Page 1: Composite Beams (cont’d). Girder Floor beam L S.

Composite Beams (cont’d)

Page 2: Composite Beams (cont’d). Girder Floor beam L S.
Page 3: Composite Beams (cont’d). Girder Floor beam L S.
Page 4: Composite Beams (cont’d). Girder Floor beam L S.

Girder

Floor beam

L

S

Page 5: Composite Beams (cont’d). Girder Floor beam L S.

b

tc

h

Page 6: Composite Beams (cont’d). Girder Floor beam L S.

Effective concrete-steel T-Beam

• The composite beam can be designed as an effective T-Beam, where width of the slab on either side is limited to:– 1/8 of the beam span– ½ distance to centerline of adjacent beam– The distance to the end of the slab

Page 7: Composite Beams (cont’d). Girder Floor beam L S.

Shoring

• Temporary shores (supports) during construction are optional.

• If temporary shores are NOT used, the steel section must have adequate strength to support all loads prior to concrete attaining 75% of f’c

Page 8: Composite Beams (cont’d). Girder Floor beam L S.

Shear Strength

• Design shear strength and allowable shear strength of composite beams are based on just the steel section!

Page 9: Composite Beams (cont’d). Girder Floor beam L S.

Flexural Strength

• Positive Flexural strength bMn (or Mn/b) are determined as follows:– b = 0.90 (LRFD) and/or b = 1.67 (ASD)

• Mn depends on h/tw as follows:• If determine Mn for yield from plastic

stress distribution on composite section (flange yield)• Else, determine Mn from yielding from superposition of

elastic stresses, considering shoring€

htw

≤ 3.76 E σyf

Page 10: Composite Beams (cont’d). Girder Floor beam L S.

b

tc

h

a

0.85 f’c

y

Page 11: Composite Beams (cont’d). Girder Floor beam L S.

Negative moment

• The design Negative moment can be based on the steel section alone.

• Could be based on plastic stress distribution through composite section provided– Steel beam is adequately braced compact section– Shear connectors in the negative moment area– Slab reinforcement parallel to steel is properly

developed

Page 12: Composite Beams (cont’d). Girder Floor beam L S.

Shear Connectors Concrete Slab Ribbed steel deck

Steel section

Page 13: Composite Beams (cont’d). Girder Floor beam L S.

Effective width

b

Yc

tw

tf

bf

tc

hr

d

Page 14: Composite Beams (cont’d). Girder Floor beam L S.

Composite beamwith formed steel deck

• Nominal rib height is limited to 3 inches. • Width of rib or haunch must be at least 2 inch.

For calculations, never more than minimum clear width

• Must be connected with shear connectors ¾” or less in diameter. Can be welded through deck or to steel cross-section.

• Connectors must not extend more than 1.5” above the top of the deck.

• Must be at least ½” cover

Page 15: Composite Beams (cont’d). Girder Floor beam L S.

Composite beam with formed steel deck (cont)

• Slab thickness must be at least 2”• Deck must be anchored to all supporting

members at max spacing of 18”.• Stud connectors, or a combination of stud

connectors and arc spot (puddle) welds may be used

• If ribs are perpendicular to steel, concrete below the steel deck must be neglected for calculation section properties and concrete area

Page 16: Composite Beams (cont’d). Girder Floor beam L S.

Composite beam with formed steel deck (cont)

• For deck ribs parallel to steel beam, concrete below top of steel deck may be included in determining composite section properties and area of concrete.

• Deck ribs over beams may be split and separated to form concrete haunch.

• When depth of deck is 1.5” or greater, average width of supported haunch or rib must be at least 2” for the first stud plus four stud diameters for each additional stud.

Page 17: Composite Beams (cont’d). Girder Floor beam L S.
Page 18: Composite Beams (cont’d). Girder Floor beam L S.
Page 19: Composite Beams (cont’d). Girder Floor beam L S.

Shear Connectors

• Shear force is transferred by the connectors• The total horizontal shear force, V’, between

max positive moment and zero moment is the smallest of– Concrete crushing: V’ = 0.85 f’c Ac

– Steel yielding: V’ = As y

– Connectors fail: V’ = ∑Qn

Page 20: Composite Beams (cont’d). Girder Floor beam L S.

Shear Connectors

• For negative moments, concrete cannot withstand tension. Rebar yields– Tensile yielding: V’ = Ar yr

– Shear connectors: V’ = ∑ Qn

Page 21: Composite Beams (cont’d). Girder Floor beam L S.

Number of shear connectors

• Number of shear connectors = V’/Qn

• Strength of one shear connector

Asc = x-sectional area of 1 connector,

Rg and Rp on next pages

u = tensile strength of connector€

Qn = 0.5Asc fc'Ec ≤ RgRpAscσ u

Page 22: Composite Beams (cont’d). Girder Floor beam L S.

Rg

• Rg = 1 for – One stud welded in steel deck rib with deck perpendicular to

steel shape; – Any number of studs welded in a row through steel deck with

deck parallel to steel shape and ratio of rib width to depth ≥ 1.5• Rg = 0.85 for

– Two studs welded through steel deck rib with deck perpendicular;

– One stud welded through deck parallel to steel and rib width to depth < 1.5

• Rg = 0.7 for– Three or more studs welded in the deck rib, perpendicular to

steel

Page 23: Composite Beams (cont’d). Girder Floor beam L S.

Rp

• Rp = 1.0 for– Studs welded directly to steel shape (not through steel deck) and

having a haunch detail with not more than 50% of the top flange covered by deck or sheet steel closures.

• Rp = 0.75 for– Studs welded in composite slab, deck perpendicular to steel, emid-ht ≥ 2

inch– Studs welded through deck, deck parallel to steel

• Rp = 0.6 for– Studs welded in composite slab, deck perpendicular to steel and emid-ht

< 2 inch• emid-ht = distance from edge of stud shank to steel deck web

measured at mid height of deck rib in the load bearing direction of the stud (direction of maximum moment)

Page 24: Composite Beams (cont’d). Girder Floor beam L S.

Channels• Channels welded to steel beam may be used as

shear connectors.• Welds must develop the shear resistance Qn

• Effects of eccentricity must be considered

• Where tf = flange thickness of channel connector• tw = web thickness of channel shear connector• Lc = length of channel shear connector€

Qn = 0.3 t f + 0.5tw( )Lc fc'Ec

Page 25: Composite Beams (cont’d). Girder Floor beam L S.

Compressive Strength

– Concrete crushing: Cc = 0.85 f’c Ac

– Steel yielding: Ct = As y

– Connectors fail: Cs = ∑Qn

• Similar to shear values

• The location of the plastic neutral axis affects the failure criteria

Page 26: Composite Beams (cont’d). Girder Floor beam L S.

Location of Plastic Neutral Axis

• Case 1: PNA is in the web of the steel. Occurs when concrete compressive force is less than web force, Cc ≤ Pyw

• Case 2: PNA is in the thickness of the top flange. Pyw < Cc < Ct

• Case 3: PNA is in the concrete slab. Cc ≥ Ct

– Note: in Case 3, concrete below PNA is neglected!

Page 27: Composite Beams (cont’d). Girder Floor beam L S.

Case 1

Eff slab

d

hr

d/2

tf

PNA

0.85f’c

a

y

y

Cc

e

Page 28: Composite Beams (cont’d). Girder Floor beam L S.

Case 2

Eff slab

d

hr

d/2

tf

PNA

0.85f’c

a

y

y

Cc

e

Page 29: Composite Beams (cont’d). Girder Floor beam L S.

Case 3

Eff slab

d

hr

d/2

tf

PNA

0.85f’c

a

y

Cc

e

Page 30: Composite Beams (cont’d). Girder Floor beam L S.

Example• Composite framing in typical multi-story building• 3.25” lightweight concrete, 2” steel deck.– Concrete: = 115 lb/ft2; f’c = 3 ksi– Additional 30% dead load assumed for equipment during

construction• Deck is supported on steel beams with stud

connectors.– ¾” diameter, 3.5” long

• Unshored construction– Beams must support their own weight, weight of concrete

before it hardens, deck weight and construction loads.• Check floor for vibration with damping ration of 5%.

Page 31: Composite Beams (cont’d). Girder Floor beam L S.

Example (p2)

• Typical beam is 30 ft long.• Distance to adjacent beams is 10 ft.• Ribs are perpendicular to the beam• Uniform dead loads on beam are, 500 lb/ft +

30% for equipment loads• Superimposed loads are 250 lb/ft• Live loads (uniform) 500 lb/ft

Page 32: Composite Beams (cont’d). Girder Floor beam L S.

Example (p3)

• Have to pick a beam. Must handle 1.3*0.5 + wt of beam.

• Using A992 (50 ksi) steel. Assume 22 lb/ft starting estimate

• W = 1.3*0.5 + 0.022 kip/ft = 0.672 kip/ft• Factored load: 1.4*0.672 = 0.941• Factored moment: 0.941 * L2/8 = 0.941*302/8

= 105.8 kip-ft

Page 33: Composite Beams (cont’d). Girder Floor beam L S.

Plastic section modulus

Z =Mu

φσ y=

105.8 ×12

0.9 × 50= 28.2 in3

Fortunately, a W14x22 has a Z=33.2 in3, I=199 in4, and w=22

Page 34: Composite Beams (cont’d). Girder Floor beam L S.

Deflection of the beam

• The deflection of the beam is given as

• So camber the beam by 1.6” prior to pouring the concrete. Probably make it 1.5” in drawings.

δ =5wL4

384EI=

5 × 0.522 × 304 ×123

384 × 29,000 ×199=1.6"

Page 35: Composite Beams (cont’d). Girder Floor beam L S.

Next step

• We know that a W14x22 will handle the unshored loads. We need to consider live loads as well.

• We can apply the load reduction factor considering our area (30’ x 10’ between beams and supports)

• R = 0.0008(A-150) = 0.0008(300-150)=0.12• So our live load is 0.5*(1-0.12) = 0.44 kip/ft

Page 36: Composite Beams (cont’d). Girder Floor beam L S.

Factored load

• Greater of– 1.2(0.5+0.25+0.022) + 1.6(0.44) = 1.63 kip/ft– 1.4(0.5+0.25+0.22) = 1.081 kip/ft

• Factored moment is thus– Mn = 1.63 * 302/8 = 183.4 kip-ft

Page 37: Composite Beams (cont’d). Girder Floor beam L S.

Concrete compressive force

• Concrete flange with is lesser of– B = 10x12 = 120” or– B = 2 (30 x 12/8) = 90” **

• Compressive force in concrete is smaller of– Cc = 0.85 f’c Ac = 0.85 x 3 x 90 x 3.25 = 745.9 kips

– Ct = As y = 6.49 x 50 = 324.5 kips **

Page 38: Composite Beams (cont’d). Girder Floor beam L S.

Depth of concrete stress block

a =C

0.85 fc'b

=324.5

0.85 × 3.0 × 90=1.414 in

Since Cc > Ct, PNA is in the concrete slab. The distance between the compression and tension forces, e, on the W14x22e = 0.5d + 5.25 – 0.5a = 0.5 x 13.7 + 5.25 – 0.5*1.414 = 11.393 in

φMn = 0.9Cte = 0.9 × 324.5 ×11.393/12 = 277.3

We are expecting 183.4, so this passes