26.70
DPDT Pilot Light KUD12P14d 28.70
DPDTManual Operator and Pilot Light
KUD12M1P14d 30.80
3PDT None KUD13d 24.60
3PDT Manual Operator KUD13M1d 28.70
3PDT Pilot Light KUD13P14d 30.80
3PDTManual Operator and Pilot Light
KUD13M1P14d 35.00
Table 23.40: Contact Ratings (Contacts are Silver Tin Oxide)AC DC
Type ACVolts
Resistive 75% PF Continuous
AmperesHp DC
VoltsResistive Amperes
KP120 10 c 1/3
28 12240 6.5 b 1/2
KUKFd
120 12 1/328 12
240 12 1/2
KL 120 10 1/3
28 10240 10 1/2
Table 23.41: How to OrderTo Order Specify: Catalog Number
• Class Number• Type Number• Voltage Code
(See Stocked Relay Table above)
Class Type Voltage Code
8501 KP12 V20
CP2 Discount Schedule
General Purpose Relays Type KClass 8501 / Refer to Catalog 8501CT0301
Square D™ Miniature Plug-in Relays8501R miniature plug-in relays have a 10 A resistive rating, the same as the Type K plug-in relays, but are much smaller. The compact size of these relays makes them ideal for downsizing equipment and applications where space is at a premium.
a Relays have a B300 rating with UL.
b Voltage code must be specified to order this product. Refer to standard voltage codes listed in Table 23.47 and insert as shown in Table 23.53: How to Order.
c When used with the appropriate 8501NR socket.
For sockets and accessories, see page 23-14. For track, see page 24-16.
• SPDT through 4PDT• AC or DC operated• Horsepower rated• Socket compatible
• Manual operator/ green LED pilot light options
• Silver tin oxide contacts
Table 23.46: Contact Ratings (Contact material is Silver Tin Oxide)
Type Voltage ResistiveRating Voltage General Use
RatingHorsepower
Rating
8501RS41 a120 Vac 15 120 Vac 10 1/3 @120 Vac
240 Vac 12 240 Vac 10 1/3 @240 Vac
8501RSD41a 28 Vdc 15 28 Vdc 15 —
8501RS42a120 Vac 10 120 Vac 10 1/3 @120 Vac
240 Vac 10 240 Vac 10 1/2 @240 Vac
8501RSD42a 30 Vdc 10 28 Vdc 10 —
8501RS43a120 Vac 10 150 Vac 10 —
277 Vac 10 250 Vac 6.6 —
8501RSD43a 28 Vdc 10 28 Vdc 10 —
8501RS44a120 Vac 10 150 Vac 7.5 —
277 Vac 10 250 Vac 5 —
8501RSD44a 28 Vdc 10 28 Vdc 10 —
Table 23.47: Voltage Codes and Stocked Relays
TypeAC Voltage 50/60 Hz
TypeDC Voltage
6 12 24 120 240 6 12 24 110
Voltage Code V35 V36 V14 V20 V24 Voltage Code V50 V51 V53 V60
RS41 S S RSD41 S SRS41M1 RSD41M1RS41P14 S S RSD41P14 S
RS41M1P14 S S RSD41M1P14 SRS42 S S S S RSD42 S S
RS42M1 RSD42M1RS42P14 S S RSD42P14 S S
RS42M1P14 S RSD42M1P14 SRS43 S S RSD43 S
RS43M1 RSD43M1RS43P14 S RSD43P14
RS43M1P14 S RSD43M1P14RS44 S S S RSD44 S S
RS44M1 RSD44M1RS44P14 S RSD44P14 S
RS44M1P14 S RSD44M1P14Note: S = Stocked.
Factory order items require a minimum order quantity of 25 and have a lead time of 12 weeks.
Table 23.48: SPDT with Silver Tin Oxide ContactsInput
Voltage Options Type $ Price
AC50/60Hz
None RS41b 29.60
Manual Operator RS41M1b 31.70
Pilot Light RS41P14b 37.20
Manual Operator and Pilot Light RS41M1P14b 39.30
DC
None RSD41b 29.60
Manual Operator RSD41M1b 31.70
Pilot Light RSD41P14b 37.20
Manual Operator and Pilot Light RSD41M1P14b 29.60
Table 23.49: DPDT with Silver Tin Oxide ContactsInput
Voltage Options Type $ Price
AC50/60Hz
None RS42b 35.00
Manual Operator RS42M1b 37.10
Pilot Light RS42P14b 43.10
Manual Operator and Pilot Light RS42M1P14b 45.20
DC
None RSD42b 35.00
Manual Operator RSD42M1b 37.10
Pilot Light RSD42P14b 43.10
Manual Operator and Pilot Light RSD42M1P14b 45.20
Table 23.50: 3PDT with Silver Tin Oxide ContactsInput
Voltage Options Type $ Price
AC50/60Hz
None RS43b 39.30
Manual Operator RS43M1b 41.40
Pilot Light RS43P14b 47.60
Manual Operator and Pilot Light RS43M1P14b 49.90
DC
None RSD43b 39.30
Manual Operator RSD43M1b 41.40
Pilot Light RSD43P14b 47.60
Manual Operator and Pilot Light RSD43M1P14b 49.90
Table 23.51: 4PDT with Silver Tin Oxide ContactsInput
General Purpose Relays Type RClass 8501 / Refer to Catalog 8501CT0301
Square D™ Miniature Plug-in Relays8501R relays are suited for use as logic elements and power switching output devices. The short stroke motion of the armature provides long mechanical life required for high speed operation of control systems. Different contact compositions allow these relays to be used in a variety of applications. Fine silver (gold flashed) and bifurcated crossbar (gold overlay silver) are suitable for high contact reliability and low level switching requirements. Silver tin oxide is best suited for inductive loads. Class I Division II sealed relays can be used in specified hazardous locations.
a Voltage code must be specified to order this product. Refer to standard voltage codes shown in Table 23.59.
b Do not ground the frame.
Pilot Light OptionAn internal green pilot light is available in both AC and DC versions for positive indication of power to the coil.
Manual Operation OptionTo speed circuit testing, a manual operator (test button) can be provided. The relay can be manually switched to simulate normal operation.NOTE: All Type R relays with a manual operator must
be used on circuits of the same polarity.
c RS4/RSD4, RS14/RSD14 have NEMA C300 pilot duty rating.
Note: S = Stocked. Factory Order items require a minimum order quantity of 25 and have a lead time of 12 weeks.
For sockets and accessories, see page 23-14. For track, see page 24-16.
• 1, 3, or 5 A versions• 4PDT• Complete socket line
• Horsepower rated• AC or DC operation• Manual operator/pilot
General Purpose Relays Type NClass 8501 / Refer to Catalog 8501CT0301
Square D™ Sockets
8501NR sockets are designed for use with plug-in Class 8501 Type K, KA, and R relays, and 9050JCK timers. The 8501NR45 screw terminal sockets have pressure wire clamps that accept 1 or 2 #16–22 wires. All other sockets have pressure clamps that will accept 1 or 2 #12–22 wires.The recommended tightening torque for all terminals is 7-8 lb-in.• All devices stocked in central warehouse• DIN track mount or direct panel mount• Tubular sockets available in easy-to-wire single tier or double tier versions• RoHS compliant
a Must be ordered in multiples of the quantity listed. Units provided in standard quantity of one are individually packaged; devices with B suffix have a standard quantity of 10 per bulk pack.
b Finger Safe
For DIN 3 mounting track and end clamps, see page 24-16, or refer to:• NEMA Style terminal block section of catalog 9080CT9601• IEC Style terminal block section of catalog 9080CT9901
c Must be ordered in multiples of the quantity listed.
— 14 Pin SpadeDouble Tier Screw Terminal 300 V, 10 A 300 V, 10 A
NR45 28.70 1
NR45B 26.70 10
Table 23.63: Socket AccessoriesSocket For Use With Description Type $ Price ea. Std. Pack c
8501NR518501KP12, KPD12 Hold Down Clip NH51 1.00 109050JCK Hold Down Spring NH7 8.30 1
8501NR528501KP12, KPD12 Hold Down Clip NH52 1.00 109050JCK Hold Down Spring NH7 8.30 1
8501NR618501KP13, KPD13 Hold Down Clip NH61 1.00 109050JCK Hold Down Spring NH7 8.30 1
8501NR628501KP13, KPD13 Hold Down Clip NH52 1.00 109050JCK Hold Down Spring NH7 8.30 1
8501NR82 8501KU and KL Hold Down Clip NH82 1.00 108501NR41 8501RS41, RSD41 Hold Down Clip Supplied with socket as standard — —8501NR42 8501RS42, RSD42 Hold Down Clip 8501NH42 1.00 108501NR43 8501RS43, RSD43 Hold Down Clip 8501NH42 1.00 108501NR34 8501RS44, RSD44 Hold Down Clip 8501NH42 1.00 10
Note: S = Stocked. Factory order items require a minimum order quantity of 25 and have a lead time of 12 weeks.
Approximate Dimensions and Wiring Diagrams
Square D™ Power Relays8501C relays are ideally suited for controlling single-phase motors, electric heaters, pumps, conveyors, material handling equipment, and other applications.
N.O. N.C. Type $ Price Type $ Price 277 Vac 600 V 120 V 230 V 600 V AC Coil DC Coil
AC Rated Contacts
SPST 1 0 CO6a 32.70 CDO6a 32.70 600 40 10 2 2 2 10 VA 4 W
DPST 2 0 CO7a 51.30 CDO7a 51.30 600 40 5 1.5 1.5 1.5 10 VA 4 W
SPST 0 1 CO8a 32.70 CDO8a 32.70 600 40 10 2 2 2 10 VA 4 W
SPDT 1 1 CO15a 57.30 CDO15a 57.30 600 40 5 1.5 1.5 1.5 10 VA 4 W
DPDT 2 2 CO16a 69.60 CDO16a 69.60 600 40 5 1.5 1.5 1.5 10 VA 4 W
DC Rated Contacts 110 V 220 V
SPST 1 0 CO21a 71.70 CDO21a 71.70 500 20 8N.A.
10 VA 4 W
DPDT 2 2 CO22a 84.00 CDO22a 84.00 325 10 4 10 VA 4 W
a Voltage codes must be specified to order this product. Refer to standard voltage codes listed in Table 23.66 and insert as shown in Table 23.68: How to Order.
8501CDO6V51
Table 23.65: Operating DataOperating Voltages/Voltage Range
AC coils – 6 through 480 volts, + 10/-15% of nominal at 25 oCDC coils – 6 through 110 volts, + 10/-20% of nominal at 25 oC
TeSys™ D IEC Style RelaysThese 600 volt relays are approved for use around the world. TeSys D relays are usually mounted on 35 mm DIN 3 track, but can also be mounted directly to a panel. The fixed contacts in these relays have a NEMA A600 and Q600 ratings, in addition to the standard IEC ratings, making them suitable for use in most any control circuit. Low consumption versions of this relay are available for use with low level DC signals from a computer or a PLC. Adder decks can be added to a basic five pole relay to make it up to an 11 pole relay. The serrated silver-nickel contacts with wiping action provide excellent reliability in 12 or 24 volt control circuits. Special auxiliary contacts are available for switching low power down to 5 volts at 10 mA. Timer and mechanical latch attachments are available.
a Add the proper voltage code from Table 23.72 to the end of catalog number (for example, CAD50B7).
b Auxiliary contact blocks with four contacts cannot be used on relays with low consumption coils.c Includes 1 N.O. and 1 N.C. overlapping contact.
d Grounding terminal points (2 terminals jumpered together; see diagram on page 8 of Catalog 8501CT0101).e Auxiliary contact blocks with four contacts cannot be used on relays with low consumption coils.
f Add the proper voltage code to the end of catalog number.
For replacement AC coils, see page 18-16. DC coils are not replaceable.
Industrial Relays CA2SK and CA3SKRefer to Catalog 8501CT0101
TeSys™ SK IEC Style Relays
a Use the appropriate voltage code to complete the catalog number (for example: CA2SK11G7)
Transient Suppressor ModuleDampens the voltage spike that may occur when the relay coil is de-energized. The spike may adversely affect solid state equipment near the relay. The transient suppressor module snaps into a cavity located in the side of the relay. These modules can be used with CA2SK and CA3SK relays.
b Alternating relays CA2SKE available in these voltages only. No other voltages are available.
Alternating Relays, CA2SKERefer to Catalog 8501CT9701
These alternating relays are used to alternate the use of 2 motor circuits. When the coil is energized the first time, one contact closes and will open when the coil is de-energized. When the coil is energized again, the other contact will close and will open when the coil is de-energized. The contacts from these alternators are to be used in the control circuit of the starters that are controlling pump or compressor motors. Approvals: UL File: E164353 CCN: NKCR; CSA File: LR43364 Class: 3211 03.
a Use the appropriate voltage code to complete the catalog number (for example, CAZSK11G7). Only available with voltages indicated above.
Table 23.92: IEC Style Industrial Control Relays• Miniature size saves space.• Mounts on 35 mm DIN 3 track• Up to 4 poles.
Control Circuit Supply Consumption Type of TerminationContact Configuration
AC Control Relays• Straight-through wiring• Plug-in contact cartridges for easy contact conversion and
replacement• Contact conversion without removing terminal screws or wires• Self-lifting pressure wire connectors• Replaceable coil
a A maximum of 8 N.C. contacts is allowed on 9–12 pole relays.
AC Master Relays• 20 ampere contact rating due to use of master contact
cartridges. d• Provisions for standard cartridges to be used in contact
cavities not occupied by master cartridges in 2-8 pole AC relay.
b Attachments not permitted on this relay.
AC Timing Relays• Easily convertible On Delay or Off Delay• Two adjustable timing ranges• Repeat accuracy well above ±10%• Convertible 1 N.O. and 1 N.C. timed contacts• Large knob for easy adjustment of time delay• Off Delay mode times out even after loss of power.
AC Latching Relays• Mechanical latch holds all contacts switched even after
removal of power from replaceable latching coil.• Provides sequence memory in the event of power loss. Ideal
for press control, process control and punch presses.• Replaceable unlatch coil to switch contacts back to original
state.
c Voltage Code must be specified to order these products. Refer to Table 23.104 and insert the code as shown in Table 23.107: How to Order.
Approvals:
d Maximum of six 8501 Type XC4 Master Cartridges may be used on only 7 and 8 pole AC Devices
AC Control Relays and AC Master Relays
AC Latching Relay Dimensions
For replacement coils, see page 23-24.
Table 23.98: AC Control Relays
Normally Open ConvertibleInstantaneous Contacts
Control Relay a
Typec $ Price
023468
1012
XO00XO20XO30XO40XO60XO80
XO1000XO1200
98.00144.00169.00192.00242.00288.00336.00385.00
Table 23.99: AC Master Relays
Number of N.O. 20 Ampere Convertible Contacts
Open Typeb
Typec $ Price
246
XMO20XMO40XMO60
204.00336.00457.00
Table 23.100: AC Timing Relays
Timing Mode
N.O.Convertible
Instantaneous Contacts
Timed Convertible
Contacts
Timing Relay
$ Price0.2–60 s 5–180 s
N.O. N.C. Typec Typec
On Delay
024
111
111
XO00XTE1XO20XTE1XO40XTE1
XO00XTE2XO20XTE2XO40XTE2
432.00480.00529.00
Off Delay
024
111
111
XO00XTD1XO20XTD1XO40XTD1
XO00XTD2XO20XTD2XO40XTD2
432.00480.00529.00
Table 23.101: AC Latching Relays
N.O. Convertible Instantaneous Contacts
Latching Relay
Typec $ Price
23468
XO20XLXO30XLXO40XLXO60XLXO80XL
313.00336.00360.00408.00457.00
FileCCN
E78403NKCR
FileClass
0609053211 03
IEC 60947-1
Type XMO40Control Relay
Type XMO40Master Relay
Type XO40XTE1Timing Relay
Type XO40XLLatching Relay
Table 23.102: AC Contact Ratings (for DC ratings, see page 23-23)
Type of Cartridge V
Inductive35% Power Factor
Resistive75% Power
Factor
NEMARating
Make BreakContinuous
Amperes
Make, Break and
Continuous Amperes
A VA A VA
Standardor
Overlapping
120240480600
A600
60301512
7200
63
1.51.2
720 10 10
Masterd — A600 Same as standard cartridge above except substitute 20 A for the continuous ampere rating
Logic Reed — — 150 Vac, 150 mA, 8 W Maximum
Table 23.103: Average Operating Time (ms)Device Pick-Up Drop-Out
CSA File: 217698 Class 3211 07CEGL except RE11 RMX MU and RE11 RME MU
Ambient air temperature around the device
Storage oF (oC) –22 to +140 (–30 to +60)Operation oF (oC) –4 to +140 (–20 to +60)
Table 23.125: RE11 Modular Timers—17.9 mm wide (Multi-function, dual function or single function)Functions Supply Voltages Rated Current Catalog Number $ Price
Storage oF (oC) –22 to 140 (–30 to +60Operation oF (oC) –4 to 140 (–20 to +60)
Table 23.126: RE48 Panel Mount Timers (For required socket, refer to the catalog section)Functions Supply Voltages Rated Current Catalog Number $ Price
Single function: on delay, two relay outputs 24–240 Vac/Vdc 2 x 5 A RE48ATM12MW 73.00Repeat cycle: two relay outputs 24–240 Vac/Vdc 2 x 5 A RE48ACV12MW 88.00Multi-function: on delay, one shot, off delay, repeat cycle 24–240 Vac/Vdc 2 x 5 A RE48AML12MW 86.00Multi-function: on delay and interval, two relay outputs, of which one selectable and instantaneous 24–240 Vac/Vdc 2 x 5A RE48AMH13MW 86.00
Conforming to standards IEC 61812-1, EN 50081-1/2, EM 50082-1/2, LV directives (73/23/EEC +93/68/EEC (CE marking) + ENC directive (89/336/EEC + IEC 60669-2-3)
a If the device has been stored de-energized for more than a month, it must be energized for about 15 seconds to activate it. Subsequently, a time of > 1 s is enough to activate the time delay.
Note: If this time is not complied with, the relay will remain energized indefinitely.
b By external potentiometer, to be ordered separately (see page 3 of Catalog 9050CT0001 for specifications). If external potentiometer is used, the internal potentiometer is automatically disconnected.
c A switch on the front face of the timer allows the second contact to be used in instantaneous mode.
Square D™ General Purpose Plug-In9050JCK timing relays are designed to provide low-cost timing in a plug-in housing. The Types JCK11 thru 59 provide ±1% repeat accuracy. The Types JCK60 and 70 offer ±0.1% repeat accuracy. These timers are directly interchangeable with many other 8 and 11 pin tube base timers.
• Up to ±0.1% repeat accuracy• Timing from 0.05 seconds to 999 hours• Available in 5 timing modes• DPDT contacts (2 N.O. and 2 N.C.)• 10 A contact rating• Transient protected• Hold down spring available• Variable or fixed time delay• Horsepower rated• RoHS compliant
c (XXXX) denotes the timing period in seconds. Example: Class 9050 Type JCK1F60 is an On Delay timer fixed at 60 seconds.
d Fixed repeat cycle timers can be supplied with the same or different On-Time and Off-Time.
e Initiating contact can be up to 50 feet from the timer.f Voltage code must be specified to order this product. Refer to standard voltage codes
listed below and insert as shown in How To Order.
Class 8501 Sockets For sockets, see page 23-14For DIN rail, see page 24-16
For all 9050JCK timers:
B300, R300, AC15 and DC13
Type JCK60This On Delay timer uses a 5 position rotary switch to select the timing range. The three pushbutton thumbwheels are used to select the time value.
Type JCK70Two 5 position rotary switches are used to select the timing mode and timing range. The three pushbutton thumbwheels are used to select the time value.
g The repeat cycle mode utilizes the same on-time and off-time.
9050JCK46V209050JCK32V36 with 8501NH7
Table 23.142: Variable Time DelayKnob Adjustable
Timing RangeOn
Delay $ Price OffDelayb $ Price Off Delay
Power Trigger $ Price Interval $ Price One Shotb $ Price One Shot Power Trigger $ Price Repeat
Other Products ABL8, ABL7 and ABL1Refer to Catalog 8440CT0601/08
Phaseo™ DC Power SupplyPhaseo switch mode power supplies are totally electronic and their output voltage is regulated. They offer:• Compact size• High degree of output voltage stabilityFor use with Universal power supplies, see optional function modules in catalog 8440CT0601/08, which offer a set of solutions to meet the needs for continuity of service such as:• Immunity to microbreaks • Voltage holding during power outages • Voltage holding during power supply equipment failure
Table 23.175: Dedicated, Single PhaseDesigned for integration into repetitive equipment with power ratings from 60 to 240 W and an output voltage of 12 Vdc or 24 Vdc..
a Compatible input voltage 120-370 Vdc not indicated on the product.b Compatible input voltage 180-370 Vdc not indicated on the product.
Approvals:
See www.Schneider-Electric.us for UL and CSA compliances.For additional information, refer to Catalog #8440CT0601R1/08.
Table 23.171: Modular, Single PhaseMeets all the needs of simple automation systems with power ratings from 7 to 60 W and an output voltage of 5 Vdc, 12 Vdc, or 24 Vdc.
InputVoltage (Vac)
OutputVoltage (Vdc)
NominalCurrent (I) Protection Reset Catalog Number $ Price
Table 23.172: Optimum, Single PhaseThe low-cost solution for applications supplied at 12 Vdc, 24 Vdc, or 48 Vdc and requiring currents between 3 and 5 A.
Input Voltage (Vac) Output Voltage (Vdc) Nominal Current (I) Protection Reset Catalog Number $ Price
100–240
12 5
Auto
ABL7RP1205 360.
243 ABL8REM24030 195.5 ABL8REM24050 300.
48 3 ABL7RP4803 225.
Table 23.173: Universal, Single PhaseAdapts to the majority of power distribution systems with power ratings from 72 to 480 W at 24 Vdc. The same power supply can be connected phase-to-neutral (N-L1) or phase-to-phase (L1-L2) for line supplies ranging from 100 to 500 Vac. Energy reserve, diagnostics, and choice of manual or auto reset are integrated into these units.
Input Voltage (Vac)
Output Voltage (Vdc) Nominal Current (I) Auto-Protection Reset Catalog Number $ Price
Table 23.174: Universal, Three PhaseThis three-phase, 480 to 960 W, 24 Vdc output offering is particularly suited for complex machines and processes. Energy reserve, diagnostics and choice of manual or auto reset are integrated into these units.
Input Voltage (Vac) Output Voltage (Vdc) Nominal Current (I) Auto-Protection Reset Catalog Number $ Price
Zelio™ Analog Interface ModulesThe Zelio Analog range of converters is designed to convert signals emitted by sensors or electrical measurement devices, into standard electrical signals that are compatible with automation platforms and controllers. They also allow the connection distance between a sensor and a measurement device to be increased, for example, between a thermocouple and a programmable controller
a Converters dedicated to Zelio Logic smart relays.
Approvals:
Table 23.176: Converters for Type J and K type thermocouples—supply voltage 24 Vdc ± 20%, non-isolated
TypeTemperature Range
Switchable Output Signals Catalog Number $ Price°F °C
Type J 32–302 0–150 0–10 V, 0–20 mA, 4–20 mA RMTJ40BD 141.0032–572 0–300 0–10 V, 0–20 mA, 4–20 mA RMTJ60BD 141.0032–1112 0–600 0–10 V, 0–20 mA, 4–20 mA RMTJ80BD 141.00
Type K 32–1112 0–600 0–10 V, 0–20 mA, 4–20 mA RMTK80BD 141.0032–2192 0–1200 0–10 V, 0–20 mA, 4–20 mA RMTK90BD 141.00
Table 23.177: Converters for Universal Pt100 probes—supply voltage 24 Vdc ± 20%, non-isolated
TypeTemperature Range
Switchable Output Signals Catalog Number $ Price°F °C
Pt1002-wire, 3-wire, and 4-wire
- 40–104 - 40–40 0–10 V, 0–20 mA, 4–20 mA RMPT10BD 141.00- 148–212 - 100–100 0–10 V, 0–20 mA, 4–20 mA RMPT20BD 141.0032–212 0–100 0–10 V, 0–20 mA, 4–20 mA RMPT30BD 141.0032–482 0–250 0–10 V, 0–20 mA, 4–20 mA RMPT50BD 141.0032–932 0–500 0–10 V, 0–20 mA, 4–20 mA RMPT70BD 141.00
Table 23.178: Converters for Optimum Pt100 probesa—supply voltage 24 Vdc ± 20%, non-isolated
TypeTemperature Range
Switchable Output Signals Catalog Number $ Price°F °C
Pt1002-wire, 3-wire, and 4-wire
- 40–104 - 40–40 0–10 V or 4–20 mA RMPT13BD 113.00- 148–212 - 100–100 0–10 V or 4–20 mA RMPT23BD 113.0032–212 0–100 0–10 V or 4–20 mA RMPT33BD 113.0032–482 0–250 0–10 V or 4–20 mA RMPT53BD 113.0032–932 0–500 0–10 V or 4–20 mA RMPT73BD 113.00
Table 23.179: Universal Voltage/Current ConvertersType Input signal Output signal Catalog Number $ Price
Supply voltage 24 Vdc ± 20%, non-isolated 0–10 V or 4–20 mA 0–10 V or 4–20 mA RMCN22BD 95.00
Supply voltage 24 Vdc ± 20%, isolated
0–10 V, ± 10 V,0–20 mA, 4–20 mA
Switchable:0–10 V, ± 10 V,0–20 mA, 4–20 mA
RMCL55BD 141.00
0–50 V, 0–300 V, 0–500 VDC or AC, 50/60 Hz
Switchable:0–10 V, 0–20 mA, 4–20 mA RMCV60BD 154.00
0–1.5 A, 0–5 A, 0–15 ADC or AC, 50/60 Hz 0–10 V, 0–20 mA, 4–20 mA RMCA61BD 154.00
FileCCN
E164353NKCR
FileClass
089150_S_0003211 07 IEC 60947-1 RoHS
Compliant
Table 23.180: How to OrderTo Order Specify: Catalog Number
Other Products SR2 Compact and SR3 ModularRefer to Catalog DIA3ED2031108EN
Zelio™ Logic 2 Smart Relays
a The modular base can be fitted with one I/O extension module. The 24 Vdc modular base can be fitted with one communication module and/or one I/O extension module.
b Replace the p by the number 1 to order a smart relay with relay output or by 2 for a smart relay with transistor output (Example: SR3B101BD).c Please consult local Schneider Electric representative for list prices.
a The power supply of the extension modules is provided via the Zelio Logic 2 modular relays.b max. 1 PT 100 input
a CD-ROM includes Zelio Soft software, application library, self-training manual, installation instructions and user’s manual
a Modems to be supplied by user.
Approvals:
Table 23.184: Modular Smart Relays a with Display, DC and AC Power Supply
Supply voltage 12 Vdc 24 Vdc 24Vac 100-240 Vac
Number of inputs/outputs 26 10 26 10 26 10 26
Number of inputsDiscrete inputs 16 6 16 6 16 6 16
Including 0-10 V analog inputs 6 4 6 — — — —
Number of outputs 10 relay 4 relay 10 relay 4 relay 10 relay 4 relay 10 relay
Dimensions, W x D x H (mm) 124.6x59.5x107.6 71.2x59.5x107.6 24.6x59.5x107.6 71.2x59.5x107.6 124.6x59.5x107.6 71.2x59.5x107.6 124.6x59.5x107.6
Clock yes yes yes yes yes yes yes
Catalog NumberSR3B261JD SR3B10pBD bc SR3B26pBD bc SR3B101B SR3B261B SR3B101FU SR3B261FU
$ Price 380.00 — — 282.00 476.00 292.00 486.00
Table 23.185: Extension Modules for Zelio Logic 2 SR3B•••••a
Communication Discrete Inputs/Outputs Analog Inputs/Outputs
Application MODBUS network — —
Number of inputs/outputs — 6 10 14 4
Number of inputsDiscrete inputs — 4 6 8 —
Analog (0–10 V, 0–20 mA, PT100) — — — — 2b
Number of outputsRelay — 2relay 4 relay 6 relay —
Analog (0-10 V) — — — — 2
Dimensions, W x D x H (mm) 35.5x59.5x107.6 35.5x59.5x107.6 72x59.5x107.6 72x59.5x107.6 35.5x59.5x107.6
Table 23.187: Communication interface for SR2/SR3Interface, Zelio Logic 2 Alarm Software Communication Interface a Alarm Management Software Zelio Logic GSM Modem
Supply voltage 12-24 Vdc — 24 VdcDescription — PC CD-ROM (Windows 98, NT, 2000, XP) GSM modemDimensions, W x D x H 72x59.5x107.6 mm —Catalog Number SR2COM01 SR2SFT02 SR2MOD02$ Price 230.00 60.00 545.00
FileCCN
E164866NRAQ
FileClass
LR2176982252 01
I Discount Schedule
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
Manual Motor Starters, Controllers, and ProtectorsTable of Contents
(1) Mounting of a GVAE contact block or a GV2AK00 visible isolation block on GV2P and GV2L.(2) Choice of N/C or N/O contact operation, depending on which way round the reversible block is mounted, flip window 180°.(3) The GVAD is always mounted next to the circuit-protector. For Spring terminals add 3 to the catalog number. Example: GV2ME013.
Auxiliary Contact Blocksounting Location Max. No. of Blocks Contact Type Sold in Lots Of Catalog Number Weight / kg (lbs)
Manual Motor Starters, Controllers, and ProtectorsAccessories Selection
10/02
Courtesy of www.mdwindustrialsupply.com
Courtesy o
(1) To order an undervoltage trip: replace the dot (p) with a U, example: GVAU025. To order a shunt trip: replace the dot (p) with an S, example: GVAS025.
(2) Visible isolation of the 3 poles upstream of circuit-breaker GV2P and GV2L.
(3) Mounting of a GVAE contact block or a GV2AK00 visible isolation block on GV2P and GV2L.
Electric Trips
Description Voltage Hz Catalog Number Weight lb (kg)
Undervoltage or shunt trips (1)
Side(1 block on RH sideof GV2)
24 V50 Hz GVAp025 0.23 (0.105)
60 Hz GVAp026 0.23 (0.105)
48 V50 Hz GVAp055 0.23 (0.105)
60 Hz GVAp056 0.23 (0.105)
100 V 50 Hz GVAp107 0.23 (0.105)
100…110 V 60 Hz GVAp107 0.23 (0.105)
110…115 V50 Hz GVAp115 0.23 (0.105)
60 Hz GVAp116 0.23 (0.105)
120…127 V 50 Hz GVAp125 0.23 (0.105)
127 V 60 Hz GVAp115 0.23 (0.105)
200 V 50 Hz GVAp207 0.23 (0.105)
200 V…220 V 60 Hz GVAp207 0.23 (0.105)
220 V…240 V50 Hz GVAp225 0.23 (0.105)
60 Hz GVAp226 0.23 (0.105)
380 V…400 V50 Hz GVAp385 0.23 (0.105)
60 Hz GVAp386 0.23 (0.105)
415 V…440 V 50 Hz GVAp415 0.23 (0.105)
415 V 60 Hz GVAp416 0.23 (0.105)
440 V 60 Hz GVAp385 0.23 (0.105)
480 V 60 Hz GVAp415 0.23 (0.105)
500 V 50 Hz GVAp505 0.23 (0.105)
600 V 60 Hz GVAp505 0.23 (0.105)
Undervoltage trip, INRS (can only be mounted on GV2-ME)Safety device for dangerous machines, conforming to INRS and VDE 0113
Side(1 block on RH sideof GV2)
110…115 V50 Hz GVAX115 0.24 (0.110)
60 Hz GVAX116 0.24 (0.110)
127 V 60 Hz GVAX115 0.24 (0.110)
220…240 V50 Hz GVAX225 0.24 (0.110)
60 Hz GVAX226 0.24 (0.110)
380…400 V50 Hz GVAX385 0.24 (0.110)
60 Hz GVAX386 0.24 (0.110)
415…440 V 50 Hz GVAX415 0.24 (0.110)
440 V 60 Hz GVAX385 0.24 (0.110)
Add-on contact blocksDescription Mounting Maximum number Catalog Number Weight lb (kg)Visible isolation block (2) Front (3) 1 GV2AK00 0.33 (0.150)
LimitersAt top (GV2ME and GV2P) 1 GV1L3 0.29 (0.130)
Independent 1 LA9LB920 0.70 (0.320)
Fuse Holder, 30 amp maximum
Description For Fuse Type For Use InSold in Lots of
Catalog NumberWeight lb (kg)
Screw clamp terminals, 3-pole CC, KTK-R 0.41 X 1.5 (10.3 X 38 mm) US Markets 1 LS1D30 0.5 (0.23)
Spring Terminals, 3-pole CC, KTK-R 0.41 X 1.5 (10.3 X 38 mm) US Markets 1 LS1D303 0.5 (0.23)
Screw clamp terminals, 3-pole aM, gG 0.39 X 1.5 (10 X 38 mm) European Markets 1 LS1D32 0.5 (0.23)
Sprint terminals, 3-pole aM, gG 0.39 X 1.5 (10 X 38 mm) European Markets 1 LS1D323 0.5 (0.23)
Screw clamp terminals, 4-pole aM, gG 0.39 X 1.5 (10 X 38 mm) European Markets 1 LS1DT32 0.5 (0.23)
Manual Motor Starters, Controllers, and ProtectorsAccessories Selection
10/02
Description App
Clip-On Connectors
For G1.5–
For G1.5–
Spreaders To in
Terminal Shields IP 405 Supp
Phase Barriers Prov
Insulating Screens Prov
Kit for combination with contactor
Provprov
05/04
Courtesy of www.mdwindustrialsupply.com
Courtesy o
GV7 ACCESSORIES
Standard manual controllers and protectors include terminal and device mounting hardware. Cable clamps and accessories should be selected from the table below.
Terminal shields cannot be used together with phase barriers. The kit comprises links, a protective shield and a depth adjustable metal bracket for the breaker.
Cabling Accessories
licationSold in Lots Of
For Contactor Catalog Number Weight / kg (lbs)
V7R•40 through GV7R •150,95 mm2 (#14 to # 3/0 awg).
3 — GV7AC021 0.300 (0.66)
V7R•220185 mm2 (#14 to 350 mcm).
3 — GV7AC022 0.350 (0.77)
crease the center line distance between phase to 45 mm. 3 — GV7AC03 0.180 (0.40)
lied with the sealing accessory. 1 — GV7AC01 0.125 (0.28)
ides maximum phase separation at the power connection points. 2 — GV7AC04 0.075 (0.17)
ides insulation between the connections and the backplate. 2 — GV7AC05 0.075 (0.17)
iding a direct link between the starter and the contactor, the cover ides protection against direct finger contact.
Manual Motor Starters, Controllers, and ProtectorsSpecifications
44
Courtesy of www.mdwindustrialsupply.com
Courtesy
GV7 OPERATING CURVES
The current limiting capacity of the motor starter and protector is expressed by two curves which give, as a function of the prospective short-circuit current (the current which would flow if no protection devices were installed):
• The actual peak current (limited),
• The thermal stress (in A2s), i.e. the energy dissipated by the short-circuit in a conductor with a resistance of 1 Ω.
Example: The real value of a 70 kA prospective short-circuit current limited by a GV7RS220 is 20kA peak, see page 46.
PRC = Cross-linked polyethylene
Example 1: For a GV7RS220, the peak value is limited to 20 kA for a prospective Isc of 40 kA.
Example 2: For a GV7RS220, and with a prospective Isc of 40 kA, an I2t of 7.5 x 105 A2s is obtained, which requires the use of a PVC insulated copper cable with a cross-sectional area of 10 mm2 (# 8 AWG).
Permissible Thermal Stresses for Cables (A2s)
S (mm2) 1.5 2.5 4 6 10 16 25 35 50
AWG #16 #14 #12 #10 #8 #6 #4 #2 #1
PVCInsulation
Cu 2.97 x 104 8.26 x 104 2.12 x 105 4.76 x 105 1.32 x 106 3.4 x 106 8.26 x 106 1.62 x 107 3.31 x 107
Al – – 5.41 x 105 1.39 x 106 3.38 x 106 6.64 x 106 1.35 x 107 – –
PRCCu 4.10 x 104 1.39 x 105 2.92 x 105 6.56 x 105 1.82 x 106 4.69 x 106 1.39 x 107 2.23 x 107 4.56 x 107
Al – – 7.52 x 105 1.93 x 106 4.70 x 106 9.23 x 106 1.88 x 107 – –
Maximum current 65 A 85 A 160 A 250 A 400 A 630 A 85 A 250 AInternal diameter Ø 30 Ø 50 Ø 80 Ø 120 Ø 200 Ø 300 Ø 46 Ø 110References 50437 50438 50439 50440 50441 50442 50485 50486
Maximum current 65 A 85 A 160 A 250 A 400 A 630 A 85 A 250 AInternal diameter Ø 30 Ø 50 Ø 80 Ø 120 Ø 200 Ø 300 Ø 46 Ø 110References 50437 50438 50439 50440 50441 50442 50485 50486
Varlo Switch AccessoriesAuxilliary Contacts (10A)1 N.O. / 1 N.C. (early make, late break0 VZ72 N.O. VZ20HandleMounting Single Hole Four HoleColor red yellow black/grey red/yellow black/greyFront Plate Dimensions (mm) 45x45 mm 60x60 mm 45x45mm 60x60mm 45x45mm 60x60mm 90x90mm 45x45mm 60x60mm 90x90mmPadlockable for base switch V02 to V2 KCC1YZ KCD1PZ KAD1PZ KCE1YZ KCF1PZ KAF1PZ
V3 to V4 KCF2PZ KAF2PZV5 to V6 KCF3PZ KAF3PZ
Non-Padlockable for base switch V02 to V2 KCC1LZ KDD1PZ KAC1BZ KBD1PZ KCE1LZ KDF1PZ KAE1BZ KBF1PZV3 to V4 KDF2PZ KBF2PZV5 to V6 KDF3PZ KBF3PZ
Shaft Kits & PlatesBase Switch Maximum Panel Depth Shaft Kit Door Interlock Plate Door Mounting PlateV02 to V2 330mm VZ17 KZ32 KZ83
429mm VZ30 KZ32 KZ83V03 to V4 320mm VZ18 KZ74 KZ81
419mm VZ30 KZ74 KZ81V05 to V6 351mm VZ18 KZ74 KZ81
450mm VZ31 KZ74 KZ81
1/L1
2/T1
3/L2
4/T2
5/L3
6/T3
Other versions: Please consult our Customer Care Centre.
21
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
Other versions: please consult our Customer Care Centre.4/22
4
TeSys DF Fuse carriers0.5…125 A
Type Fuse carriers without “blown fuse” indicator
Rated operational voltage (Ui) 600 V (UL & CSA) 690 V (cURus certifi ed component)
Fuse size Class CC 10 x 38 mm 14 x 51 mm 22 x 58 mmConventional thermal current (Ith) 30 A 32 A 50 A 125 ACatalog number Number of poles 1P DFCC1 DF101 DF141 DF221
Rated operational voltage (Ui) 600 V (UL & CSA) 690 V (cURus certifi ed component)
Fuse size Class CC 10 x 38 mm 14 x 51 mm 22 x 58 mmConventional thermal current (Ith) 30 A 32 A 50 A 125 AReferences Number of poles 1P DFCC1V DF101V DF141V DF221V
Type Auxiliary early break and blown fuse signalling contactsFuse carrier to be equipped DF14 (not UL or CSA) DF22 (not UL or CSA)
Size of cartridge fuse or link 14 x 51 mm 22 x 58 mmNumber of contacts 1 2 1 2References DF14AM1 DF14AM2 DF22AM1 DF22AM2
Type Fuse carrier assembly kitsFuse carrier to be assembled DFCC DF8 DF10 DF14 DF22Size of cartridge fuse or link Class C 8.5 x 31.5 mm 10 x 38 mm 14 x 51 mm 22 x 58 mmKit contents 1 pin, 2 clips 1 pin, 3 clipsReferences DF10AP DF14AP DF22AP
22
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
Other versions: please consult our Customer Care Centre.4/234/23
4
TeSys LS1
Fuse carriers0…32 A
Basic blocksconnection
Fuse Carriers
Rated operational voltage with links, a.c. supply 600 V 690 V 690 VMaximum continuous current for ambient temperature ≤ 40° C
with links (mm2/A)with CC or KTK-R (wire gauge/A) 2 - #8 AWG/30A max
with aM fuses (mm2/A)
4/25A or 2.5/16A4/22A or 2.5/20A
6/32A or 4/25A or 2.5/16A
6/32A or 4/22A or 2.5/20A
6/32A or 2.5/20A or 1.5/16Awith gG fuses (mm2/A) 2.5/20A or 1.5/16A
Conforming to standards CSA/ULNF EN 60947-3IEC 947-3
Product certifi
cationsFuse carrier type
Rating 30A 25A 32ACartridge fuse size Type CC or KTK-R 10 x 38 10 x 38Screw clamp connection 3-pole LS1D30 LS1-D32 4-pole LS1-D32+LA8-D324Spring terminal connection 3-pole LS1D303 LS1D323
LS1D30 LS1D323BV UR BV UR
LS1D32
Add-on blocksContact blocksFor use on LS1D30 LS1D32 LS1D323Contact type N/O+N/C N/O+N/O N/O+N/C N/O+N/O N/O+N/C N/O+N/OInstantaneous auxiliary contacts Front mounting GVAE11 GVAE20 GVAE11 GVAE20 GVAE113 GVAE203
Other versions: Please consult our Customer Care Centre.
23
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
Other versions: please consult our Customer Care Centre.4/24
4
GS1/2 Fusible disconnect switch 30-800A
Catalog Number S1DDU3 GS1DU3 GS2GU3N GS2JU3N GS2MU3N GS2QU3N GS2SU3 GS2TU3Switch Type Compact Fused Compact Fused Fused Fuse used Fused Fused Fused
Catalog Number Standard Standard GS1AW403 GS1AW403 GS1AW503 GS1AW503 GS1AW903 GS1AW903 GS1AW903
*Note (1) Shaft Guide for compact Non-fused = LK4AEAH12CN
Compact 30A SwitchLK4DU3
200A SwitchLK4MU3
200A SwitchGS2MU3
800A SwitchGS2TU3
Other versions: Please consult our Customer Care Centre.
25
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
Other versions: please consult our Customer Care Centre.4/26
4
Standard control circuit voltages24 V DC BL24 V AC B48 V AC / 48...72 V DC ES110...240 V AC / 110...220 V DC FU
(2) Complete the references of the power bases according to the following table. Example: LU2B12 **(3) Complete the references of the control units according to the following table. Example: LUCA/B/D/M6X **
Manual reset following thermal fault. • Thermal overload test function. • Overtorque and no-load running, alarm, • Motor operation log, • Motor parameters display on LUCM.., PC or HMI • Integrated Modbus communication.
TeSys U Type E Self Protected Motor Startersand non combination motor starters
(1) Current limiter LUALB1 required for 600V type E applications, Phase barrier LU9SP0 required for UL approval
= +
26
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
Other versions: please consult our Customer Care Centre.4/34
4Contactors in Safety Circuits
Contactors are an integral part of safety applications. Schneider Electric offers a wide variety of contactors which are suitable for use in safety applications due to mechanically linked power contacts and mirror contacts.
A number of standards have been published in recent years that use the concept of functional safety. Examples include IEC 61508, IEC 62061, IEC 61511, ISO 13849-1, and IEC 61800-5-2 which have all been adopted in Europe and published as ENs. Functional safety is a relatively recent concept that replaces the old `Categories' of behavior under fault conditions that were defi ned in EN 954-1, and were often mistakenly described as `Safety Categories'.
Now that EN 954-1 is withdrawn, the available alternatives are EN 62061 and EN ISO 13849-1.The performance of each safety function is specifi ed as either a SIL (Safety Integrity Level) in the case of EN 62061 or PL (Performance Level) in the case of EN ISO 13849-1. In both cases the architecture of the control circuit which delivers the safety function is a factor, but unlike EN 954-1 these new standards require consideration of the reliability of the selected components.
In the past there has been a tendency for components specifi ed to a high category of EN 954-1 to be chosen instead of components that have a lower category, but might actually have more suitable functions. This might be as a result of the misconception that the categories are hierarchical such that for example, category 3 is always “better” than category 2 and so on. Functional safety standards are intended to encourage designers to focus more on the functions that are necessary to reduce each individual risk, and what performance is required for each function, rather than simply relying on particular components.
For more information on Functional Safety, please visit our web site at: www.schneider-electric.com under: Solutions > Machines for OEMs > Machine control solutions
Elevator approvals per CSA22.2 / CSA B44.1 / ASME 17.5File LR43364
Single Phase
240V
Three Phase
200/208V 230/240V 480V 600V TeSys Series Previous Generation
Standard TeSys products can be used for elevator and safety applications when applied as followings:
34
Combination Starters – Type E & Type F
UL508A & Control Panels
Group Protection
TeSys Applications InformationGroup Motor and Type E
Combination Starters are the most common type of packaged motor starter. They are called ‘Combination’ because of their structure and their combined functions. The fi gure opposite shows the four combined functions that constitute a complete motor starter circuit, defi ned as a “Motor branch circuit” by the CEC and NEC. CSA 22.2 no 14 and UL508 currently give different types of combination starter that meet the requirements of a «Motor branch circuit».
Type E, called “self-protected combination starter”, covers all these functions and can be controlled manually (thermal-magnetic circuit-breaker) or remotely (starter-controller). Type E starters withstand faults within their declared nominal rating without sustaining damage, after which they can be put back into service. In addition, they can withstand more severe short-circuit and durability performance tests without welding or excessive wear of the contact tips.
Type F, called “Combination motor starter”, consists of a type E manual starter (thermal-magnetic circuit-breaker) combined with a contactor. These starters are evaluated by means of basic short-circuit tests, but are not considered as “self-protected”. For this combination, the type E starter must be marked “Combination Motor Controller when used with ...”, followed by the reference of the load side contactor.
At present, CSA does not recognize Type F combinations. Manual starters used with contactors can be used in Group Protection as described below.
To help users properly coordinate their motor control equipment with their distribution system in the event of a fault, article 409 of the 2005 NEC requires panel builders to list the short-circuit withstand rating of their motor control panels. According to standard UL508A, manufacturers must use the short-circuit withstand value of the lowest rated device as the nominal withstand rating of the panel, unless the devices have been tested together for a higher coordinated rating. The minimum “short-circuit current rating” (SCCR), on motor control components for horsepower ratings of 50 hp or below is 5000 A. Using a type E or type F combination starter eliminates the coordination problems of using individual components for the “motor branch circuit protection”, “motor controller” and “motor overload protection” functions. The panel builder uses the declared short-circuit current rating for the combination starter. This value is generally higher than 5000 A. This makes it easier to list the short-circuit current ratings and to check the compatibility of a UL508A motor control panel within a given distribution system.
1 Motor disconnect (disconnect switch) 2 Motor Branch Circuit Protection (short circuit protection) 3 Motor controller (contactor) 4 Motor Overload Protection (thermal overload relay)
Both the CEC and NEC allow a single short-circuit protection device to be used for more than one motor circuit if the components used are marked and listed for such use. Components suitable for use in group protection, known as “motor group installations”, can be marked in one of the following two ways: Case n° 1 The contactor and the motor overload relay are both listed as suitable for group installation. An inverse time circuit-breaker can be used as the short-circuit protection device if it is also listed as suitable for group installation. The panel builder must therefore make sure that the short-circuit protection device selected (fuses or inverse time circuit-breaker) does not exceed the value allowed by rule 28-206 of the CEC or article 430.40 of the NEC for the smallest overload relay used in the circuit. Once these conditions have been met, the panel buil-der can reduce the size of the conductor connecting the short-circuit protection device to the individual motor contactor/overload relay, to one third of the size of the upstream circuit conductor supplying the protection device. The panel builder must limit the length of the motor starter conductor (connecting the short-circuit protection device to the motor contactor/overload relay) to a maximum of 7.5 m (25 feet). Case n° 2 (Not approved under the CEC for US export applications only) The motor contactor and overload relay are listed as suitable for “tap conductor protection” in group installations. This category allows the panel designer to reduce the size of the conductor connecting the short-circuit protection device to the individual motor contactor/overload relay, to one tenth of the size of the upstream circuit conductor supplying the protection device. The designer must limit the length of this conductor to a maximum of 3.05 m (10 feet). In both cases, the supply circuits must not be less than 125 % of the connec-ted motor FLA (Full Load Amps) rating. For panel builders, using type F combination starters in group installations simplifi es group motor considerations. Each starter is a fully coordinated motor branch circuit. The panel builder follows the same NEC requirements for sizing the supply conductors as those required for single motor branch circuits. The size of the supply conductors can be reduced in accor-dance with the specifi cations of article 430.28. This allows the same fl exibility in conductor sizing as that offered in article 430.53 (D), without a requirement to check the short-circuit protection rating marked on the components and the overload relay limit. A UL508A panel does not need a short-circuit protection device when each motor starter installed is a type F. The upstream short-circuit protection device supplying the starter protects the panel. The panel builder only has to consider the panel/enclosure disconnect requirements specifi ed by the NEC or local codes.
M
1
2
3
4
Other versions: Please consult our Customer Care Centre.
35
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
Other versions: please consult our Customer Care Centre.4/354/35
4
Combination Starters – Type E & Type F
UL508A & Control Panels
Group Protection
TeSys Applications InformationGroup Motor and Type E
Combination Starters are the most common type of packaged motor starter. They are called ‘Combination’ because of their structure and their combined functions. The fi gure opposite shows the four combined functions that constitute a complete motor starter circuit, defi ned as a “Motor branch circuit” by the CEC and NEC. CSA 22.2 no 14 and UL508 currently give different types of combination starter that meet the requirements of a «Motor branch circuit».
Type E, called “self-protected combination starter”, covers all these functions and can be controlled manually (thermal-magnetic circuit-breaker) or remotely (starter-controller). Type E starters withstand faults within their declared nominal rating without sustaining damage, after which they can be put back into service. In addition, they can withstand more severe short-circuit and durability performance tests without welding or excessive wear of the contact tips.
Type F, called “Combination motor starter”, consists of a type E manual starter (thermal-magnetic circuit-breaker) combined with a contactor. These starters are evaluated by means of basic short-circuit tests, but are not considered as “self-protected”. For this combination, the type E starter must be marked “Combination Motor Controller when used with ...”, followed by the reference of the load side contactor.
At present, CSA does not recognize Type F combinations. Manual starters used with contactors can be used in Group Protection as described below.
To help users properly coordinate their motor control equipment with their distribution system in the event of a fault, article 409 of the 2005 NEC requires panel builders to list the short-circuit withstand rating of their motor control panels. According to standard UL508A, manufacturers must use the short-circuit withstand value of the lowest rated device as the nominal withstand rating of the panel, unless the devices have been tested together for a higher coordinated rating. The minimum “short-circuit current rating” (SCCR), on motor control components for horsepower ratings of 50 hp or below is 5000 A. Using a type E or type F combination starter eliminates the coordination problems of using individual components for the “motor branch circuit protection”, “motor controller” and “motor overload protection” functions. The panel builder uses the declared short-circuit current rating for the combination starter. This value is generally higher than 5000 A. This makes it easier to list the short-circuit current ratings and to check the compatibility of a UL508A motor control panel within a given distribution system.
1 Motor disconnect (disconnect switch) 2 Motor Branch Circuit Protection (short circuit protection) 3 Motor controller (contactor) 4 Motor Overload Protection (thermal overload relay)
Both the CEC and NEC allow a single short-circuit protection device to be used for more than one motor circuit if the components used are marked and listed for such use. Components suitable for use in group protection, known as “motor group installations”, can be marked in one of the following two ways: Case n° 1 The contactor and the motor overload relay are both listed as suitable for group installation. An inverse time circuit-breaker can be used as the short-circuit protection device if it is also listed as suitable for group installation. The panel builder must therefore make sure that the short-circuit protection device selected (fuses or inverse time circuit-breaker) does not exceed the value allowed by rule 28-206 of the CEC or article 430.40 of the NEC for the smallest overload relay used in the circuit. Once these conditions have been met, the panel buil-der can reduce the size of the conductor connecting the short-circuit protection device to the individual motor contactor/overload relay, to one third of the size of the upstream circuit conductor supplying the protection device. The panel builder must limit the length of the motor starter conductor (connecting the short-circuit protection device to the motor contactor/overload relay) to a maximum of 7.5 m (25 feet). Case n° 2 (Not approved under the CEC for US export applications only) The motor contactor and overload relay are listed as suitable for “tap conductor protection” in group installations. This category allows the panel designer to reduce the size of the conductor connecting the short-circuit protection device to the individual motor contactor/overload relay, to one tenth of the size of the upstream circuit conductor supplying the protection device. The designer must limit the length of this conductor to a maximum of 3.05 m (10 feet). In both cases, the supply circuits must not be less than 125 % of the connec-ted motor FLA (Full Load Amps) rating. For panel builders, using type F combination starters in group installations simplifi es group motor considerations. Each starter is a fully coordinated motor branch circuit. The panel builder follows the same NEC requirements for sizing the supply conductors as those required for single motor branch circuits. The size of the supply conductors can be reduced in accor-dance with the specifi cations of article 430.28. This allows the same fl exibility in conductor sizing as that offered in article 430.53 (D), without a requirement to check the short-circuit protection rating marked on the components and the overload relay limit. A UL508A panel does not need a short-circuit protection device when each motor starter installed is a type F. The upstream short-circuit protection device supplying the starter protects the panel. The panel builder only has to consider the panel/enclosure disconnect requirements specifi ed by the NEC or local codes.
M
1
2
3
4
Other versions: Please consult our Customer Care Centre.
Side-mounting accessories (snap onto the starters without the use of a tool)
On the left side, contact blocks which provide the following:• N.O. + N.O. or N.O. + N.C. instantaneous contacts• N.O. or N.C. trip signaling contact incorporating a mechanical flag indicator and an N.O. or N.C.
instantaneous contact• C/O magnetic trip signaling contact, associated with a mechanical flag indicator, used for reset.On the right side:• Shunt trip or undervoltage trip
Other accessories
• Combination block for use with TeSys® contactor
• Bus bars and connectors
• Visible isolation block, mounting on the incoming terminals of the device
• Door interlock mechanism
—
Selection Page 38 Page 38 Page 38 Page 39
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and ProtectorsShort-Circuit Current Ratings
UL 508 Type E Manual Self-Protected Combination Motor Controller, TeSys® GVManual Self-Protected Combination Starter Meeting UL 508 Type E, UL File E164871
Table 2: TeSys GV2P Horsepower and SCCR RatingsIn combination with line spacer GV2GH7 (stand-alone starters) or GV1G09 terminal and GV2G busbars (multiple starters)
Standard Motor Ratings @ 50/60 Hz (hp)Associated Cable, AWG 75 °C, Cu
Manual Self-Protected Starter
Overload Trip Range (A)
SCCR (kA) 480Y/277V1 Ø 3 Ø
120 V 240 V 200 V 240 V 480 V 600 V
10 GV2P01 0.1–0.16 100
10 GV2P02 0.16–0.25 100
10 GV2P03 0.25–0.4 100
10 GV2P04 0.4–0.63 100
0.5 10 GV2P05 0.63–1 100
0.75 10 GV2P06 1–1.6 100
0.5 0.5 1 10 GV2P07 1.6–2.5 100
0.75 1 2 10 GV2P08 2.5–4 100
1.5 1.5 4 10 GV2P10 4–6.3 100
0.5 1 2 3 5 7.5 10 GV2P14 6–10 100
1 2 3 3 10 10 8 GV2P16 9–14 10
1 3 5 5 10 15 8 GV2P20 13–18 10
2 3 5 7.5 15 20 6 GV2P21 17–23 10
2 3 5 7.5 15 20 6 GV2P22 20–25 10
Table 3: TeSys GV3P Horsepower and SCCR RatingsIn combination with line spacer GV3G66 and magnetic trip unit GVAM11 for stand-alone starters
Standard Motor Ratings @ 50/60 Hz (hp)Associated Cable, AWG 75 °C, Cu
Manual Self-Protected Starter
Overload Trip Range (A)
SCCR (kA)
1 Ø 3 Ø480Y/277 V 600Y/347 V
120 V 240 V 200 V 240 V 480 V 600 V
1 2 3 3 7.5 10 8 GV3P13 9–13 100 25
1 3 3 5 7.5 10 8 GV3P18 12–18 100 25
2 3 5 7.5 15 20 6 GV3P25 17–25 100 25
2 3 7.5 7.5 20 25 6 GV3P32 23–32 100 25
3 5 10 10 25 30 3 GV3P40 30–40 65 25
3 7.5 10 10 30 40 3 GV3P50 37–50 65 25
5 10 15 15 40 50 3 GV3P65 48–65 65 25
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and ProtectorsShort-Circuit Current Ratings
UL 508 Type F Combination Motor Controller, TeSys® GVManual Self-Protected Combination Starter Meeting UL 508 Type F, UL File E164871
Table 4: TeSys GV2P Horsepower and SCCR RatingsIn combination with line spacer GV2GH7 (stand-alone starters) or GV1G09 terminal and GV2G busbars (multiple starters)
Standard Motor Ratings @ 50/60 Hz (hp)Associated Cable, AWG 75 °C, Cu
Manual Self-Protected Starter
Overload Trip Range (A)
Type of Contactor Required
SCCR (kA)480Y/277 V1 Ø 3 Ø
120 V 240 V 200 V 240 V 480 V 600 V
10 GV2P01 0.1–0.16 LC1D09 or D12 100
10 GV2P02 0.16–0.25 LC1D09 or D12 100
10 GV2P03 0.25–0.4 LC1D09 or D12 100
10 GV2P04 0.4–0.63 LC1D09 or D12 100
0.5 10 GV2P05 0.63– 1 LC1D09 or D12 100
0.75 10 GV2P06 1–1.6 LC1D09 or D12 100
0.5 0.5 1 10 GV2P07 1.6–2.5 LC1D09 or D12 100
0.75 1 2 10 GV2P08 2.5– 4 LC1D09 or D12 100
1.5 1.5 4 10 GV2P10 4–6.3 LC1D09 or D12 100
0.5 1 2 3 5 7.5 10 GV2P14 6–10 LC1D09 or D12 100
1 2 3 3 10 10 8 GV2P16 9–14 LC1D12 or D18 42
1 3 5 5 10 15 8 GV2P20 13–18 LC1D12 or D18 42
2 3 5 7.5 15 20 6 GV2P21 17–23 LC1D25 or D32 42
2 3 5 7.5 15 20 6 GV2P22 20–25 LC1D25 or D32 42
Table 5: TeSys GV3P Horsepower and SCCR RatingsIn combination with line spacer GV3G66 and magnetic trip unit GVAM11 for stand-alone starters
Standard Motor Ratings @ 50/60 Hz (hp) Associated Cable, AWG 75 °C, Cu
UL 508 Group Motor Installations Manual Combination Motor Controller, TeSys® GVGV2ME: UL File E164864(MC 164581, Report 1012350, Project 2152063)
Table 6: TeSys GV2ME Horsepower and SCCR RatingsIn association with LC1D contactors, suitable for group installation when protected by fuses or an inverse-time circuit breaker (when used with GV1G09 terminal or GV2G05 blocks plus GV2G busbars)
Standard Motor Ratings @ 50/60 Hz (hp)Associated Cable, AWG 75 °C, Cu
Manual Motor Starter
Overload Trip Range (A)
SCCR (kA)1 Ø 3 Ø
Contactor 240/480 V
600Y/347 V
480 V with GV1L3 Limiter
Contactor600 V with LA9LB920 Limiter120 V 240 V 200 V 240 V 480 V 600 V
10 GV2ME01 0.1–0.16 LC1D09 or D12 65 42 65 LC1D09 or
D12 42
10 GV2ME02 0.16–0.25 LC1D09 or D12 65 42 65 LC1D09 or
D12 42
10 GV2ME03 0.25–0.4 LC1D09 or D12 65 42 65 LC1D09 or
D12 42
10 GV2ME04 0.4–0.63 LC1D09 or D12 65 42 65 LC1D09 or
D12 42
0.5 10 GV2ME05 0.63–1 LC1D09 or D12 65 42 65 LC1D09 or
D12 42
0.75 10 GV2ME06 1–1.6 LC1D09 or D12 65 42 65 LC1D09 or
D12 42
0.5 0.5 1 10 GV2ME07 1.6–2.5 LC1D09 or D12 65 42 65 LC1D09 or
D12 42
0.75 1 2 10 GV2ME08 2.5–4 LC1D09 or D12 65 42 65 LC1D09 or
D12 42
1.5 1.5 4 10 GV2ME10 4–6.3 LC1D09 or D12 65 42 65 LC1D09 or
D12 42
0.5 1 2 3 5 7.5 10 GV2ME14 6–10 LC1D09 or D12 65 42 65 LC1D09 or
D12 42
1 2 3 3 10 10 8 GV2ME16 9–14 LC1D12 or D18 22 10 65 LC1D32 or
D38 42
1 3 5 5 10 15 8 GV2ME20 13–18 LC1D12 or D18 22 10 65 LC1D32 or
D38 42
2 3 5 7.5 15 20 6 GV2ME21 17–23 LC1D25 or D32 10 10 65 LC1D32 or
D38 42
2 3 5 7.5 15 20 6 GV2ME22 20–25 LC1D25 or D32 10 10 65 LC1D32 or
D38 42
2 5 10 10 20 30 6 GV2ME32 24–32 LC1D25 or D32 5 5 65 LC1D32 or
D38 42
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and ProtectorsSpecifications and Operating Curves
RE40–RE100 RS40–RS100 RE150 RS150 RE220 RS220Rating 25–40 A to 60–100 A 90–150 A 90–150 A 132–220 A 132–220 A
Breaking capacity conforming to IEC 60947-2
230/240 VIcu [2] 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA
Ics% [3] 100% 100% 100% 100% 100% 100%
400/415 VIcu [2] 25 kA 70 kA 35 kA 70 kA 35 kA 70 kA
Ics% [3] 100% 100% 100% 100% 100% 100%
440 VIcu [2] 25 kA 65 kA 35 kA 65 kA 35 kA 65 kA
Ics% [3] 100% 100% 100% 100% 100% 100%
500 VIcu [2] 18 kA 50 kA 30 kA 50 kA 30 kA 50 kA
Ics% [3] 100% 100% 100% 100% 100% 100%
690 VIcu [2] 8 kA 10 kA 8 kA 10 kA 8 kA 10 kA
Ics% [3] 100% 100% 100% 100% 100% 100%1 GV7R motor controllers and protectors are not recommended for use with variable speed controllers or soft start units in applications under 40 Hz.2 Icu = interrupting capacity at full voltage.3 Ics = short-circuit interrupting capacity as a percentage of Icu.
Table 32: UL Maximum SCCR (rms) (kA) [1, 2]
1 Group Installation: Maximum NTD fuse size: 1200 A. Maximum manual starter and protector rating: 1200 A.2 Suitable for use on a circuit with an available SCCR no greater than the SCCR of the manual motor controller or manual starter
and protector, whichever is less.
Type RangeSCCR
240 V [3]
3 Nominal system voltage.
480 V [3] 600 V [3]
GV7RE40 25–40 A 25 25 10
GV7RE50 30–50 A 25 25 10
GV7RE80 48–80 A 25 25 10
GV7RE100 60–100 A 25 25 10
GV7RE150 90–150 A 25 25 10
GV7RE220 132–220 A 25 25 10
GV7RS40 25–40 A 65 65 10
GV7RS50 30–50 A 65 65 10
GV7RS80 48–80 A 65 65 10
GV7RS100 60–100 A 65 65 10
GV7RS150 90–150 A 65 65 10
GV7RS220 132–220 A 65 65 10
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and ProtectorsSelection
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and ProtectorsSelection
426/2010
Table 52: Electrical Trip Units
Description Voltage Hz Catalog No. [1]
1 To order an undervoltage trip unit: replace the bullet (•) with a U, for example: GVAU025. To order a shunt trip unit: replace the bullet (•) with an S, for example: GVAS025.
Catalog number TSXCTY2A TSXCTY4A TSXCTY2C TSXCCY1128
(1) For 2/3-wire PNP/NPN 24 VDC sensors.
(2) For 5 VDC RS422, 10–30 VDC Totem Pole incremental encoders.
(3) For SSI serial or parallel output absolute encoders.
(4) For RS485 serial or parallel output absolute encoders.
Module type For translators For analog control servomotors(amplifier for stepper motor) (for asynchronous and brushless motors)
Control outputs RS 422 +/- 10 V
Compatible with drives Lexium 05, Twin Line Lexium 05/17D, Twin Line
Functions Linear axes – Limited Limited or infinite Limited or infinite(5)
Slave axes – With static ratio With dynamic ratio –
Frequency for each axis 187 kHz 500 kHz with incremental encoder, 200 kHz with absolute encoder (6)
Number of axes 1 2 2 4 2 4 3
Catalog number TSXCFY11 TSXCFY21 TSXCAY21 TSXCAY41 TSXCAY22 TSXCAY42 TSXCAY33
(5) With linear interpolation on 2 or 3 axes .
(6) SSI serial or with parallel outputs.
Module type Servomotors with SERCOS® digital ring(for brushless motors)
Control outputs SERCOS® network r ing
Compatible with ranges Lexium 17D
Functions Linear or infinite independent axes, slave axes with cam profile or ratio
Processing 4 sets of axes with linear 4 sets of axes with linear and circular 4 sets of axes with linear
interpolation from 2 to 8 axes inter polation from 2 to 3 axes (7) inter polation from 2 to 8 axes
Frequency for each axis 4 Mb SERCOS® network r ing
Number of axes 8 (8) 8 (8) 16 (9)
Catalog number TSXCSY84 TSXCSY85 TSXCSY164
(7) TSXCSY85 module supplied with TJE trajectory editor: linear trajectories with links between segments according to polynomial or circular inter polation and circular trajectories.
(8) 8 real axes , 4 imaginary axes and 4 remote axes.
(9) 16 axes (real axes, imaginary and remote axes).
Type of module ISP Plussupplied uncalibrated supplied calibrated and offer
Load cell inputs / outputs 50 measurements (for 1 to 8 load cells) / 2 discrete and 1 RS 485 for display unit
Catalog number Without display unit TSXISPY101 Please consult your Schneider Electric agency
With display unit TSXXBTH100 TSXISPY111 Please consult your Schneider Electric agency
Connection accessories: See www.us.telemecanique.com
ModiconPremium
Weighing modules
Motion control modules
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
For other versions, please consult with your local Schneider Electric/
Square D sales office: visit www.us.telemecanique.com3/44
3
Automation platformIntrinsically safe I/O modules
Type of module Inputs/OutputsDiscrete Analog
Conformity Directive ATEX 94/9/EC, EN 50014, EN 50020, EN 50284, EN 50281-1
Zone D (dust) Mounted outside zone (to be used in conjunction with products for zone 20, 21 or 22)
EC type examination cer tificate number / marking SIRA 02ATEX2345X / II (1) G/D-[EEx ia] IIC
Connection By screw ter minal 140XTS33200 (to be ordered separately)
Combination AFI devices provide protection against both high-energy paral-lel arcing (same as existing branch/feeder AFCI’s) and low energy (5A) series arcing.
Circuit Breaker Factory Installed AccessoriesRequires Additional Pole Space. Only one accessory per breaker. QO accessory terminals for (2) #14-12 Cu. Accessories are not available for Q2, QOM1, or QOB-VH (110-150 A) circuit breakers or QO molded case switches.
Add suffix - 1021 for 240Vac shunt trip. Factory Installed Accessory Do not exceed the load centre mains rating. Main Breakers include factory installed handle padlock attachment (padlock
QOM main circuit breaker in the 'off' position).
QO One Polewith Shunt Trip
QOK KeyOperated
DE1_p03-16.fm Page 7 Friday, December 2, 2016 1:08 PM
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
Canadian HomeLine™ Circuit Breakers and LoadcentresProduct Description
DE
1L
OA
DC
EN
TR
ES
DE1-2112/16
Notes:
1. CHOM 1pole - 1" wide, 1 space required.
2. CHOM 2pole - 2" wide, 2 spaces required.
3. CHOMT 1pole tandem - 1" wide, 1 space required,represents two 1pole circuit breakers, i.e. CHOMT1515.
4. CHOMT 2pole tandem quad - 2" wide, 2 spaces required, represents two 1pole outer poles and one 2pole inner circuit breaker with common trip,
i.e. CHOMT1515220.
Canadian Catalogue Number logicHomeLine™ Loadcentres
Number Segment Character Description CHOM 3060 L 200 G — C
Load Center Family CHOM CSA Listed
Spaces / Circuits 3060
Mains TypeM Main circuit breaker
L Main lugs
Amps
Ground Bar G Factory included
Cover
C Combination flush / surface indoor cover
F Flush
RB Rainproof
S Surface
HomeLine™ Circuit Breakers
Number Segment Character Description CHOM 1 15 —
BrandCHOM Full Size
CHOMT Tandem/Quad
Number of Poles
Amps
Device Name
AFI Arc fault circuit interruption
BB High amp branch breaker
CAFI Combination arc fault circuit interruption
EPD Equipment protection device, 30mA
GFI Ground fault circuit interruption, 5mA
HM High magnetic trip
DF Dual function
DE1_p21.fm Page 21 Friday, December 2, 2016 8:05 PM
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
DE1-24
Canadian HomeLine™ Circuit Breakers and LoadcentresCircuit Breakers and Accessories
DE
1L
OA
DC
EN
TR
ES
12/16
Note: Canadian HomeLine and QO loadcentre accessories may
Canadian HomeLine Breaker Accessories
Description Cat. No.
Handle attachments
Handle tie, converts any 2 adjacent 1P HOM circuit breakers to independent trip 2P HOM1HT
Handle tie, converts any adjacent 1P side by side HOMT CB's to independent 2P HOMTHT
Handle lock, ON or OFF, nonpadlocking HomeLine 1p 15-50A CB QO1LO
Handle blocking device, attaches to a HOM 2P CB for holding the handle in the OFF position HOM2HBD
Handle lock, ON or OFF, padlocking HomeLine 1p 15-50A CB HOM1PA
2 pole standard HomeLine handle lock ON or OFF, Padlocking
- Handle padlock attachment, for padlocking 2P 15-70A HOM2PALA
- Handle padlock attachment, for padlocking 2P 80-125A HOM2PAHA
- Handle padlock attachment, for padlocking 2P 150-200A HOM2PAVHA
Handle Padlock Attachment, for padlocking 1P CAFI,DF, GFI, and EPD CHOM breakers in ON or OFF position HOMELEC1PA
Handle Padlock Attachment, for padlocking 2P CAFI, GFI, and EPDC CHOM breakers in ON or OFF position HOMELEC2PALA
Handle padlock attachment, for padlocking centre poles of HOM quad breakers in the OFF position HOMQPA
Handle lock, OFF for QOM1 50-125A Main Circuit Breaker QOM1PA
Handle lock, OFF for QOM2 100-225A Main Circuit Breaker QOM2PA
Bus and networks Ethernet, IEEE 802.3 10/100 BASE-T, RJ 45
Video input NTCS/PAL (59.5/50 Hz) RCA connector (75 ohms)
Audio input (microphone) mini-jac k connector
Expansion For Modbus Plus network connection
Third par ty protocols Mitsubishi (Melsec), Omron (Sysmac), Rockw ell Automation (Allen Bradley), Siemens (Simatic)
Development software Vijeo Designer VJDpppTGSVppM (on Windows 2000 and XP)
Dimensions W x D x H 215 60 x 170 mm
Compatibility with PLCs Twido, Nano, TSX Micro, Premium, Quantum
Compact Flash card slot yes
Character fonts ASCII, (including European characters), Japanese (ANK, Kanji), Chinese (simplified Chinese), Taiwanese (traditional Chinese), K orean
Built-in Ethernet TCP/IP yes
Supply voltage 24 VDC
Catalog number XBTGT4320 XBTGT4330 XBTGT4340
(1) NTIC: New Technology for Information and Communication
XBTGT XBTG
MagelisCourtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
For other versions, please consult with your Schneider Electric/
Square D Sales office: visit www.us.telemecanique.com2/40
2
Magelis AccessoriesFor display units and terminals
Connection cables PC to Magelis transfer cables2.5 m 2.5 m 2 m 2 m 2 m
Application PC to all XBTN200, PC to all XBT except PC to XBTGT1000 PC to
N400 and R400 XBTN200, N400, XBTGT2000 to
R400 and XBTGT11p0 XBTGT7000
Type of connector RJ45/MiniDin + SUBD 9 SUBD 9/SUBD 25 SUBD 9/MiniDin USB/MiniDin USB/USB
Physical link RS 232C RS 232C TTL TTL
Catalog number XBTZ945 (1) XBTZ915 (1) XBTZG915 XBTZG925 XBTZG935
(1) Adaptor SR2CBL06 for linking USB por t of PC, to be used in conjunction with connecting cables XBTZ945 and XBTZ915 for connecting displa y units or terminals
XBTN/R/H/P/E/HM/PM/F.
Connection cables Telemecanique PLC connection cables (2.5 m)
Application XBTGT, XBTN200, N400, All XBT except XBTGT11p0, XBTN200, N400, R400, NU400 to:
R400, NU400 to:
Twido, Nano, Twido, Nano, Quantum Momentum
TSX Micro, Premium TSX Micro, Premium (port 1)
Type of connector RJ45 / MiniDin MiniDin / SUBD 25 SUBD 9 / SUBD 25 RJ45 / SUBD 25
Physical link RS 485 RS 485 RS 232 RS 232
Catalog number XBTZ9780 XBTZ968 XBTZ9710 XBTZ9711
Cordsets for direct connection XBTGT terminals to Telemecanique products
Automation product Connector Protocol XBT type terminal, On Length Catalog Weight
type type physical link XBT por t number
(product side) kg
Twido, Ter minal port Uni-TE XBTGT11p0, RS485 COM1 2.5 m XBTZ9780 0.180
Catalog number TSXCTY2A TSXCTY4A TSXCTY2C TSXCCY1128
(1) For 2/3-wire PNP/NPN 24 VDC sensors.
(2) For 5 VDC RS422, 10–30 VDC Totem Pole incremental encoders.
(3) For SSI serial or parallel output absolute encoders.
(4) For RS485 serial or parallel output absolute encoders.
Module type For translators For analog control servomotors(amplifier for stepper motor) (for asynchronous and brushless motors)
Control outputs RS 422 +/- 10 V
Compatible with drives Lexium 05, Twin Line Lexium 05/17D, Twin Line
Functions Linear axes – Limited Limited or infinite Limited or infinite(5)
Slave axes – With static ratio With dynamic ratio –
Frequency for each axis 187 kHz 500 kHz with incremental encoder, 200 kHz with absolute encoder (6)
Number of axes 1 2 2 4 2 4 3
Catalog number TSXCFY11 TSXCFY21 TSXCAY21 TSXCAY41 TSXCAY22 TSXCAY42 TSXCAY33
(5) With linear interpolation on 2 or 3 axes .
(6) SSI serial or with parallel outputs.
Module type Servomotors with SERCOS® digital ring(for brushless motors)
Control outputs SERCOS® network r ing
Compatible with ranges Lexium 17D
Functions Linear or infinite independent axes, slave axes with cam profile or ratio
Processing 4 sets of axes with linear 4 sets of axes with linear and circular 4 sets of axes with linear
interpolation from 2 to 8 axes inter polation from 2 to 3 axes (7) inter polation from 2 to 8 axes
Frequency for each axis 4 Mb SERCOS® network r ing
Number of axes 8 (8) 8 (8) 16 (9)
Catalog number TSXCSY84 TSXCSY85 TSXCSY164
(7) TSXCSY85 module supplied with TJE trajectory editor: linear trajectories with links between segments according to polynomial or circular inter polation and circular trajectories.
(8) 8 real axes , 4 imaginary axes and 4 remote axes.
(9) 16 axes (real axes, imaginary and remote axes).
Type of module ISP Plussupplied uncalibrated supplied calibrated and offer
Load cell inputs / outputs 50 measurements (for 1 to 8 load cells) / 2 discrete and 1 RS 485 for display unit
Catalog number Without display unit TSXISPY101 Please consult your Schneider Electric agency
With display unit TSXXBTH100 TSXISPY111 Please consult your Schneider Electric agency
Connection accessories: See www.us.telemecanique.com
ModiconPremium
Weighing modules
Motion control modules
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
For other versions, please consult with your local Schneider Electric/
Square D sales office: visit www.us.telemecanique.com3/44
3
Automation platformIntrinsically safe I/O modules
Type of module Inputs/OutputsDiscrete Analog
Conformity Directive ATEX 94/9/EC, EN 50014, EN 50020, EN 50284, EN 50281-1
Zone D (dust) Mounted outside zone (to be used in conjunction with products for zone 20, 21 or 22)
EC type examination cer tificate number / marking SIRA 02ATEX2345X / II (1) G/D-[EEx ia] IIC
Connection By screw ter minal 140XTS33200 (to be ordered separately)
(1) Must be used with a line choke, see page 4/20. (2) Drive supplied without EMC filter.
(3) To order a reinforced version of the dr ive for specific environmental conditions, conforming to IEC 60721-3-3 class 3c2, add S337 at the end of the catalog number.
(4) Refer to page 4/24 for information on option cards if additional I/O is needed.
Dimensions (mm) width x height x depth
Size 2: 130 x 230 x 175 Size 3: 155 x 260 x 187
Size 4: 175 x 295 x 187 Size 5A: 210 x 295 x 213
Size 5B: 230 x 400 x 213 Size 6: 240 x 420 x 236
Size 7A: 240 x 550 x 266 Size 7B: 320 x 550 x 266
Size 8: 320 x 630 x 290 Size 9: 320 x 920 x 377
Size 10: 360 x 1022 x 377 Size 11: 340 x 1190 x 377
Size 12: 440 x 1190 x 377 Size 13: 595 x 1190 x 377
Size 14: 890 x 1390 x 377 Size 15: 1120 x 1390 x 377
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
For other versions, please consult with your local Schneider Electric/
Square D sales office: visit www.us.telemecanique.com 4/17
4
Type of drive Three phase Three phase range in ready-assembled enclosure (5)
380–480 V (3) 380–480 VDegree of protection UL Type 12/IP54 IP54 enclosure
Output frequency 0.5–1600 Hz up to 37 kW (50 Hp); 0.5–500 Hz from 45 to 630 kW (60 to 900 Hp)
Type of control Asynchronous motor Flux vector control with or without sensor
Synchronous motor Vector control without speed feedbac k
Transient overtorque 110% to 120% of the nominal drive current for 60 seconds
Speed range 1–100 in open loop mode
I/O 6
Logic inputs (4)
Analog inputs 2
Analog outputs 1
Relay outputs 2
Safety input 1
Dialog Remote g raphic display ter minal or PowerSuite software workshop (see page 4/32)
Communication Integrated Modbus and CANopen(see page 4/32) Available as an option HVAC protocols: LonWorks, BACnet, METASYS N2, APOGEE FLN
Cards (available as an option) Multi-pump cards, I/O extension cards, “Controller Inside” programmable card
Reduction of current harmonics Integrated DC chok e (optional chokes and passive filters, see page 4/20)
EMC Class A Integrated filter Integrated filter
Class B Integrated filter External filter availab le as an option
Motor power kW/Hp 0.75 1 ATV61W075N4 Size A2 ATV61W075N4C Size A2 –
1.5 2 ATV61WU15N4 Size A2 ATV61WU15N4C Size A2 –
2.2 3 ATV61WU22N4 Size A2 ATV61WU22N4C Size A2 –
3 – ATV61WU30N4 Size A3 ATV61WU30N4C Size A3 –
4 5 ATV61WU40N4 Size A3 ATV61WU40N4C Size A3 –
5.5 7.5 ATV61WU55N4 Size B ATV61WU55N4C Size B –
7.5 10 ATV61WU75N4 Size B ATV61WU75N4C Size B –
11 15 ATV61WD11N4 Siz e C ATV61WD11N4C Siz e C –
15 20 ATV61WD15N4 Siz e D ATV61WD15N4C Siz e D –
18.5 25 ATV61WD18N4 Siz e D ATV61WD18N4C Siz e D –
22 30 ATV61WD22N4 Size E ATV61WD22N4C Size E –
30 40 ATV61WD30N4 Size F ATV61WD30N4C Size F –
37 50 ATV61WD37N4 Size F ATV61WD37N4C Size F –
45 60 ATV61WD45N4 Size G ATV61WD45N4C Size G –
55 75 ATV61WD55N4 Size G ATV61WD55N4C Size G –
75 100 ATV61WD75N4 Size G ATV61WD75N4C Size G –
90 125 ATV61WD90N4 Size G ATV61WD90N4C Size G –
110 150 – – ATV61HC11N4 A1
132 200 – – ATV61HC13N4 A1
160 250 – – ATV61HC16N4 A1
220 350 – – ATV61HC22N4 A1
250 400 – – ATV61HC25N4 A2
315 500 – – ATV61HC31N4 A2
250 400 – – ATV61HC25N4 A2
315 500 – – ATV61HC31N4 A2
400 600 – – ATV61HC40N4 A3
500 700 – – ATV61HC50N4 A3
630 900 – – ATV61HC63N4 A4
(5) The Altivar 61 range in ready-assembled enclosure consists of:
– An ATV61H… drive
– A switch and fast-acting fuses
– An IP65 remote mounting kit for graphic display terminal
IP54 drives Available in 2007Dimensions (mm) width x height x depth
ATV61W… ATV61E5C… in enclosure
Size A2: 235 x 490 x 272 A1 : 616 x 2000 x 600
Size A3: 235 x 490 x 286 A2 : 816 x 2000 x 600
Size B: 255 x 525 x 286 A3 : 1016 x 2000 x 600
Size C: 290 x 560 x 315 A3 : 1220 x 2000 x 600
Size D: 310 x 665 x 315 A3 : 2024 x 2000 x 600
Size E: 284 x 720 x 315 A4 : 1216 x 2000 x 600
Size F: 284 x 880 x 343 A4 : 1820 x 2000 x 600
Size G: 362 x 1000 x 364 A4 : 2224 x 2000 x 600
Ready-assembled enclosure with
braking transistor integrated in the
drive
Ready-assembled enclosure with
braking unit in the enclosure
Ready-assembled enclosure
without braking unit
Altivar 61Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
For other versions, please consult with your local Schneider Electric/
Square D sales office: visit www.us.telemecanique.com4/22
4
Complex, high-power machinesIP21 drives
Altivar 710.5–700 Hp, 0.37–500 kW
Type of drive Single phase Three phase Three phase Three phase on base plateSupply voltage 200–240 V (3) 200–240 V (3) 380–480 V (3) 380–480 V (3)
Degree of protection IP21 for unprotected dr ives and IP41 on the upper par t
Output frequency 0.1–1600 Hz up to 37 kW / 50 HP, 0.1–500 Hz from 45 to 500 kW / 60 to 700 HP
Type of control Asynchronous motor Flux vector control with or without sensor, voltage/frequency ratio (2 or 5 points), ENA System
Synchronous motor Vector control without speed feedback
Transient overtorque 220% of nominal motor torque for 2 seconds, and 170% for 60 seconds
Speed range 1–1000 in closed loop mode with encoder feedback, 1–100 in open loop mode
I/O (4) Analog inputs 2
Logic inputs 6
Analog outputs 1
Relay outputs 2
Safety input 1
Dialog Remote graphic display terminal or PowerSuite software workshop (see pages 4/25 and 4/28)
Communication Integrated Modbus and CANopen(see page 4/32) Available as an option Ethernet TCP/IP, Modbus/Uni-Telway, Fipio, Modbus Plus, Profibus DP, DeviceNet, INTERBUS
Cards (availab le as an option) Encoder interface cards, I/O extension cards, “Controller Inside” prog rammable card
Reduction of current harmonics DC choke integrated or supplied with the product, (optional chokes and passive filters, see page 4/26)
EMC Class A Integrated filter
Class B External filter available as an option
Motor power kW/Hp 0.37 0.5 ATV71H075M3 Size 2 ATV71H037M3 Size 2 – –
(1) Must be used with a line choke, see page 4/26.
(2) Drive supplied without EMC filter.
(3) To order a reinforced version of the dr ive for specific environmental conditions, conforming to IEC 60721-3-3 class 3c2, add S337 at the end of the catalog number.
e.g. ATV71H075N4S337
(4) Refer to page 4/24 for information on option cards if additional I/O is needed.
Dimensions (mm) width x height x depth
Size 2 : 130 x 230 x 175 Size 3 : 155 x 260 x 187
Size 4 : 175 x 295 x 187 Size 5A : 210 x 295 x 213
Size 5B : 230 x 400 x 213 Size 6 : 240 x 420 x 236
Size 7A : 240 x 550 x 266 Size 7B : 320 x 550 x 266
Size 8 : 320 x 630 x 290 Size 9 : 320 x 920 x 377
Size 10 : 360 x 1022 x 377 Size 11 : 340 x 1190 x 377
Size 12 : 440 x 1190 x 377 Size 13 : 595 x 1190 x 377
Size 14 : 890 x 1390 x 377 Size 15 : 1120 x 1390 x 377
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
For other versions, please consult with your local Schneider Electric/
Square D sales office: visit www.us.telemecanique.com 4/23
4
IP54 drives
Type of drive Three phase Three phase range in ready-assembled enclosure (4)
380–480 V (3) 380–480 VDegree of protection UL Type 12/IP54 IP54 enclosure
Drive Output frequency 0.1–1600 Hz up to 37 kW, 0.1–500 Hz from 45 to 500 kW
Type of control Asynchronous motor Flux vector control with or without sensor, voltage/frequency ratio (2 or 5 points), ENA System
Synchronous motor Vector control without speed feedback
Transient overtorque 220% of nominal motor torque for 2 seconds, and 170% for 60 seconds
Speed range 1–1000 in closed loop mode with encoder feedback, 1–100 in open loop mode
I/O (4) Analog inputs 2
Logic inputs 6
Analog outputs 1
Relay outputs 2
Safety input 1
Dialog Remote g raphic display ter minal or PowerSuite software workshop (see page 4/28)
Communication Integrated Modbus and CANopen(see page 4/28) Available as an option Ether net TCP/IP, Modbus/Uni-Telway, Fipio, Modbus Plus, Profibus DP, DeviceNet, INTERBUS
Cards (available as an option) Encoder interface cards, I/O extension cards, “Controller Inside” programmable card
Reduction of current harmonics Optional chokes and passive filters (see page 4/26)
EMC Class A Integrated filter
Class B External filter available as an option
Motor power kW/HP 0.75 1 ATV71W075N4 Size A2 –
1.5 2 ATV71WU15N4 Size A2 –
2.2 3 ATV71WU22N4 Size A2 –
3 – ATV71WU30N4 Size A3 –
4 5 ATV71WU40N4 Size A3 –
5.5 7.5 ATV71WU55N4 Size B –
7.5 10 ATV71WU75N4 Size B –
11 15 ATV71WD11N4 Size C –
15 20 ATV71WD15N4 Size D –
18.5 25 ATV71WD18N4 Size D –
22 30 ATV71WD22N4 Size E –
30 40 ATV71WD30N4 Size F –
37 50 ATV71WD37N4 Size F –
45 60 ATV71WD45N4 Size G –
55 75 ATV71WD55N4 Size G –
75 100 ATV71WD75N4 Size G –
90 125 – ATV71HD90N4 ATV71E5D90N4 A1
110 150 – ATV71HC11N4 A1
132 200 – ATV71HC13N4 A1
160 250 – ATV71HC16N4 A1
200 300 – ATV71HC20N4 A2
220 350 – ATV71HC25N4 A2
280 450 – ATV71HC28N4 A2
200 300 – ATV71HC20N4 A2
220 350 – ATV71HC25N4 A2
280 450 – ATV71HC28N4 A2
315 500 – ATV71HC31N4 A3
400 600 – ATV71HC40N4 A3
500 700 – ATV71HC50N4 A4
(4) The Altivar 71 range in ready-assembled enclosure consists of:
– An ATV71H… drive
– A switch and fast-acting fuses
– An IP65 remote mounting kit for graphic display terminal
Dimensions (mm) width x height x depth
ATV71W… ATV71E5C… in enclosure
Size A2 : 235 x 490 x 272 A1 : 616 x 2000 x 600
Size A3 : 235 x 490 x 286 A2 : 816 x 2000 x 600
Size B : 255 x 525 x 286 A3 : 1016 x 2000 x 600
Size C : 290 x 560 x 315 A3 : 1220 x 2000 x 600
Size D : 310 x 665 x 315 A3 : 2024 x 2000 x 600
Size E : 284 x 720 x 315 A4 : 1216 x 2000 x 600
Size F : 284 x 880 x 343 A4 : 1820 x 2000 x 600
Size G : 362 x 1000 x 364 A4 : 2224 x 2000 x 600
Ready-assembled enclosure with
braking transistor integrated in the
drive
Read y-assembled enclosure with
braking unit in the enclosure
Read y-assembled enclosure without
braking unit
Altivar 71Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
For other versions, please consult with your local Schneider Electric/
Square D sales office: visit www.us.telemanique.com. 5/7
5
Suppressor modulesVaristors (peak limiting)
Protection provided by limiting the transient voltage to 2 Uc max.
Maximum reduction of transient voltage peaks.
Slight increase in drop-out time (1.1 to 1.5 times the normal time)
Mounting For use with contactor Type Catalog number
Rating VAC VDCClip-on D09–D38 (3P) 12–24 V - LAD4VE
DT20–DT40 (4P) 50–127 V - LAD4VG
110–240 V - LAD4VU
Screw clamp D40–D115 (3P) 24–48 V - LA4DE2E
and 50–127 V - LA4DE2G
D65–D115 (4P) 110–250 V - LA4DE2U
D40–D115 (3P) - 24–48 V LA4DE3E
and - 50–127 V LA4DE3G
D65–D115 (4P) - 110–250 V LA4DE3U
Diodes
No overvoltage or oscillating frequency.
Increase in drop-out time (6 to 10 times the normal time).
Polarised component.
Screw clamp D40–D95 (3P) - 24–250 V LA4DC3U
D65 and D80 (4P)
Bidirectional peak limiting diode
Protection provided by limiting the transient voltage to 2 Uc max.
Maximum reduction of transient voltage peaks.
Clip-on D09–D38 (3P) 24 V - LAD4TB
DT20–DT40 (4P) 72 V - LAD4TS
Screw clamp D40–D95 (3P) 24 V - LA4DB2B
D65 and D80 (4P) 72 V - LA4DB2S
D40–D95 (3P) - 24 V LA4DB3B
D65 and D80 (4P) - 72 V LA4DB3S
RC circuits (Resistor-Capacitor)
Effective protection for circuits highly sensitive to "high frequency" interference.
For use only in cases where the voltage is virtually sinusoidal, i.e. less than - 5% total harmonic distortion.
Voltage limited to 3 Uc max and oscillating frequency limited to 400 Hz max.
Slight increase in drop-out time (1.2 to 2 times the normal time)
Clip-on D09–D38 (3P) 12–24 V - LAD4RCE
DT20–DT40 (4P) 110–240 V - LAD4RCU
Screw fixing D40–D150 (3P) 24–48 V - LA4DA2E
and 50–127 V - LA4DA2G
D65–D115 (4P) 110–240 V - LA4DA2U
380–415 V - LA4DA2N
TeSysD-line
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
For other versions, please consult with your localSchneider Electric /
Square D sales office: visit www.us.telemanique.com.5/10
5
Thermal-magnetic circuit-breakers GV2ME for connection by spring terminals
Add the figure 3 to the end of the catalog number. Example GV2ME223 (available up to GV2ME22)
TeSysType GVZMEand GV2P
Manual motor starters0.1–30 Hp
Manual motor starters GV2ME and GV2P for connection by screw clamp terminalsGV2ME with pushbutton control, GV2P control by rotary knob
Horsepower ratings of 3-phase motors 50/60 Hz Setting range Magnetic Catalog Number
200 V 230 V 460 V 575 V of thermal tripping
trips current Push button Rotary Handle
A A
- - - - 0.1–0.16 1.5 GV2ME01 GV2P01
- - - - 0.16–0.25 2.4 GV2ME02 GV2P02
- - - - 0.25–0.40 5 GV2ME03 GV2P03
- - - - 0.40–0.63 8 GV2ME04 GV2P04
- - 0.5 0.5 0.63–1 13 GV2ME05 GV2P05
- - 0.75 1 1–1.6 22.5 GV2ME06 GV2P06
0.5 0.5 1 1.5 1.6–2.5 33.5 GV2ME07 GV2P07
0.75 1 2 3 2.5–4 51 GV2ME08 GV2P08
1.5 1.5 3 5 4–6.3 78 GV2ME10 GV2P10
2 3 5 7.5 6–10 138 GV2ME14 GV2P14
3 3 10 10 9–14 170 GV2ME16 GV2P16
5 5 10 15 13–18 223 GV2ME20 GV2P20
5 7.5 15 20 17–23 327 GV2ME21 GV2P21
5 7.5 15 20 20–25 327 GV2ME22 GV2P22
10 10 20 30 24–32 416 GV2ME32 GV2P32
Thermal-magnetic circuit-breakers GV2ME for connection by spring terminals
Add the number 3 to the end of the catalog number. Example GV2ME223 (available up to GV2ME22)
Fuse holder—30 A rated, type CC or KTK-R fuses
Catalog Number
With screw terminals LS1D30
With spring terminals LS1D303
Auxiliary pole (screw terminals; LA8D324
mount on left or right side)
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
For other versions, please consult with your localSchneider Electric /
Square D sales office: visit www.us.telemanique.com.5/14
Control voltage / output voltage 24 VDC / 24 VDC 24 VDC / 24 VDC
LED per channel – With
Number of terminals per channel/on row number 1/2 1/1 2/2 3/3
Dimensions W x D x H 55 x 59 x 67 mm 106 x 60 x 49 mm
Catalog number – ABE7H16C11 ABE7H16C21 ABE7H16C31
Cable L = 1 m ABE7H20E100 (1) – – –
Cable L = 2 m ABE7H20E200 (1) – – –
Cable L = 3 m ABE7H20E300 (1) – – –
Connection cable recommended for Modicon, TSX Micro and Premium PLCs, L = 1 m (2) ABFH20H100
(1) Connection cable supplied for PLCs.
(2) For a 2 m length cable, replace the number 1 in the catalog number by 2, and for a 3 m length, by 3. (Example: ABFH20H100 becomes ABFH20H200).
Type of connection sub-base Universal
Number of channels 16
Max. current per channel 0.5 A
Control voltage / output voltage 24 VDC / 24 VDC
LED per channel – With – – With With
Number of terminals per channel/on row number 1/1 1/1 1/2 2/2 2/2 3/3
Dimensions W x D x H 125 x 58 x70 mm 84x58x70 mm 125 x 58 x 70 mm
Catalog number ABE7H16R10 ABE7H16R11 ABE7H16R50 ABE7H16R20 ABE7H16R21 ABE7H16R31
Connection cable recommended for Modicon, TSX Micro and Premium PLCs, L = 1 m: ABFH20H100 (2)
(2) For a 2 m length cable, replace the number 1 in the catalog number by 2, and for a 3 m length, by 3. (Example: ABFH20H100 becomes ABFH20H200).
Type of connection sub-base For counter and Passive distribution Distribution and supplyanalog channels with shielding continuity of analog channels
Number of channels 1 counter channel (3) 8 8
Max. current per channel 25 mA 25 mA 25 mA
Control voltage / output voltage 24 VDC / 24 VDC
Number of terminals per channel 2 2 or 4 2 or 4
Dimensions WxDxH (mm/in) 143 x 58 x 70 mm 125 x 58 x 70 mm 125 x 58 x 70 mm
Catalog number ABE7CPA01 ABE7CPA02 ABE7CPA03
Connection cable recommended TSX Micro L = 2.5 m TSXCCPS15 – –for Modicon PLCs (4) Premium L = 3 m TSXCAP030
(3) Or 8 inputs + 2 outputs, analog.
(4) Connection cables available for other PLCs, please refer to your Schneider Electr ic agency.
Advantys ABE7Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
For other versions, consult with your local Schneider Electric/
Square D sales office: visit www.us.telemecanique.com 7/7
7
Sockets with plug-in relays and terminals
Type of connection sub-base With soldered solid-state With soldered solid-state With soldered electro-relay inputs relay outputs mechanical relay outputs
(1) Version with 32 inputs. For version with 16 inputs, replace 32 in the catalog number by 16 (example: XPSMC32Z becomes XPSMC16Z).
(2) XPSMCWIN configuration software, configuration cable TSXPCX1031, adaptor XPSMCCPC and a set of plug in connectors with screw terminals XPSMCTS16 or
XPSMCTS32 or set of plug in connectors with spring terminals XPSMCTC16 or XPSMCTC32 to be ordered separately.
(3) For version with non-removable ter minal block, delete the letter P from the end of the catalog number (example: XPSMP11123P becomes XPSMP11123).
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
For other versions, please consult with your local Schneider Electric/
Square D sales office: visit www.us.telemecanique.com
9
9/6
Universal
Universal
Universal
Maximum category of the solution SIL 3 per EN/IEC 61508Category 4 per EN 954-1
Number of circuits Safety 2 x 2 N.O. + 6 solid-state
Additional –
Display (number of LEDs) 30
Width of housing 74 mm
Communication interface Modbus Modbus, CANopen Modbus, Profibus DP
Universal solutions: safety controllers (for monitoring several safety functions simultaneously)Supply voltage 24 VDC XPSMC32Z (1)(2) XPSMC32ZC (1)(2) XPSMC32ZP (1)(2)
Light curtains
Maximum category of the solution SIL 3 per EN/IEC 61508 Category 4Category 4 per EN 954-1 per EN 954-1
Number of circuits Safety 2 x 2 N.O. + 6 solid-state 2 x 3 N.O. per function 6 PNP solid-state
Additional – 3 solid-state 1 PNP + 1 NPN
Display (number of LEDs) 30 12 14 + double display units
Width of housing 74 mm 45 mm 100 mm
Integral Muting function Yes No Yes
Communication interface Modbus Modbus, CANopen Modbus, Profibus DP
Universal solutions: safety controllers (for monitoring several safety functions simultaneously)Supply voltage 24 VDC XPSMC32Z(1)(2) XPSMC32ZC(1)(2) XPSMC32ZP(1)(2) XPSMP11123P (3) XPSLCM1150
Zero speed and time delay
Maximum category of the solution SIL 3 per EN/IEC 61508Category 4 per EN 954-1
For monitoring Motor zero speed condition
Number of circuits Safety 2 x 2 N.O. + 6 solid-state
Additional –
Display (number of LEDs) 30
Width of housing 74 mm
Communication interface Modbus Modbus, CANopen Modbus, Profibus DP
(1) Version with 32 inputs, for version with 16 inputs, replace 32 in the catalog number by 16 (example: XPSMC32Z becomes XPSMC16Z).
(2) XPSMCWIN configuration software, configuration cable TSXPCX1031, adaptor XPSMCCPC and a set of plug in connectors with screw terminals XPSMCTS16 or
XPSMCTS32 or set of plug in connectors with spring terminals XPSMCTC16 or XPSMCTC32 to be ordered separately.
(3) For version with non-removable ter minal block, delete the letter P from the end of the catalog number (example: XPSMP11123P becomes XPSMP11123).
PreventaAutomation
Safety controllersTwo-hand control
Courtesy of www.mdwindustrialsupply.com
Courtesy of www.mdwindustrialsupply.com
For other versions, please consult with your local Schneider Electric/
Square D sales office: visit www.us.telemecanique.com
9
9/9
Interface type For mushroom head push buttons (3) Control stationsMetal (1) Plastic (1) Plastic
Degree of protection IP 20 IP 20 IP 20 IP 20 IP 65 IP 65
Dimensions W x D x H 40 x 90 x 68 mm 40 x 80 x 40 mm 40 x 90 x 64 mm 40 x 90 x 40 mm 66 x 95 x 78 mm 66 x 95 x 78 mm
(3) Mushroom head push button to be ordered separately.
(4) Turn to release latching mushroom head push button.
(5) Key release (n° 455) latching mushroom head push button.
M12 connector outputs or ISO M16/20
Type
Description
Degree of protection
Length of cable
Catalog number
Accessories
(2) IDC: Insulation Displacement Connector.(6) For connection using 2 pre-wired connectors, or 1 pre-wired connector + 1 connector.(7) For 1 x ISO M20 entr y, use adaptor sho wn below.
2 x M12 entries (6) 1 x M12 entry 1 x ISO M16 entry (7)Type of entry
Degree of protection
Dimensions W x D x H
AS-Interface profile
Consumption from AS-Interface
Infrared addressing
Connection on AS-Interface
Catalog number
IP 67 IP 67 IP 67
40 x 40 x 58 mm 40 x 40 x 58 mm 40 x 40 x 57.5 mm
S.0.B.F.F S.0.B.F.F S.0.B.F.F
45 mA 45 mA 45 mA
Yes Yes Yes
IDC (2) IDC (2) IDC (2)
ASISSLC2 ASISSLC1 ASISSLLS
Safety interfacesFor Ø 22 Emergency stop
Tap-off for Connectors Pre-wired AdaptorAS-Interface cable connector (sold in lots of 5)
M12 female, threaded elbowed straight straight ISO M16/M20