COMPACT SCP Installation & Maintenance These instructions must be read fully before commencing installation.
COMPACT SCP Installation & Maintenance
These instructions must be read fully before commencing installation.
Tel 01384 275800 Fax 01384 275810 Email [email protected] Website eltafans.com2
Installation InstructionsCOMPACT SCP AC
1.0 General1.1 It is important these Installation and Maintenance Instructions are fully adhered to.1.2 Full details of the unit supplied are shown on the product nameplate. If in doubt about any detail contact Elta Fans Ltd or its agents for clarification.1.3 All electrical installation must be carried out by suitably qualified and competent personnel in accordance with all current statutory requirements.1.4 These instructions cover only the Elta Fans Ltd product and do not include the supply or installation of any safety equipment that may be required e.g. adequate guarding or protection from rotating parts and proper electrical isolation.1.5 Any declarations made by Elta Fans Ltd about product installation and safety, are dependant on the fan equipment being used within installations which themselves meet the requirements of the relevant Standards and Directives of your region.1.6 The fan is designed for use in an ambient temperature of -20°C up to a maximum of +70°C, speed controlled operating temperatures of -20°C and +50°C and up to 95% relative humidity. EC fans are designed for ambient temperatures up to +60°C. The fan is not suitable for corrosive or explosive atmospheres.1.7 The installer should provide easy access to the fan to facilitate future maintenance.1.8 The installer should ensure the fan is adequately supported.1.9 This product is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the product by a person responsible for their safety. Children should be supervised to ensure that they do not play with the product.1.10 At end-of-life, the unit must be disposed of in an environmentally friendly manner by suitably qualified and competent personnel in accordance with the requirements of applicable Standards and Directives.
2.0 Installation
WARNING – The fan must be isolated from the power supply during installation and maintenance. The fan must be earthed in accordance with the local regulations.
2.1 Upon receipt, the fan equipment should be visually inspected to check for any damage. Ensure that the impeller is free to rotate.2.2 If there are any queries concerning the fan equipment, Elta Fans Ltd should be contacted prior to the installation.2.3 The fan must be securely mounted in the desired position to suit the application. The fan can be mounted at any angle.2.4 Check the details on the motor rating plate to ensure that the correct power supply (voltage, frequency and phase) is available. An incorrect power supply will lead to permanent damage to the fan motor.2.5 Refer to the appropriate wiring diagram. Ensure that all earth connections are made.2.6 Means for electrical disconnection must be incorporated in the wiring installation in accordance with the relevant wiring and electrical regulations.2.7 Precaution must be taken to locate the exhaust discharge terminal so as to avoid the backflow of gases into the room from the open flue of gas or other fuel burning appliances.
3.0 Start Up3.1 Before power is supplied to the unit, check that the wiring is correct as per the fan connection diagram.3.2 At initial start-up, check that impeller rotation and airflow direction is correct.3.3 Check that the motor amperage drawn does not exceed the nameplate rating. EC fans only:3.4 Minimum interval between consecutive starts: 5 minutes.3.5 Maximum 1 connection from power supply cycle per 5 minutes.
4.0 Fan Maintenance4.1 Inspection of the fan at least once every 12 months is recommended to ensure that the motor, fan blades, and supporting guards, are clean. Any build up of dust and deposits on the blades or guards should be removed using a non-abrasive cleaner.4.2 All fastenings should be checked for tightness. In addition, all rotating items should be checked.4.3 Bearings are of the ‘sealed for life’ type and will not need a detailed inspection.
WARNING – This fan is fitted with an auto-reset thermal contact which switches the fan off in the event of a fault condition. Once the motor cools down the fan may start unexpectedly. Only a suitably qualified and competent person may carry out maintenance after the electrical supply has been isolated.
5.0 Guarantee Elta Fans Ltd will, free of charge, within a period of 1 year from the date of dIspatch from their works, repair or at its option replace any goods which are proved to have defects as a result of defective materials or workmanship. The goods MUST be returned to Elta Fans Ltd carriage paid for examination.
Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication. Confirmation of dimensions and data will be supplied on request. 3
COMPACT SCPInstallation Instructions
GND 10V E1
MIN MAX
E1GND
ST1
ST2
ST2
E110VGND
MAXMIN
ST1
GND E1
THE ABOVE DIAGRAM SHOWS "ST2".
"ST2" CONNECTIONS ARE FACTORY FITTED.
GND = COMMON•10V = 10VDC INPUT•E1 = 0-10VDC OUTPUT•
YOU CAN DETERMINE THE CURRENT VDC OUTPUT BYDISCONNECTING POWER TO THE UNIT, SETTING AMULTIMETER TO OHMS (Ω) AND PLACING THE TEST PROBESBETWEEN GND AND E1
PLEASE USE THE ESTIMATED ADJUSTMENT GUIDE FOR REFERENCE
THIS IS THE INTERNAL POTENTIOMETERTHIS POTENTIOMETER CAN BE ADJUSTED FOR SINGLE SPEED SETTING OR MAX SPEED SELECTION
THIS LINK/JUMPER SHOULD BE REMOVEDWHEN USING AN EXTERNAL POTENTIOMETEROR EXTERNAL CONTROL SIGNAL CONNECTEDTO "ST1"
THE ABOVE DIAGRAM SHOWS "ST1".
"ST1" CONNECTIONS ARE CLASSED AS"CUSTOMER/USER CONNECTIONS".
GND = COMMON•+ = VDC OUTPUT AS SET BY•
INTERNAL POTENTIOMETERE1 = 0-10VDC INPUT•
149-CD-POT
10/07/2018MK-149-CD-POT Issue: Saved Date:A
All wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. 149-CD-POT Issue A: 10.07.2018Check the individual product accessories table for fan controller compatibility.
149-CD-POTThe 149-CD-POT is a commissiong device designed to be used with our EC range of fans. The device will allow the for the installer to set the maximum operating speed of the fan that it is connected to. The installer or commissioning engineer can adjust the fan speed using the potentiometer built onto the 149-CD-POT board. This potentionmeter can either be used for single speed adjustment or to set a maximum speed for the fan to operate at when an external control source is used. If external speed control is required, the jumper connection next to the potentionmeter on the board would need to be removed, the installer can then connect to ST1 (using the diagram provided). When an external speed control is fitted, the maximum speed setting available to the external control is limited by the potentiometer setting of the commissioning device.
EC
Please note: This is an estimated adjustment guide
149-CD-POT
The 149-CD-POT is a commissiong device designed to be used with our EC range of fans.
This device will be as standard with our box fan range from May 2018.
The device will allow the for the installer to set the maximum operating speed of the fan that it isconnected to.
The installer or commissioning engineer can adjust the fan speed using the potentiometer built onto the149-CD-POT board. This potentionmeter can either be used for single speed adjustment or to set amaximum speed for the fan to operate at when an external control source is used.
If external speed control is required, the jumper connection next to the potentionmeter on the boardwould need to be removed, the installer can then connect to ST1 (using the diagram provided).
When an external speed control is �tted, the maximum speed setting available to the external control islimited by the potentiometer setting of the commissioning device.
10/07/2018MK-149-CD-POT Issue: Saved Date:A
Level / Speed OHMS (Ω)
10 10 (Ω)
9 9 (Ω)
8 8 (Ω)
7 7 (Ω)
6 6 (Ω)
5 5 (Ω)
4 4 (Ω)
3 3 (Ω)
2 1.5 (Ω)
1 500 (Ω)
0 1 (Ω)149-CD-POT
Tel 01384 275800 Fax 01384 275810 Email [email protected] Website eltafans.com4
Wiring DiagramsCOMPACT SCP AC
Please use the table(s) below to match up the product code and the wiring diagram number.
Single Phase 220V to 240V / 50Hz Three Phase 380V - 415V / 50Hz
PageNo.
Product Code
Wiring Diagram No.
6 SCP250/4-1AC 152-500
6 SCP315/4-1AC 152-500
6 SCP350/4-1AC 152-500
6 SCP500/4-1AC 152-500
6 SCP560/4-1AC 152-500
6 SCP630/4-1AC 152-500
PageNo.
Product Code
Wiring Diagram No.
7 SCP250/4-3AC 152-611
7 SCP315/4-3AC 152-611
7 SCP350/4-3AC 152-611
7 SCP400/4-3AC 152-611
7 SCP450/4-3AC 152-611
7 SCP450/4B-3AC 152-611
7 SCP500/4-3AC 152-611
8 SCP500/6-3AC 152-608
7 SCP560/4-3AC 152-611
8 SCP560/6-3AC 152-608
7 SCP630/4-3AC 152-611
8 SCP630/6-3AC 152-608
9 SCP710/4/6-3AC 152-614
9 SCP710/6/8-3AC 152-614
9 SCP800/6/8-3AC 152-614
Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication. Confirmation of dimensions and data will be supplied on request. 5
Single Phase 220V - 277V / 50Hz or 60Hz
PageNo.
Product Code
Wiring Diagram No.
10 SCP250-1EC 152-711
10 SCP315-1EC 152-711
10 SCP350-1EC 152-711
10 SCP400-1EC 152-711
10 SCP450-1EC 152-711
10 SCP500-1EC 152-711
10 SCP560-1EC 152-711
10 SCP630-1EC 152-711
10 SCP710-1EC 152-711
Wiring Diagrams
Please use the table(s) below to match up the product code and the wiring diagram number.
COMPACT SCP EC
Tel 01384 275800 Fax 01384 275810 Email [email protected] Website eltafans.com6
Wiring Diagrams152-500 AC
FAN TERMINALBOX
LINK NEEDSTO BE FITTED
TB (W
HITE
)
220 - 240V 1PH 50Hz SUPPLY
E (GR
EEN/
YELL
OW)
TB (W
HITE
)
BROW
N
BLUE
U2 (B
LACK
)
U1 (R
ED)
Z1 (B
LUE)
CAPACITOR
EL N
FIXED SPEED CONNECTION
GREE
N/YE
LLOW
BROW
N
BLUE
L/U1 N/U2TBTB AUX
Z2 (Y
ELLO
W)
THERMAL CUT - OUTCONNECT INTO
STARTER CONTROLCIRCUIT
TB (W
HITE
)
E (GR
EEN/
YELL
OW)
TB (W
HITE
)
Z2 (Y
ELLO
W)
BROW
N
BLUE
U2 (B
LACK
)
U1 (R
ED)
Z1 (B
LUE)
CAPACITOR
FAN TERMINALBOX
GREE
N/YE
LLOW
L/U1 N/U2TBTB AUX
220 - 240V 1PH 50Hz SUPPLY
N
CONTROLLERTERMINAL BOX
LE
GREE
N/YE
LLOW
BLUE
BROW
N
BLUE
BROW
N
BROW
N
VARIABLE SPEED CONNECTION CONTROLLER TYPE TC12, TC14, TC18, TC110, TC112
THERMAL CUT - OUTCONNECT INTO
STARTER CONTROLCIRCUIT
L NN AUX EL
TB (W
HITE
)
E (GR
EEN/
YELL
OW)
TB (W
HITE
)
Z2 (Y
ELLO
W)
BROW
N
BLUE
U2 (B
LACK
)
U1 (R
ED)
Z1 (B
LUE)
CAPACITOR
FAN TERMINALBOX
L/U1 N/U2TBTB AUX
EU1TKTK L AUXU2N
BLUE
BROW
N
GREE
N/YE
LLOW
BROW
N
BROW
N
BLUE
VARIABLE SPEED CONNECTION CONTROLLER TYPE EL31TK, EL61TK
GREE
N/YE
LLOW
220 - 240V 1PH 50Hz SUPPLY
N
CONTROLLERTERMINAL BOX
L E
ALL WIRING AND CONTROL EQUIPMENT MUST COMPLY TO THELATEST IEE REGULATIONS, IN PARTICULAR PART 552-01-02/03
02/03/2015MK-152-500 Issue: Saved Date:EAll wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. MK-152-500 Issue E: 02.03.2015Check the individual product accessories table for fan controller compatibility.
Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication. Confirmation of dimensions and data will be supplied on request. 7
Wiring Diagrams152-611 AC
GREE
N/YE
LLOW
EL1
FAN TERMINALBOX
380 - 440V 3PH 50Hz SUPPLY
FIXED SPEED CONNECTION
L3L2
GREY
BLAC
K
BROW
N
W2 V1 V2 W1U2U1TBTB
THERMAL CUT-OUTCONNECT INTO
STARTER CONTROLCIRCUIT
U1 U2 W1V2V1W2
L1/L U V WL3L2/N 4 5 6 731 2 8 11109
FAN TERMINALBOX
BROW
N
BLAC
K
GREY
BROW
N
BLAC
K
GREY
GREE
N/YE
LLOW
EL1
380 - 440V 3PH 50Hz SUPPLY
VARIABLE SPEED CONNECTION C/W 3PH - 3PH IP55/66 INVERTER
L2 L3
1 TO 7PRE - WIRED
10 RELAY COMMON11 RELAY CONTACT
3PH - 3PHIP55/66 INVERTER
ANALOG / DIGITALINPUT CONNECTIONS
TBTB
GREE
N/YE
LLOW
THERMAL CUT-OUTCONNECT INTO
STARTER CONTROLCIRCUIT
L1/L U V WL3L2/N 4 5 6 731 2 8 11109
ENSURE FAN IS SUITABLE FOR THIS CONNECTION.IF IN DOUBT CONTACT ELTA FANS
BROW
N
BLUE
GREE
N/YE
LLOW
EL
220 - 240V 1PH 50Hz SUPPLY
VARIABLE SPEED CONNECTION C/W 1PH - 3PH IP20 INVERTER
N
1PH - 3PHIP20 INVERTER
ANALOG / DIGITALINPUT CONNECTIONS
1: +24V OUTPUT2: STOP/RUN DI13: FWD/REV DI24: ANALOG/PRESET DI35: +10V OUTPUT6: ANALOG INPUT7: 0V
10 RELAY COMMON11 RELAY CONTACT
FAN TERMINALBOX
THERMAL CUT-OUTCONNECT INTO
STARTER CONTROLCIRCUIT
GREE
N/YE
LLOW
TB TB
GREY
BLAC
K
BROW
N
W2 V1 V2 W1U2U1
L1/L U V WL3L2/N 4 5 6 731 2 8 11109
ANALOG / DIGITALINPUT CONNECTIONS
1PH - 3PHIP55/66 INVERTER
10 RELAY COMMON11 RELAY CONTACT
1 TO 7PRE - WIRED
N
VARIABLE SPEED CONNECTION C/W 1PH - 3PH IP55/66 INVERTER
220 - 240V 1PH 50Hz SUPPLY
L E
GREE
N/YE
LLOW
BLUE
BROW
N
ENSURE FAN IS SUITABLE FOR THIS CONNECTION.IF IN DOUBT CONTACT ELTA FANS
FAN TERMINALBOXU1 U2 W1V2V1W2
BROW
N
BLAC
K
GREY
TBTB
GREE
N/YE
LLOW
THERMAL CUT-OUTCONNECT INTO
STARTER CONTROLCIRCUIT
L1/L U V WL3L2/N 4 5 6 731 2 8 11109
ANALOG / DIGITALINPUT CONNECTIONS
10 RELAY COMMON11 RELAY CONTACT
L3L2
VARIABLE SPEED CONNECTION C/W 3PH - 3PH IP20 INVERTER
380 - 440V 3PH 50Hz SUPPLY
L1 E
GREE
N/YE
LLOW
GREY
BLAC
K
BROW
N
1: +24V OUTPUT2: STOP/RUN DI13: FWD/REV DI24: ANALOG/PRESET DI35: +10V OUTPUT6: ANALOG INPUT7: 0V 3PH - 3PH
IP20 INVERTER
FAN TERMINALBOX
THERMAL CUT-OUTCONNECT INTO
STARTER CONTROLCIRCUIT
GREE
N/YE
LLOW
TB TB
GREY
BLAC
K
BROW
N
W2 V1 V2 W1U2U1
ALL WIRING AND CONTROL EQUIPMENT MUST COMPLY TO THELATEST IEE REGULATIONS, IN PARTICULAR PART 552-01-02/03
21/05/2015MK-152-611 Issue: Saved Date:CAll wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. MK-152-611 Issue C: 21.05.2015Check the individual product accessories table for fan controller compatibility.
Tel 01384 275800 Fax 01384 275810 Email [email protected] Website eltafans.com8
Wiring Diagrams152-608 AC
All wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. MK-152-608 Issue E: 21.06.2018Check the individual product accessories table for fan controller compatibility.DM25/06/2013
MBK0066EARTH TERMINALSRELOCATED
C
DM16/01/2013
RE-ORDERED L3, L2, L1TO L1, L2, L3 ON TOPRIGHT DIAGRAM.REPLACED TERMINALSTRIP VISUAL, WITHCONNECTION TEXT.
DMOK0041B
MB06-07-2015
REMOVED 'N (BLACK)'NOTE AND WIRE
AWMK0132D
DMO21/06/18
UPDATED WIRINGTAGS AND COLORSTO MATCHMANUFACTURING
PBK0233E
L1/L U V WL3L2/N 4 5 6 731 2 8 11109
THERMAL CUT-OUTCONNECT INTO
STARTER CONTROLCIRCUIT
FAN TERMINALBOX
TB (W
HITE
)
E (GR
EEN/
YELL
OW)
TB (W
HITE
)
U1 (R
ED)
V1 (Y
ELLO
W)
W1 (
BLUE
)
L3
VERIABLE SPEED CONNECTION CONTROLLER TYPE 3PH - 3PH IP20 INVERTER
ANALOG / DIGITALINPUT CONNECTIONS
3PH - 3PHIP20 INVERTER
10 RELAY COMMON11 RELAY CONTACT
L2
380 - 440V 3PH 50Hz SUPPLY
L1 E
GREE
N/YE
LLOW
GREY
BLAC
K
BROW
N
GREE
N/YE
LLOW
GREY
BLAC
K
BROW
N
1: +24V OUTPUT2: STOP/RUN DI13: FWD/REV DI24: ANALOG/PRESET DI35: +10V OUTPUT6: ANALOG INPUT7: 0V
TB TB W1V1U1TB TB W1V1U1
THERMAL CUT-OUTCONNECT INTO
STARTER CONTROLCIRCUIT
FAN TERMINALBOX
TB (W
HITE
)
E (GR
EEN/
YELL
OW)
TB (W
HITE
)
U1 (R
ED)
V1 (Y
ELLO
W)
W1 (
BLUE
)
L3
VERIABLE SPEED CONNECTION CONTROLLER TYPE 3PH - 3PH IP55 INVERTER
ANALOG / DIGITALINPUT CONNECTIONS
3PH - 3PHIP55 INVERTER
10 RELAY COMMON11 RELAY CONTACT
L2
380 - 440V 3PH 50Hz SUPPLY
L1 E
1 - 7 PRE WIRED
GREE
N/YE
LLOW
GREY
BLAC
K
BROW
N
GREE
N/YE
LLOW
GREY
BLAC
K
BROW
N
L2/N L3 WVUL1/L 9 10 11821 3 7654
THERMAL CUT-OUTCONNECT INTO
STARTER CONTROLCIRCUIT
W1 (
BLUE
)
V1 (Y
ELLO
W)
U1 (R
ED)
TB (W
HITE
)
E (GR
EEN/
YELL
OW)
TB (W
HITE
)
FAN TERMINALBOX
GREE
N/YE
LLOW
GREY
BLAC
K
BROW
N
U1 V1 W1TBTB
L3L2 EL1 U WV
380 - 440V 3PH 50Hz SUPPLY
EL1 L2 L3
CONTROLLERTERMINAL BOX
GREE
N/YE
LLOW
GREY
BLAC
K
BROW
N
VARIABLE SPEED CONNECTION CONTROLLER TYPE TC33, TC35, TC310
W1 (
BLUE
)
V1 (Y
ELLO
W)
U1 (R
ED)
TB (W
HITE
)
THERMAL CUT-OUTCONNECT INTO
STARTER CONTROLCIRCUIT
L1 L2 L3
E (GR
EEN/
YELL
OW)
TB (W
HITE
)
FAN TERMINALBOX
E
380 - 440V 3PH 50Hz SUPPLY
GREE
N/YE
LLOW
GREY
BLAC
K
BROW
N
FIXED SPEED CONNECTION
U1 V1 W1TBTB
A3A3152-608
NTS
C
DRAWING No.
SHEET OF ISSUE
DRAWN BY
DATE
SCALE STATUS
APPROVED
CHECKEDELTA FANS LTD,17 BARNES WALLIS ROAD,SEGENSWORTH INDUSTRIAL ESTATE,FAREHAM, HAMPSHIRE. PO15 5ST.Tel. 01489 566500 Fax. 01489 566555
Elta Fans Ltd. own the copyright of this drawing/
in writing from its owners Elta Fans Ltd.and must not be reproduced without permission
con�dence and which must not be used for anyspeci�cation document which is supplied in
C
FINISH
DIMENSIONS ARE IN mm UNLESS STATED OTHERWISE
BYISS CN.
DATE CHKD
ISS CN. BY
DATE CHKD
ISS CN. BY
DATE CHKD
ISS CN. BY
DATE CHKD
A C D E
1 1 E
24-11-11
PG
PB
Ipurpose other than that for which it is supplied
B
1010 N/A
AWM
Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication. Confirmation of dimensions and data will be supplied on request. 9
AC
All wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. MK-152-614 Issue B: 29.04.2015Check the individual product accessories table for fan controller compatibility.
Wiring Diagrams152-614
THERMAL CUT-OUTCONNECT INTO
STARTER CONTROLCIRCUIT
GREE
N/YE
LLOW
EL1
FAN TERMINALBOX
380 - 440V 3PH 50Hz SUPPLY
LOW SPEED CONNECTION(STAR CONFIGURATION)
L3L2
GREY
BLAC
K
BROW
N
W2 V1 V2 W1U2U1TBTB
V2 (O
RANG
E)
W1 (
BLUE
)
U2 (B
LACK
)
V1 (Y
ELLO
W)
W2 (
WHI
TE)
U1 (R
ED)
E (GR
EEN/
YELL
OW)
TB (B
LACK
& W
HITE
)
TB (B
LACK
& W
HITE
)
V2V1W2 W1U2U1TBTB
1: +24V OUTPUT2: STOP/RUN DI13: FWD/REV DI24: ANALOG/PRESET DI35: +10V OUTPUT6: ANALOG INPUT7: 0VBR
OWN
BLAC
K
GREY
GREE
N/YE
LLOW
BROW
N
BLAC
K
GREY GR
EEN/
YELL
OW
EL1
380 - 440V 3PH 50Hz SUPPLY
L2
10 RELAY COMMON11 RELAY CONTACT
3PH - 3PHIP20 INVERTER
ANALOG / DIGITALINPUT CONNECTIONS
VARIABLE SPEED CONNECTION CONTROLLER TYPE 3PH - 3PH IP20 INVERTER
L3
THERMAL CUT-OUTCONNECT INTO
STARTER CONTROLCIRCUIT
9 10 11821 3 7654L2/N L3 WVUL1/L
4 5 6 731 2 8 11109L1/L U V WL3L2/N
BROW
N
BLAC
K
GREY
GREE
N/YE
LLOW
BROW
N
BLAC
K
GREY GR
EEN/
YELL
OW
1 - 7 PRE WIRED
EL1
380 - 440V 3PH 50Hz SUPPLY
L2
10 RELAY COMMON11 RELAY CONTACT
3PH - 3PHIP55 INVERTER
ANALOG / DIGITALINPUT CONNECTIONS
VARIABLE SPEED CONNECTION CONTROLLER TYPE 3PH - 3PH IP55 INVERTER
L3
THERMAL CUT-OUTCONNECT INTO
STARTER CONTROLCIRCUIT
TB TB U1 U2 W1W2 V1 V2
GREE
N/YE
LLOW
EL1
FAN TERMINALBOX
380 - 440V 3PH 50Hz SUPPLY
HIGH SPEED CONNECTION(DELTA CONFIGURATION)
L3L2
GREY
BLAC
K
BROW
N
W2 V1 V2 W1U2U1TBTB
V2 (O
RANG
E)
W1 (
BLUE
)
U2 (B
LACK
)
V1 (Y
ELLO
W)
W2 (
WHI
TE)
U1 (R
ED)
E (GR
EEN/
YELL
OW)
TB (B
LACK
& W
HITE
)
TB (B
LACK
& W
HITE
)
THERMAL CUT-OUTCONNECT INTO
STARTER CONTROLCIRCUIT
ALL WIRING AND CONTROL EQUIPMENT MUST COMPLY TO THELATEST IEE REGULATIONS, IN PARTICULAR PART 552-01-02/03
29/04/2015MK-152-614 Issue: Saved Date:B
Tel 01384 275800 Fax 01384 275810 Email [email protected] Website eltafans.com10
Wiring Diagrams152-711
All wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. MK-152-711 Issue C: 15.01.2019Check the individual product accessories table for fan controller compatibility.
0-10V DC INPUT (IF REQUIRED)
GND 0-10 VDC
ALL WIRING AND CONTROLS EQUIPMENT MUST COMPLY TO THELATEST IET REGULATIONS, IN PARTICULAR PART 552-01-02/03
15/01/2019MK-152-711 Issue: Saved Date:C
5
NOTE: TAG REFERENCES RELATE TO MOTOR CONTROL WIRES, AND NOT 149-POT-10
65
BLACK
BROWN
JUMPERREMOVED *
MAX SPEEDTRIMMER
PENL
POW
ERCO
NTRO
LS
RED
BLUE
WHITE
YELLOW
G/Y
BLUE
BROWN
220 - 277V 1PH 50HzMAINS SUPPLY
LN
SINGLE FAN
1PH EC SINGLE FAN C/W 149-CD-POT & 149-POT-10
BLUEBROW
N
GREE
N/YE
LLOW
GND 10V E1
MIN MAX
E1GND
ST1
ST2
149-CD-POT
23
41
FOR USE WITH:SCP250-1ECSCP315-1ECSCP350-1ECSCP400-1ECSCP450-1ECSCP500-1ECSCP560-1ECSCP630-1ECSCP710-1EC
65
BLACK
BROWN
REMOVE LINK WHEN USINGEXTERNAL POTENTIOMETER OREXTERNAL CONTROL SIGNAL
POTENTIOMETER FOR SINGLESPEED ADJUSTMENT OR MAXSPEED SELECTION
PENL
POW
ERCO
NTRO
LS
RED
BLUE
WHITE
YELLOW
G/Y
BLUE
BROWN
220 - 277V 1PH 50HzMAINS SUPPLY
LN
SINGLE FAN
1PH EC SINGLE FAN C/W 149-CD-POT & 0-10VDC INPUT
BLUE
BROW
N
GREE
N/YE
LLOW
GND 10V E1
MIN MAX
E1GND
ST1
ST2
149-CD-POT
23
41
FOR USE WITH:SCP250-1ECSCP315-1ECSCP350-1ECSCP400-1ECSCP450-1ECSCP500-1ECSCP560-1ECSCP630-1ECSCP710-1EC
149-POT-10
2 7 61
NOTE:*JUMPER REMOVED WHEN EXTERNALCONTROL SOURCE IS USED.
Tag Purpose Description
L Live Live power supply, 220-277V
N Neutral Neutral from power supply
Permanent Earth Permanent earth from power supply
1 DC Voltage [2-10V] DC control voltage input(2 to 10VDC input)2 DC Current [4-20mA] DC control current input(4 to 20mA input)
3 Frequency [10-95%]Frequency duty-cycle (PWM)
Voltage: 10 to 24VpkFrequency: 80Hz(10 to 95% input)
4 Speed Reference Tacho output
5 10VDC output 10VDC source output
6 GND / Common DC Common
EC
Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication. Confirmation of dimensions and data will be supplied on request. 11
EC Declaration of Conformity EC Declaration of Incorporation
Description of Equipment:Building Services Ranges - Air movement fan
Equipment model numbers for safe area fans:SCP, SPA, SAX, SCD, SDA, SCC, SLC, SCPP, SPP, SAMF, HIT, SEM, SEL, ISEO IMF, SH, SSD, SQS, SQSDCV, SQU, SMB, STD, SQT, SQT-DCV, SCH, SCHT, SSDR, SSDRDCV, STDR, STDRDCV, SB, SQU-HT, SSQU-HT, SDF, ZFHIC, SRC, CF, TF
Relevant / applied directives:Machinery directive 2006/42/EC, Low voltage directive 2014/35/EU
Relevant / applied directives where applicable:Energy related products directive 2009/125/EC (when used in Europe) Electromagnetic compatibility directive 2014/30/EU (where driven via Inverter)
Relevant / applied directives where applicable:BS EN ISO 12100 : 2010BS EN 14694 : 2003 + A1 : 2011BS EN 308:1997BS EN ISO 5801:2008
In accordance with the Machinery Directive 2006/42/EC;
The design of the partly completed machine, listed above, complies with the Essential Health and Safety Requirements (EHSRs) of ANNEX I, sections 1.1.2, 1.1.5, 1.4.1, 1.5.1 in EC Machinery Directive 2006/42/EC.
Machinery is incomplete and must not be put into service until such time as the machinery which is partly complete, is to be incorporated, and has been assessed and Declared in Conformity with the provi-sions of any relevant parts of the Machinery Directive.
We undertake to transmit, upon reasoned request by appropriate na-tional authorities, relevant information relating to the partly completed machinery identified above.
Manufacturer:Elta Fans Limited46 Third AvenuePensnett Trading EstateKingswinfordWest MidlandsDY6 7USUnited Kingdom
Date / Signature of Manufacturer: Document last revised: 28th March 2017
Name / Position of Signatory: Mr. Robert Rees Q.A.Manager Elta Fans LtdThis is an electronic document and is valid without a signature or date. Issue Status B
Herewith we declare that the air movement equipment below, on the basis of its design and construction as partly completed machines brought onto the market complies with relevant health and safety requirements of the EC Directives stated below. In the event that alterations are made to the machinery without prior consent from Elta Fans Ltd, this declaration becomes invalid.
EC Declaration of conformity/incorporation
535-IOM0015 Issue D
eltafans.com
Tel +44 (0) 1384 275800Fax +44 (0) 1384 275810Email [email protected]
46 Third Avenue, Pensnett Trading Estate, Kingswinford, West Midlands, DY6 7US United Kingdom
Tel +44 (0) 1489 566500Fax +44 (0) 1489 566555Email [email protected] / [email protected]
17 Barnes Wallis Road, Segensworth East Industrial Estate, Fareham, Hampshire, PO15 5ST United Kingdom
Applied Technology & Building Services Export
Building Services
BS EN ISO 9001:2015 FM 556465
A member ofHEVAC ASSOCIATION