Control Valve • Actuator – Pneumatic – Hydraulic Electromechanical motor Valve Body Changes clearance between plug and seat available for flow Thus alters flow Design decides valve characteristics
26
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Control Valve

Control Valve

• Actuator– Pneumatic– Hydraulic– Electromechanical motor

• Valve Body– Changes clearance between plug and seat available

for flow– Thus alters flow– Design decides valve characteristics

Page 2: Control Valve

Fig.2: AIR OPERATED DIAPHRAGM CONTROL VALVE

Page 3: Control Valve

Fig. 3: COMPONENTS OF A CONTROL VALVE

Page 4: Control Valve

Control Valve• Should respond accurately to change in signal• Operate over a wide range of flows• Exhibit little dead time• Exhibit little hysteresis• React to incremental changes in signal (resolution)• Respond with appropriate speed (stroking speed)• Offer acceptable mechanical/hydraulic behavior

(noise, vibrations, unbalanced forces, pressure drop, etc.)

Page 5: Control Valve

Control Valve Basics

• Inherent Valve Characteristics– Depends on valve geometry– Independent of flow characteristics– Flow rate v lift at constant P

• Installed Valve Characteristics– Flow rate v lift at actual P– Coupled with characteristics of elements in the flow

circuit– Could be very different from installed characteristics

Page 6: Control Valve

Inherent Valve Characteristics• The flow rate through a control valve is given by

where,q is flow ratep1 is upstream pressurep2 is downstream pressureC is flow coefficient is densitya is area available for flow

)21

( ppCaq

Page 7: Control Valve

• Valve designs differ in the way ‘a’ is related to ‘x’, the fraction of valve stroke.

• The a-x relationship decides the q-x relationship.

• Standard q-x relationships are:– Linear– Equal percentage– Square root

Page 8: Control Valve

Linear Characteristics

• q / qmax = x

Where, x = fraction of total valve stroke = 0, fully closed valve

= 1, fully open valveqmax = maximum flow (q at x = 1)

Page 9: Control Valve

Equal Percentage

• d (q/qmax) / dx = k (q/qmax)

• (q/qmax) = (qmin/qmax) at x = 0

• (q/qmax) = (qmax/qmax) =1, at x = 1

• (q/qmax) = (qmin/qmax) (qmax/qmin)x

Page 10: Control Valve

Square Root

• d (q/qmax) / dx = k / (q/qmax)

• (q/qmax) = 0 at x = 0

• (q/qmax) = 1, at x = 1

• (q/qmax) = x

Page 11: Control Valve

Fig. 5: CONTROL VALVE CHARACTERISTICS

Page 12: Control Valve

Choice of Valve

• Process considerations become important in selection of proper inherent valve characteristics.– Temperature Control of HX outlet temperature– Constant terminal pressure circuit– Pump circuit with constant source-sink pressures

• Valve-system combination (installed valve) should have linear characteristics or constant gain while each could separately have non-linear behavior

Page 13: Control Valve

Fig.6: BLOCK DIAGRAM - TEMPERATURE CONTROL SCHEME

Page 14: Control Valve

Fig.7: VALVE FLOW CIRCUIT - CONSTANT TERMINAL PRESSURES

Page 15: Control Valve

Fig. 8: PRESSURE DROP PROFILE

Page 16: Control Valve

Fig. 9a

Page 17: Control Valve

Fig. 9B

Page 18: Control Valve

Fig. 10: FLOW CIRCUIT WITH DUMP

Page 19: Control Valve

Fig. 11: PRESSURE PROFILE

Page 20: Control Valve

Fig. 13: NOMOGRAPH FOR SIZING CONTROL VALVES

Page 21: Control Valve

Selection Heuristics

• Choose Valve with Linear Inherent Characteristics – For liquid level or flow control service– When P across valve is expected to be fairly

constant– When major portion of system P (i.e. across

process and valve together) is across control valve

Page 22: Control Valve

Selection Heuristics

• Choose Valve with Equal Percentage Inherent Characteristics – For temperature control service– For pressure control service– When major portion of system P (i.e. across

process and valve together) is across control valve

Page 23: Control Valve

Valve Heuristics

• The valve gain should be > 0.5 everywhere• Use only 10-80% of the stroke for better

control• Pressure drop in CV in steam lines to

turbines, reboilers or process vessels should be 10% of the design pressure of the steam system or 5 psi, whichever is greater.

Page 24: Control Valve

Valve Heuristics

• If static pressure is the moving force for liquid transport from one vessel to other, allocate 10% of the lower terminal vessel pressure to CV or 50% of the dynamic pressure loss, whichever is higher

• For CV in a suction or discharge line of a centrifugal compressor, allocate 5% of suction pressure or 50% dynamic to CV.

Page 25: Control Valve

Valve Heuristics

• In a pump circuit, pressure drop allocation to CV should be 33% of the dynamic losses in the system at rated flow or 15 psi, whichever is larger.

• Do not recommend 1 size lower if it means significantly different CV size as compared to line size.

Page 26: Control Valve

Valve Noise

• Caused by vibrations, cavitation, high velocity pressure oscillations, unsteady flow etc.

• Typically 100 dB• Normal conversation 60 dB• Pain threshold of ear-drums : 130 dB• Convey noise specs of process to

supplier.