Jun 19, 2015
A complete system of compatible equipment
DF6000
Key panel features
DF6000
DF6000• Large versatile touch screen display• Single two and four loop versions• Spur tolerant soft addressing
– Device addressing done by panel not by installer– Eliminates manual addressing– Faster to install– Avoids addressing errors
• Large selection of Compatible ancillaries• Full network capability• Optional integral printer• Integral battery and power supply• 150 addresses per loop
– (512 per panel as per EN54)• 96 zonal LED’s
Touch screen display
Touch any box to activate function
Indicates which menu is currently selected
Touch for further details / select
To change menus touch a tab
Touch screen display
Soft addressing
1 2 34 5 6 78 9 10 11 D
F600
0
D F6000
Panel reads first address (254)
Allocates new address 1
Panel instructs short circuit isolator to close
Panel reads next address (254)
Allocates new address 2Panel instructs
short circuit isolator to close
Allocates new address 3
Panel reads next address (254)
Spur tolerant soft addressing
Soft addressing with spurs
1 2 34 5 6 78 9 10 11 D
F600
0
D F6000
1 2
Panel identifies a spur
Addresses the spur
Then continues with the loop
3
4 5 6
7
8
910
11
1213
Spur isolator
DF6000 – Detailed features
• Cause and effect programming– Coincidence / double knock detection– Specific internal or external devices to respond to specific
devices or signals
DF6000 – Detailed features
• Input Programming– Day night mode
• Set by time or by input– Photo-thermals go to thermal only– ROR go to high temp– High temp to to ROR
– Disable pre assigned group of addresses– Non latching zone input– Evacuate
• Detailed event log
DF6000 service and commissioning features
• Change text at panel – via touch screen• Sounder level test (30 seconds on 30 seconds off)• Device test mode• Alarm counter• Programming upload and Download• Reconfigure heat detectors
Additional features
• 1 shot weekly test• Walk test mode• View analogue levels in real time• Changeable user code• Add simple devices directly at the panel• Check auto-config menu:
– Pinpoints exact point of loop breaks– Identifies type code mismatches
Integral battery and power supply
• Standard panel has 12 A/H battery• Deeper back box version with double battery capacity
Battery
Power supply
Choice of panel colours
• Light grey (standard)• Graphite (extra cost)
Optional lockable hinged clear cover
• Protects Touch screen display• Prevents unauthorised access
Optional lockable hinged clear cover
• Protects Touch screen display• Prevents unauthorised access• Includes scroll and buzzer mute buttons• Can be retro – fitted• Still allows full system visibility
Optional integral printer
Blanking plug if no printer fitted
Optional integral printer
• Simple safe access to printer via locked door• Drop in paper cradle• Printer self loads
Compatible devices
Soft addressed detectors
• Photo electric• Ionisation• Multi – mode heat
– Can be programmed as:• Rate of rise device (A1R characteristic) • Fixed temp BS (medium) characteristic• Fixed temp CS (high temperature) characteristic.
• Photo – thermal– Can be programmed as
• Combined photo thermal• Thermal only
Dedicated analogue base
• Includes shorting switch for analogue loop continuity• Includes Screen termination point
Compatible callpoints
• Soft addressed • Status LED
Compatible callpoints
• Soft addressed • Status LED• 3 types:
– Surface– Flush– Weatherproof
Callpoint accessories
Optional hinged cover
Optional resettable element Optional bezel
DF6000 sounders
• Loop powered stand alone sounder• 3 volume settings (controlled by panel)
– Low (87dB) +/-3dB– Medium (93dB) +/-3dB– High (100dB) +/-3dB
• 3 tones (controlled by panel)– Continuous 984Hz– Pulsed 984 / 0Hz pulse 1Hz– Two Tone 644 / 984Hz @ 1Hz cycle– Slow whoop 500-1200Hz in 3.5 seconds / 0.5secs gap
DF6000 sounders
• Loop powered IP66 stand alone sounder• 3 volume settings (controlled by panel)
– Low (87dB) +/-3dB– Medium (93dB) +/-3dB– High (100dB) +/-3dB
• 3 tones (controlled by panel)– Continuous 984Hz– Pulsed 984 / 0Hz pulse 1Hz– Two Tone 644 / 984Hz @ 1Hz cycle– Slow whoop 500-1200Hz in 3.5 seconds / 0.5secs gap
DF6000 sounders
• Loop powered base mounted sounder• 3 volume settings (controlled by panel)
– Low (84dB) +/-3dB– Medium (92dB) +/-3dB– High (95dB) +/-3dB
• 3 tones (controlled by panel)– Continuous 910Hz– Pulsed 910 / 0Hz pulse 1Hz– Two Tone 610 / 910Hz @ 1Hz cycle– Slow whoop 500-1200Hz in 3.5 seconds / 0.5secs gap– Optional lockable cover for use as stand alone sounder
DF6000 loop powered beacon
• Loop powered• LED technology• Fast fit mounting base• Low current
DF6000 interfaces
• 3 Channel I/O device. (MIO324)– 3 separate inputs and outputs– Inputs can be fire or non fire– Inputs monitored for open and short circuits
• Both generate faults– Only takes a single address – Fits onto a standard deep backbox
DF6000 interfaces
• 1 Channel I/O device - mains rated output switching (MIO1240)– Separate input and output– Mains rated output contact– Input can be fire or non fire– Input monitored for open and short circuits– Only takes a single address
DF6000 interfaces
• Zone monitor unit (MIU871) – Allows a zone of conventional detectors to be connected– Uses JSB base and EOLM - 1
DF6000 interfaces
• Shop unit Interface (MSU840)– Facilities to accept conventional detection zone– Output relay (activates on fire)– Facility to connect power supply (monitored)
DF6000 interfaces
• Spur Isolator (MSI850)– Allows a spur of analogue devices– Includes short circuit isolator
DF6000 interfaces
• 4 Way sounder circuit controller (MPU424)– Integral power supply and battery– 4 separately programmable sounder circuits– Sounder circuits can have cause and effect programming
Application schematic
D F6000
M a in lo o p
MIO 1240
Fire or non fire input
Mains rated output relay contact
3 independent Volt free output contacts
3 separate inputs to accept fire or non fire inputs
MIO324M PU424
4 Independently controlled conventional sounder Circu its
Spur o f ana logue devices
M SI850
MIU871
Zone o f com patib le conven tional ca llpoin ts and sounders
Zone o f com patib le conven tional callpo ints and de tectors
2 C ircuits o f conven tional sounders
Power supply
DF6000 repeaters
• DF6000 panels can be connected as active repeaters• Low cost passive repeater also available
– Can be loop connected (hold and displays text for own panel only)
– Can be Network connected (gets text for entire system via network)
– LCD display (not touch screen)– Silence evacuate and reset functionality
DF6000 connected to Network
Low cost repeater connected to network gets entire system text from network
1 2 3 4 5
FIREFAULT
Repeater connected to loop
Low cost repeater connected to ind ividual panel holds and d isp lays text for that panel only - M ANUA L TE XT U PDATE NEE DED
1 2 3 4 5
FIREFAULT
System networking
• Up to 63 panels can be networked• Panels are connected in a loop• Network is monitored• If any panel is disconnected master and faulty panel shows fault
& details
Programming overview
Create all the panels for the site
Select a panel and a loop
Add zones to the loop and populate them
Devices are colour coded for ease of recognition
Indicates an address which is used in a different zone
3 stage programming for each sounderDefinable at each stage:
Source of trigger
By panel
By address
By zone
Type of output
Continuous
Pulsing
Time delayed
Type of trigger
Double knock
Standard trigger
If non global trigger select inputs
Select up to 16 zones, addresses or panels as relevant for each stage for each sounder
Sounder settings are individually programmable
All inputs are individually configured
Select required action