CONSTRUCTION MODIFICATION #014 16 October 2018 Randall Coonrod, Coonrod & Associates Construction Co. Greater Wichita YMCA, East Branch Addition/Remodel 5358.00 Teresa Burk ☐E-Mail ☒Online ☐Mail ☒Delivery ☐Fax Total Pages: 9 ARCHITECT’S SUPPLEMENTAL INSTRUCTIONS CONTRACTOR - PLEASE make revisions as noted: • Add fire sprinkler zone: Wet Fire Sprinkler shall be added to Building #1, north and east of the 2-hour fire wall separation. Code sheet G14.1 revised to indicate zone for additional sprinkler area plus wet area of Building #2, and to reallocate corridor occupant loads to below 30 at both 111 and 176. Corridor 111 is part of fully sprinkled building #2 allowed to be non-rated per IBC Table 1018.1 with occupant load < 30. Corridor 176 is within the sprinkled portion of Building #1 and totally separated from unsprinkled areas by 2-hr fire rated separation walls. With consent of MABCD committee, this is requested for consideration of equivalent substitution to the intent of IBC IBC Table 1018.1, with sprinkler requirements shown to be sufficient by sealed document provided by FSC, Inc. Consulting Engineers and provided to MABCD via email dated October 8, 2018. • Fire separation indicated: 2-hr Fire-rated wall indicated at original 1994 construction documents (per UBC 505(f)2) separating Natatorium from Locker rooms is added to current Code Sheet G14.1. • Revise storage 114: Omit planned wall cuts at either side of existing storage room 113 and provide mandoor thru west wall as indicated on attached sheets A21.1, A21.2, A22.3, A22.3D, A22.4, A23.2, A72.1. PLEASE DO NOT HESITATE TO CONTACT ME WITH ANY QUESTIONS ABOUT THIS INSTRUCTION. THANK YOU. Date: Attention: Project: Project No.: From: Issued via: The Work shall be carried out in accordance with the above supplemental instructions issued in accordance with the Contract Documents without change in Contract Sum or Contract Time. Proceeding with the Work in accordance with these instructions indicates your acknowledgment that there will be no change in the Contract Sum or Contract Time. By: TD Burk.. Document2
9
Embed
CONSTRUCTION MODIFICATION # 014 · 2018. 10. 17. · 1994 construction documents (per UBC 505(f)2) separating Natatorium from Locker rooms is added to current Code Sheet G14.1. •
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
CONSTRUCTION MODIFICATION #014
16 October 2018
Randall Coonrod, Coonrod & Associates Construction Co.
Greater Wichita YMCA, East Branch Addition/Remodel
5358.00
Teresa Burk
☐E-Mail ☒Online ☐Mail ☒Delivery ☐Fax Total Pages: 9
ARCHITECT’S SUPPLEMENTAL INSTRUCTIONS
CONTRACTOR - PLEASE make revisions as noted:
• Add fire sprinkler zone: Wet Fire Sprinkler shall be added to
Building #1, north and east of the 2-hour fire wall separation. Code
sheet G14.1 revised to indicate zone for additional sprinkler area plus
wet area of Building #2, and to reallocate corridor occupant loads to
below 30 at both 111 and 176. Corridor 111 is part of fully sprinkled
building #2 allowed to be non-rated per IBC Table 1018.1 with occupant
load < 30. Corridor 176 is within the sprinkled portion of Building #1
and totally separated from unsprinkled areas by 2-hr fire rated
separation walls. With consent of MABCD committee, this is requested
for consideration of equivalent substitution to the intent of IBC IBC
Table 1018.1, with sprinkler requirements shown to be sufficient by
sealed document provided by FSC, Inc. Consulting Engineers and
provided to MABCD via email dated October 8, 2018.
• Fire separation indicated: 2-hr Fire-rated wall indicated at original
1994 construction documents (per UBC 505(f)2) separating Natatorium
from Locker rooms is added to current Code Sheet G14.1.
• Revise storage 114: Omit planned wall cuts at either side of existing
storage room 113 and provide mandoor thru west wall as indicated on
• FIRE EXTINGUISHERS• EXIT LIGHTS & EMERGENCY LIGHTS
-DIESEL GENERATOR BACKUP
PASSIVE FIRE SAFETY SYSTEM: NONE PROVIDED, NONE REQUIRED
SMOKE CONTROL SYSTEM:NONE PROVIDED, NONE REQUIRED
ACTIVE FIRE SAFETY SYSTEM:• FIRE ALARM SYSTEM PROVIDED• SMOKE DETECTION PROVIDED AT RATED DOORS WITH
HOLD OPENS AND HVAC EQUIPMENT ABOVE 2000 CFM • AREA SMOKE DETECTION COVERAGE AT ELC• EXIT LIGHTS AND EMERGENCY LIGHTS PROVIDED WITH
BATTERY BACKUP• FIRE SPRINKLER - BUILDING #2: DOUBLE INTERLOCK
DRY SYSTEM W/ EXTERIOR FDC WALL MOUNTED AT RISER CLOSET, CONNECTION TO MEET WFD REQUIREMENTS - FLOW TEST AND HYDRAULIC CALCULATIONS TO BE PERFORMED BY CONTRACTOR
• FIRE SPRINKLER - BUILDING #1, NORTH AND EAST OF 2-HR FIRE WALLS: WET SYSTEM AS INDICATED BY SHADED AREA. DELUGE WATER CURTAINS INSTALLED EACH SIDE OF OPENING 101C.
ALLOWABLE AREA CALCULATIONS - BUILDING #2 INCLUDING NEW ADDITION At = 9,500 SFP = 616 FTF = 236 + 72 + 33.5 = 341.5W = (341.5 X (30 / 341.5)) = 30If = (F / P - 0.25) W / 30
= [(341.5 / 616) - 0.25] (30 / 30) = 0.3044Is = 2 (SPRINKLER ADDED THIS PROJECT - SEE BELOW)Aa = [At + (At X If) +(At X Is)
= [9,500 + (9,500 X 0.3044) + (9,500 X 2)]= 31,391.8 SF/FLOOR
ACTUAL SF = COMPLIANT?LEVEL 1 = 13,857 EXISTING + 3,053 NEW
• C.M. TO FIELD VERIFY ALL FIRE EXTINGUISHER LOCATIONS. SUPPLY ADDITIONAL FIRE EXTINGUISHER CABINETS AS NEEDED SO THAT TRAVEL DISTANCE DOES NOT EXCEED 75' FROM ANY POINT IN THE BUILDING TO THE NEAREST FIRE EXTINGUISHER. VERIFY LOCATIONS IN FIELD WITH ARCHITECT PRIOR TO INSTALLATION.
• KANSAS FIRE PREVENTION CODE - KSA 31-133 AND 31-134a. MOST BUILDINGS NEW OR EXISTING HAVE ONE OR MORE DEVIATIONS FROM ONE OF THE RECOGNIZED BUILDING CODES. STATE LAW MANDATES COMPLIANCE TO THE KANSAS STATE FIRE PREVENTION CODE (KFPC) IN ALL OCCUPIED STRUCTURES. STATE LAW CAN BE SUMMARIZED AS: A) EXISTING STRUCTURES CANNOT HAVE 'DISTINCTLY HAZARDOUS CONDITIONS' - THOSE THAT IMPEDE SPEEDY EXIT; B) NEW CONSTRUCTION AND CHANGES IN OCCUPANCY SHALL COMPLY TO CURRENT STANDARDS; C) ADDITION OR CHANGES IN EXISTING BUILDINGS CANNOT MAKE THE EXISTING CONDITION WORSE OR BLOCK EXITING. MOST CORRECTIONS TO DISTINCTLY HAZARDOUS CONDITIONS COMPENSATE FOR IMPAIRED EXITING. MANY COMPENSATORY MEASURES ACCEPTABLE TO THE KANSAS STATE FIRE MARSHAL'S OFFICE DO NOT UPGRADE THE BUILDING OR MEET THE LETTER OF A BUILDING, FIRE OR LIFE SAFETY CODE. EXISTING PORTIONS OF MANY BUILDINGS DO NOT COMPLY WITH A CERTAIN BUILDING CODE AND SHOULD BE SPECIFIED AS MEETING THE KANSAS FIRE PREVENTION CODE.
REQUIRED FIXTURES FOR 1344 OCCUPANTS (IBC TABLE 2902.1): A-3 OCCUPANCY
WATER CLOSETS LAV'S DRINKING FOUNTAINSMEN (672 OCC.) 1 PER 125 = 6 1 PER 200 = 4 1 PER 500 = 3WOMEN (672 OCC.) 1 PER 65 = 10 1 PER 200 = 4
ACTUAL FIXTURES:WATER CLOSETS LAV'S DRINKING FOUNTAINS
MEN 8 + 3 URINALS 9 13WOMEN 9 8UNISEX 4 4
ARCHITECT: SCHAEFER JOHNSON COX FREY & ASSOCIATES, P.A.I CERTIFY THAT THE SUBMITTED PLANS FOR THE PROJECT REFERENCED ABOVE COMPLY WITH THE REQUIREMENTS OF THE FOLLOWING:
2012 INTERNATIONAL BUILDING CODE2015 INTERNATIONAL MECHANICAL CODE2015 UNIFORM PLUMBING CODE2017 NATIONAL ELECTRIC CODE (NFPA 70-90)2010 ADAAG ACCESSIBILITY GUIDELINES FOR BUILDINGS AND FACILITIES2012 INTERNATIONAL FIRE CODE
PER 2012 IBC SECTION 104.10, THE KANSAS STATE FIRE MARSHALL ACCEPTS APPLICATION OF THE 2012 IBC TO THIS PROJECT AS PROVIDING AN EQUIVALENT LEVEL OF MINIMUM LIFE SAFETY AS REQUIRED BY THE KANSAS FIRE PREVENTION CODE.
TYPE OF CONSTRUCTION: NEW CONSTRUCTION AND EXISTING BUILDING RENOVATIONLOCATION: 9333 E. DOUGLAS OWNER: GREATER WICHITA AREA YMCA, 402 N MARKET ST, WICHITA, KS 67202 PH: 316.219.9622 COUNTY: SEDGWICKCITY: WICHITAARCHITECT: SJCF ARCHITECTURE, 257 N BROADWAY, WICHITA, KS 67202 PH: 316.684.0171HANDICAP PROVISIONS: PATH OF TRAVEL, RESTROOMS, EXITSWATER SUPPLY: CITY OF WICHITASEWAGE TREATMENT: CITY OF WICHITAGAS: KANSAS GASELECTRICITY: WESTARFIRE SERVICE: CITY OF WICHITAUSE: FITNESSAUTHORITY HAVING JURISDICTION: STATE ARCHITECT, STATE FIRE MARSHALLOCAL CODE ENFORCEMENT: CITY OF WICHITA
100
.2
20"
34"
FEC
FE
1500
150 SF(300)
Name Of Room
# OF OCCUPANTS
ROOM AREA
OCCUPANT LOAD FACTOR
# OF OCCUPANTS
EGRESS WIDTH PER OCCUPANT
REQ'D WIDTH
ACTUAL WIDTH
FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER
LINE OF EXIT PATH
1500
150 SF(300)
Name Of Room
25OCCUPANT LOAD FROM A TRIBUTARY AREA OF THE ADJACENT FLOOR ABOVE OR BELOW
INDICATES THE OCCUPANT LOAD EXITING FROM THE BUILDING
INDICATES THE OCCUPANCY LOAD OF A SPECIFIC ROOM OR AREA REQUIRING ONE EXIT
INDICATES THE OCCUPANCY LOAD OF A SPECIFIC ROOM OR AREA REQUIRING TWO OR MORE EXITS
# OF OCCUPANTS
ROOM AREA
OCCUPANT LOAD FACTOR
LOCATION OF EXIT
EXISTING 1HR FIRE RATING
EXISTING 2HR FIRE RATING
EXISTING 2HR RATED CORRIDOR
2-HR. 8" BLOCK AREA SEPARATION WALLS U.L. U9052-HR. 6" METAL STUD AREA SEPARATION WALL U.L. U424
137
.2
24.0"
27.4"
72
.2
14.4"
34"
38
.2
7.6"
34"
28
.2
5.6"
68"
169
.2
31.8"
33.8"
170
.2
34"
34"
69
.2
13.8"
34"
164
.2
32.8"
34"
164
.2
32.8"
34"
21
.2
3.8"
34"
41
.2
8.2"
34"
3
.2
.6"
34"
429 SF
1 2DL
(35)
TODDLER II
3577 SF
73
(50)
CARDIO
1277 SF
40
(35)
KID ZONE
500 SF
34
(15)
CONFERENCE
96 SF
1
OFFICE
123 SF
2
DIRECTOR
240 SF
2
HALL
127 SF
1
GYMNASTICSTOR
VEST
315 SF
4
(100)
CHECK-IN
RR
162 SF
1
GYM STOR
107 SF
1
(300)
ELEC
308 SF
7
CHECK-IN
308 SF
7
CHECK-IN
822 SF
17
(50)
CIRCULATION
294 SF
21
(15)
LOUNGE
150 SF
2
BRKRM
354 SF
4
(100)
OFFICE
99 SF
1
(300)
BRKRM
109 SF
2
(100)
OFFICE516 SF
8DL
(65)
INFANTS
171 SF
1
(300)
LAUNDRY
3490 SF
70
(50)
GYMNASTICS
6620 SF
136
(50)
GYMNASIUM
STAIR
42 SF
1
(300)
STO
976 SF
20
(50)
WOMENS LR
928 SF
19
(50)
MENS LR
395 SF
12
(35)
MOM'S DAY OUT
330 SF
2
MAINT
334 SF
2
(300)
MECH/ELEC
337 SF
2
(300)
FILTER ROOM
POOL
284
POOLS - 4422 SF / 50 SF PER OCC. = 88 OCCUPANTSDECK - 2940 SF / 15 SF PER OCC. =
196 OCCUPANTS
3297 SF
62
(50)
STRENGTH
910 SF
23
(50)
PERSONALTRAINING
93 SF
1
(300)
STORAGE
150 SF
3
(50)
PILATES
155 SF
2
(100)
OFFICE
194 SF
1
(300)
MAINT
370 SF
8
(50)
FAMLR
48 SF
1
(300)
STORAGE
158 SF
11
(15)
STM RM
80 SF
6
(15)
SAUNA
70 SF
6
(15)
SAUNA
147 SF
3
(50)
WH POOL VEST
EXITWAY
STAIR
EXITWAY
ELEV
51 SF
1
EQUIP
CORR
CORRIDOR
CORRIDOR
CORRIDOR
CORR
RR
SHOWER
SHOWER
RR
CHG
SHOWER
CHG
CHG
CHG
VEST
FIRE
STAIR
PLAYGROUND
SHOWER
WOMENS RR
MENS RR
FEC
85
24
29
49
62
85
31
2893 SF
58
(50)
FREE WEIGHT
105
84
23
190
18
18
38
148
.2
29.6"
72"
40
6
6 6 412
1
2
14
8
42019
173
103
20
8
9
729 SF
22DL
(35)
PRESCHOOL II
542 SF
13DL
(42)
PRESCHOOL I
10
.2
2"
34"
10
.2
2"
34"
8
.2
1.6"
34"
2 22 0
13
FEC
FE
C
FEC FEC
FE
C
FE
C
FE
FEC
FE
C
FE
FE
FEC
15
423 SF
12DL
(35)
TODDLER I
32 SF
1
(300)
STORAGE
BUILDING #1
BUILDING #2
BU
ILD
ING
#2
BU
ILD
ING
#3
BU
ILD
ING
#2
BU
ILD
ING
#3
20
.2
4"
34"
13
MABCD #30
13
MABCD #30
13
ASI-007
13
MABCD #29
13
ASI-007
OMIT REVISIONS
OMIT REVISIONS
17
ASI-011
17
ASI-011
101C
20
ASI-014
20
ASI-014
20
ASI-014 20
ASI-014
20
ASI-014
20
ASI-014
20
ASI-014
20
ASI-014
70 SF
1
CAMPSTORAGE
20
ASI-014
ADDED 2-HR FIRE SEPARATION BETWEEN NATATORIUM AND LOCKER ROOMS AS INDICATED ON ORIGINAL CONSTRUCTION DOCUMENT CODE SHEET
These drawings and their contents, including, but not limited to, all concepts,
designs, & ideas are the exclusive property of Schaefer Johnson Cox Frey (SJCF), and may
not be used or reproduced in any way without the express consent of SJCF.
ELE
CT
RIC
AL E
NG
INE
ER
S
ME
CH
AN
ICA
L E
NG
INE
ER
S
ST
RU
CT
UR
AL E
NG
INE
ER
S
CIV
IL E
NG
INE
ER
SM
KE
C E
NG
INE
ER
ING
MID
WE
ST
EN
GIN
EE
RIN
G, I
NC
.
DU
DLE
Y W
ILLI
AM
S &
AS
SO
CIA
TES
, P.A
.
INTE
GR
ATED
CO
NSU
LTIN
G E
NG
INEE
RS,
INC
.
G14.1
CODE COMPLIANCE -
FIRST FLOOR
GR
EA
TE
R W
ICH
ITA
YM
CA
EA
ST
BR
AN
CH
AD
DIT
ION
/ R
EN
O
29 JUNE 2018
5358.00
9333 E
. D
OU
GL
AS
WIC
HIT
A, K
S 6
7207
BUILDING INFORMATION
GENERAL NOTES
PLUMBING FIXTURE SUMMARY
PROJECT CERTIFICATIONPROJECT INFORMATION
CODE PLAN LEGEND
U.L. DATA
N
KEY PLAN
AREA 'A'
AREA 'B'
AREA 'C'
1/16" = 1'-0"
1 FIRST FLOOR CODE COMPLIANCE PLAN
0' 4' 8' 16' 32'
N
BU
ILD
ING
#3
BU
ILD
ING
#2
BUILDING #1
BUILDING #2
X FDC
FACP
2
ADDENDUM
MABCD 009
2 AD2 6.08.18
13 ASI-007 09.12.18
17 ASI-011 10.02.18
18 ASI-012 10.09.2018
19 ASI-013 10.12.18
20 ASI-014 10.16.18
MABCD #29: ELC AREA REVISED TO INDICATE DESIGN LOADS PER KDHE LICENSING ALLOWANCES. ADDED EXTERIOR DOOR AT ROOM 163 PRESCHOOL II, AND REVISED 167 CORRIDOR OCCUPANT EGRESS LOADS TO TOTAL LESS THAN 30 ELIMINATING THE REQUIREMENT FOR 1-HR RATED CORRIDOR WALLS.MABCD #30: ADDED DOORS AT HALL 154 AND CORRIDOR 176 SEPARATING FROM CIRCULATION 181. CHANGED PARTITION TYPE AT HALL 154 TO 1-HR RATED. REVISED EGRESS OCCUPANCIES TO REFLECT CHANGE IN DIRECTION OF EXITING.
13
MABCD #29& #30
18
ASI-012
OCCUPANT EGRESS LOADS ARE REVISED TO REDUCE NUMBER OF PERSONS IN CORRIDOR WHERE ADDITIONAL SPRINKLER IS TO BE ADDED AT BUILDING #1, THUS ELIMINATING REQUIREMENT FOR 1-HR RATED CORRIDOR. IBC TABLE 1018.1.
18
MABCDADD-ON
• THIS SHEET IS INTENDED FOR GENERAL INFORMATION, REFERENCE ALL SHEETS AND SPECIFICATION
MANUAL FOR ADDITIONAL DEMOLITION INFORMATION.
• REFERENCE ALSO SECTION 01 7000 OF SPECIFICATION MANUAL FOR DIRECTION ON 'ALTERATIONS'
AND 'CUTTING AND PATCHING'.
• CONTRACTOR SHALL VERIFY ALL EXISTING SITE AND BUILDING CONDITIONS PRIOR TO BID.
• CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING EQUIPMENT AND DEVICES, CUT / PATCH
WORK, ETC., AS NECESSARY FOR NEW AND REMODELED CONSTRUCTION. COORDINATE WORK ON
DEMO SHEETS WITH WORK ON FLOOR PLAN SHEETS - REF. MECHANICAL AND ELECTRICAL SHEETS
FOR DEMOLITION AND CUT / PATCH WORK REQUIRED FOR MECH. AND ELEC. WORK.
• DASHED LINES REPRESENT ITEMS FOR REMOVAL OR RELOCATION - REF. KEYED NOTES
• OWNER SHALL HAVE FIRST SALVAGE RIGHTS ON ALL ITEMS REMOVED FROM BUILDING.
CONTRACTOR SHALL VERIFY ALL ITEMS TO BE SALVAGED WITH OWNER AND COORDINATE WITH
OWNER AS REQUIRED. SALVAGED ITEMS SHALL BE REMOVED TO A LOCATION ON SITE AS
DESIGNATED BY OWNER. ITEMS NOT SALVAGED SHALL BE REMOVED AND DISPOSED BY
CONTRACTOR. SUCH ITEMS SHALL INCLUDE BUT NOT LIMITED TO: FURNITURE, CABINETS, DEVICES,
EQUIPMENT, PLUMBING, MECHANICAL, ETC.
• CONTRACTOR SHALL CUT AND PATCH FLOORS, WALLS, CEILINGS, AND ROOFS AS REQUIRED FOR
PLACEMENT OF NEW PIPING, CONDUITS, DEVICES, STRUCTURE, ETC. - REFERENCE ALL PLANS FOR
LOCATIONS.
• CONTRACTOR SHALL PROTECT ALL STRUCTURAL ELEMENTS TO REMAIN IN BUILDING.
• CONTRACTOR SHALL VERIFY ALL NEW OPENINGS FOR PIPING, DUCTS, AND CONDUIT WITH THE
EXISTING BUILDING STRUCTURAL SYSTEM. DO NOT CUT THROUGH EXISTING CONCRETE
FLOOR/ROOF BEAMS, CONCRETE FLOOR/ROOF JOISTS, CONCRETE COLUMNS, STEEL COLUMNS, OR
STEEL ROOF JOISTS UNLESS NOTED ON THE PLANS. NOTIFY ARCHITECT IMMEDIATELY OF ANY
CONFLICT.
• CONTRACTOR SHALL PROTECT ALL EXISTING COMPONENTS TO REMAIN AND SHALL REPAIR DAMAGE
TO EXISTING COMPONENTS AND FINISHES TO MATCH ADJACENT.
• CONTRACTOR SHALL PATCH, REPAIR, AND REFINISH DAMAGE TO ALL SURFACES RESULTING FROM
DEMOLITION WORK TO MATCH ADJACENT AS CLOSELY AS POSSIBLE. WALL OR FLOOR SURFACES
WHERE MILLWORK, ELECTRICAL DEVICES, OR MECHANICAL EQUIPMENT IS REMOVED SHALL BE
PATCHED AND REFINISHED TO MATCH ADJACENT.
• CONTRACTOR SHALL REMOVE ALL EXISTING SWITCHES, OUTLETS, FIRE ALARM DEVICES, INTERCOM
DEVICES, SPEAKERS, HOLD-OPENS, POWER STRIPS, ETC., NOT RECONNECTED. PROVIDE STAINLESS
STEEL COVER PLATES OVER J-BOXES NOT USED. REMOVE ALL EXPOSED CONDUIT/WIRE MOLD NOT
USED - PATCH / PAINT WALL TO MATCH ADJACENT. REFERENCE ELECTRICAL FOR EXTENT OF
ELECTRICAL COMPONENT REMOVAL.
• CONTRACTOR SHALL REMOVE DOOR / WINDOW FRAMES AND CUT OPENINGS AS INDICATED.
PREPART RESULTANT OPENING AS REQUIRED FOR NEW CONSTRUCTION.
• CONTRACTOR SHALL REMOVE ALL MECH/PLUMBING EQUIPMENT AND PIPING NOT RECONNECTED.
ITEMS INCLUDE BUT NOT LIMITED TO: VENTS, RADIATORS, VENTILATORS, WATER / STEAM SUPPLY
AND RETURN LINES, SEWER LINES, GAS LINES, INSULATION, ESCHUTEON PLATES, ELECTRICAL
CONNECTIONS, AND ASSOCIATED CONSTRUCTION EXPOSED TO VIEW. CAP LINES AS REQUIRED.
PIPING IN TUNNELS TO REMAIN UNLESS NOTED OTHERWISE. REFERENCE MECHANICAL/PLUMBING
FOR EXTENT OF COMPONENT REMOVAL.
• REFER TO MECHANICAL AND ELECTRICAL DEMOLITION SHEETS FOR ADDITIONAL INFORMATION ON
MECHANICAL AND ELECTRICAL DEMOLITION WORK.
• FLOORING TO BE DEMOLISHED SHALL BE REMOVED TO CONCRETE OR EXISTING SUB-FLOOR
STRUCTURE. ALL GLUE, GROUT, AND RESIDUE SHALL BE REMOVED TO PROVIDE A CLEAN BARE
SURFACE SUFFICIENT FOR INSTALLATION OF NEW PRODUCT.
• CONTRACTOR SHALL SALVAGE AND STOCKPILE BUILDING PRODUCTS FROM DEMOLITION TO BE
USED FOR PATCHWORK. ITEMS INCLUDE BUT ARE NOT LIMITED TO WALL TILE, DOORS, CEILING TILE,
LIGHT FIXTURES, MECHANICAL DIFFUSERS, MOLDING, TRIM, SPECIAL EQUIPMENT, ETC. - REF.
SPECIFICATION MANUAL.
• ALL CHALKBOARDS, TACKBOARDS, PROJECTION SCREENS, BLINDS, ETC. SHALL BE REMOVED FROM
AREAS BEING REMODELED IF IN CONFLICT WITH WORK WHETHER NOTED ON PLANS OR NOT. WALL
SURFACES BEHIND BOARDS SHALL HAVE GLUE REMOVED AND PATCHED AS REQUIRED TO MATCH
ADJACENT SURFACES WHERE LEFT EXPOSED. CONTRACTOR SHALL VERIFY ITEMS TO BE SALVAGED.
• CONTRACTOR SHALL REMOVE ALL ABANDONED GAS PIPING SYSTEMS IN REMODEL AREAS WHERE
GAS IS NO LONGER NEEDED. THIS SHALL INCLUDE BUT NOT LIMITED TO FORMER SCIENCE ROOMS,
SHOPS, ART ROOMS, OR KITCHENS THAT BECOME ROOMS NOT REQUIRING GAS. PLUG LINES OUT OF
VIEW & PATCH PENETRATIONS - REF. MECH.
• WHERE NEW SUSPENDED CEILINGS ARE INSTALLED ABOVE DEMOLISHED SUSPENDED CEILINGS ,
PATCH WALL WHERE DEMOLITION OCCURS.
• WHERE NEW CEILING IS REQUIRED BELOW EXISTING PLASTER CEILING, REMOVE EXISTING PLASTER
• CONTRACTOR TO VERIFY EXISTING SITE AND BUILDING CONDITIONS PRIOR TO BIDDING• REFERENCE SHEET G10.1 FOR GRAPHIC SYMBOL AND DRAWING SYMBOL DEFINITIONS.• HATCHED WALL WITH DARK (BLACK) PERIMETER LINES INDICATE NEW WALLS. EXISTING WALLS
SHOWN WITH SCREENED (GRAY) LINES WITH NO FILL.• SEE ENLARGED PLANS FOR ALL ACCESSORY LOCATIONS THAT REQUIRE IN-WALL BLOCKING FOR
ATTACHMENT.• SEE ALL MILLWORK DETAILS FOR ALL CASEWORK GOODS THAT REQUIRE IN-WALL BLOCKING FOR
ATTACHMENT.• PROVIDE 1" BULLNOSE ON ALL EXPOSED CMU CORNERS, UNLESS NOTED OTHERWISE. PROVIDE
SQUARE CMU CORNERS AT TILED WALLS.• ABBREVIATIONS:
CJ CONTROL JOINT - REF. DETAILFEC FIRE EXTINGUISHER AND CABINET - REF. SPEC.FE FIRE EXTINGUISHER AND BRACKET - REF. SPEC. MB MARKER BOARDTB TACKBOARDTS TACKSTRIPPS PROJECTION SCREEN - REF. SPEC. IDB INTERACTIVE DISPLAY BOARD - REF. SPEC. AND ELECTRICALBL WINDOW BLINDS - REF. SPEC.WS WINDOW SHADES - REF. SPEC. DS DOWNSPOUT LOCATIONRD ROOF DRAIN - REF. MECHANICALOD OVERFLOW ROOF DRAIN - REF. MECHANICALNIC NOT IN CONTRACT, ITEM PROVIDED AND INSTALLED BY OWNERVIF VERIFY IN FIELD ACTUAL CONDITIONS
7.33 2 HR RATED WALL ASSEMBLY SHALL EXTEND FROM CJ @ EXISTINGMASONRY WALL ACROSS TO EAST SIDE OF WINDOWS A13-FR & A14-FR.UL-U424: 6" METAL STUD @ 16" O.C., R-19 BATT INSULATION; EXTERIORSIDE - MASONRY VENEER, AIR GAP, RIGID INSULATION,WEATHERPROOFING, 5/8" EXTERIOR SHEATHING; INTERIOR SIDE - 3LAYERS 1/2" TYPE X GYP BOARD, VAPOR BARRIER AS REQUIRED - REF.SPEC.
9.28 INFILL BETWEEN EXISTING WOOD FLOOR AND CONCRETE INFILL CURBWITH DIMENSIONED FLOORING SECTIONS SALVAGED FROM DEMO @LEVEL 2 CARDIO. SEAL JOINT AT SILL PER SPEC. FINISH INFILL TO MATCHEXISTING ADJACENT WOOD FLOOR; COORDINATE W/ OWNER
11.34 UNDER COUNTER REFRIGERATOR - PROVIDED AND INSTALLED BYOWNER
22.07 DRINKING FOUNTAINS - REF. PLUMBING
32.08 METAL PLAYGROUND FENCING, MATCH EXISTING - PAINT - REF. SITEPLAN.
32.11 6'x3' WIDE SWINGING GATE, MATCH EXISTING - PAINT.
1/8" = 1'-0"
1 FLOOR PLAN - LEVEL 1 - AREA B
N
KEY PLAN
AREA 'A'
AREA 'B'
AREA 'C'
0' 4' 8' 16' 32'
4
ADDENDUM
5
ADDENDUM
5
ADDENDUM
10
MABCD#23a
3 AD3 6.15.18
4 AD4 6.22.18
5 AD5 6.29.18
8 ASI-002 7.23.18
10 MABCD 8.03.2018
14 ASI-008 09.21.18
15 ASI-009 09.26.2018
20 ASI-014 10.16.18
20
ASI-014
• CONTRACTOR TO VERIFY EXISTING SITE AND BUILDING CONDITIONS PRIOR TO BIDDING.• DIMENSIONS:
• INTERIOR• TO FACE OF CMU OR CONCRETE, UNLESS NOTED OTHERWISE• TO FACE OF METAL STUD, UNLESS NOTED OTHERWISE• ROUGH OPENING EDGES, UNLESS NOTED OTHERWISE• TO CENTER OF STEEL COLUMN, UNLESS NOTED OTHERWISE
These drawings and their contents, including, but not limited to, all concepts,
designs, & ideas are the exclusive property of Schaefer Johnson Cox Frey (SJCF), and may
not be used or reproduced in any way without the express consent of SJCF.
ELE
CT
RIC
AL E
NG
INE
ER
S
ME
CH
AN
ICA
L E
NG
INE
ER
S
ST
RU
CT
UR
AL E
NG
INE
ER
S
CIV
IL E
NG
INE
ER
SM
KE
C E
NG
INE
ER
ING
MID
WE
ST
EN
GIN
EE
RIN
G, I
NC
.
DU
DLE
Y W
ILLI
AM
S &
AS
SO
CIA
TES
, P.A
.
INTE
GR
ATED
CO
NSU
LTIN
G E
NG
INEE
RS,
INC
.
A22.3D
DIMENSION PLAN -
LEVEL 1 - AREA B
GR
EA
TE
R W
ICH
ITA
YM
CA
EA
ST
BR
AN
CH
AD
DIT
ION
/ R
EN
O
29 JUNE 2018
5358.00
9333 E
. D
OU
GL
AS
WIC
HIT
A, K
S 6
7207
GENERAL FLOOR PLAN NOTES
1/8" = 1'-0"
1 DIMENSION PLAN - LEVEL 1 - AREA B
0' 4' 8' 16' 32'
N
N
KEY PLAN
AREA 'A'
AREA 'B'
AREA 'C'
2
ADDENDUM
8
ASI-002
2 AD2 6.08.18
8 ASI-002 7.23.18
20 ASI-014 10.16.18
20
ASI-014
• CONTRACTOR TO VERIFY EXISTING SITE AND BUILDING CONDITIONS PRIOR TO BIDDING• REFERENCE SHEET G10.1 FOR GRAPHIC SYMBOL AND DRAWING SYMBOL DEFINITIONS.• HATCHED WALL WITH DARK (BLACK) PERIMETER LINES INDICATE NEW WALLS. EXISTING WALLS
SHOWN WITH SCREENED (GRAY) LINES WITH NO FILL.• SEE ENLARGED PLANS FOR ALL ACCESSORY LOCATIONS THAT REQUIRE IN-WALL BLOCKING FOR
ATTACHMENT.• SEE ALL MILLWORK DETAILS FOR ALL CASEWORK GOODS THAT REQUIRE IN-WALL BLOCKING FOR
ATTACHMENT.• PROVIDE 1" BULLNOSE ON ALL EXPOSED CMU CORNERS, UNLESS NOTED OTHERWISE. PROVIDE
SQUARE CMU CORNERS AT TILED WALLS.• ABBREVIATIONS:
CJ CONTROL JOINT - REF. DETAILFEC FIRE EXTINGUISHER AND CABINET - REF. SPEC.FE FIRE EXTINGUISHER AND BRACKET - REF. SPEC. MB MARKER BOARDTB TACKBOARDTS TACKSTRIPPS PROJECTION SCREEN - REF. SPEC. IDB INTERACTIVE DISPLAY BOARD - REF. SPEC. AND ELECTRICALBL WINDOW BLINDS - REF. SPEC.WS WINDOW SHADES - REF. SPEC. DS DOWNSPOUT LOCATIONRD ROOF DRAIN - REF. MECHANICALOD OVERFLOW ROOF DRAIN - REF. MECHANICALNIC NOT IN CONTRACT, ITEM PROVIDED AND INSTALLED BY OWNERVIF VERIFY IN FIELD ACTUAL CONDITIONS
X1X2X3X4X5X6X7X8X9
A32.1 3
XBXA
XC
XD
XE
XF
XG
XH
XJ
XK
AL14AL14AL14AL14
CAMPSTORAGE
114
AL15
GYM STOR
112
A32.1
4
STRENGTH
123
PERSONALTRAINING
124
GYMNASIUM
115
PILATES
122
OFFICE
119
EXITWAY
118
EXITWAY
117
STAIR
116
STAIR
127
STORAGE
125
EQUIP
121
STORAGE
128
115
ELEV
120
FREE WEIGHT
126
CORR
111
2A42.2
2A42.2
22.07
4.18
9.28 9.28 9.28 9.28
6.22
22.07
2G
REVIEW CURRENT CONDITION FOR ADA COMPLIANT DOOR AT TEMPORARY CHECK-IN
These drawings and their contents, including, but not limited to, all concepts,
designs, & ideas are the exclusive property of Schaefer Johnson Cox Frey (SJCF), and may
not be used or reproduced in any way without the express consent of SJCF.
ELE
CT
RIC
AL E
NG
INE
ER
S
ME
CH
AN
ICA
L E
NG
INE
ER
S
ST
RU
CT
UR
AL E
NG
INE
ER
S
CIV
IL E
NG
INE
ER
SM
KE
C E
NG
INE
ER
ING
MID
WE
ST
EN
GIN
EE
RIN
G, I
NC
.
DU
DLE
Y W
ILLI
AM
S &
AS
SO
CIA
TES
, P.A
.
INTE
GR
ATED
CO
NSU
LTIN
G E
NG
INEE
RS,
INC
.
A22.4
FLOOR PLAN -
LEVEL 1 - AREA C
GR
EA
TE
R W
ICH
ITA
YM
CA
EA
ST
BR
AN
CH
AD
DIT
ION
/ R
EN
O
29 JUNE 2018
5358.00
9333 E
. D
OU
GL
AS
WIC
HIT
A, K
S 6
7207
GENERAL FLOOR PLAN NOTES
KEYED NOTES
4.18 4" MASONRY FILL BEHIND WINDOW. PAINT EXTERIOR SIDE BLACK PRIOR TO INSTALLINGWINDOW.
6.22 ADJUSTABLE LAMINATE WOOD SHELVES, REF. DETAIL AND SPEC. PROVIDE SIX SHELVES PERSYSTEM
9.28 INFILL BETWEEN EXISTING WOOD FLOOR AND CONCRETE INFILL CURB WITH DIMENSIONEDFLOORING SECTIONS SALVAGED FROM DEMO @ LEVEL 2 CARDIO. SEAL JOINT AT SILL PERSPEC. FINISH INFILL TO MATCH EXISTING ADJACENT WOOD FLOOR; COORDINATE W/ OWNER
11.34 UNDER COUNTER REFRIGERATOR - PROVIDED AND INSTALLED BY OWNER
22.07 DRINKING FOUNTAINS - REF. PLUMBING
1/8" = 1'-0"
1 FLOOR PLAN - LEVEL 1 - AREA C
0' 4' 8' 16' 32'
N
KEY PLAN
AREA 'A'
AREA 'B'
AREA 'C'
5 AD5 6.29.18
15 ASI-009 09.26.2018
20 ASI-014 10.16.18
15
ASI-009
20
ASI-014
F/SF/S
• CONTRACTOR TO VERIFY EXISTING BUILDING CONDITIONS PRIOR TO BIDDING. • THIS SHEET IS FOR GENERAL INFORMATION ONLY. NOT ALL CEILING LIGHT
FIXTURES, DEVICES, MECHANICAL DIFFUSERS, GRILLES, ETC. ARE SHOWN. REF. MECHANICAL AND ELECTRICAL FOR ADDITIONAL INFORMATION.
• ALL CONDUIT RUNS SHALL BE CONCEALED AT EXPOSED CEILINGS - REF. ELECTRICAL.
• SPRINKLER PIPE AT EXPOSED CEILINGS (EXCEPT STORAGE, MECHANICAL, LAUNDRY OR CUSTODIAL ROOMS): ONLY THE SPRINKLER LINES SERVING THE EXPOSED CEILING ROOM SHALL BE EXPOSED AND BE NEATLY ARRANGED WITH THE EXPOSED STRUCTURE OF THE ROOM. SPRINKLER PIPING SHALL BE HUNG FROM THE EXPOSED TOP FLANGE OF BEAMS OR JOISTS AND RUN PARRALLEL WITH THE BEAM OR JOISTS. DO NOT HANG SPRINKLER PIPING FROM DECK. MAINS SHALL BE CONCEALED IN SOFFITS WHERE PROVIDED OR RUN IN ADJACENT ROOM AND HAVE ONLY THE EXPOSED SPRINKLER PIPES SERVING THAT ROOM BE EXPOSED.
• SPRINKLER PIPE AT STAGE: COORDINATE THE LOCATION OF SPRINKLER LINES WITH THE LINE SETS AND RUN PARALLEL WITH THE LINE SETS. THE MAIN SHALL RUN PERPENDICULAR TO THE LINE SETS AND RUN OPPOSITE OF THE RIGGING BLOCKS, TIGHT TO THE WALL.
• REFER TO WALL SECTIONS FOR HEIGHTS OF SOFFITS UNLESS NOTED. • ALL GYPSUM BOARD SOFFITS SHALL HAVE PAINTED GYPSUM BOARD VERTICAL
FACES UNLESS DETAILED OTHERWISE.• COORDINATE INSTALLATION OF MECH. EQUIPMENT, DUCTS, LIGHTS AND
SPRINKLER LINES WITH STRUCTURE TO MAINTAIN THE SCHEDULE CEILING HEIGHT. IT IS THE RESPONSIBLITY OF THE G.C. TO COORDINATE AMOUNG THE TRADES AND REPORT ANY DISCREPANCIES TO SJCF PRIOR TO INSTALLATION.
• ALL EXPOSED DUCTWORK, PIPING, AND DECK SHALL BE PAINTED.• ONLY CEILING FINISHES ARE DESIGNATED IN SYMBOLS. REFER TO ROOM FINISH
SCHEDULE AND A28 SERES SHEETS FOR ROOM FINISHES.
4A42.1
3A42.1
1A42.1
1 2 3 4 5 6 7 8 9 10 11.7 1311
A
B
C
D
E
F
G
H
J
K
L
2A42.1
12
5A43.2
5A42.1
5A42.1
1A42.2
8A43.1
7A43.1
9A43.1
5A43.2
A1 10'-8"
A1 9'-4"A1 9'-4"
GP 9'-4"
GP 9'-4"
GP 9'-4"
CARDIO
103
VEST
100B
GYMNASTICS
110
LOBBY
101
CHECK-IN
102
ELEC
108STORAGE
107
FIRE
106
STORAGE
104
LOUNGE
180
STAIR
109
VEST
100A
A2 9'-0"
A1 10'-0"
GP 10'-0"
GP 10'-0"
GYM STOR
112
CAMPSTORAGE
114
EX
8.21 8.21 8.21 8.21 8.21
EX
EX
EX
EX
EX
EX
EX
5.05
26.01
5.05
21.01
7.18
EX
26.01
26.01
EX
GYMNASTICSTOR
113
GP 10'-0"
COORDINATE THRU-WALL DUCT PENETRATIONSWITH ADJACENT SPACE CEILING AND LIGHTING
14
ASI-008E1
GP9'-111/4"
GP9'-111/4"
20
ASI-014
REF. ELEC FOR LIGHTING
GYPSUM BD. SOFFIT/CEILING (PAINT)
TILE CEILING
ACOUSTICAL CEILING- REF. SPEC. AND FINISH SCHEDULE
HVAC DIFFUSER / RETURN AIR GRILLE- REF. MECHANICAL
• ALL DOORS ARE UNDERCUT AS SPECIFIED.• SAFETY GLAZING LISTED IS REQUIRED ONLY IN LOCATIONS TO MEET CODE REQUIREMENTS EXCEPT
WHEN SHOWN IN REMARKS COLUMN OR DRAWINGS.• DOOR DIMENSIONS REFER TO OPENING DIMENSIONS OF FRAME.• WOOD DOORS TO BE FACTORY FINISHED UNLESS NOTED OTHERWISE - REF. SPEC.• HOLLOW METAL DOORS TO BE PAINTED UNLESS NOTED OTHERWISE - REF. SPEC• ALUMINUM DOORS, STOREFRONT AND CURTAIN WALL TO BE FACTORY FINISH UNLESS NOTED
OTHERWISE - REF. SPEC• FURNISH AND INSTALL ALUMINUM STOREFRONT OR CURTAIN WALL FRAMES AND TRIM PER SPEC.• FIELD VERIFY ALL DIMENSIONS OF OPENINGS TO RECEIVE NEW STOREFRONT, CURTAIN WALL OR
DOOR FRAMES PRIOR TO FABRICATION. SIZES SHOWN ARE FOR ESTIMATING PURPOSES AND DESIGN INTENT, ACTUAL CONDITIONS MAY VARY. ADJUST DIMENSIONS TO INCLUDE NECESSARY SHIMS, SEALANTS AND FLASHING. G.C. TO COMMUNICATE DIMENSIONAL DISCREPANCIES TO ARCHITECT PRIOR TO FABRICATION.
• REPLACEMENT OF EXISTING WINDOW OR STOREFRONT:1. KEEP DUST TO A MINIMAL AND CLEAN UP AFTER WORK IN THAT AFFECTED AREA'S UPON
COMPLETION.2. REPAIR ALL DAMAGED AREAS CAUSED BY WINDOW OR STOREFRONT REPLACEMENT INCLUDING
(BUT NOT LIMITED TO) PLASTER OR GYP. BD. WALLS, WOOD TRIM, MILLWORK, CEILINGS, ETC. (VERIFY ALL EXISTING CONDITIONS PRIOR TO WORK).
3. FIELD VERIFY ALL DIMENSIONS OF EXISTING OPENINGS TO RECEIVE NEW WINDOWS OR STOREFRONT PRIOR TO FABRICATION.
4. CONTRACTOR SHALL REMOVE OLD UNITS AND INSTALL NEW WINDOW OR STOREFRONT UNITS IN THE SAME WORKING DAY.
• REMOVE ALL SEALANT FROM EXISTING SURFACES AFTER EXISTING WINDOW IS REMOVED. PREP. AREA TO RECEIVE NEW WINDOW OR STOREFRONT.
• WHERE DIMENSIONS ARE NOT SPECIFIED ON FRAME TYPE, REFERENCE DOOR SCHEDULE FOR SPECIFIC REQUIREMENTS PER LOCATION.
• DOOR AND WINDOW FRAMES SHALL BE EITHER "HM - HOLLOW METAL" OR "AL - ALUMINUM" PER FRAME TYPE TITLE. REFERENCE SPEC FOR SPECIFIC FRAME TYPE REQUIREMENTS.
These drawings and their contents, including, but not limited to, all concepts,
designs, & ideas are the exclusive property of Schaefer Johnson Cox Frey (SJCF), and may
not be used or reproduced in any way without the express consent of SJCF.
ELE
CT
RIC
AL E
NG
INE
ER
S
ME
CH
AN
ICA
L E
NG
INE
ER
S
ST
RU
CT
UR
AL E
NG
INE
ER
S
CIV
IL E
NG
INE
ER
SM
KE
C E
NG
INE
ER
ING
MID
WE
ST
EN
GIN
EE
RIN
G, I
NC
.
DU
DLE
Y W
ILLI
AM
S &
AS
SO
CIA
TES
, P.A
.
INTE
GR
ATED
CO
NSU
LTIN
G E
NG
INEE
RS,
INC
.
A72.1
DOOR AND FRAME
SCHEDULE
GR
EA
TE
R W
ICH
ITA
YM
CA
EA
ST
BR
AN
CH
AD
DIT
ION
/ R
EN
O
29 JUNE 2018
5358.00
9333 E
. D
OU
GL
AS
WIC
HIT
A, K
S 6
7207
GENERAL NOTES
1/4" = 1'-0"
HM01 FRAME ELEVATION
1/4" = 1'-0"
HM02 FRAME ELEVATION
DOOR TYPES
FRAME TYPES
DOOR & FRAME SCHEDULE
DOOR
TAG
DOOR FRAME DETAILS FIRE
RATING
HDW
SET REMARKSW H MAT. TYPE FINISH GL. MAT. TYPE FINISH GL. JAMB HEAD SILL100A 4'-0" 8'-0" AL FGX PRE-FINISHED SG-1 AL AL01 PRE-FINISHED REF. ELEV. B4/A68.1 D4/A68.1 MANUF - 1.0 SLIDING PANEL; OUTWARD SWING EMG EGRESS < 50# FORCE
100B 4'-0" 8'-0" AL FGX PRE-FINISHED SG-1 AL AL01 PRE-FINISHED REF. ELEV. B4/A68.1 D4/A68.1 MANUF - 1.0 SLIDING PANEL; OUTWARD SWING EMG EGRESS < 50# FORCE
101A 4'-0" 8'-0" AL FGX PRE-FINISHED SG-2 AL AL07 PRE-FINISHED GL-1, SG-2 D1/A68.1 B1/A68.1 MANUF - 1.0 SLIDING PANEL; OUTWARD SWING EMG EGRESS < 50# FORCE
101B 4'-0" 8'-0" AL FGX PRE-FINISHED SG-2 AL AL07 PRE-FINISHED GL-1, SG-2 D1/A68.1 B1/A68.1 MANUF - 1.0 SLIDING PANEL; OUTWARD SWING EMG EGRESS < 50# FORCE
101C 16'-0" 11'-0" STL OCS PRE-FINISHED - STL MANUF. - - D4/A68.2 C4/A68.1 E4/A68.2 90 MIN. 5.0 ROLL UP FIRE DOOR
103A 3'-0" 7'-10" AL FG PRE-FINISHED SG-3 AL AL08 PRE-FINISHED SG-3, GL-4 D1/A68.1 B1/A68.1 - - 6.0
103B 3'-0" 7'-10" AL FG PRE-FINISHED SG-3 AL AL08 PRE-FINISHED SG-3, GL-4 D1/A68.1 B1/A68.1 - - 6.0
103C 3'-0" 7'-10" AL FGX PRE-FINISHED SG-1 AL AL15 PRE-FINISHED SG-1, GL-1 B3/A68.1 A3/A68.1 F4/A68.1 - 2.0
178 3'-0" 7'-0" HM D PAINT - HM HM03 PAINT - B2/A68.1 B2/A68.1 - - 19.0 DOOR LOCATION SIMILAR TO EXISTING. REPOSITION TO USEEXISTING LINTEL IF STILL IN PLACE. NOTIFY ARCHITECT OF EXISTINGCONDITION; PINCH-PROOF HINGE PROTECTION
179A 8'-0" 7'-0" AL OCS PRE-FINISHED - AL MANUF. - - D5/A68.1 C5/A68.1 E5/A68.1 - 5.0
179B 3'-0" 7'-10" AL FG PRE-FINISHED SG-1 AL AL19 PRE-FINISHED SG-1, GL-1 B4/A68.1 D4/A68.1 F4/A68.1 - 3.0 PINCH-PROOF HINGE PROTECTION; PARTIAL REPLACE UNLESS ALT. 1