COMSOFT GmbH | NetTEST II | June 2009 | Page 1 Professional Test Tool for PROFIBUS DP Networks NetTEST II PROFIBUS Analysis and Test Tool
Mar 29, 2015
COMSOFT GmbH | NetTEST II | June 2009 | Page 1
Professional Test Tool
for PROFIBUS DP Networks
NetTEST II
PROFIBUS Analysis
and Test Tool
COMSOFT GmbH | NetTEST II | June 2009 | Page 2
NetTEST II with Online-Function for the use with NetTEST II with Online-Function for the use with operational PROFIBUS networks operational PROFIBUS networks
NetTEST II with DP-Mono-Master functionNetTEST II with DP-Mono-Master functionfor DP-Slave configuration for DP-Slave configuration
NetTEST II Basis System for performing NetTEST II Basis System for performing physical measurementsphysical measurements
NetTEST – available in three versionsNetTEST – available in three versions
COMSOFT GmbH | NetTEST II | June 2009 | Page 3
95% of all problems in PROFIBUS DP networks are caused by incorrect
installations. Installation errors enormously increase interference
susceptibility, whether it is a missing terminator or a broken shield. This
results in sporadic non-reproducible errors which can be caused for
example by an increased EMC-load. Trouble shooting can cost days or
even weeks.
NetTEST II checks your PROFIBUS DP networks in detail and detects
most typical installation problems.
Find out for yourself that NetTEST II proves to be a powerful tool for
eliminating PROFIBUS problems.
CostsCosts
Stop of delay
Stop of delayInterru
ption
Interruption
Standstill of
Standstill of
DelaysDelays
NetTEST II checks your PROFIBUS DP networkNetTEST II checks your PROFIBUS DP network
COMSOFT GmbH | NetTEST II | June 2009 | Page 4
Graphical 128 x 64 Pixels LCD-Display with background illumination
Power supply via a rechargeable battery pack
Battery capacity for approximately 4 hours of operation
9-pole SUB-D gender changer for connection to PC and PROFIBUS
6 x 4 - Keyboard
Complete transport case with international battery charging set incl. power supply, additional battery, power supply adapter, PROFIBUS configuration tool and various adapter cables for PC and PROFIBUS
NetTEST NetTEST – a flexible system for mobile operation– a flexible system for mobile operation
COMSOFT GmbH | NetTEST II | June 2009 | Page 5
Determines the
Impedance
Cable Length
as well as the
of the connected PROFIBUS line
Detailed measurements on physical levelDetailed measurements on physical level
COMSOFT GmbH | NetTEST II | June 2009 | Page 6
Disruption of strand A, strand B and shield (with distance measured in m)
Correct terminating resistor (number and value)390
220
390
5 V
Non-powered terminating resistors390
220
390
Branches (with distance measured in m)
Inhomogeneous line segments (with distance measured in m)
Short circuits (with distance measured in m)
Switched pairs of strands
Detection of the most typical installation problemsDetection of the most typical installation problems
COMSOFT GmbH | NetTEST II | June 2009 | Page 7
Display of Live List of DP Slaves
Display of Ident-Numbers of DP Slaves
Signal Quality of DP Slaves
Baud Rate Detection und Signal Quality at Running Systems
Helpful analysis functions for superior error detectionHelpful analysis functions for superior error detection
COMSOFT GmbH | NetTEST II | June 2009 | Page 8
Generation, display and storage of up to 20 test reports
Management and archiving of the test reports via connected PC or notebook
Communication from PC to NetTEST II via COM-interface und standard-terminal-software (e.g.Hyperterminal). No special software is required.
NetTEST IINetTEST II –– logs logs && archives your measurements archives your measurements
COMSOFT GmbH | NetTEST II | June 2009 | Page 9
Analysis of the tested PROFIBUS segment at one glance. All requirements of modern quality systems are met:
Evidence of Functionality Archiving Traceability Reproducibility
************************************************Resulting protocol for PROFIBUS network************************************************Test companyName: COMSOFT GmbHStreet: Wachhausstr. 5aCity : 76227 KarlsruhePhone: +49 721/9497-290E-mail : [email protected] name : Kurpat************************************************CustomerName : Customer 1 Street:City: Phone:E-mail:***********************************************Unit: Area 1Name: Segment 1PROFIBUS address: 001Number of 12 Mbit/s-conns in seg.: 000Number of PROFIBUS devices in seg.: 002Baud rate: 1.5 MbaudSlot time: 000300Date: 15/11/07Time: 10:54:21***********************************************Analysis result for test with no terminationAnalysis result: No fault!*****************************************Irregularity A<->B not detectableIrregularity B<->Shield not detectableIrregularity A<->Shield not detectableCapacitive load junction orImpedance changes not detectableBroken line not detectableCabling okImpedance app. 133 ohmsCable length app. 26m
*********************************************************Analysis result for test with 1 terminationAnalysis result: No fault!****************************************Irregularity B<->Shield not detectableIrregularity A<->Shield not detectableCorrect terminationNumber of retries: 3*********************************************************Analysation result for Test with 2 term.Analyzation result: No fault!****************************************Irregularity B<->Shield not detectableIrregularity A<->Shield not detectableCorrect terminationNumber of retries: 1*********************************************************Detected slaves in the segmentPB address Level Status Ident. [Name]----------------------------------------------------------------002 4.3V OK 0xAAAA003 4.9V OK 0xF013004 5.4V OK 0x7510005 4.6V OK 0xAAAB006 4.3V OK 0x00C4007 4.7V OK 0x000C008 5.0V OK 0x9510009 5.7V OK 0x00C4010 5.8V OK 0x00C4011 5.8V OK 0x00C4012 5.1V OK 0xAAAA013 4.9V OK 0x00DD098 5.1V OK 0x9510099 5.1V OK 0x9510125 5.7V OK 0x0000Expected value for level measurement: 2.5V<x<7.2V*********************************************************PROFIBUS Baud rate detectionBaud rate: 1.5 MbaudLevel: 6.0V Status: OKExpected value for level measurement: 2.5V<x<7.2V*********************************************************End of protocolUser name Customer____________ __________
NetTEST IINetTEST II Measurement Report Measurement Report
COMSOFT GmbH | NetTEST II | June 2009 | Page 10
Performing the Measurement Performing the Measurement
COMSOFT GmbH | NetTEST II | June 2009 | Page 11
Strand A* Terminating resistor 1*Strand B* Terminating resistor 2*Shield* DP Master and DP Slaves*
0 V
+5 V
390
220
390
Terminating Resistor
0 V
+5 V
390
220
390
Terminating Resistor
Shield
A
B
Drives Gateways Field DeviceMaster
Typical PROFIBUS DP RS485 segmentTypical PROFIBUS DP RS485 segment
COMSOFT GmbH | NetTEST II | June 2009 | Page 12
0 V
+5 V
390
220
390
TerminatingResistor
NetTEST II is connected instead of the DP Master
at either one of the two bus ends
Shield
DP Slaves can be left connected to the bus in online mode
B
A
Drives Gateways Field DeviceMaster
Connection with the PROFIBUSConnection with the PROFIBUS
0 V
+5 V
390
220
390
TerminatingResistor
COMSOFT GmbH | NetTEST II | June 2009 | Page 13
1. without terminating resistors
2. with one terminating resistors
3. with both terminating resistors
0 V
+5 V
390
220
390
TerminatingResistor
A
Shield
B
Drives Gateways Field Device
During the measurement procedure NetTEST II requests the user to switch on and off the respective terminating resistors
Performing a 3-stage test Performing a 3-stage test
0 V
+5 V
390
220
390
TerminatingResistor
COMSOFT GmbH | NetTEST II | June 2009 | Page 14
PROFIBUS address
System Baud rate
Slot time
Number of 12 Mbit/s plugs used
Number of devices connected to the bus
Simple & quick adaptation to the DP segmentSimple & quick adaptation to the DP segment
COMSOFT GmbH | NetTEST II | June 2009 | Page 15
The physical measurement of the PROFIBUS line is only carried out within electrical segments, without including repeaters.
The minimum length of line to be measured is 10 m. The shorter the line lengths, the more inexactly the measurement may become.
Only active stations (Masters) have to be disconnected from the bus, slaves may stay connected.
NetTEST II is designed for standard PROFIBUS cable type A(150 Ohm surge impedance, core cross section >0,34 mm²). Different types of cables, e.g. obsolete cable type B(100 Ohm surge impedance) are not to be used and are recognized as faulty by NetTEST II.
StartStart
Useful information for physical measurementsUseful information for physical measurements
COMSOFT GmbH | NetTEST II | June 2009 | Page 16
Setting into operation of DP Slaves without time-consuming implementation of an SPS
Configuration of DP Slaves via comfortable PC tool on the basis of GSD file and integrated download function
Comfortable access to the I/O-Data of DP Slaves via freely definable tags
Display and coding of DP Slave diagnostic data
NetTEST II with DP Master functionNetTEST II with DP Master function
COMSOFT GmbH | NetTEST II | June 2009 | Page 17
The COMSOFT PROFIBUS Configurator supplies NetTEST II with the DP Slave configuration
NetTEST II –NetTEST II – Trouble-free & c Trouble-free & comfortableomfortable
COMSOFT GmbH | NetTEST II | June 2009 | Page 18
StartStart
Changing all DP Slave parameters
Execution of single PROFIBUS DP services
Simple DP Slave start-up – not just for PROFIBUS experts
Direct access to selective I/O-Data, e.g. digital outputs
NetTEST II –NetTEST II – Multi-Talent as DP MasterMulti-Talent as DP Master
COMSOFT GmbH | NetTEST II | June 2009 | Page 19
NetTEST II was enhanced by very powerful
online measurement functions which even on
the operative PROFIBUS give detailed
information about existing installation
problems.
NetTEST II with Online Function up to 12 Mbit/sNetTEST II with Online Function up to 12 Mbit/s
COMSOFT GmbH | NetTEST II | June 2009 | Page 20
Drives Gateways Field Devices
Master
Measurements on the operative busMeasurements on the operative bus
COMSOFT GmbH | NetTEST II | June 2009 | Page 21
Baud rate detection Generate live list Rotation time Signal level measurement Signal level summary list Event log Event count Diagnostic event
The following measurements can be conducted in online mode:
Measurements with PLCMeasurements with PLC
COMSOFT GmbH | NetTEST II | June 2009 | Page 22
During this Baud rate scan the overall signal quality at the PROFIBUS is measured and a status is indicated.
Baud rate detectionBaud rate detection
COMSOFT GmbH | NetTEST II | June 2009 | Page 23
Current Slave Live List
NetTEST II analyses the bus traffic and generates a Live List of all active and passive bus subscribers broken down by Masters and Slaves.
Current Master Live List
Generating a Live ListGenerating a Live List
COMSOFT GmbH | NetTEST II | June 2009 | Page 24
NetTEST II determines the time the DP Master needs in order to poll all configured DP Slaves.
The minimum and maximum values are stored and indicated.
Rotation time is an explicit indicator for performance problems, e.g. in a sporadically disfunctional PROFIBUS network
Roatation TimeRoatation Time
COMSOFT GmbH | NetTEST II | June 2009 | Page 25
NetTEST II measures the signal quality of each DP Slave and visualises the value in a bar graph.
Discrepancies of the measured signal levels from the allowed range point to specific errors of the PROFIBUS network, e.g. signal levels above the allowed maximum are typical for reflexions in the PROFIBUS network.
Level MeasurementLevel Measurement
COMSOFT GmbH | NetTEST II | June 2009 | Page 26
In the signal level sum list, the result of the signal level measurement is indicated in form of a table:
- ADD – Participant address
- COUNT – Number of measurements (excl. Time-outs)
- MIN – Minimum Values
- AV – Average Values
- MAX – Maximum Values
Signal level sum listSignal level sum list
COMSOFT GmbH | NetTEST II | June 2009 | Page 27
NetTEST II analyses the data traffic between DP Master and DP Slaves and triggers upon communication status changes. The event log is represented in form of a table:
- ADD – DP Slave address
- DATA OK – DP Slave is in status of data exchange
- DATA NR – No Response, DP Slave is notresponding
- TRY – DP Slave responds only after multiple retries by DP Master
- CFG – DP Slave was parameterisedor configured
- DIA – Diagnostic messages pendingat DP Slave
Event logEvent log
COMSOFT GmbH | NetTEST II | June 2009 | Page 28
Should a singular DP Slave show communication problems in the event protocol, it can be analysed in detail by the event counting.
The event count shows the communication statistic for a single DP Slave in detail. Also retries and communication errors are counted.
Event countEvent count
COMSOFT GmbH | NetTEST II | June 2009 | Page 29
The diagnostic event is an extended function of the event counting and serves the detailed analysis of an event.
NetTEST II offers the choice between 6 events that may be triggered, e.g. diagnostic data or input/output data can be analysed.
Should the selected event occur, all relevant data are displayed along with it.
Diagnostic eventDiagnostic event
COMSOFT GmbH | NetTEST II | June 2009 | Page 30
Then contact us:
COMSOFT GmbHWachhausstr. 5a76227 KarlsruheGermany
Tel: +49-(0)721 9497-291Fax: +49-(0)721 9497-129E-mail: [email protected]: www.comsoft.de
StartStart