EXHAUST FANS CUD & CUB UPBLAST FANS • Suitable for roof or wall mount • Backward inclined, nonoverloading wheels • Spun aluminum housing • Blades & inlets fabricated from aluminum • Easy access to motor compartment • Fully ventilated motor cooling • Direct drive capacities to 3,400 cfm • Belt drive capacities to 17,725 cfm Custom Fan Solutions rM
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
EXHAUST FANS
CUD & CUB UPBLAST
FANS
• Suitable for roof or wall mount
• Backward inclined, nonoverloading wheels
• Spun aluminum housing
• Blades & inlets fabricated from aluminum
• Easy access to motor compartment
• Fully ventilated motor cooling
• Direct drive capacities to 3,400 cfm
• Belt drive capacities to 17,725 cfm
Custom Fan SolutionsrM
CUD DIRECT DRIVE UPBLAST FANS FEATURES & BENEFITS
• Suitable for roof or wall mount • Backward inclined, nonoverloading wheels • Spun aluminum housing for weather resistant durability • Fully enclosed drive compartment protects motor from airborne contaminants • Fully ventilated motor cooling compartment for long motor life • Quick release latches for easy access to motor compartment • Blades and inlets fabricated from aluminum • Variable speed control (standard on single phase units only) • Disconnect switch • Fully welded leakproof grease drain (except for model CUD10) • 300 F max. temperature rating (except for model CUD10) • Available in the following voltages:
o 115V 1 phase o 208/230460V 3 phase
ACCESSORIES / OPTIONS
• Gravity damper • Motorized damper • Bird screen • Wall mount brackets • Roof curb (vented or nonvented)
• Suitable for roof or wall mount (up to model CUB24/2HP) • Backward inclined, nonoverloading wheels • Spun aluminum housing for weather resistant durability • Fully ventilated motor cooling compartment for long motor life • Quick release latches for easy access to motor compartment • Blades and inlets fabricated from aluminum • Variable pitch motor pulley allows for field adjustment and system balancing • High efficiency wheels and low tip speeds result in quiet operation • Disconnect switch • Fully welded leakproof grease drain • Vibration isolation • 300 F max. temperature rating • Available in the following voltages:
o 115208/230V 1 phase o 208/230460V 3 phase o 208/230V 1 phase o 575V 3 phase
1.0 GENERAL A. Fans shall be model CUD Direct Drive or CUB Belt Drive Upblast Fans as manufactured by Continental Fan
Manufacturing Inc., of Buffalo, NY, and of the size and capacity as indicated on the drawings and fan schedule.
2.0 FAN HOUSING DIRECT DRIVE MODEL CUD A. Fan housing shall be constructed of spun aluminum, roof or wall mount, and direct drive configuration. B. The discharge apron shall have a rolled bead for added strength. C. Curb base shall be constructed of welded galvanized steel. D. The motor mounting plate shall be constructed of heavy gauge steel and isolated from the fan structure with vibration
isolators. E. Motor compartment shall be of a two piece construction, the top cap has quick release clips for easy access.
2.1 FAN HOUSING BELT DRIVE MODEL CUB A. Fan housing shall be constructed of spun aluminum, roof or wall mount (up to model CUB/2HP), and belt drive
configuration. B. The discharge apron shall have a rolled bead for added strength. C. Curb base shall be constructed of welded galvanized steel. D. The motor mounting plate shall be constructed of heavy gauge steel and isolated from the fan structure with vibra
tion isolators. E. Motor compartment shall be of a two piece construction, the top cap has quick release clips for easy access.
3.0 FAN IMPELLER A. Centrifugal impeller shall be backward inclined, nonoverloading. B. The blades and inlets shall be fabricated from aluminum. C. The blades shall be welded to the wheel inlet cone.
4.0 FAN MOTOR AND DRIVE A. Motor shall be ODP. B. Motor shall be of voltage, horsepower, RPM and enclosure as indicated on the fan schedule. C. The fan sheaves shall be cast iron, adjustable pitch, appropriately sized and aligned (CUB models only). D. The belts shall be static conducting, plus oil and heat resistant (CUB models only). E. The fan shaft shall be precision ground and polished (CUB models only). F. The fan shaft bearings shall be heavy duty, prelubricated (CUB models only).
5.0 OPTIONAL FAN ACCESSORIES A. Where indicated, fan shall be provided with the following optional accessories:
• Gravity Dampers • Motorized Dampers • Roof curb (vented or nonvented) • Wall mount brackets • Bird screen
6.0 FAN TESTING A. Centrifugal impeller shall be balanced and mounted in fan assembly. B. Fan assembly shall be run and tested prior to shipment. C. A test report shall be maintained on file for each individual fan.