The IQ8Control C as an efficient fire alarm control panel for the property supervision of small to mid-sized objects facilitates simultaneous detection, control and alarm signaling both on the analogous ring as well as on the spur. Within the multifunctional IQ8Control C panel, the operation type (powered-loop or non- powered-loop) can be selected via a jumper located on the control panel power supply unit. Depending on which loop operation type has been selected, the respective loop module/ modules are required. Control Panels IQ8Control IQ8Control C/Intelligent Addressable VdS, CNBOP, BOSEC Approval: Management System WINMAG Repeater Fibre optic converter esserbus transponder IQ8Control C IQ8Control C essernet Loop length max. 1 km (with repeater max. 3 km) esserbus Loop length max. 3.5 km -PLus external equipment 12V DC Connection example Technical Data Rated voltage 230 V AC Rated frequency 50 ... 60 Hz Rated current 0.35 A (standard); 0,7 A (powered loop) Quiescent current approx. 215 mA (basic configuration without operating unit) approx. 230 mA (basic configuration with operating unit) Current consumption for ext. devices 2 A Battery capacity 2 x 12 Ah, 2 x 24 Ah in extension housing Ambient temperature -5 °C ... 45 °C Storage temperature -5 °C ... 50 °C Type of protection IP 30 Housing ABS, 10% glass fibre reinforced, V - 0 Color grey similar to Pantone 538 Weight approx. 6.5 kg Dimensions W: 450 mm H: 320 mm D: 185 mm CE certificate 0786-CPD-20827 Features • Max. two micromodules • Max. two esserbus analog loop modules • Short circuit and open circuit resistant loop opera- tion • Loop installation with I-Y(ST)Y 0.8 mm cable for a maximum length of 3.5 km • Up to 127 esserbus devices (fire detectors respectively manual call points)/detector zones per loop • Up to 32 esserbus transponders per loop/ operation of wireless components (see chapter 10) • Operation types TM and PM as per DIN VDE 0833 - 2 to avoid unwanted alarms being triggered • Fire brigade operating panel and alarm transmis- sion unit interface on the peripheral module • Three common relays, freely programmable, monitored, floating for up to 24 V DC/1A (on the peripheral module) • TTY or RS 485, RS 232 interface • Integration in the short circuit and open circuit resistant essernet network with up to 31 fire detection panels depends on transmission rate • Connection to graphical supervisor WINMAG via serial essernet interface (SEI) • Operating panel with alphanumerical display • 2 x 20 backlit LCD display • Event memory for up to 10,000 events • All System 8000 micromodules are compatible • Printer interface for internal printer • Two batteries with monitoring circuit • Monitored input for external power supply unit Additional features for powered loop • Max. 2 analog powered loop modules • BUS powered, synchronously controlled, acoustic alarm signalling devices as per DIN EN 54-3 with alarm tone as per DIN 33404 • Up to 48 powered loop base sounders (series 9200) per loop • Up to 32 powered loop IQ8Alarm per loop • Up to 48 IQ8Quad with alarm device per loop - The IQ8Control fire detection panels are fully compatible with FACP 8000 panels within essernet applications - FACP 8000 micromodules are also compatible with IQ8Control devices - Housing form and colour comply with the FACP 8000 generation - The IQ8Control panels can only be programmed with the tools 8000 software solution (part no. 789861) and the field bus interface (part no. 789862.10) or directly via USB with the RS-232 interface (part no. 769828), with the field bus interface or the RS232 interface. Combined with 808619 or 808619.10 FSA transponders, the control panel can be used to control automatic door arrester systems in compliance with the German institute for construction engineering (DIBt: Deutsches Institut für Bautechnik). www.esser-systems.com
23
Embed
Control Panels IQ8Control IQ8Control C/Intelligent Addressable · The IQ8Control M as an efficient fire alarm control panel for the property supervision of mid-sized to large objects,
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
The IQ8Control C as an efficient fire alarm control panel for the property supervision of small to mid-sized objects facilitates simultaneous detection, control and alarm signaling both on the analogous ring as well as on the spur.Within the multifunctional IQ8Control C panel, the operation type (powered-loop or non- powered-loop) can be selected via a jumper located on the control panel power supply unit.Depending on which loop operation type has been selected, the respective loop module/ modules are required.
Control Panels IQ8Control
IQ8Control C/Intelligent Addressable
VdS, CNBOP, BOSECApproval:
Management SystemWINMAG
Repeater
Fibre optic converter
esserbus transponder
IQ8Control C
IQ8Control C
essernetLoop length max. 1 km(with repeater max. 3 km) esserbus
Loop length max. 3.5 km-PLus
external equipment12V DC
Connection example
Technical Data
Rated voltage 230 V ACRated frequency 50 ... 60 HzRated current 0.35 A (standard); 0,7 A (powered loop)Quiescent current approx. 215 mA (basic configuration without operating
unit)approx. 230 mA (basic configuration with operating unit)
Current consumption for ext. devices 2 ABattery capacity 2 x 12 Ah, 2 x 24 Ah in extension housingAmbient temperature -5 °C ... 45 °CStorage temperature -5 °C ... 50 °CType of protection IP 30Housing ABS, 10% glass fibre reinforced, V - 0Color grey similar to Pantone 538Weight approx. 6.5 kgDimensions W: 450 mm H: 320 mm D: 185 mmCE certificate 0786-CPD-20827
Features
• Max. two micromodules• Max. two esserbus analog loop modules• Short circuit and open circuit resistant loop opera-
tion• Loop installation with I-Y(ST)Y 0.8 mm cable for a
maximum length of 3.5 km• Up to 127 esserbus devices (fire detectors
respectively manual call points)/detector zones per loop
• Up to 32 esserbus transponders per loop/ operation of wireless components (see chapter 10)
• Operation types TM and PM as per DIN VDE 0833 - 2 to avoid unwanted alarms being triggered
• Fire brigade operating panel and alarm transmis-sion unit interface on the peripheral module
• Three common relays, freely programmable, monitored, floating for up to 24 V DC/1A (on the peripheral module)
• TTY or RS 485, RS 232 interface• Integration in the short circuit and open circuit
resistant essernet network with up to 31 fire detection panels depends on transmission rate
• Connection to graphical supervisor WINMAG via serial essernet interface (SEI)
• Operating panel with alphanumerical display• 2 x 20 backlit LCD display• Event memory for up to 10,000 events• All System 8000 micromodules are compatible• Printer interface for internal printer• Two batteries with monitoring circuit• Monitored input for external power supply unit
Additional features for powered loop• Max. 2 analog powered loop modules• BUS powered, synchronously controlled, acoustic
alarm signalling devices as per DIN EN 54-3 with alarm tone as per DIN 33404
• Up to 48 powered loop base sounders (series 9200) per loop
• Up to 32 powered loop IQ8Alarm per loop• Up to 48 IQ8Quad with alarm device per loop
- The IQ8Control fire detection panels are fully compatible with FACP 8000 panels within essernet applications
- FACP 8000 micromodules are also compatible with IQ8Control devices
- Housing form and colour comply with the FACP 8000 generation
- The IQ8Control panels can only be programmed with the tools 8000 software solution (part no. 789861) and the field bus interface (part no. 789862.10) or directly via USB with the RS-232 interface (part no. 769828), with the field bus interface or the RS232 interface.
Combined with 808619 or 808619.10 FSA transponders, the control panel can be used to control automatic door arrester systems in compliance with the German institute for construction engineering (DIBt: Deutsches Institut für Bautechnik).
www.esser-systems.com
IQ8Control C Design and Order Diagram
1. Choice of thehousing type
2. Choice of thecontrol panel
modules(only 1 module at a time)
3.Choice of themicromodules
4.Choice of the
operating module front
language codes available:
5.Choice of an
extension housing(optional)
IQ8ControlC standard housing 808003 IQ8ControlC for 19” cabinet 808139
All operating fronts, except SZI 192 detector zones are suitable for both housing types*Space for only 1 battery **Requires an additional extension housing
Slot for one micromodule as standard
7860_ _Operating front
7864_ _
Operating front with 1/4 VGA display
7868_ _Operating front with printer, w/o take-up reel*
7869_ _Operating front w. 1/4 VGA display, printer , w/o take-up reel
7861_ _Operating front w. SZI f. 64 detector zones
7865_ _Operating front w. 1/4 VGA display & SZI for 64 zones
7863_ _Operating front for printer, w. take-up reel**
786000SZI front for 192detector zones
78809319” rack mounting kit for SZI 192 detector zones
786100Filler panel front, neutral for IQ8Control C/M
789300Battery extension housing
789301Extension housing for batteries andSZI 192 detector zones
789302Extension housing for SZI 192 detector zones
Please notice the control panel packages available!
01 Germany02 England03 Italy04 Portugal05 Poland06 Spain07 Austria 08 Netherlands09 Czech Republic10 Russia11 Hungary12 Denmark13 Sweden14 Croatia15 France16 Slovakia18 Romania 19 Slovenia20 Turkey21 Greek22 Flemish23 Walloon25 Arabic / English
772477Peripheral module with one additional micromodule slot
772478Extension module with one additional micromodule slot
772479Peripheral module
784382.D0Analog loop module
784385Master box interface module
804382.D0Analog loop module powered loop
784842 RS 232/TTY serial interface module
7875304-relay module
784840.10essernet module 62,5kBd
784841.10essernet module 500kBd
7875313-relay module
7875323-relay common fault module
Control Panels IQ8Control
1
2
3
4
5
6
7
8
9
10
11
12
17
16
13
14
15
1
¬qq$N
¬qrHU
808003
808139
Fire alarm panel IQ8Control C
Fire alarm panel IQ8Control C for 19" cabinet
Basic design.
As 808003 but 19" version (7 HU) for upright cabinet installation.
Control Panels
Control Panels IQ8Control
Housing with standard rear panel and front frame for operating panel fronts, interface board, power supply module, system software.
FACP 808003 IQ8Control C, including 19" installation frame and flat cable for 19" installation 750707.
The operating front must be ordered separately and is not included in the price.
The operating front must be ordered separately and is not included in the price.
www.esser-systems.com
¬o~!]
¬o~"`
789300
789301
Battery extension housing
Extension housing for batteries and SZI 192 detector zones
Extension housing for additional batteries.
Accessories FACP IQ8Control C
Control Panels IQ8Control
Housing complete with battery rear panel, connecting cable for battery, mounting positions for 2 x 12V/24Ah batteries. Neutral front and material for attaching to the existing panel housing, battery connecting cables, 800 mm.
Housing complete with battery rear panel, connecting cable for batteries, mounting positions for 2 x 12V/24Ah batteries, single zone indicator front for 192 detector zones and material for attaching to the existing panel housing.
1. 2. 3.
Assembling the housing parts IQ8Control
Take off the 4 standard covers.
Insert the 2 connecting elements.
Put the 2 housings on top of each otherand push them together.
Connection between the central housing and the extension housing
Technical Data
Ambient temperature -5 °C ... 45 °CStorage temperature -10 °C ... 50 °CType of protection IP 30Housing ABS, 10% glass fibre reinforced, V - 0Weight approx. 5 kg (without battery)Dimensions W: 450 mm H: 320 mm D: 185 mm
Technical Data
Quiescent current approx. 5 mACurrent consumption 1.5 mA when LED activatedAmbient temperature -5 °C ... 45 °CType of protection IP 30Housing ABS, 10% glass fibre reinforced, V - 0Color grey similar to Pantone 538Weight approx. 5.5 kg (without battery)Dimensions W: 450 mm H: 320 mm D: 185 mm
Batteries are not included and must be ordered separately.
This housing cannot be used if an operating module front with single zone indicator unit for 64 zones is already fitted. Batteries are not included and must be ordered separately.
A single zone indicator unit can only be used in connection with an operating module front.
1
2
3
4
5
6
7
8
9
10
11
12
17
16
13
14
15
1
¬o~#c
¬qq5£
789302
808020
Extension housing for SZI 192 detector zones
Package IQ8Control C with two slots for micromodules
The housing can be used to mount additional modules, e.g. an esserbus transponder.
Control Panel Packages IQ8Control C
Control Panels IQ8Control
Housing complete with standard rear panel, single zone indicator front for 192 detector zones and material for attaching to the existing panel housing.
1 x control panel 8080031 x extension module 772478
Technical Data
Quiescent current approx. 5 mACurrent consumption 1.5 mA when LED activatedAmbient temperature -5 °C ... 45 °CType of protection IP 30Housing ABS, 10% glass fibre reinforced, V - 0Color grey similar to Pantone 538Weight approx. 5 kgDimensions W: 450 mm H: 320 mm D: 185 mm
This housing cannot be used if an operating module front with single zone indicator unit for 64 zones is already fitted. A SZI unit can only be used in combination with an operating module front.
The operating front must be ordered separately.
www.esser-systems.com
The IQ8Control M as an efficient fire alarm control panel for the property supervision of mid-sized to large objects, facilitates simultaneous detection, control and alarm signalling both on the analogous ring as well as on on the spur.The loop operation type of the panel (powered-loop or non-powered-loop) can be selected via a jumper located on the power supply card.Depending on which loop operation type has been selected, the respective analog module/ modules should be used.
Control Panels IQ8Control
IQ8Control M/Intelligent Addressable
VdS, CNBOP, BOSEC
VdS-system recognition: S 294050
Approval:
ManagementsystemWINMAG
Repeater
Fibre optic converter
esserbus transponder
IQ8Control C
IQ8Control M
essernetLoop length max. 1 km(with repeater max. 3 km) esserbus
Loop length max. 3.5 km-PLus
external equipment12V DC
Application example
Technical Data
Rated voltage 230 V ACRated frequency 50 ... 60 HzRated current 0.35 A (standard); 0,7 A (powered loop)Output voltage 12 V DCQuiescent current approx. 215 mA (basic configuration without operating
unit)approx. 230 mA (basic configuration with operating unit)
Current consumption for ext. devices 2 ABattery capacity max. 2 x 12 V/24 AhAmbient temperature -5 °C ... 45 °CStorage temperature -10 °C ... 50 °CType of protection IP 30Housing ABS, 10% glass fibre reinforced, V - 0Color grey similar to Pantone 538Weight approx. 11.5 kgDimensions W: 450 mm H: 640 mm D: 185 mmCE certificate 0786-CPD-20827
Features
• Max. five micromodules, with peripheral module 772477
• Max. seven esserbus analog loops, with extension module 772476
• Short circuit and open circuit tolerant loop opera-tion
• Loop installation with I-Y(ST)Y 0.8 mm cable for a maximum length of 3.5 km
• Up to 127 esserbus devices (fire detectors respectively manual call points)/detector zones per loop
• Up to 32 esserbus transponders per loop/ operation of wireless components (see chapter 10)
• Operation types TM and PM as per DIN VDE 0833 - 2 to avoid unwanted alarms being triggered
• Fire brigade operating panel and transmission interface on the peripheral module
• Three common relays, freely programmable, monitored, floating for up to 24 V DC/1A (on the peripheral module)
• TTY or RS485 or RS 232 interface• Integration in the short circuit and open circuit
resistant essernet network with up to 31 fire detection panels depends on transmission rate
• Connection to graphical supervisor WINMAG via serial essernet interface (SEI)
• Operating panel with alphanumerical display• 2 x 20 backlit LCD display• Event memory for up to 10,000 events• All Systems 8000 micromodules are compatible• Printer interface for internal printer• Two batteries with monitoring circuit• Monitored input for external power supply unit
Additional features for powered loop• Max. 6 analog powered loops and expandable up
to 124 power loops• BUS supplied, synchronously controlled, acoustic
alarm signalling devices as per DIN EN 54 - 3 with alarm tone as per DIN 33404
• Up to 48 powered loop base sounders (series 9200) per loop
• Up to 32 powered loop IQ8Alarm per loop• Up to 48 IQ8Quad with alarm device per loop
- The IQ8Control fire detection panels are fully compatible with FACP 8000 panels
- FACP 8000 micromodules are also compatible with IQ8Control devices
- Housing form and colour comply with the FACP 8000 generation
- The IQ8Control generation can only be programmed with the tools 8000 software solution (part no. 789861) and the field bus interface (part no. 789862.10) or directly via USB with the RS-232 interface (part no. 769828), with the field bus interface or RS232 interface.
Combined with the 4 zone/2 relay-transponder 808619 or 808619.10, the control panel can be used to control automatic door arrester systems in compliance with the German institute for building technology (DIBt: Deutsches Institut für Bautechnik).
1
2
3
4
5
6
7
8
9
10
11
12
17
16
13
14
15
1
IQ8Control M Design and Order Diagram (Basic Design)
1. Choice of thehousing type
2. Choice of thecontrol panel
modules2 Extension modules
or1 Extension module
+1 Peripheral module
3.Choice of themicromodules
5.Choice of an
extension housing(optional)
Wall housing808004
772477Peripheral module with one additional micromodule slot
772476Extension module with three additional micromodule slots
772478Extension module with one additional micromodule slot
772479Peripheral module
7860xxOperating front
7864xxOperating front with 1/4 VGA display
7868xxOperating front with printer
7869xxOperating front w. 1/4 VGA display, printer , w/o take-up reel
7861xxOperating front w. SZI f. 64 detector zones
7865xxOperating front w. 1/4 VGA display & SZI for 64 zones
7863xxOperating front for printer, w. take-up reel**
786000SZI front for 192detector zones
78809319” rack mounting kit for SZI 192 detector zones
786100Filler panel front, neutral
789303Extension housing f. additional modules
789304Extension housing incl. printerwith paper take-up reel
Please notice the control panel packages available!
IQ8Control M for 19" cabinet808219
All operating fronts, except SZI 192 detector zones are suitable for both housing types*Requires an additional extension housing
As 808004 but 19" version (7HU) for upright cabinet installation.
With 4 micromodule slots.
With 4 micromodule slots and 64 single zone indicator units.
Control Panels
Control Panel Packages IQ8Control M
Control Panels IQ8Control
Housing with rear panel and front frame for operating panel fronts, interface board, power supply module and system software.
FACP IQ8Control M 808004, including 19" mounting frame and flat cable for 19" installation 750707.
1 x control panel 8080041 x operating panel front 7860xx1 x neutral front 7861001 x extension module 772476
1 x control panel 8080041 x operating panel front 7861xx1 x neutral front 7861001 x extension module 772476
The operating front must be ordered separately and is not included in the price.
The operating front must be ordered separately and is not included in the price.
Space for up to 2 x 12V / 24Ah batteries (Part No. 018006).
The operating front must be ordered separately and is not included in the price.
Space for up to 2 x 12V / 24Ah batteries (Part No. 018006).
The operating front must be ordered separately and is not included in the price.
1
2
3
4
5
6
7
8
9
10
11
12
17
16
13
14
15
1
¬qs1y
¬qs2|
¬qs3¡
¬o~%i
808216
808217
808218
789304
Package 3 of FACP IQ8Control M
Package 4 of FACP IQ8Control M
Package IQ8Control M black box
Extension housing for Package Part No. 808218 IQ8Control M
With 4 micromodule slots and integrated printer without paper take-up reel.
With 4 micromodule slots and 192 single zone indicator units.
With 4 micromodule slots without operating front.
Control Panels IQ8Control
1 x control panel 8080041 x operating panel front 7868xx1 x neutral front 7861001 x extension module 772476
1 x control panel 8080041 x operating panel front 7860xx1 x single zone indicator unit front 192 (Part No.) 7860001 x extension module 772476
1 x control panel 8080041 x neutral front 7861001 x extension module 7724761 x essernet micromodule: 62.5 kBd (Part No. 784840.10) or 500 kBd (Part No. 784841.10) option
1 x operating panel front 7863xx1 x printer1 x paper take-up reel
Technical Data
Ambient temperature -5 °C ... 45 °CStorage temperature -10 °C ... 50 °CType of protection IP 30Housing ABS plastic, 10% glass fibre reinforced, V - 0Color grey similar to Pantone 538Weight approx. 6 kgDimensions W: 450 mm H: 320 mm D: 185 mm
Space for up to 2 x 12V / 24Ah batteries (Part No. 018006).
The operating front must be ordered separately and is not included in the price.
Space for up to 2 x 12V / 24Ah batteries (Part No. 018006).
The operating front must be ordered separately and is not included in the price.
Space for up to 2 x 12V / 24Ah batteries (Part No. 018006). The essernet micromodule must be ordered separately.
The operating front must be ordered separately and is not included in the price. The extension housing must always be mounted on top of the double housing of the IQ8Control M (Part No. 808218). For expanding the IQ8Control M fire alarm panel by an integrated printer with paper take-up reel, the extension housing (Part No. 789304) must be mounted above the fire alarm panel.
www.esser-systems.com
¬qq?8
¬qq@;
808030
808031
Package IQ8Control M with four slots for micromodules
Package IQ8Control M with seven slots for micromodules
Control Panels IQ8Control
1 x control panel 8080041 x extension module 772476
1 x control panel 8080042 x extension modules 772476
The operating front must be ordered separately.
The operating front must be ordered separately.
1
2
3
4
5
6
7
8
9
10
11
12
17
16
13
14
15
1
¬o]"§786001 Operating front - Esser, German
Control Panels IQ8Control
IQ8Control C/M
IQ8Control C/M operating fronts
Technical Data
Quiescent current approx. 45 mA
Features
• alphanumerical display• 2 x 20 backlit LCD display
ESSER - front (786001, 786101, 786301, 786401, 786501, 786801 and 786901) is also available with the respective country specification - except the special versions. When ordering, please fill in the last two digits with the specific language code.
Example:
The German version of the standard operating front C/M would have the part no. 7860-01.
For the Dutch version, the number would have to be changed to 7860-08.
Specific language code:
(Not all variants are available in all languages. Please contact your sales representative for details)
Operating front w. single zone indication 64 - ESSER, German
Operating front with printer, w/o take-up reel - ESSER, German
Operating front for printer w. take-up reel - ESSER, German
Operating front with 1/4 VGA display - ESSER, German
Operating front with 1/4 VGA display - ESSER, Chinese
Two-line additional text can be programmed using the programming software package.
Control Panels IQ8Control
The printer kit with paper take-up reel (Part No. 784892) must be ordered separately.
Technical Data
Quiescent current approx. 50 mACurrent consumption single zone indication: per activated LED 1.5mA
Technical Data
Quiescent current approx. 45 mA
Technical Data
Quiescent current approx. 45 mA
Technical Data
Quiescent current approx. 170 mAResolution 320 x 240 pixels
This operating module front can only be used on IQ8Control M and a separate extension housing Part No. 789304 must be ordered separately.
Remote diagnosis is not possible if a two-line extra text is programmed.
1
2
3
4
5
6
7
8
9
10
11
12
17
16
13
14
15
1
¬ob"(
¬obUZ
¬of"0
¬ofUb
¬o]!¤
¬o^!¦
786501
786552
786901
786952
786000
786100
Operating front w. 1/4 VGA display & SZI for 64 zones - ESSER, German
Operating front 1/4 VGA and SZI for 64 zones - ESSER, Chinese
Operating front w. 1/4 VGA display, printer - ESSER, German
Operating module front with 1/4 VGA display + printer - ESSER, Chinese
SZI front for 192 detector zones
Filler panel front, neutral for IQ8Control C/M
Two-line additional text can be programmed using the programming software package.
Two-line additional text can be programmed using the programming software package.
Control Panels IQ8Control
Including insertable foils with country-specific versions
Technical Data
Quiescent current approx. 170 mACurrent consumption single zone indication: per activated LED 1.5mAResolution 320 x 240 pixels
Technical Data
Quiescent current approx. 170 mACurrent consumption printer: 45mAResolution 320 x 240 pixels
Technical Data
Quiescent current approx. 5 mACurrent consumption single zone indication: per actuated LED 1.5mA
Remote diagnosis is not possible if a two-line extra text is programmed.
Remote diagnosis is not possible if a two-line extra text is programmed.
www.esser-systems.com
¬oq~%
¬o_^o
¬o__r
¬o_`u
788093
786261
786262
786263
19” rack mounting kit for SZI 192 detector zones
IQ8Control C/M operating unit front with FBOIU-ESSER, German/ Switzerland
IQ8Control C/M operating unit front with FBOIU-ESSER, Italian/ Switzerland
IQ8Control C/M operating front with FBOIU-ESSER, French/ Switzerland
7 HU for upright cabinet mounting.
With integrated Swiss fire department operating and indicating unit (FBOIU) - German lettering
As 786261, but with Italian lettering
As 786261, but with French lettering
Control Panels IQ8Control
772445 mounting frame786000 SZI front for 192 detector zones, including insertable foils with country-specific versions
Technical Data
Quiescent current approx. 5 mACurrent consumption 1.5 mA per actuated LED
1
2
3
4
5
6
7
8
9
10
11
12
17
16
13
14
15
1
¬n9pX
¬n9nR
¬n9oU
¬n9mO
¬qQq'
772479
772477
772478
772476
804880
Peripheral module
Peripheral module with one additional micromodule slot
Extension module with one additional micromodule slot
Extension module with 3 additional micromodule slots
Kit DCF77 radio time module for IQ8Control & FlexES control
The peripheral module contains a fire brigade operating panel interface as well as a alarm transmission unit interface and three freely programmable, optionally monitored or up to 24V DC floating common relays. The peripheral module can only be used on system terminal 1 of the control panel interface board.
As 772479 but with one additional micromodule slot. The peripheral module can only be used on system terminal 1 of the control panel interface board.
The extension module is plugged onto the interface board of the control panel. The exten-sion module can only be used on system terminal 1 of the control panel interface board.
The extension module is plugged onto the interface board of the control panel. This exten-sion module can be used on plug connectors 1 and 2 of the basic control panel module.
Used in conjunction with the Kit DCF77 allows radio reception of the DCF77 time signal (CET and CEST time). The DCF77 time signal is sent from a German central transmission point in Frankfurt/Main and Mainflingen and can be received at a distance of up to approx. 2.000 km.By connecting the Kit DCF77 to the fire alarm system IQ8Control or FlexES control, the system time will be automatically set to this time signal. This applies to stand-alone fire alarm control panel.
Accessories for IQ8Control C/M
Control Panels IQ8Control
Control Panel Modules for IQ8Control C/M
Technical Data
Quiescent current approx. 15 mA
Technical Data
Quiescent current approx. 15 mA (without micromodule)
Technical Data
Quiescent current approx. 5 mA (without micromodule)
Technical Data
Quiescent current approx. 10 mA (without micromodule)
Only one 772477/78/79 module can be plugged onto the interface board.
Only one 772477/78/79 module can be plugged onto the basic module.
Only one 772477/78/79 module can be plugged onto the interface board.
The 772476 extension module can only be used in the IQ8Control C/M fire alarm panel.
Each fire alarm control panel (FACP) or essernet network must only be connected to a single DCF77 time master.
www.esser-systems.com
¬oQI
¬j_D¥
¬o~$f
784892
736235
789303
Printer kit with paper take-up reel for IQ8Control C/M
Printer paper for printer 736233/736234
Extension housing
40 characters, printer with fixed print head.
Printer paper for part no. 736233 printer without paper take-up reel and for part no. 736234 printer with take-up reel.
The standard extension housing can be used to mount additional modules, e.g. esserbus transponders.
Control Panels IQ8Control
Mounting frame complete with Part No. 736234 plain text thermal printer including winder and end-of-paper recognition.
Housing complete with standard rear panel, neutral front and material for attaching to the existing control panel housing.
Accessories
736235 Printer paper for printer 736233 / 736234
1. 2. 3.
Assembling the housing parts IQ8Control
Take off the 4 standard covers.
Insert the 2 connecting elements.
Put the 2 housings on top of each otherand push them together.
Connection between the central housing and the extension housing
Technical Data
Dimensions L: 2500 mm W: 58 mm
Technical Data
Ambient temperature -5 °C ... 45 °CStorage temperature -10 °C ... 50 °CType of protection IP 30Housing ABS plastic, 10% glass fibre reinforced, V - 0Color grey similar to Pantone 538Weight approx. 5 kgDimensions W: 450 mm H: 320 mm D: 185 mm
Features
• For the installation of up to 10 transponders and FO converters with installation kit 788650.
When the printer is installed in the FACP IQ8Control C, the battery case, including toroidal transformer, must be replaced by the mounting rack. The batteries and the toroidal transformer must be installed in an additional extension housing, either 789300 or 789301.
1
2
3
4
5
6
7
8
9
10
11
12
17
16
13
14
15
1
¬n9NY
¬o~+
772445
789310
Mounting frame 19" IQ8Control C/M
Intermediate distribution frame for IQ8Control C
The mounting box assembly (part no. 789310) is a first fix component for the installation of the 8000 C/M or IQ8Control C/M fire alarm control panel and is specially designed to allow termination of fire cables.
Control Panels IQ8Control
Mounting frame with 6 HU for mounting of operating front and printer.
Mounting example
Technical Data
Ambient temperature -5 °C ... 45 °CStorage temperature -10 °C ... 50 °CType of protection IP 31Color similar Pantone 538 light-greyWeight approx. 1.1 kgDimensions W: 450 mm H: 320 mm D: 35 mm
Features
• Allows termination of fire cables• Ten cable entry points• Wall adjust elements for panel installation on
uneven surface• Simple installation
www.esser-systems.com
¬oLs§/E1n
¬qLs§/E1p
¬oLv*
¬oQK£
¬ol?,
¬ol@/
¬olA2
784382.D0
804382.D0
784385
784842
787530
787531
787532
Analog loop module
Analog loop module powered loop
Master box interface module
RS 232/TTY serial interface module
4-relay module
3-relay module
3-relay common fault module
Single loop circuit module for up to 127 Series 9200/IQ8Quad intelligent fire detectors or bus devices, divisible into 127 zones.
Single loop circuit module for up to 127 bus devices. Series 9200/IQ8Quad intelligent fire detectors and esserbus transponders (part no. 80xxxx) or addressable sounders and powered loop base sounders.
Single master box interface module for activating and processing acknowledgement signals from master boxes; programmable as constant or pulsed master box activation.
Serial interface module with optional RS 232 or TTY typ, for operating external devices such as external printers, printers, modems for remote diagnosis.
4-relay module with freely programmable output functions, each of which can operate as an NC or NO contact (not monitored) for potential-free activation.
3-relay module with output functions which can be programmed either as NC or NO contacts, 3 x latching "monitored" relay outputs.
3-relay module with pre-set functions such as common fault, 2 x freely programmable monitored relay outputs.
Control Panels IQ8Control
Micromodules for IQ8Control C/M
Technical Data
Quiescent current approx. 25 mA
Technical Data
Quiescent current approx. 15 mA
Technical Data
Quiescent current approx. 35 mA (RS 232)approx. 55 mA (TTY)
Technical Data
Quiescent current approx. 10 mAContact load relay max. 30 V DC / 1 A
Technical Data
Quiescent current approx. 5 mAContact load relay max. 30 V DC / 1 A
Technical Data
Quiescent current approx. 15 mAContact load relay max. 30 V DC / 1 A
Powered loop compatible only with IQ8Control.
1
2
3
4
5
6
7
8
9
10
11
12
17
16
13
14
15
1
¬oQK§/G1s
Accessories for System 8000 and IQ8
784842.F0 Module d’interface série RS 232/TTY
Control Panels IQ8Control
Technical Data
Quiescent current approx. 35 mA (RS 232), approx. 55 mA (TTY)
¬kA-j743212 Spare key 1D009 for FACP
For upright cabinets 769163 and 769164.
Two keys
¬kANf743245 Lever lock - type 17 for key no. 801
Two keys and one cylinder lock.
¬m¦/*769914 Spare key 801 for FACP
For fire alarm panels 2001, IQ8Control C/M, 8000 M/C, 8007, 8008, for operating panel, printer and housing.
Two keys.
¬kAQo743248 Lever lock - type for key no. 901
Two keys and one cylinder lock.
¬m¦0-769915 Spare key 901 for FACP
For fire alarm panels 2001, IQ8Control C/M, 8000 C/M, 8008 for operating panel, printer and housing.
Two keys.
www.esser-systems.com
¬kI?I
¬kI<@
¬kI=C
¬kI>F
744030
744027
744028
744029
Dummy cover 19", 2 HU
Dummy cover 19", 3 HU
Dummy cover 19", 5 HU
Dummy cover 19", 9 HU
For covering free installation space in upright cabinets and wall cabinets, 2 HU.
As 744030, but 3 HU.
As 744030, but 5 HU.
As 744030, but 9 HU.
IQ8Control
Technical Data
Material sheet steelColor grey similar to Pantone 538
Technical Data
Color grey similar to Pantone 538
One height unit (HU) covers 44.45 mm.
Control Panels
1
2
3
4
5
6
7
8
9
10
11
12
17
16
13
14
15
1
¬o¥^P
¬o¥]§/21(
789861
789860.10
tools 8000 programming software
tools 8000 PLus equipment starter kit
Convenient Windows programming software CD for programming the fire alarm panels belonging to Series 8000 C/M, 8008, IQ8Control, Gateway, extended supplementary text in ¼ VGA display and ABIGA.
For programming, the 789862.10 field bus interface is required.
Complete package for programming of the fire alarm control panels 8007, 8000C/M, 8008, gateway, ABIGA and IQControl via PC or Notebook.
Maintenance and Test Equipment
Control Panels IQ8Control
789861 Programming software for system 8000 and IQ8Control789862.10 Field bus and control panel interface PLus789863 USB cable789864 Serial Connecting Cable
Accessories
BME2Z002 Switched-mode power supply with cylindrical plug
esserbus-PLusLoop length max. 3,5 km
esserbus-transponder
Control Panel
Field bus interface
USB
Application example
This software is also to be used for the LCD panels 785101 and 785103.
System requirements:
- FACP 8000 C/M, FACP 8008 or IQ8Control C/M as of software version V2.20
- PC/Notebook as of Windows 98 SE, but no Windows NT (no USB support)
- Recommended configuration: 128 MB RAM, 500 MHz CPU
The field bus interface is used as a programming interface between the FACP and the PC/ notebook.
Furthermore the field bus interface facilitates the direct connection of a ring bus to the convenient monitoring of a finished installation and the elimination of possible cabling mistakes.
www.esser-systems.com
¬o¥_§/21.
¬o¥`V
789862.10
789863
Field bus interface PLus
USB cable A/B for 789862 field bus & panel interface
Interface for the programming of the fire alarm control panels 8007, 8000C/M, 8008, gateway, ABIGA and IQ8Control or for the direct field-side connection of a single installed analog loop. With the optional switched-mode power supply BME2Z002, bus-supplied alarm signaling equipment can be tested independently from the control panel via the direct connection to the field bus interface 789862.10. (V1.12 or above of programming software tools 8000 is required)
For connecting service PC / laptop with the tools 8000 field bus and panel interface.
Control Panels IQ8Control
One interface and two 6-pin plugs.
Accessories
BME2Z002 Switched-mode power supply with cylindrical plug
esserbus-PLusLoop length max. 3,5 km
esserbus-transponder
USB
Power supply for bus suppliedalarm signalling devices
Field bus interface EFI-Plus
Application example
Technical Data
Ambient temperature 5 °C ... 45 °CStorage temperature 0 °C ... 50 °CType of protection IP 40Housing plastic, PS (Polystyrene)Color white, similar to RAL 9010 / grey, similar to RAL 7035Weight approx. 300 gDimensions W: 68 mm H: 30 mm D: 135 mm
Technical Data
Cable length 1.8 m
Connecting cables 789863 and 789864 are not included in delivery.
Windows NT does not support any USB interface. Therefore the use of the programming software tools 8000 is possible under Windows NT only with the usage of programming interface RS 232 (part no. 769828).
1
2
3
4
5
6
7
8
9
10
11
12
17
16
13
14
15
1
¬o¥aY
¬o¥c_
«CNF3[1138
789864
789866
BME2Z002
Serial connecting cable for 789862
USB programming cable for panel 8010
Switched-mode power supply with cylindrical plug
For connecting the field bus interface to panels 8007, 8000C/M, 8008, Gateway, ABIGA and IQ8Control. With 4-pin special plug for the control panel.
Connecting lead for programming the extinguishing control panel 8010.