Top Banner

of 123

Configuration Suite Manual

Apr 08, 2018

Download

Documents

kingsly
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 8/7/2019 Configuration Suite Manual

    1/123

    DEEP SEA ELECTRONICS

    DSE7000 Series PC configuration suite

    Document Number 057-077

    Author: Anthony Manton

    COMPLEX SOLUTIONSMADE SIMPLE

  • 8/7/2019 Configuration Suite Manual

    2/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM2

    DEEP SEA ELECTRONICS PLC

    Highfield HouseHunmanbyNorth YorkshireYO14 0PH

    ENGLAND

    Sales Tel: +44 (0) 1723 890099Sales Fax: +44 (0) 1723 893303

    E-mail : [email protected] : www.deepseaplc.com

    DSE7000 Series configuration suite

    Deep Sea Electronics PlcAll rights reserved. No part of this publication may be reproduced in any material form (including photocopyingor storing in any medium by electronic means or other) without the written permission of the copyright holder

    except in accordance with the provisions of the Copyright, Designs and Patents Act 1988.Applications for the copyright holders written permission to reproduce any part of this publication should beaddressed to Deep Sea Electronics Plc at the address above.

    The DSE logo and the names DSEUltra, DSEControl, DSEPower, DSEExtra, DSEMarine and DSENet are UKregistered trademarks of Deep Sea Electronics PLC.

    Any reference to trademarked product names used within this publication is owned by their respectivecompanies.

    Deep Sea Electronics Plc reserves the right to change the contents of this document without prior notice.

    Amendments List

    Amd.

    No.

    Comments Minimum

    Moduleversionrequired

    Minimum

    Configuration SuiteVersion required

    1-4 Added Negative Phase Sequence, kW Overload, Earth Fault trip,Alternative Configurations

    2.0.3

    5-10 Added Dual Mutual Standby and Coolant Cooler/Heater Control, ACSystem images, EJP input and output for EDF Energy Tariff changes(France), Maintenance Alarm 1, Configurable Status Screens

    2.2.8 2.0.3.53

    11-16 Added Modbus port selection, Virtual LEDs, Control Logic,Maintenance alarms 2 and 3, Load Shed and Dummy load controls,Manual Speed trim

    3.0.18 2.0.4.68

    17 Added 2510/2520 display expansion.Added changes to Dual Mutual Standby, Fuel usage, dummy loadcontrol, load shedding, and protections disabled. More details in manyareas. Addition of 4

    thlevel to the contents page to ease searching for

    details of sub pages.

    4.x.x. 2.0.6.x

    18 Changes to the Communications page (7300) 4.5.2 2.0.6.12319 Additions for V5 modules: Bidirectional language strings for module

    inputs, Updated control logic to allow one to feed into another,additional start delay timers, addition of electrical trip coolant tempalarm, sensor curve manager, language editor, additional electrical tripon selected alarms, remote control output sources.

    5.x.x 2.0.8.19

    20 Additions for V6 modules. 7320 breaker control in manual modechanged now push to open, push to close. Mains current protectionenabled when CT is in Load leg. Short circuit protection added to 7310controller.

    6.x.x V2010 1 4.0.4.0

    21 Added information on to changing strings for the SCADA alarms/eventlog through the language editor tool. Also added information on theAddress Book.

    - 4.14.26.0

    Typeface : The typeface used in this document is Arial. Care should be taken not to mistake the upper case letter I with the numeral 1. Thenumeral 1 has a top serif to avoid this confusion.

  • 8/7/2019 Configuration Suite Manual

    3/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 3

    TABLE OF CONTENTS

    1 BIBLIOGRAPHY .............................................................................................. 62 DESCRIPTION ................................................................................................. 6

    2.1 SOFTWARE INSTALLATION INSTRUCTIONS ............................................................................... 72.1.1 MINIMUM SYSTEM REQUIREMENTS ........................................................................................................... 72.1.2 INSTALLATION .............................................................................................................................................. 72.1.3 TROUBLESHOOTING SOFTWARE INSTALLATION .................................................................................. 10

    2.1.3.1 WINDOWS 7 ..................................................................................................................................................................... 102.1.3.2 WINDOWS VISTA ............................................................................................................................................................. 102.1.3.3 WINDOWS XP .................................................................................................................................................................. 102.1.3.4 WINDOWS NT, WINDOWS MILLENIUM, WINDOWS 98, WINDOWS 95, WINDOWS 3.1 ........................................... 102.1.3.5 APPLE MAC, WINDOWS CE, PALM OS, SMARTPHONE, PDA .................................................................................... 10

    3 HARDWARE INSTALLATION ....................................................................... 113.1 TROUBLESHOOTING INSTALLATION ......................................................................................... 11

    4 USING THE CONFIGURATION SUITE ......................................................... 125 MENUS AND TOOLBAR ............................................................................... 13

    5.1 FILE MENU ..................................................... ........................................................... ...................... 135.2 TOOLS MENU ................................................................................................................................. 14

    5.2.1 UPDATE FIRMWARE ................................................................................................................................... 165.3 LANGUAGE EDITOR ...................................................................................................................... 19

    5.3.1 GETTING STARTED .................................................................................................................................... 195.3.2 EDITING THE STRINGS ............................................................................................................................... 205.3.3 UPDATING THE MODULE LANGUAGE ...................................................................................................... 205.3.4 UPDATING THE SCADA ALARMS/EVENT LOG LANGUAGE .......................... ...................... ................... 21

    5.4 HELP MENU .................................................................................................................................... 235.5 TOOLBAR ....................................................................................................................................... 235.6 ADDRESS BOOK ..................................................... ........................................................... ............ 25

    5.6.1 CREATING A NEW ENTRY .......................................................................................................................... 255.6.2 USING AN ENTRY........................................................................................................................................ 26

    6 EDIT CONFIG ................................................................................................ 276.1 SCREEN LAYOUT .......................................................................................................................... 276.2 MODULE ......................................................................................................................................... 28

    6.2.1 MODULE OPTIONS ................... ..................... ..................... ...................... ..................... ..................... ......... 296.2.2 CONFIGURABLE STATUS SCREENS ........................................................................................................ 316.2.3 EVENT LOG ................................................................................................................................................. 32

    6.2.3.1 DISPLAY OPTIONS .......................................................................................................................................................... 326.2.3.2 LOGGING OPTIONS ........................................................................................................................................................ 326.2.3.3 SMS MESSAGING ............................................................................................................................................................ 32

    6.3 APPLICATION .......................................................... ........................................................... ............ 336.3.1 ECU (ECM) OPTIONS .................................................................................................................................. 346.3.2 CAN DATA FAIL ALARM ............................................................................................................................. 356.3.3 DUAL MUTUAL STANDBY .......................................................................................................................... 35

    6.3.3.1 OPERATION ..................................................................................................................................................................... 356.3.3.2 TYPICAL WIRING DIAGRAM ........................................................................................................................................... 36

    6.3.4 AUTO VOLTAGE SENSING ......................................................................................................................... 366.3.5 DISABLE PROTECTIONS ............................................................................................................................ 37

    6.4 INPUTS ........................................................... ........................................................... ...................... 386.4.1 OIL PRESSURE ........................................................................................................................................... 386.4.2 COOLANT TEMPERATURE ........................................................................................................................ 39

    6.4.2.1 COOLANT TEMPERATURE ALARMS ............................................................................................................................ 396.4.2.2 COOLANT TEMPERATURE CONTROL .......................................................................................................................... 40

    6.4.3 FUEL LEVEL ................................................................................................................................................ 416.4.4 FLEXIBLE SENSOR ..................................................................................................................................... 426.4.5 EDITING THE SENSOR CURVES ................................................................................................................ 436.4.6 DIGITAL INPUTS ................... ...................... ..................... ..................... ..................... ...................... ............ 446.4.7 DIGITAL INPUT FUNCTIONS....................................................................................................................... 45

    6.5 OUTPUTS ....................................................... ........................................................... ...................... 496.5.1 DIGITAL OUTPUTS ................... ..................... ..................... ...................... ..................... ..................... ......... 496.5.2 VIRTUAL LEDS ............................................................................................................................................ 496.5.3 CONTROL LOGIC ........................................................................................................................................ 50

    6.5.3.1 EXAMPLE USING BOTH OR & AND FUNCTIONS ......................................................................................................... 506.5.3.2 EXAMPLE OF A LATCHED OUPUT ................................................................................................................................ 516.5.3.3 EXAMPLE USING OR FUNCTIONS ONLY ..................................................................................................................... 516.5.3.4 EXAMPLE USING AND FUNCTION ONLY ..................................................................................................................... 52

    6.5.4 OUTPUT SOURCES ..................................................................................................................................... 536.6 TIMERS ........................................................................................................................................... 58

    6.6.1 START TIMERS ..................... ...................... ..................... ..................... ..................... ...................... ............ 586.6.2 LOAD / STOPPING TIMERS ........................................................................................................................ 596.6.3 MODULE TIMERS ........................................................................................................................................ 596.7 GENERATOR .................................................................................................................................. 606.7.1 GENERATOR OPTIONS .............................................................................................................................. 60

    6.7.1.1 GENERATOR CONTACTOR ALARM .............................................................................................................................. 616.7.1.2 GENERATOR PHASE ROTATION .................................................................................................................................. 616.7.1.3 GENERATOR KW RATING .............................................................................................................................................. 61

  • 8/7/2019 Configuration Suite Manual

    4/123

  • 8/7/2019 Configuration Suite Manual

    5/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 5

    8 ALARM TYPES ............................................................................................ 122

  • 8/7/2019 Configuration Suite Manual

    6/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM6

    1 BIBLIOGRAPHY

    This document refers to and is referred to by the following DSE publications which can be obtained from theDSE website www.deepseaplc.com:

    DSE PART DESCRIPTION

    057-004 Electronic Engines and DSE wiring

    057-073 DSE7310 Remote Start Module operator manual057-074 DSE7320 AMF Module operator manual

    057-082 DSE2130 input expansion manual057-083 DSE2157 input expansion manual057-084 DSE2548 input expansion manual057-105 DSE2500 display expansion manual

    The following third party documents are also referred to:

    ISBN DESCRIPTION

    1-55937-879-4 IEEE Std C37.2-1996 IEEE Standard Electrical Power System Device Function Numbersand Contact Designations. Published by Institute of Electrical and Electronics EngineersInc

    2 DESCRIPTION

    This manual covers the operation of the configuration suitefor 7200 and 7300 series modules. Separatemanuals cover other DSE modules.

    The DSE7000 Series configuration suite allows the 7000 family of modules to be connected to a PC viaUSB A USB B cable. Once connected the various operating parameters within the module can be viewed oredited as required by the engineer. This software allows easy controlled access to these values and also hasdiagnostic monitoring facilities.

    The configuration suite should only be used by competent, qualified personnel, as changes to the operation ofthe module may have safety implications on the panel / generating set to which it is fitted. Access to criticaloperational sequences and settings for use by qualified engineers, may be barred by a security code set bythe generator provider.The information contained in this manual should be read in conjunction with the information contained in theappropriate module documentation. This manual only details which settings are available and how they maybe used.A separate manual deals with the operation of the individual module (See section entitled Bibliographyelsewhere in this document).

  • 8/7/2019 Configuration Suite Manual

    7/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 7

    2.1 SOFTWARE INSTALLATION INSTRUCTIONS

    2.1.1 MINIMUM SYSTEM REQUIREMENTS

    Operating System Windows Vista, Windows XP or Windows 2000 with Microsoft .Net 2.0 frameworkMonitor 17 inch recommended (1024 x 768 resolution)

    Communications USB required o configure the module.

    NOTE: - As 7000 Series configuration software for Windows is a 32-Bit application requiringMicrosoft .net 2 framework, it will not operate on Windows 2.0, 3.0, 3.1,3.11, 95, 98 or Me.

    NOTE: - Microsoft .Net 2.0 Framework can be obtained from Microsofts website. Alternatively itis included in the DSE Configuration Suite Software CD version which can be obtained on CD fromDeep Sea Electronics PLC or by downloading the CD version from the DSE website.

    NOTE: - Exit all other programs before installing the software. It is recommended that any earlierreleases of the software be uninstalled prior to installing this version.

    NOTE: - Please register online at www.deepseaplc.com Once registered you will be able to

    download updates to the software to ensure that you always have access to the latest features.

    2.1.2 INSTALLATION

    Insert the Software CD into the CD-ROM drive on the PC. The CD will then Auto-run if this feature is enabledon your PC.

    Alternatively:

    Double click on Computer

    Double click on CD-ROM Drive

    Double click CDSetup

    Click Next to continue

  • 8/7/2019 Configuration Suite Manual

    8/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM8

    Select Disk Costto view remaining disk space, Click Next to continue.

    Example showing the Disk Costwindow.

  • 8/7/2019 Configuration Suite Manual

    9/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 9

  • 8/7/2019 Configuration Suite Manual

    10/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM10

    2.1.3 TROUBLESHOOTING SOFTWARE INSTALLATION

    It is very rare that problems are encountered when installing the system, however if problems arise, use thefollowing checklist to troubleshoot your software installation

    2.1.3.1 WINDOWS 7

    32 bit and 64 bit versions

    Ensure the operating system is logged onto using an Administrator Account. Failure to do this resultsin installation failure due to incorrect user permissions disallowing registration of some parts of theConfiguration Suite Software.

    When installing the software, instead of clicking the icon with the left mouse button, click on theinstallation icon with the right mouse button, then select Run as Administrator.

    Ensure the operating system is fully up to date using the Microsoft WindowsUpdate facility. Ensure that Windows Installeris fully up to date using the Microsoft WindowsUpdate facility.

    Ensure the operating system has Microsoft .net 2 Framework redistributable (for x86) installed and isfully up to date. This is available from Microsofts website.

    2.1.3.2 WINDOWS VISTA

    32 bit and 64 bit versions

    Ensure the operating system is logged onto using an Administrator Account. Failure to do this resultsin installation failure due to incorrect user permissions disallowing registration of some parts of theConfiguration Suite Software.

    When installing the software, instead of clicking the icon with the left mouse button, click on theinstallation icon with the right mouse button, then select Run as Administrator.

    Ensure the operating system is fully up to date using the Microsoft WindowsUpdate facility.

    Ensure that Windows Installeris fully up to date using the Microsoft WindowsUpdate facility.

    Ensure the operating system has Microsoft .net 2 Framework redistributable (for x86) installed and isfully up to date. This is available from Microsofts website.

    2.1.3.3 WINDOWS XP

    Ensure the operating system is logged onto using an Administrator Account. Failure to do this resultsin installation failure due to incorrect user permissions disallowing registration of some parts of theConfiguration Suite Software.

    Ensure the operating system is fully up to date using the Microsoft WindowsUpdate facility. Ensure that Windows Installeris fully up to date using the Microsoft WindowsUpdate facility.

    Ensure the operating system has Microsoft .net 2 Framework redistributable (for x86) installed and isfully up to date. This is available from Microsofts website.

    2.1.3.4 WINDOWS NT, WINDOWS MILLENIUM, WINDOWS 98, WINDOWS 95,

    WINDOWS 3.1

    DSE Configuration Suite does not support these operating systems. It is recommended that thesystem is operated under Windows 7, Windows Vista or Windows XP operating systems.

    2.1.3.5 APPLE MAC, WINDOWS CE, PALM OS, SMARTPHONE, PDA

    DSE Configuration Suite requires a Windows Personal Computer (PC). It is recommended that thesystem is operated under Windows 7, Windows Vista or Windows XP operating systems.

  • 8/7/2019 Configuration Suite Manual

    11/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 11

    3 HARDWARE INSTALLATION

    Ensure the Configuration Suite Software is installed on the PC as described above.The installation of the PC software also installs the DSE Controller USB Driver automatically.Connect the USB cable to the module and to the PC as shown below.

    Windows detects the module when power is applied to it.

    You are now ready to configure or monitor the module using the Configuration Suite Software.

    3.1 TROUBLESHOOTING INSTALLATION

    Occasionally USB devices are disabled by the Windows operating system, the following procedure will re-

    enable the device in these instances.

    Disconnect the Deep Sea Electronics Controller from the USB port. Wait a moment, then reconnectand try again. If you still encounter problems then :

    Try another USB cable. If you dont have one, its the same type of cable as usually used between aPC and a USB printer (Type A to Type B). If you still encounter problems then :

    Disconnect the Deep Sea Electronics Controller. Shutdown, then restart the PC. Reconnect theinterface, then try again. If you continue to experience problems then :

    check the USB port with another device (for instance a mouse, printer or digital camera).

  • 8/7/2019 Configuration Suite Manual

    12/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM12

    4 USING THE CONFIGURATION SUITE

    To run the Configuration Suite Software for Windows program click the Windows start button

    or depending upon your version of Windows.

    Then select All Programs - Deep Sea Electronics PLC DSE Configuration Suite DSE Configuration

    Suite

    After a short delay to load the application, the splash screen is shown, after which the screen willdisplay:-

    This is the initial start-up screen and can be disabled by checking the box Hide this screen at start-up.The screen prompts the user to select between the three main uses for the software:

    Creating a new configuration. Select the module type under Create new configuration. This allowsyou to create a configuration for the latest module version. Use File | Convert to... to convert theconfiguration to suit an earlier module version or use Tools | Update firmwareto update an earliermodule to the latest firmware version.

    Editing a configuration previously saved to disk or flash memory device. Select the configuration fileeither from the Open recent configurationarea or by clicking Open a configuration fileand browsingto the file.

    Reading and changing the configuration of a connected module. Click Read configuration from amodule. The file is read from a currently connected 7000 Series controller and is available for editingin the Configuration Suite.

    Alternatively you can ignore this screen and continue to use the program in the background. Once you make aconnection or load/create a configuration, the start-up screen will disappear.

  • 8/7/2019 Configuration Suite Manual

    13/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 13

    5 MENUS AND TOOLBAR

    The menu and toolbar are located at the top of the screen:

    5.1 FILE MENU

    Create a new configuration file. You are prompted to select what kind ofmodule you want to create the configuration for.The settings of the new configuration file match the factory settings for thechosen module type.You can only select to create a configuration file for the latest version ofcontroller. If you want to create a configuration for an earlier version ofcontroller, you can use Convert to... to make your configuration suitable for theearlier controller or use Tools | Update firmwareto update the earlier moduleto the latest version.

    Open an existing file from disk or flash memory device.Close the currently open file.

    Save the currently open file to the location it was loaded from previously. If thisis a new file, you are prompted to enter a filename.Save the currently open file, under a new name. You will be prompted to entera filename.

    Send the currently open configuration settings to the controller.

    Read the settings out of the connected controller for viewing / editing.

    Read the settings from the connected 7000 Series controller and convert tothe currently selected configuration type.Read the settings from a 7000 Series configuration fi le on disk or flashmemory device and convert to the currently selected configuration type.Convert the currently loaded configuration file to suit another module type or

    another module version.

    Print the currently open configuration file.

    Preview what the configuration file will look like on the page after printing.

    Select printer type and printer settings.

    Exit the software. If the currently open file has changed since it was lastsaved, you will be prompted to save it.

  • 8/7/2019 Configuration Suite Manual

    14/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM14

    5.2 TOOLS MENU

    Options Opens the Settingsscreen containing customisation options for theConfiguration Suite.

    Logo insert Only available when currently viewing the Modulesection of theconfiguration.

    This allows the user to create Logo Inserts for the DSE7000 Seriesmodules to customise the controller to suit the generator manufacturer.

    Text Insert Only available when currently viewing the Modulesection of theconfiguration.

    This allows the user to create Text Inserts for the configurable LEDs on theDSE7000 Series modules.

    Changefont

    Changebackgroundcolour

    Reset fontand colourchanges

    Print thisinsert card

    Load an imageinto the logoinsert program

    Print thislogo insertcard

  • 8/7/2019 Configuration Suite Manual

    15/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 15

    Annunciator text insert Not available for DSE7210 / DSE7220.

    Only available when currently viewing the DSE2548 configurations in theExpansion | 2548 Annunciator Modulessection of the configuration.

    This allows the user to create Text Inserts for the DSE2548 ExpansionAnnunciator modules

    Update FirmwareAllows the user to update the firmware (internal software) of the 7000Series controller. For a complete description see the section entitled

    Update Firmware elsewhere in this document.Manage curves Allows the management (editing or deleting) of custom sensor curves

    AlarmOnly available for 86xx & 87xx

    Allows the user to log any alarms that have been received by telephonemodem from a suitable configured controller.

    Event LogOnly available for 86xx & 87xx

    Allows the user to log all the events from any module connected to the PCvia SCADA.

    Address BookAllows the user to create an Address Book of connects. For a completedescription see the section entitled Address Book else where in thisdocument.

    Language editorVersion 5.x.x or later

    Allows the editing of the text displayed by the module. For a completedescription see the section entitled Language Editor elsewhere in thisdocument.

    Changefont

    Changebackgroundcolour

    Reset font

    and colourchanges

    Print thisinsert card

    Load an imageinto the logoinsert program

  • 8/7/2019 Configuration Suite Manual

    16/123

  • 8/7/2019 Configuration Suite Manual

    17/123

  • 8/7/2019 Configuration Suite Manual

    18/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM18

    If the file you attempt to send to themodule is not compatible with thecurrently connected module, theupdate cannot continue.In this example an attempt wasmade to send a 7210 firmware fileto a 7220 module!

    Power up the module. It will beautomatically detected and the

    update process will begin.

    The update is now in progress and willtake under one minute.

    During this phase:

    DO NOT DISCONNECT THE USBCONNECTION

    DO NOT TURN OFF YOUR PC

    DO NOT REMOVE POWERFROM THE DSE7000 SeriesCONTROLLER

    The update is now complete.

    The module will automatically restartwith the updated firmware (internalsoftware program).

    It is now safe to disconnect the USBlead and power down the module oryour PC.

    Click OK to continue.

  • 8/7/2019 Configuration Suite Manual

    19/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 19

    5.3 LANGUAGE EDITOR

    The language editoris compatible with version 5.x.x and later modules only. Languages created with thelanguage editorare compatible with module versions 5.x.x and later only

    The Language editor(Tools | Language Editor) is included to allow the user to tailor the text of the 7000 series

    controller to suit their own requirements, it also allows the user to tailor the text of all DSE controllers for theSCADA alarms to suit their own requirements. An obvious use for this facility is to allow the user to changethe entire module text to another language. Other uses include changing some wording to better reflect thecustomers application. For instance Shutdown can be renamed to Critical Alarm and Warning can bechanged to Prompt Alarm.

    5.3.1 GETTING STARTED

    To start a new translation, go to the File menu. The user can choose tocreate a new module translation or SCADA/event log translation(Module alarm strings) or open an existing one for editing.

    The text strings are grouped together to make finding aparticular string easier.

    A summary shows how many strings do not have textentered, and if any are incorrect (are too long to display onthe module screen) these will be shown as errors.

    Give the new text file a name, for instance the name of thelanguage you are translating it to.

  • 8/7/2019 Configuration Suite Manual

    20/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM20

    5.3.2 EDITING THE STRINGS

    5.3.3 UPDATING THE MODULE LANGUAGE

    Click the + symbol to open up thatsection and view/modify the textstrings. Click to close this group

    Click the column headings to sortthe strings into alphabetical order

    Enter the new text into the Translationcolumn. The Mimiccolumn shows how it will appear on the module display.

    A tick shows that the textfits onto the display.A cross means the text istoo long for the display.

    When youre ready to test your new text file in the connected module, send it using thebutton provided.Remember you must select this new language file in the modules display configurationeditor. You can also upload language files to the module using the SCADA |LANGUAGES section of the Configuration Suite Software.

  • 8/7/2019 Configuration Suite Manual

    21/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 21

    5.3.4 UPDATING THE SCADA ALARMS/EVENT LOG LANGUAGE

    NOTE: - The SCADA text file is only applicable to the PC that it has been selected on.

    NOTE: - The SCADA text file will be used until the user configures it back to default (leaving thefile location blank) or selecting another file.

    NOTE: - The SCADA text file only affects the alarms page and the event log in the SCADAsection.

    When youre ready to test your new text file for the SCADA alarms and event log, savethe file with an appropriate name, e.g. the name of the language you are translating it to,to a folder on your computer you know the location of.

    When you have saved the new text file for the SCADA alarms, go to the Optionspage(Tools | Options) and click the Browsebutton for SCADA Module alarm translations tolocate the new text file. When you have selected the new text file for the SCADA alarms,press the Ok button to save the changes.

  • 8/7/2019 Configuration Suite Manual

    22/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM22

    An example of auser configuredSCADA alarmstring for Fail toStop

    An example ofa defaultSCADA alarmstring for Failto Stop

    An example ofa defaultevent logstring for Failto Stop

    An example of auser configuredevent log stringfor Fail to Stop

  • 8/7/2019 Configuration Suite Manual

    23/123

    5.4 HELP MENU

    Show

    5.5 TOOLBAR

    The toolbar contains the most usecommands.

    Creat

    Open

    Save ta newPrint t

    Previe

    Send

    Read

    Allowsdescri

    AllowsSCADOnly av

    Allowsfrom aOnly av

    Show

    SelectPCs

    USB To cowish t

    Modem To co

    Thenwish t

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-

    the version number of the configuration suite

    commands from the menus and is often a quicker w

    a new configuration file

    an existing file from disk or flash memory device

    he currently open file to the location it was loaded frofile, you are prompted to enter a filename.

    he currently open configuration file

    w what the configuration file will look like on the page

    he currently open configuration settings to the controll

    he settings out of the connected controller for viewing

    the user to create an Address Book of connects. Forption see the section entitled Address Book else whe

    the user to log all the events from any module conneA.ilable for 86xx & 87xxthe user to log any alarms that have been received bsuitable configured controller.ilable for 86xx & 87xxthe version number of the configuration suite

    oltages are shown as phase to phase voltages in the

    oltages are shown as phase to neutral voltages in the

    the communication method. The choices present areonfiguration.

    nect via USB directly to the controller, select USBanconnect too:

    nect to a module via modem, select your PC modem

    lick Modem Settingsand enter the telephone numberdial :

    Module Phone Number:The tthe module you wish to dial.

    Modem timeout:If the connectrespond to the PC Configuratiperiod of the Modem Timeout

    connection will be terminated.

    DialDial the number currently entePhone Numbersetting.

    Hang-up Close the phone connection.

    Answer modeThe Configuration Suite goes iawaiting a connection from a r

    77 ISSUE 7 AM 23

    y of accessing these

    previously. If this is

    after printing.

    er

    / editing

    a completere in this document.

    ted to the PC via

    telephone modem

    onfiguration editor

    configuration editor

    dependent upon your

    the controller you

    from the list :

    of the module you

    lephone number of

    ed module does notn Suite for the

    setting, the

    red into the Module

    nto Answer Modeemote module.

  • 8/7/2019 Configuration Suite Manual

    24/123

  • 8/7/2019 Configuration Suite Manual

    25/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 25

    5.6 ADDRESS BOOK

    The Address Book(Tools | Address Book) is included to allow the user to create and store address entries tomake connection to a defined module with ease. An obvious use for this facili ty is to allow the user to createand store address entries for modules which are connected with modems to make communication withoutentering the information into the software multiple times.

    5.6.1 CREATING A NEW ENTRY

    To create a new Address Bookentry, click on the Address Bookicon or go to (Tools | Address Book).

    Availablecommunication ports

    The user can choose to create a newAddress Book entry, open an existingone for editing or delete an old one.

    Click the column headingsto sort them into order.

    Select the port to communicatewith module.

    Enter the address details, if an identicalname is used multiple times, a number willbe automatically added after each entry.

    Enter the modules PIN number ifconfigured to allow access. If themodule does not have a PIN numberconfi ured, leave as shown.

    Select baud rate and the slave idof the module.

    To save the address entry,press the Ok button.

  • 8/7/2019 Configuration Suite Manual

    26/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM26

    5.6.2 USING AN ENTRY

    The new entry can now be selectedby double clicking with the leftmouse button or using the Connectvia drop down menu

    If the user has multipleAddress Book entries, the last5 used will be shown in theConnect via drop downmenu.

  • 8/7/2019 Configuration Suite Manual

    27/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 27

    6 EDIT CONFIG

    This menu allows module configuration, to change the function of Inputs, Outputs and LEDs, system timersand level settings to suit a particular application.

    6.1 SCREEN LAYOUT

    The type ofconfigurationfile being edited

    Close thisconfiguration file

    Move to thePreviousor Nextconfiguration page

    The colouredshading showsthe currentlyselected page.

    Click + or toshow or hidethe sub settingswithin eachsections.

    Click to selectthe subsectionto view / edit

    Click to returnto this page atan time

    Step forward orbackward throughpreviously viewedpages

  • 8/7/2019 Configuration Suite Manual

    28/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM28

    6.2 MODULE

    The module page is subdivided into smaller sections.Select the required section with the mouse.

    This section allows the user to change the options related to the module itself.

  • 8/7/2019 Configuration Suite Manual

    29/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 29

    6.2.1 MODULE OPTIONSFree entry boxes to allow the user togive the configuration file adescription. Typically this is used toenter the job number, customername, engineers name etc.

    Allows the user toselect the functionof the modulesuser configurable

    LED indicators.For details ofpossibleselections, pleasesee sectionentitled Outputsourceselsewhere in thisdocument.

    Allows the user tocreate logo and textinsert cards

  • 8/7/2019 Configuration Suite Manual

    30/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM30

    MiscellaneousOptionsEnable fast loadingfeature

    = Normal Operation, the safety on timer will be observed in full. This feature is useful if themodule is to be used with some small engines where pre-mature termination of the delaytimer can lead to overspeed alarms on start up. = The module will terminate the safety on timer once all monitored parameters have

    reached their normal settings. This feature is useful if the module is to be used as a standbycontroller as it allows the generator to start and go on load in the shortest possible time.

    NOTE: - Enabling Fast Loading is only recommended where steps have beentaken to ensure rapid start up of the engine is possible. (For example when fitted withengine heaters, electronic governors etc.)

    Audible alarm priorto starting

    = The module will start with no audible indication = The module will give an audible warning during the pre-start sequence as an indicatorthat the set is about to run. This is often a sites specification requirement of AUTO modeoperation.

    All warnings arelatched

    = Normal Operation, the warnings and pre-alarms will automatically reset once thetriggering condition has cleared. = Warnings and pre-alarms latch when triggered. Resetting the alarm is performed by

    either an external reset applied to one of the inputs or, the Stop/Reset pushbutton must beoperated (once the triggering condition has been cleared).

    Enable sleep mode =Normal operation =A configuration option which will allow the module to go into "sleep mode

    Enable manual fuelpump control

    =Normal operation =Allows manual fuel pump control when the fuel level instrument page is being viewed.

    Enable manualspeed trim control

    =Normal operation =Allows manual speed trim control when the engine speed is being viewed.

    Support right-leftlanguages inmodule stringsVersion 5.x.x or later

    Determines the direction of text input where supported (i.e. configurable input text)=left to right language support =right to left language support

    Enable Alternative

    Breaker ControlButtonVersion 6.x.x or later

    Controls the operation of the fascia mounted breaker control buttons (manual mode only)

    =Normal operation. Only a transfer is possible. =Alternative operation. If a supply is on load and that supplys breaker button is pressed,the breaker opens. Pressing the button again closes the button. Pressing the other buttonwhen a supply is on load causes a transfer to the other supply (if available).

  • 8/7/2019 Configuration Suite Manual

    31/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 31

    6.2.2 CONFIGURABLE STATUS SCREENS

    NOTE: - This feature is available only on DSE7000 Series modules, V2.2 and above. On previousversion modules, the status screen is fixed.

    Configurable Status Screens allow the operator to design the status screen to match the requirements of the

    end user or application more closely. For instance it is possible to configure the module to show the factoryset summary screen and then cycle the display to show instruments specified by the end user. This displaycycling occurs with no user intervention.

    This is the page that appearsautomatically when the engine isrunning (either instrumentation or status)

    These instruments are displayed one after the other whenthe set runs. If an entry is set to Not Used, or is notapplicable, the entry is skipped over and not displayed.

  • 8/7/2019 Configuration Suite Manual

    32/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM32

    6.2.3 EVENT LOG

    NOTE: - This feature is available only on DSE7000 Series modules, V3.0 and above

    6.2.3.1 DISPLAY OPTIONS

    The module display option allows the operator to choose between `Date and Time` or `Engine Hours`displayed on the bottom of the screen.

    6.2.3.2 LOGGING OPTIONS

    The event log can be configured to allow users to select which events are stored.

    6.2.3.3 SMS MESSAGINGWhen using the 7300 series controller, logged events will also cause modem dial outs and SMS messages tobe sent if the module is configured to do so and connected to a suitable external GSM modem withfunctioning SIM card.

  • 8/7/2019 Configuration Suite Manual

    33/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 33

    6.3 APPLICATION

    See overleaf for description of the parameters....

    Allows selection of the Engine typebeing used (ie Conventional DieselEngine, Gas Engine or ElectronicEngine)

    Configuration of the CAN data failalarm, providing protection againstthe failure of the engine ECU datalink.

    Allows all protections to bedisabled and give run todestruction functionality.

    Dual Mutual feature for a two setsystem, one set as standby shouldthe master set fail.

    Auto Voltage Sensing to facilitateeasy module reconfigurationautomatically.

  • 8/7/2019 Configuration Suite Manual

    34/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM34

    6.3.1 ECU (ECM) OPTIONS

    Parameter Description

    Engine type Select the engine type appropriate to your system

    Conventional Engine :Select this if you have a traditional (non ECU) engine, either Energise

    to Run or Energise to Stop.

    Conventional Gas Engine :Select this if you have a traditional (non ECU) engine and requireGAS engine functionality. This enables control of configurable outputs for Gas Choke andGas Ignitionand instructs the module to follow the gas engine timers.

    Other Engines :The list of supported CAN (or Modbus) engines is constantly updated, checkthe DSE website at www.deepseaplc.com for the latest version of Configuration Suitesoftware.

    Enhanced J1939 = The module will read Basic instrumentation from the engine ECU and display (wheresupported by the engine) :

    Engine Speed Oil Pressure

    Engine Coolant Temperature

    Hours Run

    = The module will read and display an Enhanced instrumentation list (where supportedby the engine) :

    Engine Speed Oil Pressure

    Engine Coolant Temperature

    Hours Run Engine Oil Temperature Exhaust Temperature

    Fuel Pressure

    Total Fuel used Fuel Consumption

    Inlet Manifold Temperature Coolant Pressure

    Turbo Pressure

    Where an instrument is not supported by the engine ECU, the instrument is not displayed.

    AlternativeEngine Speed

    = The engine is instructed to run at its Nominal Speedas configured by the EngineManufacturer.

    = The engine is instructed to run at its Alternative Speedas configured by the EngineManufacturer.

    Modbus EngineComms Port NOTE: - This feature is available only on DSE7300 Series modules, V3.0 and

    above.

    RS485 Port : The modules RS485 port is used to communicate to the engine (when aModbus engine type is selected.

    DSENet Port : The modules DSENet port is used to communicate to the engine (when aModbus engine type is selected. This frees the RS485 port in case connection to BMS orother RS485 compatible equipment is required.

  • 8/7/2019 Configuration Suite Manual

    35/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 35

    6.3.2 CAN DATA FAIL ALARM

    Parameter Description

    CAN data failalarm

    Action:None :Should communications from the engine ECU not be present, no action is taken. TheDSE7000 series module ignores shutdown messages from the engine ECU leaving these tobe handled by the engine ECU. The DSE module continues to provide protection on any

    parameters measured directly

    Shutdown :The engine is immediately shutdown upon loss of communications from theengine ECU.

    Warning : Should communications from the engine ECU not be present, a warning alarm isgenerated. The DSE7000 series module ignores shutdown messages from the engine ECUleaving these to be handled by the engine ECU. The DSE module continues to provideprotection on any parameters measured directly

    Arming :From safety On :The communications link monitoring is activated after the termination of theSafety Delay Timer.

    From Starting: The communications link monitoring is activated once the engine cranking

    begins.

    6.3.3 DUAL MUTUAL STANDBY

    NOTE: - This feature is available only on DSE7300 Series modules, V2.0 and above.

    ApplicationOptions

    Dual MutualStandby Inactive The module operates as a standalone module

    Master The module operates as the Master in a Dual Mutual or Dual Mutual Standbysystem.

    Slave The module operates as the Slave in a Dual Mutual or Dual Mutual Standby system.

    Load BalancingEnable

    = No Load Balancing takes place. The master controller will always be master.

    = Load Balancing is enabled. Based upon the configuration of the load balancing timeofthe master controller, the engines will change over at regular intervals.

    Load Balancingtime

    The master controller will run for the period of the Load Balancing Time. After this time, themaster will call for the slave to run for the same duration. If the slave is not available, themaster will continue to run.

    6.3.3.1 OPERATION

    If no mains supply is available (DSE7x10) or the mains supply has failed (DSE7x20), then the moduleconfigured as Masterwill start the generator set to power the load.If the Mastermodule fails to start, or is unavailable due to maintenance, engine shutdown etc, the Slavemodule will start and take over from the Masterto power the load.

    This operation depends upon the correct interconnection of the modules as follows.

    Configure a digital output of each module to Dual Mutual Standby.

    Use this output to drive an external slave relay. This relay should be normally open and close a battery negative signal to a digital input on the other

    DSE module.

    This DSE module should be configured to Dual Mutual Standby.

  • 8/7/2019 Configuration Suite Manual

    36/123

  • 8/7/2019 Configuration Suite Manual

    37/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 37

    6.3.5 DISABLE PROTECTIONS

    NOTE:- This feature is available in module versions 4 and above.

    This feature is provided to assist the system designer in meeting specifications for Warning only,Protections Disabled, Run to Destruction, War mode or other similar wording.

    Options Description

    Enable = The module will operate as normal and provide engine shutdown if required. = Protections disabledfunction is activated. Operation depends upon the followingconfiguration.

    NOTE:-Writing a configuration to the controller that has Protections Disabledconfigured, results in a warning message appearing on the PC screen for the user toacknowledge before the controllers configuration is changed. This preventsinadvertent activation of the feature.

    Disable AllProtections

    Never: The protections are not disabledAlways: Protections are always overridden by the DSE controller.

    On Input: Protections are disabled whenever a configurable input set to ProtectionsDisabledis activated

    ProtectionsDisabled AlarmAction

    If Disable All Protectionsis set to On Input, this selection allows configuration of an alarm tohighlight that the protections have been disabled on the engine.

    Indication :Any output or LCD display indicator configured to Protections Disabledwill bemade active, however the internal alarm sound will not operate.Warning :Any output or LCD display indicator configured to Protections Disabledwill bemade active, and the internal alarm sound will operate.

    When protections are disabled, Protections Disabledwill appear on the module display toinform the operator of this status.

  • 8/7/2019 Configuration Suite Manual

    38/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM38

    6.4 INPUTS

    The inputs page is subdivided into smaller sections.Select the required section with the mouse.

    6.4.1 OIL PRESSURE

    Click to edit thesensor curve. Seesection entitledEditing the sensorcurve.

    Enable or disablethe alarms. Therelevant valuesbelow will appeargreyed outif thealarm is disabled.

    Select thesensor type

    Click and drag tochange the settings

    Type the value or click the up anddown arrows to change the settings

  • 8/7/2019 Configuration Suite Manual

    39/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 39

    6.4.2 COOLANT TEMPERATURE

    6.4.2.1 COOLANT TEMPERATURE ALARMS

    Options Description

    Pre alarm = Pre-alarm is disabled = If the temperature exceeds the tripsetting, an alarm is generated. The temperaturemust fall below the returnsetting to cease the alarm.

    Electrical TripVersion 5.x.x or later

    = Electrical trip is disabled = If the temperature exceeds the tripsetting, an alarm is generated, the load switch isopened and the module enters the cooling timer after which the set is stopped.

    Shutdown If the temperature exceeds the tripsetting, an alarm is generated, the load switch is openedand the set is immediately stopped.

    Click to edit thesensor curve. Seesection entitledEditing the sensorcurve.

    Select thesensor type

    Click and drag tochange the settings

    Type the value or click the up anddown arrows to change the settings

    Enable or disablethe alarms. Therelevant valuesbelow will appeargreyed outif thealarm is disabled.

  • 8/7/2019 Configuration Suite Manual

    40/123

  • 8/7/2019 Configuration Suite Manual

    41/123

  • 8/7/2019 Configuration Suite Manual

    42/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM42

    6.4.4 FLEXIBLE SENSOR

    Click to edit thesensor curve. Seesection entitled

    Editing the sensorcurve.

    Select thesensor type

    Click and drag tochange the settings

    Type the value or click the up anddown arrows to change the settings

    Click to enable ordisable the alarms.The relevant valuesbelow will appeargreyed outif thealarm is disabled.

    Type the text you want to appear on thescreen when the alarm is triggered.

    Version 5.x.x or laterSelect the type ofalarm required.For details of these,see the sectionentitled AlarmTypeselsewhere inthis document.

  • 8/7/2019 Configuration Suite Manual

    43/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 43

    6.4.5 EDITING THE SENSOR CURVES

    While the configuration suiteholds sensor specification for the most commonly used resistive sensors,occasionally it is required that the 7000 Series module be connected to a sensor not listed by theconfiguration suite. To aid this process, a sensor editor has been provided.Deleting custom sensor curves that have been added is performed in the main menu, select Tools | CurveManager.

    In this example, the closest match to the sensor

    in use is the VDO 10-180 fuel level sensor.

    Click to edit thesensor curve.

    Click and drag thepoints on thegraphs to change

    the settings

    Or use the mouseto select the graphpoint, then enter the

    value in the box orclick up/down tochange the value

    Click OK to acceptthe changes andreturn to theconfiguration editor

    Click CANCEL toignore and lose anychanges you havemade

    Click SAVE AS, you are prompted to nameyour curve....

    Click OK to save the curve.

    Any saved curves become selectable in theInput Typeselection list.

    Hint : Deleting, renaming or

    editing custom sensor curvesthat have been added isperformed in the main menu,select Tools | Curve Manager..

  • 8/7/2019 Configuration Suite Manual

    44/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM44

    6.4.6 DIGITAL INPUTS

    The digital inputspage is subdivided into smaller sections.Select the required section with the mouse.

    Input function. See sectionentitled Input functionsfordetails of all available functions

    Example of a user configuredinput

    Closeor open to activate

    Select the type ofalarm required.

    For details of these,see the sectionentitled AlarmTypeselsewhere inthis document.

    Click and drag to changethe setting. This is used togive a delay on acceptanceof the input. Useful for liquidlevel switches or to maskshort term operations of theexternal switch device.

    This is the text thatwill be displayed onthe module screenwhen the alarm istriggered.

    Configures when theinput is active:Never, always, activefrom starting, activefrom the end of thesafety timer

    As this example shows apredefinedfunction,these parameters aregreyed outas they arenot applicable

  • 8/7/2019 Configuration Suite Manual

    45/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 45

    6.4.7 DIGITAL INPUT FUNCTIONS

    Where a digital input is NOT configured as user configured, a selection can be made from a l ist ofpredefined functions. The selections are as follows:

    Under the scope of IEEE 37.2, function numbers can also be used to represent functions in microprocessordevices and software programs. Where the DSE input functions can be represented by IEEE 37.2, the

    function number is listed below.

    = Only applicable to DSE7220 / DSE7320 AMF Modules

    Function Description

    Alarm Mute This input is used to silence the audible alarm from an external source,such as a remote mute switch.

    Alarm Reset This input is used to reset any latched alarms from a remote location. Itis also used to clear any latched warnings which may have occurred (ifconfigured) without having to stop the generator.

    Alt Config 1-3 SelectDSE7300 Series V2.0.0 or aboveonly

    These inputs are used to instruct the DSE7300 Series module to followone of the alternativeconfiguration settings instead of the mainconfiguration settings.

    Auto Restore InhibitIEEE 37.2 - 3 checking or

    interlocking relay

    In the event of a remote start/mains failure, the generator will beinstructed to start and take load. On removal of the remote start

    signal/mains return the module will continue to run the generator onload until the Auto Restore Inhibitinput is removed. This input allowsthe controller to be fitted as part of a system where the restoration tomains is controlled remotely or by an automated system.

    Auto start InhibitIEEE 37.2 - 3 checking orinterlocking relay

    This input is used to provide an over-ride function to prevent thecontroller from starting the generator in the event of a remotestart/mains out of limits condition occurring. If this input is active and aremote start signal/mains failure occurs the module will not give a startcommand to the generator. If this input signal is then removed, thecontroller will operate as if a remote start/mains failure has occurred,starting and loading the generator. This function can be used to give anAND function so that a generator will only be called to start if themains fails and another condition exists which requires the generator torun. If the Auto start Inhibit signal becomes active once more it will be

    ignored until the module has returned the mains supply on load andshutdown.This input does not prevent starting of the engine in MANUAL or TESTmodes.

    Auxiliary Mains Fail The module will monitor the incoming single or three phase supply forOver voltage, Under Voltage, Over Frequency or Under frequency. Itmay be required to monitor a different mains supply or some aspect ofthe incoming mains not monitored by the controller. If the devicesproviding this additional monitoring are connected to operate this input,the controller will operate as if the incoming mains supply has fallenoutside of limits, the generator will be instructed to start and take theload. Removal of the input signal will cause the module to act if themains has returned to within limits providing that the mains sensing alsoindicates that the mains is within limits.

    Coolant Temperature Highswitch This input is used to give a Coolant Temperature High shutdown from adigital normally open or closed switch. It allows coolant temperatureprotection using the switch and the analogue input can be used inparallel to give protection or configured to be used for indication only.

    Droop enable This input is used to switch the engine into droop mode on CANengines that support this function.

    Dual Mutual StandbyDSE7000 Series V2.0.0 or aboveonly

    This input provides interface to another DSE7000 Series module toachieve Dual Mutual or Dual Mutual Standby functionality.This is described fully in the section entitled Moduleelsewhere in thismanual.

  • 8/7/2019 Configuration Suite Manual

    46/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM46

    Function Description

    EJP1DSE7000 Series V2.0.0 or aboveonly

    For the French EJP (Effacement Jours de Pointe) tarrif system.

    This input is functionally identical to Remote Start Off Load.If this input is active, operation will be similar to the Remote Start onload function except that the generator will not be instructed to take theload. This function can be used where an engine only run is requirede.g. for exercise.

    EJP2DSE7000 Series V2.0.0 or aboveonly

    For the French EJP (Effacement Jours de Pointe) tarrif system.

    This input is functionally identical to Remote Start On Load.

    When in auto mode, the module will perform the start sequence andtransfer load to the generator.If in Manual mode, the load will be transferred to the generator if theengine is already running, however in manual mode, this input will notgenerate start/stop requests of the engine.

    Generator Closed AuxiliaryIEEE 37.2 - 3 Checking orinterlocking relay

    This input is used to provide feedback to allow the 7xxx to give trueindication of the contactor or circuit breaker switching status. It shouldbe connected to the generator load switching device auxiliary contact.

    Action:

    Warning (Alarm only, No shutdown)Generator Load InhibitIEEE 37.2 - 52 AC circuit breaker

    This input is used to prevent the 7xxx from loading the generator. If thegenerator is already on load, activating this input will cause the 7xxx tounload the generator. Removing the input will allow the generator to beloaded again.

    NOTE: -This input only operates to control the generator-switching device if the 7xxx load switching logic is attempting toload the generator. It will not control the generator-switchingdevice when the mains supply is on load.

    Inhibit scheduled runIEEE 37.2 - 3 checking orinterlocking relay

    This input is used to provide a means of disabling a scheduled run.

    Lamp Test This input is used to provide a test facility for the front panel indicatorsfitted to the 7xxx module. When the input is activated all LEDs shouldilluminate.

    Main Config SelectDSE7300 Series V2.0.0 or aboveonly

    This input is used to select the Mainconfiguration when Alternativeconfigurations are enabled.

    Mains closed AuxiliaryIEEE 37.2 - 3 Checking orinterlocking relay

    This input is used to provide feedback to allow the 7x20 to give trueindication of the contactor or circuit breaker switching status. It shouldbe connected to the mains load switching device auxiliary contact.Incorrect application of this signal does not trigger an alarm condition, itis used solely for indication of the breaker status.

    Mains Load InhibitIEEE 37.2 - 3 checking orinterlocking relay

    This input is used to prevent the 7x20 from loading the mains supply. Ifthe mains supply is already on load activating this input will cause the7x20 to unload the mains supply. Removing the input will allow themains to be loaded again.

    NOTE: -This input only operates to control the mainsswitching device if the 7x20 load switching logic is attempting toload the mains. It will not control the mains switching device whenthe generator is on load.

    Manual Restore contactIEEE 37.2 - 3 checking orinterlocking relay

    Used to hold off transfer back to the mains after a mains failure andkeep the generator on load. Transfer back to the mains supply is heldoff in Auto modewhile the input is present. Typically, a key switchprovides this input with spring return to closedfunctionality.

    Oil Pressure Switch A digital normally open or closed oil pressure switch gives this input. Itallows oil pressure protection using the switch and the analogue input tobe used in parallel to give protection or to be used for oil pressureindication only.

  • 8/7/2019 Configuration Suite Manual

    47/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 47

    Function Description

    Panel Lock This input is used to provide security to the installation. If the ExternalPanel lock input is active, the module will not respond to operation ofthe Mode select or start buttons. This allows the module to be placedinto a specific mode (such as Auto) and then secured. The operation ofthe module is not affected and the operator will still be able to view thevarious instrumentation pages etc. (Front panel configuration access isstill possible while the system lock is active).

    NOTE: - External control sources (i.e. Simulate Start Button)are not affected by the external panel lock input and will continueto operate normally.

    Protection Disabled The system designer provides this switch (not DSE) so its location willvary depending upon manufacturer, however it normally takes the formof a key operated switch to prevent inadvertent activation. Dependingupon configuration, a warning alarm may be generated when the switchis operated.When active, and the module is suitably configured (see section entitledApplication) this prevents the engine being stopped upon critical alarm

    (Sometimes called War Mode or Run to Destruction)Remote Start off load If this input is active, operation will be similar to the Remote Start on

    load function except that the generator will not be instructed to take theload. This function can be used where an engine only run is requirede.g. for exercise.

    Remote Start on load When in auto mode, the module will perform the start sequence andtransfer load to the generator.In Manual mode, the load will be transferred to the generator if theengine is already running, however in manual mode, this input will notgenerate start/stop requests of the engine.

    Simulate Auto mode button

    NOTE:NOTE:NOTE:NOTE: ---- If a call to start is present when AUTO MODE is entered,the starting sequence will begin. Call to Start can come from a numberof sources depending upon module type and configuration and includes

    (but is not limited to) : Remote start input present, Mains failure,Scheduled run, Auxiliary mains failure input present, Telemetry startsignal from remote locations.

    This input mimics the operation of the Auto button and is used toprovide a remotely located Auto mode push button.

    Simulate Lamp test button This input is used to provide a test facility for the front panel indicatorsfitted to the module. When the input is activated all LEDs shouldilluminate. The input also serves a second function, in that it alsoprovides a mute signal to silence the audible alarm. The input isrecognised by the module as though it was the Push button on themodule itself being operated.

    Simulate Mains available This function is provided to override the modules internal monitoringfunction. If this input is active, the module will not respond to the state of

    the incoming AC mains supply.Simulate Manual Button This input mimics the operation of the Manual button and is used to

    provide a remotely located Manual mode push button.

    Simulate Start Button This input mimics the operation of the Start button and is used toprovide a remotely located start push button.

    Simulate Stop Button This input mimics the operation of the Stop button and is used toprovide a remotely located stop/reset push button.

    Simulate Test on load button This input mimics the operation of the Test button and is used toprovide a remotely located Test on load mode push button.

  • 8/7/2019 Configuration Suite Manual

    48/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM48

    Function Description

    Smoke limitIEEE 37.2 18 accelerating ordecelerating device

    This input instructs the module to give a run at idle speedcommand tothe engine either via an output configured to smoke limitor by datacommands when used with supported electronic engines.

    Stop and Panel LockDSE7300 Series V2.0.0 or aboveonly

    Combined function input that instructs the module to enter STOPMODE and also perform the Panel Lockfunction.Once the input is active, the module will not respond to operation of the

    Mode select or start buttons.

    The operator will still be able to view the various instrumentation pagesetc. (Front panel configuration access is still possible while the systemlock is active).

    Transfer to Mains/ OpenGeneratorIEEE 37.2 - 52 AC circuit breaker

    This input is used to transfer the load to the mains supply (AMFmodule) when running in MANUAL MODE or provide the OpenGenerator signal in a non AMF Module.)

    Transfer to generator/OpenMainsIEEE 37.2 - 52 AC circuit breaker

    This input is used to transfer the load to the generator when running inMANUAL MODE

  • 8/7/2019 Configuration Suite Manual

    49/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 49

    6.5 OUTPUTS

    6.5.1 DIGITAL OUTPUTS

    6.5.2 VIRTUAL LEDS

    Select if the relay is toenergiseor de-energiseupon activation of thesource

    Select what theoutput is to beused to control

    These labelsmatch thetypical wiringdiagram

    These are greyed out asthey are fixed, notadjustableunless a CANengine has beenselected

    Allows configuration ofstatus items.These items are notavailable for viewing on themodule itself but can beseen in the SCADA sectionof the PC software, or readby third party systems (ieBMS or PLCs) using theModbus protocol.

  • 8/7/2019 Configuration Suite Manual

    50/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM50

    6.5.3 CONTROL LOGIC

    Allows additional flexibility of output configuration by combining sources to create a new one.Three User Defined Controls are available that can be selected in the output source list for LEDs, Relayoutputs or virtual LEDs.

    Imagine the schematic like a simple circuit with a battery and a bulb.

    There are two switches (Output sources) in parallel to provide an OR function and one switch (Output source)in series to provide an AND function.When the conditions are satisfied, the bulb will illuminate (The User Defined Controlwill activate).

    Control blocks are processed in order (block 1, block 2 then block 3). This sequence repeats every 100mS.Careless setting of a control logic block can cause toggling of an output at a rate of 100mS on/off. This mayshorten the life and/or cause damage to externally connected slave relays or other connected equipment.

    6.5.3.1 EXAMPLE USING BOTH OR & AND FUNCTIONS

    Detailed description

    IF ( Battery High Voltagealarm is active OR the Battery Low Voltage alarmis active ) AND the module is inAuto ModeTHEN the User Defined Control 1 is activated. Any output or LCD indicator configured to UserDefined Control 1 will operate.

    An output configured to UserDefined Control 1 will activatewhen the module is in AutoModeAND when either BatteryHigh VoltageORBattery LowVoltagealarms are active

  • 8/7/2019 Configuration Suite Manual

    51/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 51

    6.5.3.2 EXAMPLE OF A LATCHED OUPUT

    This example can only be achieved with module versions 5.x.x or higher. Modules before V5.x.x will not allowthe selection of User Defined Control as an input into the logic.

    This uses a loop around to create a latched output, reset when Digital Input A is activated.

    Detailed description

    A warning alarmwill cause User Defined Control 1 to become active if Digital Input A is not active.Subsequent resetting of the common warning(warningalarms are self resetting) will keep User DefinedControl 1 active due to the loop around. The latch is reset by activating Digital Input A momentarily.

    6.5.3.3 EXAMPLE USING OR FUNCTIONS ONLY

    The AND function must be permanently active to use only the OR function. This is achieved by setting theAND condition to Not Used, Inactive.

    Detailed description

    IFAlternative config 1 is selectedOR Alternative config 2 is selectedTHEN the User Defined Control 2isactivated. Any output or LCD indicator configured to User Defined Control 2will operate.

    An output configured to UserDefined Control 2will activatewhen Alternative Config 1 OR 2is selected

    An output configured to UserDefined Control 1 will activatewhen A Common AlarmoccursOR User defined control1 isactive so long as Digital Input Ais inactive

  • 8/7/2019 Configuration Suite Manual

    52/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM52

    6.5.3.4 EXAMPLE USING AND FUNCTION ONLY

    To use the AND function only, set either one of the OR functions to Not used, Activeso that it will bepermanently open.

    Detailed description

    IFDigital Input A Is active AND Digital Input Bis active, THEN the User Defined Control 2is activated. Anyoutput or LCD indicator configured to User Defined Control 2will operate.

    An output configured to UserDefined Control 3will activatewhen Digital Input A AND Bisselected

  • 8/7/2019 Configuration Suite Manual

    53/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 53

    6.5.4 OUTPUT SOURCES

    The list of output sources available for configuration of the module relay outputs also applies to the LEDconfiguration and expansion relay outputs (7300 series only).

    Under the scope of IEEE 37.2, function numbers can also be used to represent functions in microprocessor

    devices and software programs. Where the DSE output functions can be represented by IEEE 37.2, thefunction number is listed below.

    = Only available on DSE7220 / DSE7320 AMF Modules

    Output source Activates Is not active.

    Not Used The output will not change state (Unused)

    Air Flap Relay Normally used to control an air flap, thisoutput becomes active upon an Emergency

    Stop or Over-speed situation.

    Inactive when the set has come to rest

    Arm Safety On Alarms Becomes active at the end of the safetydelaytimer whereupon all alarms configuredto From Safety On become active

    Inactive when : When the set is at rest

    In the starting sequence before theSafety Delay timer has expired

    Audible AlarmIEEE 37.2 74 alarm relay

    This output indicates that the internalsounder is operating to allow it to feed anexternal sounder. Operation of the Mutepushbutton will reset this output onceactivated.

    Inactive if the internal sounder is notoperating.

    Battery Over VoltageIEEE 37.2 59DC overvoltage relay

    This output indicates that a Battery Overvoltage alarm has occurred.

    Inactive when battery voltage is not High

    Battery Under VoltageIEEE 37.2 27DC undervoltage relay

    This output indicates that a Battery UnderVoltage alarm has occurred.

    Inactive when battery voltage is not Low

    CAN Data Fail Becomes active when no CAN data isreceived from the ECU after the safetydelay timer has expired

    Inactive when: CAN data is being received The set is at rest

    During the starting sequencebefore the safety delay timer hasexpired

    CAN ECU Warning The engine ECU has indicated that aWarning alarm is present.

    Inactive when no Warning alarm fromthe ECU is present

    CAN ECU Shutdown The engine ECU has indicated that aShutdown alarm is present.

    Inactive when no Shutdown alarm fromthe ECU is present

    CAN ECU Power Used to switch an external relay to power the CAN ECU. Exact timing of this output isdependent upon the type of the engine ECU

    CAN ECU Stop Active when the DSE controller is requesting that the CAN ECU stops the engine.

    Charge Alternator Failure(Shutdown or warning)

    Indicates that there is a charging fault withthe auxiliary charging alternator

    When the set is at rest During the starting sequence

    before the safety delay timer hasexpired

    Close GeneratorIEEE 37.2 52 ac circuit breaker

    Used to control the load switching device.Whenever the 7xxx module selects thegenerator to be on load this control sourcewill be active.

    Inactive whenever the generator is notrequired to be on load

    Close Generator PulseIEEE 37.2 52 ac circuit breaker

    Used to control the load switching device. Whenever the 7xxx module selects thegenerator to be on load this control source will be active for the duration of the BreakerClose Pulse timer, after which it will become inactive again.

    The outputs are in alphabeticalorder with the parameterfirst. Forinstance for overspeed output, its

    listed as Engine Overspeed.

  • 8/7/2019 Configuration Suite Manual

    54/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM54

    Output source Activates Is not active.

    Close MainsIEEE 37.2 52 ac circuit breaker

    Used to control the load switching device.Whenever the 7xxx module selects the mains tobe on load this control source will be active.

    The output is inactive wheneverthe mains is not required to be onload

    Close Mains PulseIEEE 37.2 52 ac circuit breaker

    Used to control the load switching device. Whenever the 7xxx module selects themains to be on load this control source will be active for the duration of the BreakerClose Pulse timer, after which it will become inactive again.

    Combined Mains Failure Active when the mains supply is out of limits OR the input for Auxiliary Mains Failure isactive

    Combined Under andOverfrequency shutdown

    Active when the generator is shutdown due to either under OR overfrequency

    Combined Under andOverfrequency warning

    Active when the generator alarm for either under OR overfrequency is active

    Combined Under and Overvoltageshutdown

    Active when the generator is shutdown due to either under OR overvoltage

    Combined Under and Overvoltagewarning

    Active when the generator alarm for either under OR overvoltage is active

    Common Alarm Active when one or more alarms (of any type) areactive

    The output is inactive when noalarms are present

    Common Electrical Trip Active when one or more E lectrical tripalarmsare active

    The output is inactive when noelectrical alarms are present

    Common Shutdown Active when one or more Shutdownalarms areactive

    The output is inactive when noshutdown alarms are present

    Common Warning Active when one or more Warningalarms areactive

    The output is inactive when nowarning alarms are present

    Coolant Cooler ControlDSE7000 Series V2.0.0 or above only

    Activated by the Coolant Cooler Control in conjunction with the Coolant TemperatureSensor.

    Coolant Heater ControlDSE7000 Series V2.0.0 or above only

    Activated by the Coolant Heater Control in conjunction with the Coolant TemperatureSensor.

    Coolant Temperature HighShutdown

    Active when the Coolant Temperatureexceeds the High Coolant TemperatureShutdownsetting

    Coolant Temperature HighWarning

    Active when the Coolant Temperatureexceeds the High Coolant Temperature Warningsetting

    Coolant Temperature Low Active when the Coolant Temperaturefalls below the Low Coolant Temperature alarmsetting

    Cooling Down Active when the Cooling timer is in progress The output is inactive at all other

    timesDigital Input A - H Active when the digital input is active Inactive when :

    If the input is not active

    If the input is active butconditioned by activation delay,safety timeror Armingrequirements.

    Dummy Load Control (1-5) Becomes active when the engine kW fallsbelow the Dummy Load Control Trip Setting.

    Inactive when the engine kW returnsto above the Dummy Load ControlReturn setting.

    Droop Enable Becomes active when an input configured to Droop enableis active or if Droop Enablehas been activated in the module configuration (CAN engine only)

    Dual Mutual StandbyDSE7000 Series V2.0.0 or above only

    This output provides interface to another DSE7000 Series module to achieve DualMutual or Dual Mutual Standby functionality.This is described fully in the section entitled Module elsewhere in this manual.

    Earth Fault Trip alarmDSE7300 Series V2.0.0 or above only

    Indicates that an earth fault alarm is active.

    EJP1 / EJP2 Indicates that an input configured to EJP1 or EJP2 is active

    Emergency Stop Active when the Emergency Stop input has been activated

    Engine Over Speed ShutdownIEEE 37.2 12 overspeed device

    Active if the engine speed exceeds the Over Speed Shutdownsetting

    Engine Over Speed WarningIEEE 37.2 12 overspeed device

    Active if the engine speed exceeds the Over Speed Warningsetting

    Engine Under Speed ShutdownIEEE 37.2 - 14 underspeed relay

    Active when the engine speed falls below the Underspeed Shutdown setting

    Engine Under Speed WarningIEEE 37.2 - 14 underspeed relay

    Active when the engine speed falls below the Underspeed Warning setting

    Energise to Stop Normally used to control an Energise to Stopsolenoid, this output becomes active whenthe controller wants the set to stop running.

    Becomes inactive a configurableamount of time after the set hasstopped. This is the ETS hold time.

  • 8/7/2019 Configuration Suite Manual

    55/123

    DSE7000 Series configuration suite

    DSE7000 Series configuration suite 057-077 ISSUE 7 AM 55

    Output source Activates Is not active.

    Fail to Stop If the set is still running a configurable amount of time after it has been given thestop command, the output will become active. This is the Fail to stoptimer.

    Fail to Start Becomes active if the set is not seen to be running after the configurable numberof start attempts.

    Fan Control Energises when the engine becomes available (up to speed and volts). Thisoutput is designed to control an external cooling fan.When the engine stops, the cooling fan will remain running for the duration of the

    Fan Overrun Delay.Fuel Level LowIEEE 37.2 71 level switch

    Active when the Fuel Level falls below the Fuel Level Lowsetting

    Fuel Pump ControlIEEE 37.2 71 level switch

    Becomes active when the Fuel levelfalls below the Fuel Pump Control ONsetting and is normally used totransfer fuel from the bulk tank to theday tank.

    If the output is already active it willbecome inactive when the Fuel levelisabove the Fuel Pump Control OFFsettings.

    Fuel Relay Becomes active when the controllerrequires the governor/fuel system tobe active.

    Becomes inactive whenever the setshould be stopped, including betweencrank attempts, upon controlled stopsand upon fault shutdowns.

    Gas Choke On Becomes active during starting for theduration of the Gas Choke timer.Normally used to choke a gas engine.

    Inactive at all other times

    Gas Ignition Becomes active during starting. Becomes inactive a configurable

    amount of time after the fuel relaybecomes inactive. This is the Gasignition offtimer.

    Generator Available Becomes active when the generator isavailable to take load.

    Inactive when

    Loading voltageand loadingfrequencyhave not been reached

    After electrical tripalarm During the starting sequence

    before the end of the warmingtimer.

    Generator Closed Aux Active when the Generator closed auxiliaryinput is active

    Gen Combined Under and OverFrequency ShutdownIEEE 37.2 - 81 frequency relay

    Active when either an under frequencyor over frequency shutdown has beenactivated.

    The output is inactive when thegenerator supply is healthy

    Gen Combined Under and Over

    Frequency WarningIEEE 37.2 - 81 frequency relay

    Active when either a generator underfrequency or over frequency warninghas been activated.

    The output is inactive when thegenerator supply is healthy

    Gen Combined Under and Over VoltageShutdownIEEE 37.2 27AC undervoltage relayIEEE 37.2 59AC overvoltage relay

    Active when either a generator undervoltage or over voltage shutdown hasbeen activated.

    The output is inactive when thegenerator supply is healthy

    Gen Combined Under and Over VoltageWarningIEEE 37.2 27AC undervoltage relayIEEE 37.2 59AC overvoltage relay

    Active when either a generator undervoltage or over voltage warning hasbeen activated.

    The output is inactive when thegenerator supply is healthy

    Generator Earth Fault Active when the Generator earth faultalarm has been triggered by excess earthcurrent.

    Generator ExciteIEEE 37.2 31 separate excitation device

    Used to control the excitation of themain alternator (AC).

    Becomes inactive when the set isstopped.

    Gen Over Current IDMTAlarm

    IEEE 37.2 51 ac time overcurrent relay

    Active when an overcurrent condition has caused the Overcurrent IDMTalarm totrigger

    Gen Over Current Immediate WarningIEEE 37.2 50 instantaneous overcurrentrelay

    Active when an overcurrent condition exceeds the Overcurrent alarm Tripsetting. At the same time, the controller begins following the IDMT curve. If theoverload condition exists for an excess time, the Overcurrent IDMTalarm willactivate.

    Generator Over Voltage ShutdownIEEE 37.2 59AC overvoltage relay

    Active when the generator voltage exceeds the High Voltage Shutdown setting

    Generator Over Voltage WarningIEEE 37.2 59AC overvoltage relay

    Active when the generator voltage exceeds the High Voltage Warning setting

    Generator Under Voltage ShutdownIEEE 37.2 27AC undervoltage relay

    Active when the generator voltagefalls below the Low Voltage Shutdown

    Inactive when

    The set is stopped During starting sequence before

    the safety delay time has expired.

    Generator Under Voltage WarningIEEE 37.2 27AC undervoltage relay

    Active when the generator voltagefalls below the Low Voltage Warningsetting

    Inactive when

    The set is stopped During starting sequence before

    the safety delay time has expired.

  • 8/7/2019 Configuration Suite Manual