Installation Instructions
CompactLogix EtherNet/IP Communication ModuleCatalog Number
1768-ENBT
Topic See Page
Important User Information 2
Minimum Spacing 7
What You Need 8
Install the Modules 8
Wire the Module 15
Connect the Module 15
Configure the Module 16
Confirm Your Installation 17
Remove a Module 18
Troubleshoot the Module 20
Specifications 22
Additional Resources 25
-
2 CompactLogix EtherNet/IP Communication Module
Important User Information
Solid-state equipment has operational characteristics differing
from those of electromechanical equipment. Safety Guidelines for
the Application, Installation and Maintenance of Solid State
Controls (Publication SGI-1.1 available from your local Rockwell
Automation sales office or online at
http://www.rockwellautomation.com/literature/) describes some
important differences between solid-state equipment and hard-wired
electromechanical devices. Because of this difference, and also
because of the wide variety of uses for solid-state equipment, all
persons responsible for applying this equipment must satisfy
themselves that each intended application of this equipment is
acceptable.
In no event will Rockwell Automation, Inc. be responsible or
liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for
illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell
Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with
respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in
part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you
aware of safety considerations.
WARNING: Identifies information about practices or circumstances
that can cause an explosion in a hazardous environment, which may
lead to personal injury or death, property damage, or economic
loss.
ATTENTION: Identifies information about practices or
circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard,
avoid a hazard and recognize the consequences.
SHOCK HAZARD: Labels may be on or inside the equipment, for
example, drive or motor, to alert people that dangerous voltage may
be present.
BURN HAZARD: Labels may be on or inside the equipment, for
example, drive or motor, to alert people that surfaces may reach
dangerous temperatures.
IMPORTANT Identifies information that is critical for successful
application and understanding of the product.
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
CompactLogix EtherNet/IP Communication Module 3
North American Hazardous Location Approval
The following information applies when operating this equipment
in hazardous locations.
Informations sur l’utilisation de cet équipement en
environnements dangereux.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for
use in Class I Division 2 Groups A, B, C, D, Hazardous Locations
and nonhazardous locations only. Each product is supplied with
markings on the rating nameplate indicating the hazardous location
temperature code. When combining products within a system, the most
adverse temperature code (lowest "T" number) may be used to help
determine the overall temperature code of the system. Combinations
of equipment in your system are subject to investigation by the
local Authority Having Jurisdiction at the time of
installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent
qu'à une utilisation en environnements de Classe I Division 2
Groupes A, B, C, D dangereux et non dangereux. Chaque produit est
livré avec des marquages sur sa plaque d'identification qui
indiquent le code de température pour les environnements dangereux.
Lorsque plusieurs produits sont combinés dans un système, le code
de température le plus défavorable (code de température le plus
faible) peut être utilisé pour déterminer le code de température
global du système. Les combinaisons d'équipements dans le système
sont sujettes à inspection par les autorités locales qualifiées au
moment de l'installation.
WARNING:Explosion Hazard -•Do not disconnect equipment
unless power has been removed or the area is known to be
nonhazardous.
•Do not disconnect connections to this equipment unless power
has been removed or the area is known to be nonhazardous. Secure
any external connections that mate to this equipment by using
screws, sliding latches, threaded connectors, or other means
provided with this product.
•Substitution of components may impair suitability for Class I,
Division 2.
• If this product contains batteries, they must only be changed
in an area known to be nonhazardous.
AVERTISSEMENT:Risque d’Explosion – •Couper le courant ou
s'assurer que
l'environnement est classé non dangereux avant de débrancher
l'équipement.
•Couper le courant ou s'assurer que l'environnement est classé
non dangereux avant de débrancher les connecteurs. Fixer tous les
connecteurs externes reliés à cet équipement à l'aide de vis,
loquets coulissants, connecteurs filetés ou autres moyens fournis
avec ce produit.
•La substitution de composants peut rendre cet équipement
inadapté à une utilisation en environnement de Classe I, Division
2.
•S'assurer que l'environnement est classé non dangereux avant de
changer les piles.
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
4 CompactLogix EtherNet/IP Communication Module
European Hazardous Location ApprovalThe following applies when
the product bears the Ex Marking.
This equipment is intended for use in potentially explosive
atmospheres as defined by European Union Directive 94/9/EC.
Intertek certifies that this equipment has been found to comply
with the Essential Health and Safety Requirements relating to the
design and construction of Category 3 equipment intended for use in
Zone 2 potentially explosive atmospheres, given in Annex II to this
Directive. The examination and test results are recorded in
confidential report No.100014190DAL-001.
Compliance with the Essential Health and Safety Requirements has
been assured by compliance with EN 60079-15.
WARNING: This equipment must be installed in an enclosure
providing at least IP54 protection when applied in Zone 2
environments.
Provision shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 40% when applied in
Zone 2 environments.
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
CompactLogix EtherNet/IP Communication Module 5
Environment and Enclosure
ATTENTION: This equipment is intended for use in a Pollution
Degree 2 industrial environment, in overvoltage Category II
applications (as defined in IEC 60664-1), at altitudes up to 2000 m
(6562 ft) without derating.
This equipment is considered Group 1, Class A industrial
equipment according to IEC/CISPR 11. Without appropriate
precautions, there may be difficulties with electromagnetic
compatibility in residential and other environments due to
conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be
mounted within an enclosure that is suitably designed for those
specific environmental conditions that will be present and
appropriately designed to prevent personal injury resulting from
accessibility to live parts. The enclosure must have suitable
flame-retardant properties to prevent or minimize the spread of
flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or
equivalent) if non-metallic. The interior of the enclosure must be
accessible only by the use of a tool. Subsequent sections of this
publication may contain additional information regarding specific
enclosure type ratings that are required to comply with certain
product safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines,
Rockwell Automation publication 1770-4.1, for additional
installation requirements.
• NEMA Standard 250 and IEC 60529, as applicable, for
explanations of the degrees of protection provided by different
types of enclosure.
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
6 CompactLogix EtherNet/IP Communication Module
Prevent Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic
discharge, which can cause internal damage and affect normal
operation. Follow these guidelines when you handle this
equipment:
• Touch a grounded object to discharge potential static.• Wear
an approved grounding wriststrap.• Do not touch connectors or pins
on component boards.• Do not touch circuit components inside the
equipment.• If available, use a static-safe workstation.• When not
in use, store the equipment in appropriate static-safe
packaging.
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
CompactLogix EtherNet/IP Communication Module 7
Minimum Spacing Plan for this minimum spacing from enclosure
walls, wireways, and other equipment.
See Specifications on page 22 for the temperature range.
Item Description
1 105 mm (4 in.)
2 90 mm (3.54 in.)
31609-M
PowerOUT
L1
L2/N
2
1
2
1
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
8 CompactLogix EtherNet/IP Communication Module
What You Need
Install the Modules
Item Cat. No. or Size
1768 CompactLogix power supply 1768-PA3
1768 CompactLogix controller 1768-L43
1769 end capConnects to the controller as the last module,
either:• without any 1769-series
modules attached to the controller (1768-series only)
• with a combination of 1768-series and 1769-series modules
attached to the controller
1769-ECR
RJ45 Ethernet connector See Wire the Module on page 15
DIN rail or mounting screws (one or the other but not both)
DIN rail Either of these sizes:
• 35 x 7.5 mm (EN 50 022 - 35 x 7.5)• 35 x 15 mm (EN 50 022 - 35
x 15)
Screws M4 or #8 panhead screws
ATTENTION: This product is grounded through the DIN rail to
chassis ground. Use zinc-plated yellow-chromate steel DIN rail to
assure proper grounding. The use of other DIN rail materials (for
example, aluminum or plastic) that can corrode, oxidize, or are
poor conductors, can result in improper or intermittent grounding.
Secure DIN rail to mounting surface approximately every 200 mm
(7.87 in.) and use end-anchors appropriately.
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
CompactLogix EtherNet/IP Communication Module 9
If You Are Using Screws to Mount Your Modules
The steps in these instructions show how to mount the modules on
DIN rail. If you are using screws instead of DIN rail, make these
changes to the instructions.
1. Follow the steps in Mount the Controller on the DIN Rail on
page 11 to connect the modules together.
2. Use the modules as a template and mark pilot holes on your
panel.
3. Drill the pilot holes for M4 or #8 screws.
4. Use M4 or #8 screws to mount the modules to your panel.
Use1.16 N•m (10 lb•in) of torque.
5. Ground the module on a ground bus with a dedicated earth
ground stake.
6. Connect the ground bus to a functional earth ground on the
DIN rail or panel.
7. Refer to Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1, for additional information.
IMPORTANT Do not use screws and DIN rail to mount the modules.
It is possible to break the mounting tabs off if you screw the
modules to the panel while they are on DIN rail.
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
10 CompactLogix EtherNet/IP Communication Module
Install the DIN RailMount the DIN rail in a suitable
location.
ATTENTION: This product is grounded through the DIN rail to
chassis ground. Use zinc plated yellow-chromate steel DIN rail to
assure proper grounding. The use of other DIN rail materials (for
example, aluminum or plastic) that can corrode, oxidize, or are
poor conductors, can result in improper or intermittent grounding.
Secure DIN rail to mounting surface approximately every 200 mm (7.8
in.) and use end-anchors appropriately.
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
CompactLogix EtherNet/IP Communication Module 11
Mount the Controller on the DIN Rail
31595-M
1
31596 -M
2
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
12 CompactLogix EtherNet/IP Communication Module
Mount the EtherNet/IP Communication Module on the DIN Rail
31597-M
1
31598 -M
2 bb
c
a
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
CompactLogix EtherNet/IP Communication Module 13
Mount the Power Supply on the DIN Rail
31599-M
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
14 CompactLogix EtherNet/IP Communication Module
Mount the I/O Modules on the DIN Rail
31600-M
1a
b d
c
31601-M
2b
c
a
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
CompactLogix EtherNet/IP Communication Module 15
Wire the ModuleUse an RJ45 connector to connect to the
EtherNet/IP network.
Connect the Module
IMPORTANT We recommend connecting the module to the network via
a 100 MB Ethernet switch, which will reduce collisions and lost
packets and increase network bandwidth. For detailed EtherNet/IP
connection information, see the EtherNet/IP Modules in Logix5000
Control Systems User Manual, publication ENET-UM001.
WARNING: If you connect or disconnect the cable with power
applied to this module or any device on the network, an electrical
arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is
nonhazardous before proceeding.
8
1
8 ------ NC7 ------ NC6 ------ RD-5 ------ NC4 ------ NC3 ------
RD+2 ------ TD-1 ------ TD+
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
16 CompactLogix EtherNet/IP Communication Module
Attach the RJ45 connector to the Ethernet port on the bottom of
the module.
Configure the ModuleTo configure your module, refer to the
configuration chapter of your EtherNet/IP Modules User Manual,
publication ENET-UM001.
Item Description
1 Ethernet port
1
31611-M
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
CompactLogix EtherNet/IP Communication Module 17
Confirm Your Installation
See Troubleshoot the Module on page 20 if the status indicators
are in other states.
Item Description
1 Solid or flashing green
2 Solid green
31608-M
PowerOUT
L1
L2/N
2 2
1
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
18 CompactLogix EtherNet/IP Communication Module
Remove a Module
31602-M
PowerOUT
L1
L2/N
1
a
c - Offb
e
fd
31607-M
PowerOUT
L1
L2/N
2a
b
c
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
CompactLogix EtherNet/IP Communication Module 19
Why Wait for the Lights to Turn Off Before I Remove a
Module?After you turn off the power, wait for all of the lights on
the power supply and controller to turn off before you disconnect
any modules.
• When you turn off the power, the controller writes its project
to memory.
• If you don’t wait for the lights to turn off, you will lose
your project.
IMPORTANT When you turn the CompactLogix power supply off, make
sure you wait for all status indicators on the power supply and
controller to turn off before disconnecting any part from the
system.
If you disconnect the CompactLogix system while the controller
is still writing its program to memory, the program write will not
be completed and you will lose your program.
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
20 CompactLogix EtherNet/IP Communication Module
Troubleshoot the ModuleThe three bi-color (red/green) status
indicators on the module provide diagnostic information about the
module and its connections to the network. If the alphanumeric
display and status indicators do not sequence through the expected
states, refer to the troubleshooting tables.
Item Description
1 Link status indicator
2 OK status indicator
3 Network status indicator
3 2
1
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
CompactLogix EtherNet/IP Communication Module 21
Status IndicatorsThe module status indicators provides the
following information.
Indicator Status Description
NET Off Module is not powered, or does not have an IP address.•
Verify there is chassis power and the module is
completely inserted into the chassis and backplane.• Make sure
the module has been configured.
Flashing Green Module has obtained an IP address, but has no
established connections.
Green Module has an IP address and at least one established
connection.
Flashing Red One or more of the connections in which the module
is the target has timed out.
Red Module has detected that its IP address is already in use.
Assign a unique IP address to the module.
Link Off No data transmission.Module is not ready to
communicate.
Green Module is ready to communicate.
Flashing Green Data transmission in progress.Module is
communicating over the network.
OK Off Module does not have 5V DC power. Verify there is power
and the module is properly installed.
Flashing Green Standby mode. Module is not configured.
Green Module is operating correctly.
Flashing Red A minor, recoverable fault has been detected. This
could be caused by an error in the configuration.
Red A major, unrecoverable fault has been detected. Recycle
power to the module. If this does not clear the fault, replace the
module.
Flashing Red and Green
Module performing power-up self-test.
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
22 CompactLogix EtherNet/IP Communication Module
Specifications
Technical Specifications - 1768-ENBT
Attribute 1768-ENBT
Backplane current 834 mA at 5.2V DC
Power consumption 4.34 W
Power dissipation 4.38 W
Isolation (continuous-voltage rating)
30V, Functional Insulation Type, Ethernet network to systemType
tested at 710V DC for 60 s
Wire Size Ethernet network connections:RJ45 connector according
to IEC 60603-7, 2 or 4 pair Category 5e minimum cable according to
TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702
Wiring category(1)
(1) Use this Conductor Category information for planning
conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1.
2 - on communication ports
North American temp code T4A
IEC temp code T4
Mounting screw torque 1.16 N•m (10 lb•in), using M4 or #8
screws
Dimensions (HxWxD), approx. 132 x 56.7 x 105.1 mm (5.20 x 2.23 x
4.12 in.)
Weight, approx. 0.213 kg (7.5 oz)
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
CompactLogix EtherNet/IP Communication Module 23
Environmental Specifications - 1768-ENBT
Attribute 1756-ENBT
Temperature, operating • IEC 60068-2-1 (Test Ad, Operating
Cold)• IEC 60068-2-2 (Test Bd, Operating Dry
Heat)• IEC 60068-2-14 (Test Nb, Operating
Thermal Shock)
0…60 °C (32...140 °F)
Temperature, nonoperating• IEC 60068-2-1 (Test Ab,
Unpackaged
Nonoperating Cold)• IEC 60068-2-2 (Test Bb, Unpackaged
Nonoperating Dry Heat)• IEC 60068-2-14 (Test Na, Unpackaged
Nonoperating Thermal Shock)
-40…85 °C (-40...185 °F)
Relative humidity• IEC 60068-2-30 (Test Db, Unpackaged
Damp Heat)
5…95% noncondensing
Vibration• IEC 60068-2-6 (Test Fc, Operating)
5 g @ 10…500 Hz
Operating shock• IEC 60068-2-27 (Test Ea, Unpackaged
Shock)
30 g
Nonoperating shock• IEC 60068-2-27 (Test Ea, Unpackaged
Shock)
50 g
Emissions• CISPR 11
Group 1, Class A
ESD immunity• IEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunity• IEC 61000-4-3
10V/m with 1 kHz sine-wave 80%AM from 30…2000 MHz10V/m with 200
Hz 50% Pulse 100%AM at 900 MHz10V/m with 200 Hz 50% Pulse 100%AM at
1890 MHz1V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz
EFT/B immunity• IEC 61000-4-4
±2 kV at 5 kHz on communication ports
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
24 CompactLogix EtherNet/IP Communication Module
Surge transient immunity• IEC 61000-4-5
±2 kV line-earth(CM) on communication ports
Conducted RF immunity• IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz
Enclosure type rating None (open-style)
Certifications
Certification (when product is marked)(1)
Value
c-UL-us • UL Listed Industrial Control Equipment, certified for
US and Canada. See UL File E65584.
• UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for U.S. and Canada. See UL File E194810.
CE European Union 2004/108/EC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN
61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions•
EN 61131-2; Programmable Controllers (Clause 8, Zone A &
B)
C-Tick Australian Radiocommunications Act, compliant with:•
AS/NZS CISPR 11; Industrial Emissions
Ex European Union 94/9/EC ATEX Directive, compliant with:• EN
60079-15; Potentially Explosive Atmospheres,
Protection "n"• EN 60079-0; General Requirements
II 3 G Ex nA IIC T4
EtherNet/IP • ODVA conformance tested to EtherNet/IP
specifications
(1) See the Product Certification link at www.ab.com for
Declarations of Conformity, Certificates, and other certification
details.
Environmental Specifications - 1768-ENBT
Attribute 1756-ENBT
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
CompactLogix EtherNet/IP Communication Module 25
Additional ResourcesThese documents contain additional
information concerning related Rockwell Automation products.
You can view or download publications at
http://www.rockwellautomation.com/literature/. To order paper
copies of technical documentation, contact your local Rockwell
Automation distributor or sales representative.
Resource Description
EtherNet/IP Modules in Logix5000 Control Systems User Manual,
publication ENET-UM001
Provides information about how to use EtherNet/IP modules with
vrious Logix5000 controllers.
1768 CompactLogix Controller Installation Instructions,
publication 1768-IN004
Provides information for installing a 1768 CompactLogix
controller.
1769 CompactLogix Power Supplies Installation Instructions,
publication 1768-IN001
Provides information about how to install CompactLogix power
supplies.
Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1
Provides general guidelines for installing a Rockwell Automation
industrial system.
Product Certifications website, http://ab.com
Provides declarations of conformity, certificates, and other
certification details.
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
26 CompactLogix EtherNet/IP Communication Module
Notes:
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
CompactLogix EtherNet/IP Communication Module 27
Notes:
Rockwell Automation Publication 1768-IN002B-EN-P - August
2010
-
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok
Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation SupportRockwell Automation provides
technical information on the Web to assist you in using its
products. At http://www.rockwellautomation.com/support/, you can
find technical manuals, a knowledge base of FAQs, technical and
application notes, sample code and links to software service packs,
and a MySupport feature that you can customize to make the best use
of these tools.
For an additional level of technical phone support for
installation, configuration, and troubleshooting, we offer
TechConnect support programs. For more information, contact your
local distributor or Rockwell Automation representative, or visit
http://www.rockwellautomation.com/support/.
Installation AssistanceIf you experience a problem within the
first 24 hours of installation, please review the information
that's contained in this manual. You can also contact a special
Customer Support number for initial help in getting your product up
and running.
New Product Satisfaction ReturnRockwell Automation tests all of
its products to ensure that they are fully operational when shipped
from the manufacturing facility. However, if your product is not
functioning and needs to be returned, follow these procedures.
Documentation Feedback Your comments will help us serve your
documentation needs better. If you have any suggestions on how to
improve this document, complete this form, publication RA-DU002,
available at http://www.rockwellautomation.com/literature/.
United States or Canada 1.440.646.3434
Outside United States or Canada
Use the Worldwide Locator at
http://www.rockwellautomation.com/support/americas/phone_en.html,
or contact your local Rockwell Automation representative.
United StatesContact your distributor. You must provide a
Customer Support case number (call the phone number above to obtain
one) to your distributor to complete the return process.
Outside United States Please contact your local Rockwell
Automation representative for the return procedure.
Publication 1768-IN002B-EN-P - August 2010 PN-83488Supersedes
Publication 1768-IN002A-EN-P - December 2005 Copyright © 2010
Rockwell Automation, Inc. All rights reserved. Printed in the
U.S.A.
Allen-Bradley, CompactLogix, Logix 5000, Rockwell Software,
Rockwell Automation, and TechConnect are trademarks of Rockwell
Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of
their respective companies.
1768-IN002B-EN-P, CompactLogix EtherNet/IP Communication Module
Installation InstructionsImportant User InformationNorth American
Hazardous Location ApprovalEuropean Hazardous Location
ApprovalEnvironment and EnclosurePrevent Electrostatic
DischargeMinimum SpacingWhat You NeedInstall the ModulesIf You Are
Using Screws to Mount Your ModulesInstall the DIN RailMount the
Controller on the DIN RailMount the EtherNet/IP Communication
Module on the DIN RailMount the Power Supply on the DIN RailMount
the I/O Modules on the DIN Rail
Wire the ModuleConnect the ModuleConfigure the ModuleConfirm
Your InstallationRemove a ModuleWhy Wait for the Lights to Turn Off
Before I Remove a Module?
Troubleshoot the ModuleStatus Indicators
SpecificationsAdditional ResourcesBack Cover
/ColorImageDict > /JPEG2000ColorACSImageDict >
/JPEG2000ColorImageDict > /AntiAliasGrayImages false
/CropGrayImages true /GrayImageMinResolution 300
/GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true
/GrayImageDownsampleType /Average /GrayImageResolution 300
/GrayImageDepth 8 /GrayImageMinDownsampleDepth 2
/GrayImageDownsampleThreshold 2.00000 /EncodeGrayImages true
/GrayImageFilter /FlateEncode /AutoFilterGrayImages false
/GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict >
/GrayImageDict > /JPEG2000GrayACSImageDict >
/JPEG2000GrayImageDict > /AntiAliasMonoImages false
/CropMonoImages true /MonoImageMinResolution 1200
/MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true
/MonoImageDownsampleType /Average /MonoImageResolution 1200
/MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000
/EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode
/MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None
] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false
/PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000
0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true
/PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ]
/PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier ()
/PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped
/False
/Description > /Namespace [ (Adobe) (Common) (1.0) ]
/OtherNamespaces [ > /FormElements false /GenerateStructure true
/IncludeBookmarks false /IncludeHyperlinks false
/IncludeInteractive false /IncludeLayers false /IncludeProfiles
true /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe)
(CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /NA
/PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged
/UntaggedRGBHandling /LeaveUntagged /UseDocumentBleed false
>> ]>> setdistillerparams> setpagedevice
Introduction_Catagory Types
This tab summarizes Rockwell Automation Global Sales and
Marketing preferred printing standards. It also provides guidance
on whether a publication should be released as JIT (print on
demand) or if it requires an RFQ for offset printing.Find your
publication type in the first section below. Use the assigned
Printing Category information to determine the standard print
specifications for that document type. The Printing Categories are
defined below the Publication Type section. Note there may be
slightly different print specifications for the categories,
depending on the region (EMEA or Americas).For more information on
Global Sales and Marketing Printing Standards, see publication
RA-CO004 in DocMan.
Publication Type and Print Category
Publication TypeOff Set Print Category Spec. (See table
below)JIT Spec. (See table below)DescriptionOrder MinOrder MaxLife
Cycle Usage / Release Option
ADNA - PuttmanNAAdvertisement Reprint ColourNANAPresale /
Internal
APA3D2Application Solution or Customer Success Story5100Presale
/ External
ARNANAArticle/Editorial/BylineNANAPresale / Internal
/News Release (press releases should not be checked into DocMan
or printed)
ATB3, B4D5Application Techniques5100Presale / External
BRA2 Primary, A1NABrochures5100Presale / External
CAC2 Primary, C1NACatalogue150Presale / External
CGNANACatalogue Guide150Presale / External
CLNANACollection550Presale / External
COA5, A6, A9D5Company Confidential InformationNANANA /
Confidential
CPE-onlyE-only, D5Competitive Information550NA /
Confidential
DCE-onlyE-onlyDiscount SchedulesNANAPresale / Internal
DIA1, A3NADirect Mail5100Presale / Internal
DMNANAProduct Demo550Presale / Internal
DSB3D5Dimensions Sheet15Post / External
DUB3D5Document Update15Post / External
GRB2D6Getting Results15Post / External
INB3D5Installation instructions15Post / External
LMNANALaunch KitMaterials550Presale / Internal
PCB3D5Packaging Contents
PLE-only Primary, B3E-onlyPrice List550Presale / Internal
PMB2D6Programming Manual15Post / External
PPA3D1Product Profile NOTE: Application Solutions are to be
assigned the AP pub type.5100Presale / External
QRB2 Primary, B3, B5D5, D6Quick Reference15Post / External
QSB2 Primary, B3, B5D5, D6Quick Start15Post / External
RMB2D5, D6Reference Manual15Post / External
RNB3D5Release Notes15Post / External
SGB1 Primary, B4D5, D6Selection Guide Colour550Presale /
External
SGB2D5, D6Selection Guide B/W550Presale / External
SPA1, A2, A3, A4NAService ProfileSales Promotion NOTE: Service
profiles are to be assigned the PP pub type.5100Presale /
Internal
SRB2, B3D5, D6Specification Rating Sheet5100Presale /
External
TDB2 Primary B3, B4, B5D5, D6Technical Data550Presale /
External
TGB2, B3D6Troubleshooting Guide15Post / External
UMB2 Primary, B4D6User Manual B/W15Post / External
WDB3D5Wiring Diagrams / Dwgs15Post / Internal
WPB3 Primary, B5D5White Paper550Presale / External
Pre-sale / MarketingAll paper in this category is White
Brightness, 85% or better. Opacity 87% or better
CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US
Paper Requirements
A14 color170gsm 2pp100# gloss cover, 100# gloss text
A24 color170gsm, folded, 4pp100# gloss cover, 80# gloss text
A34 colorCover 170gsm with Body 120gsm, > 4pp80# gloss cover,
80# gloss text
A42 color80# gloss cover, 80# gloss text
170gsm Silk – 120gsm Silk
A52 color80# gloss cover, 80# matt sheet text
170gsm Silk – 120gsm Silk
A61 color170gsm Silk – 120gsm Silk80# gloss cover, 80# matt
sheet text
A74 color cover10 Point Cover C2S
2 color textCategory being deleted50# matte sheet text
Selection Guide
A84 color coverCategory being deleted50# matte sheet text, self
cover
2 color text
Selection Guide
A92 color100gsm bond50# matte sheet text, self cover
Selection Guide
Post Sale / Technical Communication
CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US
Paper Requirements
B14 color cover270gsm Gloss 100gsm bond10 Point Cover C2S
2 color text50# matte sheet text
B21 color60# Cover
160gsm Colortech & 100gsm Bond50# matte sheet text
B31 color50# matte sheet text, self cover
100gsm bond
B42 color60# Cover
160gsm Colortech & 100gsm Bond50# matte sheet text
B52 color50# matte sheet text, self cover
100gsm bond
Catalogs
CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US
Paper Requirements
C14 color cover270gsm Gloss 90gsm silk10 Point Cover C2S
4 color text45# Coated Sheet
C24 color cover270gsm Gloss 80gsm silk10 Point Cover C2S
2 color text32#-33# Coated Sheet
JIT / POD
CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US
Paper Requirements
D14 color170gsm white silk80# gloss cover, coated 2 sides
D24 color120gsm white silk80# gloss text, coated 2 sides, self
cover
D34 colorCover 170gsm with Body 120gsm80# gloss cover, 80# gloss
text coated 2 sides
D41 color160gsm tab90# index
D51 color80gsm bond20# bond, self cover
D61 colorCover 160gsm tab with Body 80gsm bond90# index, 20#
bond
D72 color160gsm tab90# index
D82 color80gsm bond20# bond, self cover
D92 colorCover 160gsm tab with Body 80gsm bond90# index, 20#
bond
D10Combination: 4 color cover, with 2 color bodyCover 160gsm
with Body 80gsm90# index, 20# bond
Print Spec Sheet
JIT Printing SpecificationsRA-QR005E-EN-P - 5/19/2009
Printing SpecificationYOUR DATA HEREInstructionsNO
(required) Category:D5Select Print Category A,B,C or D from
category list, on "Introduction_Catagory Types" tab11” x 17”LOOSE
-Loose LeafYESPre-sale / MarketingTOP
(required) Finished Trim Size Width:4.75” x 7” (slightly smaller
half-size)8.5” x 11”PERFECT - Perfect BoundA1LEFT
(required) Publication Number :1768-IN002B-EN-PSample:
2030-SP001B-EN-P3” x 5”SADDLE - Saddle StitchA2RIGHTCORNER
Use Legacy NumberNOYES or NO18” x 24” PosterPLASTCOIL - Plastic
Coil (Coil Bound)A4BOTTOMSIDE
Legacy Number if applicable:Sample Legacy Number: 0160-5.3324” x
36” PosterSTAPLED1 -1 positionA3
Publication Title:CompactLogix EtherNet/IPCommunication
ModuleSample: ElectroGuard Selling Brief36” x 24” PosterSTAPLED1B -
bottom 1 positionA5
(required) Business Group:Marketing CommercialAs entered in
DocMan4” x 6”STAPLED2 - 2 positionsA6
(required) Cost Center:CMKMKE CM Integrated Arch - 19021As
entered in DocMan - enter number only, no description. Example -
19021CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program
- 191054.75” x 7” (slightly smaller half-size)THERMAL - Thermal
bound (Tape bound)A7
Binding/Stitching:SADDLE - Saddle StitchReview key on
right...Saddle-Stitch Items All page quantities must be divisible
by 4.20 sheets max. on 20# (text and cover); 20 sheets = 80-page
pub16 sheets max. on 20# (text) and 90# (cover); 16 sheets =
64-page pub
Perfect Bound Items475 sheets max. on 20# no cover; 475 sheets =
950-page pub470 sheets max. w/cover / 90# index unless indicated
otherwise); 470 sheets = 940-page pub
Coil Bound Items400 sheets max. of 20# (if adding cover deduct
equivalent number of pages to equal cover thickness) (90# index
unless indicated otherwise); 400 sheets = 800-page pub
Tape Bound Items125 sheets max. on 20# no cover; 125 sheets =
250-page pub120 sheets max. w/cover (90# index unless indicated
otherwise); 120 sheets = 240-page pub
Double Wire Bound Items250 sheets max. on 20# (if adding cover
deduct equivalent number of pages to equal cover thickness) (90#
index unless indicated otherwise); 250 sheets = 500-page pub4.75” x
7.75”THERMALO - Thermal Bound (Tape bound - offline)A8
(required) Page Count of Publication:24Total page count
including cover5.5” x 8.5” (half-size)Wire O - Double Wire Bound
(offline)A9
Paper Stock Color:White is assumed. For color options contact
your vendor.6” x 4”Post Sale / Technical Communication
Number of Tabs Needed:5 tab in stock at RR Donnelley7.385” x 9”
(RSI Std)B1
Stitching Location:Blank, Corner or Side8.25” x 10.875”B2
Drill Hole YES/NOYESAll drilled publications use the 5-hole
standard, 5/16 inch-size hole and a minimum of ¼ inch from the
inner page border.8.25” x 11” (RA product profile std)B3
Glue Location on Pad:Glue location on pads8.375” x 10.875B4
Number of Pages per Pad:Average sheets of paper.. 25, 50 75,100
Max9” x 12” (Folder)B5
Ink ColorOne color assumes BLACK / 4 color assume CMYK /
Indicate PMS number here…A4 (8 ¼” x 11 ¾”) (210 x 297
mm)Catalogs
Used in Manufacturing:YESA5 (5.83” x 8.26”) (148 x 210 mm)C1
Comments:1756-ENBTC2
Part Number:PN-83488JIT / POD
D1
D2
D3
D4
D5
D6
D7
D8
D9