Conditional Based Maintenance with On-line Partial Discharge Measurements of HV and MV Switchgear Systems Presented by J.J. Smit R.G.A. Zoetmulder, S. Meijer and J.J. Smit Question number 8
6

Conditional Based Maintenance with On- line Partial Discharge Measurements of HV and MV Switchgear Systems Presented by J.J. Smit R.G.A. Zoetmulder, S.

Jan 04, 2016

Download

Documents

Edmund Briggs
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Conditional Based Maintenance with On- line Partial Discharge Measurements of HV and MV Switchgear Systems Presented by J.J. Smit R.G.A. Zoetmulder, S.

Conditional Based Maintenance with On-line Partial Discharge Measurements of HV

and MV Switchgear Systems

Presented by J.J. Smit

R.G.A. Zoetmulder, S. Meijer and J.J. Smit

Question number 8

Page 2: Conditional Based Maintenance with On- line Partial Discharge Measurements of HV and MV Switchgear Systems Presented by J.J. Smit R.G.A. Zoetmulder, S.

Introduction and GoalInsulation test:1: Detection2: Defect identification3: Defect localization4: Risk assessment

Goal:

- Medium Voltage Gas Insulated Systems (MV-GIS) - Medium Voltage Air Insulated Systems (MV-AIS)- Medium Voltage Oil Insulated Systems (MV-OIS)

To apply the UHF measuring technique used for High Voltage Switchgear (HV GIS) also for :

Page 3: Conditional Based Maintenance with On- line Partial Discharge Measurements of HV and MV Switchgear Systems Presented by J.J. Smit R.G.A. Zoetmulder, S.

The measuring system

• Broadband detection > UHF (till several GHz)

• With this method noises can be suppressed by measuring at a frequency band with a low noise-level

* Hard-ware

Components:1 a: Internal UHF coupler1 b: external UHF coupler2 : Pre-amplifier3 : Spectrum analyzer4 : Computer

Page 4: Conditional Based Maintenance with On- line Partial Discharge Measurements of HV and MV Switchgear Systems Presented by J.J. Smit R.G.A. Zoetmulder, S.

10 kV Air Insulated Switchgear system-1- 10 kV Air Insulated

- Vacuum Circuit-Breaker

- Measuring locations are small inspection windows

- UHF signals can propagate through these inspection windows and can than be detected

Front-side Back-side

Advanced stadium(More affected)

Begin stadium

(less affected)

Surface discharge at one of the phase connectors of the circuit-breaker

Page 5: Conditional Based Maintenance with On- line Partial Discharge Measurements of HV and MV Switchgear Systems Presented by J.J. Smit R.G.A. Zoetmulder, S.

10 kV Air Insulated Switchgear system-2

Page 6: Conditional Based Maintenance with On- line Partial Discharge Measurements of HV and MV Switchgear Systems Presented by J.J. Smit R.G.A. Zoetmulder, S.

Conclusions

Measurements with the external UHF coupler are applicable to medium voltage switchgear installations, e.g. air insulated switchgear, as well as to HV switchgear systems.

Using advanced PD analysis techniques distinction can be made between the different patterns detected by the external UHF coupler.

UHF PD measurements can contribute to CBM procedures.

With UHF PD measurements one can also determine the position of system design errors, which then can be corrected.