Compact ACB 1600A
Compact ACB1600A
Contents
• Ratings ································································································································································································································ 03
• Ordering ·························································································································································································································· 04
• Electrical diagram ····································································································································································· 06
• Accessories ····································································································································································································· 08
• Structure ······················································································································································································································· 09
• Dimensions ········································································································································································································ 10
Compact ACB 1600A
I 3
Compact ACB 1600A
RatingsCommon CharacteristicsNumber of poles (P) 3P/4P
Frequency (Hz) 50/60Hz
Rated operating voltage (V, Ue) 690V
Rated insulation voltage (V, Ui) 1000V
Rated impulse withstand voltage (kV, Uimp) 12kV
Circuit Breaker as per IEC60947-2Type AN/AH/AR-C
Description AN-16C AH-16C AR-10C
Ampere Frame (AF) 1600 1600 1000
Rated current (In Max.)at 40℃
(A) 400 400 400
(A) 630 630 630
(A) 800 800 800
(A) 1000 1000 1000
(A) 1250 1250 -
(A) 1600 1600 -
Rated current of neutral pole (A) 1600 1600 1000
Rated breaking capacity (Icu) (kA) IEC60947-2
AC 690V/600V/550V
42
50 -
AC 500V/480V 50 -
AC 415V/380V/440V 50 -
AC 415V/380V50
66 150
AC 240V/220V 66 150
Rated breaking capacity (Ics) (kA,%×Icu) 100%
Rated making capacity (Icm) (kA) 88.2 105/138.6 -
Rated Short-time capacity (Icw) (kA) 1sec 42/50 50 -
Operating time (t) (ms)
Total breaking time 40
Closing time 70
Common Mechanical and Electrical Life Cycle
Life cycle (time)Mechanical 12,500 5,000
Electrical 6,000 3,000
Common Demension and Weight
Weight (3P/4P) (kg)Draw-out type (3P/4P) 16/19.5
Cradle (3P/4P) 22/26Fixed type (3P/4P) 16/19.5
Dimension (3P/4P) (mm)
Draw-out type(H : 361.3, D : 257)
W(3P/4P) 255.4/326
Fixed type(H : 268, D : 185.6)
W(3P/4P) 272.4/342.4
Main Characteristics ● Rated current : Cat.A ~1000A, (Ics: 150kA/415Vac Ics=100%*Icu)
Cat.B ~1600A ● Rated breaking time : 3 cycle ● Short time withstand current : 50kA/1sec (Cat.B) ● Mechanical life cycle(without maintenance) :
12,500(Cat.B), 5,000(Cat.A)● Cradle : Standard type(Bottom operating) ● Various operating(control) powers
- DC 24/48V, AC/DC110V, DC125V, AC/DC220V, AC 380V
● Accessories - ACB: UVT, Ready to Close S/W, Remote reset coil(RES), Rating Plug,
Manual Reset Button, Counter, ON/OFF Button Lock, Key Lock, etc.- Cradle: MOC(Mechanism Operating Cell s/w), Cell S/W(Cradle Position
Cell s/w), Mechanical Interlock, Door Interlock, Position Keylock, Padlock/Position Lock, Safety Shutter, etc.
Standards● IEC 60947-2● DEKRA CB & CCC Certificates
(Test for the certificates is expected to be finished in Jun.)
4I
Ordering
* TCS : Tripping coil supervision
* L,S,I,G configuration as standard (with LED indicators)
* Ground fault detection is basic. (Internal CT Vector Sum system)* L,S,I,G configuration as standard (with LED indicators)
* Comm. And output contacts DO NOT work under self-power condition. (AC0, AK0, AX0, AC5, AK5, AX5)
* Communication and output contacts for L,S,I,G do not work except OCR LED without control power supply.
- AG0, AG5, AZ0, AZ5, AE0, AE5
* Communication functions are Normal. (Function unavailable without control power supply)
* Applicable to generator protection purpose* Voltage module of P type or more is basic.
* Communication functions are Normal. (Function unavailable without control power supply)
* Applicable to generator protection purpose* Voltage module of P type or more is basic.
M1 D1 D1 NG0FX
Motor rated voltage
MA Without Motor
M1 AC/DC 100V ~ 130V
M2 AC/DC 200V ~ 250V
M3 DC 125V
M4 DC 24V ~ 30V
M5 DC 48V ~ 60V
M6 AC 380V ~ 415V
M7 AC 440V ~ 480V
M8 AC 48V
0 Without trip relay
N
OCR TYPE
N NORMAL
N
OCR TYPE
N NORMAL
A
OCR TYPE
A Ammeter
P
OCR TYPE
P Power meter
S
OCR TYPE
S Supreme meter
0 Without trip relay
G
Communication & protection
G Ground fault (Residual earth fault protection), No Communication
V
Communication & protection
V Pre-Trip Alarm
G
Communication & protection
G Ground fault (Residual earth fault protection), No Communication
E Earth Leakage(Extermal CT), No Communication
C Communication + Ground fault (Residual earth fault protection)
X Communication + Earth Leakage(Extermal CT)
G
Communication & protection
C Communication + Ground fault (Residual earth fault protection)
X Communication + Earth Leakage(Extermal CT)
G
Communication & protection
C Communication + Ground fault (Residual earth fault protection)
X Communication + Earth Leakage(Extermal CT)
0 Without trip relay
0
Control voltage & frequency
0 Self-Power, 60Hz
5 Self-Power, 50Hz
1
Control voltage & frequency
1 AC/DC 110V~220V, 60Hz
6 AC/DC 110V~220V, 50Hz
0
Control voltage & frequency
0 Self-Power, 60Hz
1 AC/DC 110V~220V, 60Hz
2 DC 24V~48V, 60Hz
5 Self-Power, 50Hz
6 AC/DC 110V~220V, 50Hz
7 DC 24V~48V, 50Hz
0
Control voltage & frequency
1 AC/DC 110V~220V, 60Hz
2 DC 24V~48V, 60Hz
6 AC/DC 110V~220V, 50Hz
7 DC 24V~48V, 50Hz
0
Control voltage & frequency
1 AC/DC 110V~220V, 60Hz
2 DC 24V~48V, 60Hz
6 AC/DC 110V~220V, 50Hz
7 DC 24V~48V, 50Hz
Closing coil rated voltage
D0 Without Closing coil
D1 AC/DC 100V ~ 130V
D2 AC/DC 200V ~ 250V
D3 DC 125V
D4 DC 24V ~ 30V
D5 DC 48V ~ 60V
D6 AC 380V ~ 480V
D7 AC 48V
Shunt coil rated voltage
D0 Without Shunt coil
D1 AC/DC 100V ~ 130V
D2 AC/DC 200V ~ 250V
D3 DC 125V
D4 DC 24V ~ 30V
D5 DC 48V ~ 60V
D6 AC 380V ~ 480V
D7 AC 48V
Auxiliary switch with charging type
FX Standard 4C with "OFF" charging type
FC Standard 4C with "ON" charging type
SCStandard 4C with "ON"
charging type for TCS type
AN-16C3-10J
I 5
Note 1) UVT and SHT2 can not be selected together, Select one of two.
Note 2) Codes for over 5 optional accessories are composed separately
* 1) AR can be selected up to Ampere Frame 1000AF.* 2) AR can be selected up to 1000AF(CT Spec.)
* UVT Delay module is available over AC / DC 48V
16 C 3
U1 AL C
J10
Ampare Frame E(CT Spec.)
- -
08 800AF
16 1600AF
- -
08 800AF
10 1000AF
Automatic circuit breaker
AN/AH
AR
Rated current
00 None
04 400A
06 630A
08 800A
10 1000A
13 1250A
16 1600A
00 None
04 400A
06 630A
08 800A
10 1000A
ConnectionsDrawout
A Bottom operating (Auto Connect)
J Bottom operating
S Side operating (Auto Connect)
T Side operating
Fixed
H Horizontal terminals
V Vertical terminals
M Horizontal for line, Vertical for load
N Vertical for line, Horizontal for load
P Front terminal
Z Horizontal with speaders
R Vertical with spreaders
T Front connection via vertical connection adapters fitted with cable-lug adapter
X Cable Lug
Phasing
• C : 800~1600AF 3/4P
Standard (N)RST
• V : 800~1600AF 4P
Reversed RST(N)
Poles
• 3 : 3P(C)
• 4 : 4P(C,V)
UVT coil rated voltage
U0 Without UVT coil
U1 AC/DC 100V ~ 130V
U2 AC/DC 200V ~ 250V
U3 DC 125V
U4 DC 24V ~ 30V
U5 DC 48V ~ 60V
U6 AC 380V ~ 480V
U7 AC 48V
Option Table
Character Option name
AL AL1 + MRB
A1 AL1 + MRB + RES(AC110~130V) * AC private use
A3 AL1 + MRB + RES(DC110~125V) * DC private use
A4 AL1 + MRB + RES(AC200~250V) ** AC private use
A5 AL1 + MRB + Auto Reset
A7 AL1 + MRB + RES(DC110~125V) + Auto Reset * DC private use
A8 AL1 + MRB + RES(AC200~250V) + Auto Reset * AC private use
A9 AL1 + MRB + RES(AC110~130V) + Auto Reset * AC private use
C C COUNTER **AH only
B B On/Off Button lock
M MI Mechanical interlock **AH only
D DI or MOC Mechanism operated cell switch
K K1 Key Lock
K2 K2 Key Interlock Set
R RCS Ready to Close switch
T TM Temperature Monitoring **AH only
H1
SHT2 Note 1)
AC/DC 100V ~ 130V
H2 AC/DC 200V ~ 250V
H3 DC 125V
H4 DC 24V ~ 30V
H5 DC 48V ~ 60V
H6 AC 380V ~ 480V
H7 AC 48V
N01 A4 (AL1 + MRB + RES(AC200~250V))+C(Counter)+B(ON/OFF Button Lock)+K(Key Lock)+R(Ready to Close switch)+M(Mechanicl Interlock)+E(Spring Auto Release)
N02 AL (AL1 + MRB)+K(Key Lock(OFF Lock))+R(Ready to Close switch)+D(Door Interlock or MOC)+H1(AC/DC 100V ~ 130V, Double Shunt coil)+E(Spring Auto Release)
N03 C(Counter)+B(ON/OFF Button Lock)+K2(Key Interlock Set)+R(Ready to Close switch)+T(Temperature Monitoring)
N04 A4(AL1 + MRB + RES(AC200~250V))+B(ON/OFF Button Lock)+K(Key Lock(OFF Lock))+M(Mechanical Interlock)+T(Temperature Monitoring)
N05 A1(AL1+MRB+RES110~130V)+B(ON/OFF Button Lock)+K(Key Lock(OFF Lock))+R(Ready to Close switch)+M(Mechanical Interlock)+T(Temprature Monitoring)Interlock)+T(Temprature Monitoring)
AN / AH / AR
/
-
6I
Electrical diagram
V1
E225
282
D2
UVT
Axb
C12
SHT2
C2
SHT1
A2CC
U1M
4131
2111
Pow
er s
uppl
y
Common
Reset
ZSI Input
ZSI Output
ZCT
Volta
ge M
odul
eTe
mpe
ratu
reM
odul
e
Inte
rnal
/ Ex
tern
al w
iring
(by
cust
omer
)
Con
nect
or o
f the
con
trol c
ircui
t ter
min
al o
f dra
wou
t typ
e
or
AC
BTr
ip re
lay
Dig
ital t
rip re
lay
Read
y to
close
Seco
ndar
ytri
p co
il
UVT
Alar
mC
onta
ctM
ain
circ
uit
181
/RES
(+)
182
/RES
(-)
Tem
pera
ture
Sens
or-2
Tem
pera
ture
Sens
or-1
Elec
trica
lop
erat
ion
circu
itCh
arge
com
plet
ion
cont
act
Aux
iliar
y sw
itch
Ther
mal
,co
mm
unic
atio
nre
mot
e co
ntro
l mod
ule
Z4Z2
485-
544
534
524
V2V3
VNE1
Z3Z1
485+
R11
R22
513
R2
R1
251
81D
1C
11C
1A
1U
2U
442
4434
2224
1214ON
T1TC
1T2
TC2
32
Axb
Axb
Axb
Axb
OFF
ON
Charged
OFF
OFF
11
81
485+
12
82
485-
~ ~
~
~ ~
4142
11
181
Z1
14
182
Z2
U1
251
Z3
U2
252
Z4
U1
R1
E1
U4
R2
E2
A1
513
VN
A2
514
V3
344
C1
R11
TC
1C
2
R22
TC
2
C11
311
C12
4144
Auxi
liary
sw
itch
"b"
cont
act
Auxi
liary
sw
itch
"a"
cont
act
Cha
rge
com
plet
ion
sig
nal
Mot
or c
harg
ing
Clo
sing
coi
l
Shun
t trip
2nd
shun
t trip
Vol
tage
inpu
t ter
min
al o
f UVT
coi
l
Ala
rm1
"b"
cont
act
Alar
m2
"b"
cont
act o
r RES
Coi
l
Rea
dy to
clo
se s
witc
Con
trol p
ower
for t
rip u
nit
Faul
t cau
se in
dica
tion
cont
acts
Alar
m re
set (
Trip
cau
se L
EDs,
cont
acts
)
RS-
485
com
mun
icat
ion
ZSI i
nput
ZSI o
utpu
t
ZCT
Volta
ge m
odul
e
Tem
pera
ture
mod
ule
Cel
l sw
itch
Term
inal
cod
e de
scrip
tion
D1
D2
~T
1T
2
Acc
esso
ry c
ode
desc
riptio
n
Aux
iliary
sw
itch
Long
tim
e de
lay
trip
indi
cato
r
Shor
t tim
e de
lay/
instan
tane
ous
Gro
und
faul
t tri
p in
dica
tor
Cel
l sw
itch
Mot
or
Clo
sing
coi
l
1st Sh
unt co
il
2nd
Shun
t co
il
UVT
coil
Ax
LTD
GT
D
ST
D/I
nst
CL1
~C
L4
M CC
UVT
SHT1
SHT2
Not
e) 1
. The
dia
gram
is s
how
n w
ith c
ircui
t de-
ener
gize
d, a
ll de
vice
s op
en a
nd c
harg
ed a
nd re
lays
in n
orm
al p
ositi
on
2. R
elay
is n
orm
al c
ondi
tion
and
char
ging
type
is "
Off-
Cha
rgin
g"
3. T
he s
tand
ard
of a
uxili
ary
cont
act i
s 4C
. The
aux
iliar
y sw
itch
in a
bove
dia
gram
is c
ompo
sed
of 4
C. S
ee 4
8 pa
ge fo
r mor
e de
tail
on a
uxili
ary
switc
hes.
4
. Opt
ion
- R
eady
to c
lose
con
tact
, Trip
ala
rm c
onta
ct, U
VT c
oil,
Fully
cha
rged
con
tact
, sec
onda
ry tr
ip c
oil
- T
empe
ratu
re m
odul
e, V
olta
ge m
odul
e, Z
CT,
ZS
I
5. P
leas
e co
nsul
t us
for t
he u
se o
f ZS
I (Zo
ne s
elec
tive
Inte
rlock
ing)
.
6. R
efer
to th
e pa
ge 3
3 fo
r the
con
nect
ion
of T
rip re
lay
and
the
page
43
for U
VT.
7.
For
con
nect
ing
RS
-485
ver
ify if
the
pola
rity
is c
orre
ct
T
his
diag
ram
is b
ased
on
“CO
NN
ECTE
D”p
ositi
on o
f a c
ircui
t bre
aker
and
Ope
ning
, Mot
or c
harg
ing,
R
elea
sing
of l
ocki
ng p
late
sho
uld
be n
orm
al c
ondi
tion.
I 7
~
~
311
111
382
254
Cell switch
MOC
Terminal code descriptionNote) 8. Contact configuration for Cell Switch can be changeable if necessary
342 344 332 334 322 324 312 314 382 384 372 374 362 364 352 354
341 331 321 311 381 371 361 351
252 242 232 222
251 241 231 221
212
211
152 142 132 122
151 141 131 121
112
111
254 244 234 224 214
253 243 233 223 213
154 144 134 124 114
153 143 133 123 113
C2
SHT1
A2
CC
U1
M
41 31 21 11
Trip Coil Supervision(Option)
Auxiliary switch
Cell switch 4C Cell switch 8C (4C Addition) MOC (Mechanical Operated Cell switchs)
C1 A1 U2 U4 42 34 22 24 12 1432
Electricaloperation circuit
Chargecompletioncontact
ON
Cha
rged
OFF
ONOFF
ON
OFF
CL4
(DIS
CO
N) o
r
CL8
(DIS
CO
N)
CL4
(TES
T)
CL3
(TES
T)
CL7
(TES
T)
CL2
(CO
NN
ECTE
D)
CL1
(CO
NN
ECTE
D)
CL6
(CO
NN
ECTE
D)
CL5
(CO
NN
ECTE
D)
Axc
Axb
Axb
Axb
Axb
Axb
Axb
Axb
Axb
Axb
Axb
Axa
Axa
Axa
Axa
Axa
Axa
Axa
Axa
Axa
Axa
Axc
Axc
Axc
8I
Accessories
ACB
Trip Relay(OCR)
Motor(M)
Closing Coil(CC)
Shunt Coil(SHT)
Under Voltage Trip Device(UVT)
Ready to Close switch(RCS)
Door Interlock(DI)
Mechanical Operated Cell SW(MOC)
Auxiliary Switch(AX)
Key Lock(K1)
Counter(C)
ON/OFF Button Lock(B)
Miss Insertion Preventing Device
(MIP)
Manual Reset Button(MRB)
Cradle
Safety Shutter(ST)
Insulation Barrier(IB)
Cell SW(CEL)
Door Interlock(DI)
Mechanical Operated Cell SW(MOC)
Miss Insertion Prevent Device(MIP)
Racking Interlock & Position Lock(RI)
Condensor Trip Device(CTD)
OCR Tester(OT)
Dust Cover(DC)
Door Frame(DF)
UVT Time Delay Controller(UDC)
Remote Close Open(RCO)
Lifting Hook(LH)
Main ACB
Cradle
I 9
Structure
[ Compact ACB 1600A Cradle Structure ]
Lower type cradle(Main-Type)
Side bracket (Lower type)
10I
Dimensions
• Fixed Type (Front view) AN/AH/AR-C 3P/4P
• Fixed Type(Horizontal type) AN/AH/AR-C 3P
• Fixed Type(Horizontal type) AN/AH/AR-C 4P
108.5
287
209 4
283
230
16
2.3
123.2193.2
342.4
108.5
283
272.4246.4
1623
0
2.9
209
70 70
15
15
246.4
272.4
94.6
57.5
35.9
3723
016
78.126.5 57.5
23.535.9
157.4
56.9
261.
115
0 283
70 70 70
15
316.4
342.4
94.6
57.5
35.9
3723
016
78.126.5 57.5 35.9
23.5
153.4
5715
026
1.1
283
15
R3.5
R3.5
I 11
• Fixed Type(Front view) AN/AH/AR-C 3P/4P
• Fixed Type(Vertical Type) AN/AH/AR-C 3P
• Fixed Type(Vertical Type) AN/AH/AR-C 4P
70707015
94.6
57.5
15
316.4
342.4
35.9
R3.5
108.5
287
209 4
283
230
16
2.3
123.2193.2
342.4
5715
0
261.
1
283
16
157.478.1
26.5 57.523.5
35.9
230
37
246.4
272.4
90.6
57.5
15
108.5
283
272.4246.4
1623
0
2.9
209
5715
0
261.
1
57.5 35.926.5
1623
037
78.1 157.4
12.4
R3.5
35.9
12I
• Draw-out Type(Front view) AN/AH/AR-C 3P/4P
• Draw-out Type(Horizontal type) AN/AH/AR-C 3P
• Draw-out Type(Horizontal type) AN/AH/AR-C 4P
10.3
44 44
15
48129.5756522055220
70 70
137.8 137.65127.735127.7
274 344201201
70 70 70
22075 129.5
90
18.534.5
DisconnectedTest
(Insulation barrier)
220
210
210
230
150
95.5
641
74
641
10.3
37
364.
33
230
210
210
55
7070 7015
70 70
10.3
44 44
15
48129.5756522055220
70 70
137.8 137.65127.735127.7
274 344201201
70 70 70
22075 129.5
90
18.534.5
DisconnectedTest
(Insulation barrier)
220
210
210
230
150
95.5
641
74
641
10.3
37
364.
33
230
210
210
55
7070 7015
70 70
10.3
44 44
15
48129.5756522055220
70 70
137.8 137.65127.735127.7
274 344201201
70 70 70
22075 129.5
90
18.534.5
DisconnectedTest
(Insulation barrier)
220
210
210
230
150
95.5
641
74
641
10.3
37
364.
33
230
210
210
55
7070 7015
70 70
Dimensions
10.3
44 44
15
48129.5756522055220
70 70
137.8 137.65127.735127.7
274 344201201
70 70 70
22075 129.5
90
18.534.5
DisconnectedTest
(Insulation barrier)
220
210
210
230
150
95.5
641
74
641
10.3
37
364.
33
230
210
210
55
7070 7015
70 70
10.3
44 44
15
48129.5756522055220
70 70
137.8 137.65127.735127.7
274 344201201
70 70 70
22075 129.5
90
18.534.5
DisconnectedTest
(Insulation barrier)
220
210
210
230
150
95.5
641
74
641
10.3
37
364.
33
230
210
210
55
7070 7015
70 70
10.3
44 44
15
48129.5756522055220
70 70
137.8 137.65127.735127.7
274 344201201
70 70 70
22075 129.5
90
18.534.5
DisconnectedTest
(Insulation barrier)
220
210
210
230
150
95.5
641
74
641
10.3
37
364.
33
230
210
210
55
7070 7015
70 70
I 13
• Draw-out Type(Front view) AN/AH/AR-C 3P/4P
• Draw-out Type(Vertical Type) AN/AH/AR-C 3P
• Draw-out Type(Vertical Type) AN/AH/AR-C 4P
10.3
44 44
15
48129.5756522055220
70 70
137.8 137.65127.735127.7
274 344201201
70 70 70
22075 129.5
90
18.534.5
DisconnectedTest
(Insulation barrier)
220
210
210
230
150
95.5
641
74
641
10.3
37
364.
33
230
210
210
55
7070 7015
70 70
10.3
44 44
15
48129.5756522055220
70 70
137.8 137.65127.735127.7
274 344201201
70 70 70
22075 129.5
90
18.534.5
DisconnectedTest
(Insulation barrier)
220
210
210
230
150
95.5
641
74
641
10.3
37
364.
33
230
210
210
55
7070 7015
70 70
10.3
44 44
15
48129.5756522055220
70 70
137.8 137.65127.735127.7
274 344201201
70 70 70
22075 129.5
90
18.534.5
DisconnectedTest
(Insulation barrier)
220
210
210
230
150
95.5
641
74
641
10.3
37
364.
33
230
210
210
55
7070 7015
70 70
10.3
44 44
15
48129.5756522055220
70 70
137.8 137.65127.735127.7
274 344201201
70 70 70
22075 129.5
90
18.534.5
DisconnectedTest
(Insulation barrier)
220
210
210
230
150
95.5
641
74
641
10.3
37
364.
33
230
210
210
55
7070 7015
70 70
10.3
44 44
15
48129.5756522055220
70 70
137.8 137.65127.735127.7
274 344201201
70 70 70
22075 129.5
90
18.534.5
DisconnectedTest
(Insulation barrier)
220
210
210
230
150
95.5
641
74
641
10.3
37
364.
33
230
210
210
55
7070 7015
70 70
10.3
44 44
15
48129.5756522055220
70 70
137.8 137.65127.735127.7
274 344201201
70 70 70
22075 129.5
90
18.534.5
DisconnectedTest
(Insulation barrier)
220
210
210
230
150
95.5
641
74
641
10.3
37
364.
33
230
210
210
55
7070 7015
70 70
14I
MEMO
I 15
2017. 05 ⓒ2017. 5 LSIS Co.,Ltd. All rights reserved. / English (01) 2017. 05 Staffcom
www.lsis.com
Specifications in this catalog are subject to change without notice due to continuous product development and improvement.
Overseas Branches• LSIS Shanghai Office (China)
Tel: 86-21-5237-9977 Fax: 86-21-5237-7189
• LSIS Beijing Office (China)Tel: 86-10-5761-3127 Fax: 86-10-5761-3128 E-Mail: [email protected]
• LSIS Guangzhou Offce (China) Tel: 86-20-8326-6784 Fax: 80-20-8326-6287 E-Mail: [email protected]
• LSIS Qingdao Office (China)Tel: 86-532-8501-6058 Fax: 86-532-8501-6057 E-Mail: [email protected]
• LSIS Chengdu Office (China)Tel: 86-28-8670-3200 Fax: 86-28-8670-3203 E-Mail: [email protected]
• LSIS ShenYang Office (China)Tel: 86-24-2321-9050 Fax: 86-24-8386-7210 E-Mail: [email protected]
• LSIS Jinan Office (China)Tel: 86-531-8699-7826 Fax: 86-531-8697-7628 E-Mail: [email protected]
• LSIS Co., Ltd. Tokyo Office (Japan)Tel: 81-3-6268-8241 Fax: 81-3-6268-8240 E-Mail: [email protected]
• LSIS Co., Ltd. Rep. Office (Vietnam)Tel: 84-8-3823-7890 E-Mail: [email protected]
• LSIS Moscow Office (Rossia)Tel: 7-495-258-1466 Fax: 7-495-258-1467 E-Mail: [email protected]
• LSIS Jakarta Office (Indonesia)Tel: 62-21-293-7614 E-Mail: [email protected]
Head Quarter127 LS-ro (Hogye-dong) Dongan-gu, Anyang-si,Gyeonggi-Do, 14119, KoreaTel. 82-2-2034-4902, 4684, 4429 Fax: 82-2-2034-4555
Overseas Subsidiaries• LSIS(Dalian) Co., Ltd. (Dalian, China)
Tel: 86-411-8730-7510 Fax: 86-411-8730-7560 E-Mail: [email protected]
• LSIS(Wuxi) Co., Ltd. (Wuxi, China) Tel: 86-510-8534-6666-8005 Fax: 86-510-8534-4078 E-Mail: [email protected]
• LS VINA Industrial Systems Co., Ltd (Hanoi, Vietnam)Tel: 84-4-6275-8055 Fax: 84-4-3882-0220
• LSIS Middle East FZE (Dubai, U.A.E.)Tel: 971-4-886-5360 Fax: 971-4-886-5361 E-Mail: [email protected]
• LSIS Europe B.V. (Amsterdam, Netherlands)Tel: 31-20-654-1420 Fax: 31-20-654-1429 E-Mail: [email protected]
• LSIS Japan Co., Ltd. (Tokyo, Japan)Tel: 81-3-6268-8241 Fax: 81-3-6268-8240 E-Mail: [email protected]
• LSIS USA Inc. (Chicago, U.S.A)Tel: 800-891-2941 Fax: 847-383-6543 E-Mail: [email protected]