Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared By: R. J. Home Inspection Services 1256 W. Lathrop Rd., #109 Manteca, CA 95336 1-877-729-0047 Toll Free [email protected] Report Number: 17-0507 Inspector: Royal Jackson Certified Inspector License #20056 © 2017 R. J. Home Inspection Services
62

Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

Aug 05, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

Commercial Building Inspection Report

2148 Brush Street, Oakland, CA 94612 Inspection Date:

July 5, 2017

Prepared For: Joel Lunenfeld

Prepared By: R. J. Home Inspection Services

1256 W. Lathrop Rd., #109 Manteca, CA 95336

1-877-729-0047 Toll Free [email protected]

Report Number: 17-0507

Inspector: Royal Jackson

Certified Inspector License #20056

© 2017 R. J. Home Inspection Services

Page 2: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 2 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Table Of Contents

INTRODUCTION 3

STRUCTURE 8

ROOFING 9

EXTERIOR 10

ELECTRICAL 12

HEATING 13

VENTILATION 14

PLUMBING 15

INTERIOR 16

SUBJECT PHOTOS 18

CITY OF OAKLAND, ADDRESS HISTORY 50

STANDARDS OF PRACTICE 53

COST SUMMARY 62

Page 3: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

Introduction As per the request of Joel Lunenfeld, and in accordance with our inspection agreement dated 7/5/2017, a visual inspection was performed of the property. Our inspection was limited to identify the existing conditions of the following readily visible building components:

Structure Exterior Components Heating Plumbing

Roofing Electrical Ventilation Interior Components

This report is intended for the exclusive use of our client. Use of the information contained within the report by any other party is not intended and, therefore, we accept no responsibility for such use.

BUILDING DESCRIPTION

This is a single-story industrial structure covering approximately 8,575 square feet There is an office area at the front, covering approximately 200 square feet. The city reports that the building was constructed in approximately 1926. The building is presently used as a auto body shop. For the purpose of this report, the front of the building is considered to be facing west.

INQUIRIES TO LOCAL AUTHORITIES As part of the Property Condition Assessment, inquiries were made at the local building department for any outstanding building code violations and to ensure a certificated of occupancy was issued for the building. An inquiry was made at the local fire department to check for any outstanding fire code violations.

The building department reports there are no outstanding building code violations.

CONVENTIONS USED IN THIS REPORT

For your convenience, the following conventions have been used in this report. Major Concern: a system or component which is considered significantly deficient or is unsafe. Significant deficiencies need to be corrected and, except for some safety items, are likely to involve significant expense.Safety Issue: denotes a condition that is unsafe and in need of prompt attention.Repair: denotes a system or component which is missing or which needs corrective action to assure proper and reliable function.Improve: denotes improvements which are recommended but not required.Monitor: denotes a system or component needing further investigation and/or monitoring in order to determine if repairs are necessary. Deferred Cost: denotes items that have reached or are reaching their normal life expectancy or show indications that they may require repair or replacement anytime during the next five (5) years.

Please note that those observations listed under “Discretionary Improvements” are not essential repairs, but represent logical long term improvements.

Page 4: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 4 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

IMPROVEMENT RECOMMENDATION HIGHLIGHTS / SUMMARY

The following is a synopsis of the potentially significant improvements that should be budgeted for over the short term. Other significant improvements, outside the scope of this inspection, may also be necessary. Please refer to the body of this report for further details on these and other recommendations.

MAJOR CONCERNS Windows Possible Major Concern, Repair: The window at the south west corner shows evidence of substantial rot to the

window frame. Repair to the window frame can usually be accomplished by a skilled carpenter; a replacement window is preferred in some cases.

SAFETY ISSUES

REPAIR ITEMS Dome Roofing Repair: The roofing membrane is near the end of its life. Minor repairs might be possible to extend the roof life and to

defer leaks. Damaged or missing roofing material should be repaired. All roof penetrations should be examined and sealed as necessary.

Repair: The wood footings on the roof for the metal support were found to be rotted in many locations. The wood damaged wood should be replaced.

Roof Drainage Repair: Drainage leader box should be cover with screening.

Exterior Walls Repair: Damaged brickwork at the east side of the building should be repaired to preserve the wall. Repair: The loose wood boards on the east side of the building should be re-secured or removed. Repair: Localized rot was observed in the siding at the west side of the building in the mural. Following repair of the

damaged areas (which should be combined with exterior maintenance) proper maintenance of the siding and control of water from roof or surface runoff can avoid further damage.

Address Repair: The address on the exterior wall is incorrect and incomplete.

Windows Repair: Localized evidence of rot was visible at window frame at the north west corner. Repairs are needed.

Door(s) Repair: The frame of the entry door west side shows evidence of localized rot at the top and needs repairs. Repair: The roll-up door on the west side of the building frame at the base shows evidence of localized rot and needs

repairs.

Sidewalk Repair, Safety Issue: The walkway presents a trip hazard where the concrete and asphalt sidewalk meets on the south

west side of the property. This condition should be altered for improved safety.

Fencing Repair: The gate at the north east corner is in only fair condition the top rail is bent. Minor repairs are needed. Repair: The gate at the north east corner is in only fair condition the bottom railing is missing. Minor repairs are

needed.

Outlets Repair: An outlet on the exterior east wall at the office is loose. It should be replaced.

Switches Repair: The loose light switch in the shop bathroom should be secured.

Page 5: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 5 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Lights Repair: The fluorescent lights in the upper level room are inoperative. If the bulbs are not blown, the circuit should be

repaired.

Exhaust Fan Repair: Office bathroom exhaust fan is inoperative.

Water Heater Repair: The discharge piping serving the Temperature and Pressure Relief (TPR) Valve for the water heater should

terminate not less than 6 inches or more than 24 inches above the floor/drip pan.

Fixtures Repair: The faucet(s) in the shop bathroom is leaking.

Windows Repair: The window is broken on the south east corner that has been boarded. Repair: The window is broken in the upper room.

Doors Repair: Missing door hardware upper room should be improved. Repair: Damaged at the base of the door in the shop bathroom should be improved.

Skylights Repair: The glass is cracked on all four skylights.

IMPROVEMENT ITEMS Lights Improve: The fluorescent light fixture covers in the office are missing and should be replaced.

Supply Plumbing

Improve: The shop bathroom only has cold water at the sink.

Floors Improve: There is evidence of vermin activity in the building. A pest control specialist should be consulted for

treatment and control advice.

Doors Improve: The east sliding glass door to the office could be improved to operate freely.

ITEMS TO MONITOR Foundation Monitor: Common minor settlement cracks were observed in the concrete slab. This implies that some structural

movement of the building has occurred. Cracks of this type should be watched for any sign of additional movement. In the absence of any sign of ongoing movement, repair should not be necessary.

Monitor: Larger than typical concrete slab settlement cracking was observed on the west side of the building. The amount of movement which has occurred is not likely to have caused other damage to the structure but this area should be monitored. If additional movement occurs, more costly repairs might be necessary. The rate of movement cannot be predicted during a one-time inspection.

Page 6: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 6 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Roof Monitor: Evidence of moisture was observed throughout on the underside of the roof sheathing. This can weaken the

sheathing and ultimately necessitate replacement. Monitor: Prior repairs to the roof structure are evident. Consult the current owner regarding this prior work.

Dome Roofing Monitor: Prior repairs to the roofing are evident. This would suggest that problems have been experienced in the past.

This area should be monitored.

Flashings Monitor: The flashing should be carefully monitored. Skylight flashings are extremely vulnerable to leakage.

Exterior Walls Monitor: The siding at the south side of the building is on the zero lot line, neighbor has items store against the wall.

Windows Monitor: The window at the south east corner is boarded with metal. Monitor: The window opening at the north east corner has been boarded.

Landscaping Monitor: Vines growing on the chain link fence on the south east corner of the property.

Patio Monitor, Safety Issue: Pronounced concrete cracks were noted in the patio area on the east side of the property. While

this amount of cracking is unusual, this slab is not a structural component you should be aware of the trip hazard. Monitor: Brick in the patio area east side of the building is uneven.

Wall / Ceiling Finishes Monitor: Damage to the interior finish was observed in the upper level room. Monitor: Damage to the interior finish was observed in the shop bathroom. Monitor: Cracks were noted in the office on the west wall. Monitor: Cracks were noted in the wall above the office on the west wall. Monitor: Damage to the interior finish was observed in the office on the south wall near the door.

Floors Monitor, Repair: The concrete floor was damaged near the floor drain on the north side of the building. Monitor, Repair: The vinyl flooring is damaged in the upper room. Monitor: The carpet is stained in the office.

Stairways Monitor: The railing for the stairway to the upper room is loose.

DEFERRED COST ITEMS

THE SCOPE OF THE INSPECTION

All components designated for inspection in the CREIA Standards of Practice are inspected, except as may be noted in the “Limitations of Inspection” sections within this report. It is the goal of the inspection to put a property buyer in a better position to make a buying decision. Not all improvements will be identified during this inspection. Unexpected repairs should still be anticipated. The inspection should not be considered a guarantee or warranty of any kind. This inspection is visual only. A representative sample of building components are viewed in areas that are accessible at the time of the inspection. No destructive testing or dismantling of building components is performed.

Please refer to the pre-inspection contract for a full explanation of the scope of the inspection.

Page 7: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 7 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

WEATHER CONDITIONS Dry weather conditions prevailed at the time of the inspection. The estimated outside temperature was 68 degrees F.

RECENT WEATHER CONDITIONSWeather conditions leading up to the inspection have been relatively dry.

Page 8: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 8 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Structure DESCRIPTION OF STRUCTURE

Foundation: Poured Concrete Slab on Grade Columns: Brick Concrete Floor Structure: Concrete Wood Joist Wall Structure: Concrete Masonry Roof Structure: Roof Joist Open Web Steel Joist Solid Plank Wood Sheathing Office Ceiling Structure: Wood Joist

STRUCTURE OBSERVATIONS

Positive Attributes The construction of the building is of average quality with typical liberties taken with good building practice and with the quality of materials employed. The inspection did not disclose significant deficiencies in the structure.

General Comments Typical minor flaws were detected in the structural components of the building. RECOMMENDATIONS / OBSERVATIONS Foundation Monitor: Common minor settlement cracks were observed in the concrete slab. This implies that some structural

movement of the building has occurred. Cracks of this type should be watched for any sign of additional movement. In the absence of any sign of ongoing movement, repair should not be necessary.

Monitor: Larger than typical concrete slab settlement cracking was observed on the west side of the building. The amount of movement which has occurred is not likely to have caused other damage to the structure but this area should be monitored. If additional movement occurs, more costly repairs might be necessary. The rate of movement cannot be predicted during a one-time inspection.

Roof Monitor: Evidence of moisture was observed throughout on the underside of the roof sheathing. This can weaken the

sheathing and ultimately necessitate replacement. Monitor: Prior repairs to the roof structure are evident. Consult the current owner regarding this prior work.

LIMITATIONS OF STRUCTURE INSPECTION

As we have discussed and as described in your inspection contract, this is a visual inspection limited in scope by (but not restricted to) the following conditions: Structural components concealed behind finished surfaces could not be inspected. Only a representative sampling of visible structural components were inspected. Equipment and/or storage restricted access to some structural components. Engineering or architectural services such as calculation of structural capacities, adequacy, or integrity are not part of a

home inspection.

Please also refer to the pre-inspection contract for a detailed explanation of the scope of this inspection.

Page 9: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 9 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Roofing DESCRIPTION OF ROOFING

Dome Roof Covering: Built Up Roofing Single Ply Membrane Polyurethane Coating Roof Drainage System: Built in at eave Drain Pipes Inside of The Building Skylights: Curbless Roof Penetrations: Exhaust Vents Plumbing Vents None Roof / Siding Support: Metal Support Wood Footings Method of Inspection: Walked on roof

ROOFING OBSERVATIONS

General Comments The roof coverings are old and are at or near end of useful life. RECOMMENDATIONS / OBSERVATIONS Dome Roofing Repair: The roofing membrane is near the end of its life. Minor repairs might be possible to extend the roof life and to

defer leaks. Damaged or missing roofing material should be repaired. All roof penetrations should be examined and sealed as necessary.

Repair: The wood footings on the roof for the metal support were found to be rotted in many locations. The wood damaged wood should be replaced.

Monitor: Prior repairs to the roofing are evident. This would suggest that problems have been experienced in the past. This area should be monitored.

Flashings Monitor: The flashing should be carefully monitored. Skylight flashings are extremely vulnerable to leakage.

Roof Drainage Repair: Drainage leader box should be cover with screening.

LIMITATIONS OF ROOFING INSPECTION

As we have discussed and as described in your inspection contract, this is a visual inspection limited in scope by (but not restricted to) the following conditions: Not all of the underside of the roof sheathing is inspected for evidence of leaks. Estimates of remaining roof life are approximations only and do not preclude the possibility of leakage. Leakage can

develop at any time and may depend on rain intensity, wind direction, ice build up, and other factors. Roof inspection may be limited by access, condition, weather, or other safety concerns.

Please also refer to the pre-inspection contract for a detailed explanation of the scope of this inspection.

Page 10: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 10 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Exterior DESCRIPTION OF EXTERIOR

Wall Covering: Brick Concrete Wood Siding Exterior Doors: Metal Roll-up Metal Window/Door Frames and Trim: Wood Frame Metal-Covered Security Bars Entry Driveways: Concrete Walkways And Patio: Concrete Asphalt Brick Surface Drainage: Level Grade Fencing: Chain Link With Slats and Razor Wire Zero Lot Lines, North and South Side

of The Property

EXTERIOR OBSERVATIONS

Positive Attributes The building has brick constructed exterior walls that has been seismic retro fitted.

General Comments The exterior of the building has not been well maintained. Repairs are needed. RECOMMENDATIONS / OBSERVATIONS Exterior Walls Repair: Damaged brickwork at the east side of the building should be repaired to preserve the wall. Repair: The loose wood boards on the east side of the building should be re-secured or removed. Repair: Localized rot was observed in the siding at the west side of the building in the mural. Following repair of the

damaged areas (which should be combined with exterior maintenance) proper maintenance of the siding and control of water from roof or surface runoff can avoid further damage.

Monitor: The siding at the south side of the building is on the zero lot line, neighbor has items store against the wall.

Address Repair: The address on the exterior wall is incorrect and incomplete.

Windows Possible Major Concern, Repair: The window at the south west corner shows evidence of substantial rot to the

window frame. Repair to the window frame can usually be accomplished by a skilled carpenter; a replacement window is preferred in some cases.

Repair: Localized evidence of rot was visible at window frame at the north west corner. Repairs are needed. Monitor: The window at the south east corner is boarded with metal. Monitor: The window opening at the north east corner has been boarded.

Door(s) Repair: The frame of the entry door west side shows evidence of localized rot at the top and needs repairs. Repair: The roll-up door on the west side of the building frame at the base shows evidence of localized rot and needs

repairs.

Sidewalk Repair, Safety Issue: The walkway presents a trip hazard where the concrete and asphalt sidewalk meets on the south

west side of the property. This condition should be altered for improved safety.

Landscaping Monitor: Vines growing on the chain link fence on the south east corner of the property.

Page 11: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 11 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Patio Monitor, Safety Issue: Pronounced concrete cracks were noted in the patio area on the east side of the property. While

this amount of cracking is unusual, this slab is not a structural component you should be aware of the trip hazard. Monitor: Brick in the patio area east side of the building is uneven.

Fencing Repair: The gate at the north east corner is in only fair condition the top rail is bent. Minor repairs are needed. Repair: The gate at the north east corner is in only fair condition the bottom railing is missing. Minor repairs are

needed.

LIMITATIONS OF EXTERIOR INSPECTION

As we have discussed and as described in your inspection contract, this is a visual inspection limited in scope by (but not restricted to) the following conditions: A representative sample of exterior components was inspected rather than every occurrence of components. The inspection does not include an assessment of geological, geotechnical, or hydrological conditions, or environmental

hazards. Screening, shutters, awnings, or similar seasonal accessories, fences, recreational facilities, outbuildings, seawalls, break-

walls, docks, erosion control and earth stabilization measures are not inspected unless specifically agreed-upon and documented in this report.

Please also refer to the pre-inspection contract for a detailed explanation of the scope of this inspection.

Page 12: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 12 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Electrical DESCRIPTION OF ELECTRICAL

Size of Electrical Service: 120/277 Volt Main Service - Service Size: 480 Service Drop: Overhead Service Equipment & Main Disconnects: Main Service Rating 480 Amps Fuses Located: South West Corner of The

Building Service Grounding: Ground Rod Connection In Building Sub-Panel(s): Panel Rating: 480 Amp Breakers Located: South West Corner of The

Building Panel Rating: 200 Amp Breakers Located: East Side of The Building Near the Roll-up Door Panel Rating:200 Amp Breakers Located: South Wall of The Building

Wiring Method: Armored Cable "BX" Switches & Receptacles: Grounded Ground Fault Circuit Interrupters: North Wall of The Building

ELECTRICAL OBSERVATIONS

Positive Attributes Generally speaking, the electrical system is in good order.

General Comments Inspection of the electrical system revealed the need for typical, minor repairs. Although these are not costly to repair, they should be high priority for safety reasons. Unsafe electrical conditions represent a shock hazard. A licensed electrician should be consulted to undertake the repairs recommended below. RECOMMENDATIONS / OBSERVATIONS Outlets Repair: An outlet on the exterior east wall at the office is loose. It should be replaced.

Switches Repair: The loose light switch in the shop bathroom should be secured.

Lights Improve: The fluorescent light fixture covers in the office are missing and should be replaced. Repair: The fluorescent lights in the upper level room are inoperative. If the bulbs are not blown, the circuit should be

repaired.

LIMITATIONS OF ELECTRICAL INSPECTION

As we have discussed and as described in your inspection contract, this is a visual inspection limited in scope by (but not restricted to) the following conditions: Electrical components concealed behind finished surfaces are not inspected. Only a representative sampling of outlets and light fixtures were tested. Furniture and/or storage restricted access to some electrical components which may not be inspected. The inspection does not include remote control devices, alarm systems and components, low voltage wiring, systems,

and components, ancillary wiring, systems, and other components which are not part of the primary electrical power distribution system.

Please also refer to the pre-inspection contract for a detailed explanation of the scope of this inspection.

Page 13: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 13 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Heating DESCRIPTION OF HEATING

Energy Source: Gas Heating System Type: Ceiling Suspended Heater Manufacturer: Reznor Vents, Flues, Chimneys: Metal-Multi Wall

HEATING OBSERVATIONS

General Comments No repairs to the heating system are necessary at this time. RECOMMENDATIONS / OBSERVATIONS

LIMITATIONS OF HEATING INSPECTION

As we have discussed and as described in your inspection contract, this is a visual inspection limited in scope by (but not restricted to) the following conditions: The adequacy of heat supply or distribution balance is not inspected. The interior of flues or chimneys which are not readily accessible are not inspected. The furnace heat exchanger, humidifier, or dehumidifier, and electronic air filters are not inspected. Solar space heating equipment/systems are not inspected.

Please also refer to the pre-inspection contract for a detailed explanation of the scope of this inspection.

Page 14: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 14 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Ventilation DESCRIPTION OF VENTILATION

Exhaust Fan/vent Locations: Office Bathroom Paint Rooms

VENTILATION OBSERVATIONS

General Comments Paint rooms vents with filters worked as intended. RECOMMENDATIONS / ENERGY SAVING SUGGESTIONS Exhaust Fan Repair: Office bathroom exhaust fan is inoperative.

LIMITATIONS OF VENTILATION INSPECTION

As we have discussed and as described in your inspection contract, this is a visual inspection limited in scope by (but not restricted to) the following conditions: Insulation/ventilation type and levels in concealed areas are not inspected. Insulation and vapor barriers are not disturbed

and no destructive tests (such as cutting openings in walls to look for insulation) are performed. Potentially hazardous materials such as Asbestos and Urea Formaldehyde Foam Insulation (UFFI) cannot be positively

identified without a detailed inspection and laboratory analysis. This is beyond the scope of the inspection. An analysis of indoor air quality is not part of our inspection unless explicitly contracted-for and discussed in this or a

separate report. Any estimates of insulation R values or depths are rough average values.

Please also refer to the pre-inspection contract for a detailed explanation of the scope of this inspection.

Page 15: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 15 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Plumbing DESCRIPTION OF PLUMBING

Water Supply Source: Public Water Supply Service Pipe to House: Not Visible Main Water Valve Location: West Side of The Property Interior Supply Piping: Copper Flex Tubing Waste System: Public Sewer System Drain, Waste, & Vent Piping: Cast Iron Water Heater: Electric Approximate Capacity (in gallons): 19 Manufacturer: A.O. Smith

Serial Number: MA96-0049007-S06 Drip Pan Located: On Top of The Office

Fuel Shut-Off Valves: Natural Gas Main Valve At The South Side of The Building at Neighbors’ Property

Other Components: Floor Drains Throughout The Building Fire Extinguishers

PLUMBING OBSERVATIONS

Positive Attributes The water pressure supplied to the fixtures is reasonably good. A typical drop in flow was experienced when two fixtures were operated simultaneously.

General Comments The plumbing system requires some typical minor improvements. RECOMMENDATIONS / OBSERVATIONS Water Heater Repair: The discharge piping serving the Temperature and Pressure Relief (TPR) Valve for the water heater should

terminate not less than 6 inches or more than 24 inches above the floor/drip pan.

Supply Plumbing Improve: The shop bathroom only has cold water at the sink.

Fixtures Repair: The faucet(s) in the shop bathroom is leaking.

LIMITATIONS OF PLUMBING INSPECTION

As we have discussed and as described in your inspection contract, this is a visual inspection limited in scope by (but not restricted to) the following conditions: Portions of the plumbing system concealed by finishes and/or storage (below sinks, etc.), below the structure, or beneath

the ground surface are not inspected. Water quantity and water quality are not tested unless explicitly contracted-for and discussed in this or a separate report. Clothes washing machine connections are not inspected. Interiors of flues or chimneys which are not readily accessible are not inspected. Water conditioning systems, solar water heaters, fire and lawn sprinkler systems, and private waste disposal systems are

not inspected unless explicitly contracted-for and discussed in this or a separate report.

Please also refer to the pre-inspection contract for a detailed explanation of the scope of this inspection.

Page 16: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 16 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Interior DESCRIPTION OF INTERIOR

Wall And Ceiling Materials Building: Brick Concrete Masonry Wall And Ceiling Materials Office: Drywall Columns: Brick ConcreteFloor Surfaces: Concrete Wood Window Type(s) & Glazing: Fixed Pane Single Pane Doors: Wood-Hollow Core

INTERIOR OBSERVATIONS

General Condition of Interior Finishes On the whole, the interior finishes of the building are in average condition. Typical flaws were observed in some areas.

General Condition of Windows and Doors The windows have been lacking maintenance.

General Condition of Floors The floors of the building are relatively level and walls are relatively plumb. RECOMMENDATIONS / OBSERVATIONS Wall / Ceiling Finishes Monitor: Damage to the interior finish was observed in the upper level room. Monitor: Damage to the interior finish was observed in the shop bathroom. Monitor: Cracks were noted in the office on the west wall. Monitor: Cracks were noted in the wall above the office on the west wall. Monitor: Damage to the interior finish was observed in the office on the south wall near the door.

Floors Monitor, Repair: The concrete floor was damaged near the floor drain on the north side of the building. Monitor, Repair: The vinyl flooring is damaged in the upper room. Monitor: The carpet is stained in the office. Improve: There is evidence of vermin activity in the building. A pest control specialist should be consulted for

treatment and control advice.

Windows Repair: The window is broken on the south east corner that has been boarded. Repair: The window is broken in the upper room.

Doors Repair: Missing door hardware upper room should be improved. Repair: Damaged at the base of the door in the shop bathroom should be improved. Improve: The east sliding glass door to the office could be improved to operate freely.

Skylights Repair: The glass is cracked on all four skylights.

Stairways Monitor: The railing for the stairway to the upper room is loose.

Page 17: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 17 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

LIMITATIONS OF INTERIOR INSPECTION

As we have discussed and as described in your inspection contract, this is a visual inspection limited in scope by (but not restricted to) the following conditions Furniture, storage, appliances and/or wall hangings are not moved to permit inspection and may block defects. Carpeting, window treatments, central vacuum systems, household appliances, recreational facilities, paint, wallpaper,

and other finish treatments are not inspected.

Please also refer to the pre-inspection contract for a detailed explanation of the scope of this inspection.

Page 18: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 18 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Subject Photos

Photo 1: West side of the building.

Photo 2: South side of the building, zero lot line area.

Page 19: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 19 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 3: South side of the building.

Photo 4: Utility company gas meter, south side of the building.

Page 20: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 20 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 5: Electrical overhead service line, south west corner of the building.

Photo 6: Window on the south west corner, note the area of dry rot. (Page 10)

Page 21: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 21 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 7: Window south west corner, area of dry rot. (Page 10)

Photo 8: West side roll-up door frame, note the area of dry rot. (Page 10)

Page 22: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 22 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 9: Wood siding, note the area of dry rot and the incorrect address. (Page 10)

Photo 10: Wood siding, note the area of dry rot. (Page 10)

Page 23: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 23 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 11: Window, west side of the building.

Photo 12: East side of the building, note the loose wood. (Page 10)

Page 24: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 24 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 13: South east corner of the building, note the boarded window. (Page 10)

Photo 14: North east corner of the property, note the chain link fence. (Page 10)

Page 25: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 25 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 15: East side of the building, note the brick patio area unevenness. (Page 10)

Photo 16: Brick siding with seismic retro fitting, also note the damaged bricks east side of the building. (Page 10)

Page 26: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 26 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 17: Skylight, note the cracks, typical for all four skylights.

Photo 18: Roof.

Page 27: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 27 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 19: Roof.

Photo 20: Roof.

Page 28: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 28 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 21: Skylight on the roof.

Photo 22: Roof.

Page 29: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 29 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 23: Roof, note the siding and roof support brackets.

Photo 24: Support bracket rotted wood mount. (Page 9)

Page 30: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 30 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 25: Roof.

Photo 26: Roof.

Page 31: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 31 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 27: Roof.

Photo 28: Roof.

Page 32: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 32 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 29: Electrical main panel, south west corner interior of building.

Photo 30: Electrical ground rod.

Page 33: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 33 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 31: Roof drainage pipe, note the damage sheathing. (Page 8)

Photo 32: Electrical sub-panel south west corner of the building.

Page 34: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 34 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 33: Electrical sub-panel, east side of the building.

Photo 34: Electrical sub-panel on the south wall of the building.

Page 35: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 35 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 35: Roof sheathing, note the water stains.

Photo 36: Roof sheathing, note the water stains.

Page 36: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 36 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 37: Roof supports.

Photo 38: Roof supports and sheathing.

Page 37: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 37 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 39: Roof support and sheathing, note prior repairs made.

Photo 40: Heater.

Page 38: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 38 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 41: Roof sheathing, note the prior repairs.

Photo 42: Water heater on top of the office.

Page 39: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 39 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 43: Paint ventilation equipment.

Photo 44: Office.

Page 40: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 40 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 45: Office.

Photo 46: Office.

Page 41: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 41 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 47: Office bathroom.

Photo 48: Shop bathroom.

Page 42: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 42 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 49: Floor drain, note the damage floor at the drain. (Page 16)

Photo 50: Stairway to the upper level.

Page 43: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 43 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 51: Upper level.

Photo 52: Broken window in the upper level.

Page 44: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 44 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 53: Shop.

Photo 54: Shop, area of broken windows on the east side of the building. (Page16)

Page 45: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 45 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 55: Shop.

Photo 56: East wall of the building.

Page 46: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 46 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 57: Note the crack in the floor.

Photo 58: North wall, note the support column.

Page 47: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 47 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 59: West wall above the office not the crack. (Page 16)

Photo 60: Shop, north east corner.

Page 48: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 48 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 61: South side of the building.

Photo 62: Area above the office.

Page 49: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 49 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Photo 63: Roof sheathing and joist, note the water damage.

Photo 64: Roof drainage.

Page 50: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 50 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

City Of Oakland, Address History

Page 51: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 51 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Page 52: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 52 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Page 53: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 53 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

CALIFORNIA REAL ESTATE INSPECTION ASSOCIATION

Standards of Practice Originally Adopted September 13, 1983

Revisions herein effective April 15, 1999 Table of Contents

I. Definitions and Scope II. Standards of Practice

MANDATORY SECTIONS: 1. Foundations, Basements, and Under-floor Areas 2. Exteriors 3. Roof Coverings 4. Attic Areas and Roof Framing 5. Plumbing 6. Electrical Systems 7. Heating Systems 8. Central Cooling Systems 9. Fireplaces and Chimneys 10. Building Interior

OPTIONAL SECTIONS: 11. Other Built-in Appliances and Systems 12. Pools and Spas

III. Limitations, Exceptions and Exclusions IV. Glossary of Terms

*Note: Italicized words in this document are defined in the Glossary of Terms

I. DEFINITIONS AND SCOPE

A. A Real Estate inspection is a non-invasive physical examination, performed for a fee, designed to identify material defects in the systems, structures, and components of a building as they exist at the time of the inspection. The specific systems, structures and components of a building to be examined are listed in these Standards of Practice.

B. A material defect is a condition that significantly affects the value, desirability, habitability, or safety of the building. Style or aesthetics shall not be considered in determining whether a specific system, structure, or component is defective.

C. These Standards provide inspection guidelines, make public the services provided by private fee-paid inspectors, and define certain terms relating to these inspections.

D. Sections 1 through 10 of these Standards are a mandatory part of all such inspections. Sections 11through 12 are optional.

E. Unless otherwise agreed between the inspector and client, these Standards shall apply to the primary building structure. The inspection shall be limited to those specific systems, structures and components that are present and visually accessible. Components and systems shall be operated with normal user controls only and as conditions permit. Inspections performed in accordance with these Standards are not intended to be technically exhaustive.

Page 54: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 54 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

F. Inspection reports shall describe and identify in written format the inspected systems, structures, and components of the building and shall identify material defects.

G. Inspection reports may contain recommendations regarding conditions reported or recommendations for further evaluation by appropriate persons.

II. STANDARDS OF PRACTICE

SECTION 1 - Foundations, Basements, and Under-floor Areas

A. Items to be identified and reported: 1. Foundation and other support components. 2. Under-floor ventilation. 3. Location of under-floor access opening(s). 4. Wood separation from soil. 5. Presence of drainage systems or sump pumps within foundation footprint. 6. Presence or absence of seismic anchoring and bracing components.

B. The inspector is not required to: 1. Enter under-floor areas that are not accessible or where entry could cause damage or pose a hazard

to the inspector. 2. Move stored items, vegetation or debris, or perform any excavations or other intrusive testing to gain

access. 3. Operate or evaluate adequacy of sump pumps or drainage systems.4. Identify size, spacing, location or adequacy of foundation bolting and bracing components or

reinforcement systems. 5. Perform any intrusive examination or testing, or use any special equipment such as, but not limited to,

levels, probes or meters.

SECTION 2 - Exteriors

A. Items to be identified and reported: 1. Surface grade, hardscaping and drainage within six feet of the inspected building or associated

primary parking structure.2. Wall cladding, veneers, flashing, trim, eaves, soffits and fascias. 3. Exterior portions of a representative sampling of doors and windows. 4. Attached decks, porches, balconies, stairs, columns, walkways, guard-rails and handrails.

B. The inspector is not required to: 1. Operate or evaluate any mechanical, electro-mechanical, or underground drainage systems. 2. Operate or evaluate storm windows, storm doors, screening, shutters or awnings. 3. Operate or evaluate remote-control devices. 4. Examine detached buildings and structures (other than the primary parking structure), patio

enclosures, fences, and retaining walls. 5. Examine items not visible from a readily accessible walking surface.

SECTION 3 - Roof Coverings

A. Items to be identified and reported: 1. Roof coverings. 2. Flashing, vents, skylights and other penetrations. 3. Roof drainage systems.

B. The inspector is not required to:

Page 55: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 55 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

1. Walk on the roof surface if, in the opinion of the inspector, there is a possibility of damage to the surface or a hazard to the inspector.

2. Perform a water test, warrant or certify against roof leakage or predict life expectancy.

SECTION 4 - Attic Areas and Roof Framing

A. Items to be identified and reported: 1. Framing and sheathing. 2. Access opening(s) and accessibility. 3. Insulation material(s). 4. Ventilation.

B. The inspector is not required to: 1. Enter attic areas that, in the opinion of the inspector, are not accessible or where entry could cause

damage. 2. Remove insulation materials or identify composition or "R" value of insulation material. 3. Activate thermostatically operated fans.

SECTION 5 - Plumbing

A. Items to be identified and reported: 1. Supply, waste, and vent piping. 2. Fixtures, faucets and drains. 3. Water heating equipment, including combustion air, venting, connections, energy sources, seismic

bracing, and temperature-pressure relief valves. 4. Functional flow of water supply and functional drainage at fixtures. 5. Gas piping and connectors. 6. Cross-connections.

B. The inspector is not required to: 1. Operate any valve other than fixture faucets and hose faucets attached to the building. 2. Operate any system, fixture or component which is shut down or disconnected. 3. Examine or verify operation of water supply or pressure assistance systems, including, but not limited

to: wells, pumps, tanks, and related equipment. 4. Verify functional flow or pressure at any fixture or faucet where the flow end is capped or connected

to an appliance, or measure pressure, volume or temperature. 5. Examine or operate any sewage disposal system or component including, but not limited to: septic

tanks and/or any underground system or portion thereof, or ejector pumps for rain or waste. 6. Examine the overflow device of any fixture. 7. Evaluate the potability of water, compliance with local or state conservation or energy standards, or

proper design or sizing of any water, waste, and venting components, fixtures, or piping. 8. Identify whether water supply and waste disposal systems are public or private. 9. Evaluate time to obtain hot water at fixtures, or perform testing of any kind to water heater elements. 10. Examine ancillary systems or components such as, but not limited to: those 11. relating to solar water heating, hot water circulation, yard sprinklers, water conditioning, swimming

pools or spas and related equipment, and fire sprinklers. 12. Test shower pans for leakage or fill any fixture with water during examination. 13. Evaluate the gas supply system for leaks or pressure. 14. Determine effectiveness of anti-siphon, back-flow prevention, or drain-stop devices. 15. Determine whether there are sufficient clean-outs for effective clearing of drains. 16. Evaluate gas, liquid propane, or oil storage tanks.

SECTION 6 - Electrical Systems

A. Items to be identified and reported: 1. Service conductors, equipment, and capacity. 2. Panels and overcurrent protection devices.

Page 56: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 56 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

3. Service and equipment grounding. 4. Wiring types and methods. 5. A representative sampling of switches, receptacles, and light fixtures. 6. Ground-fault circuit-interrupters.

B. The inspector is not required to: 1. Operate electrical systems or components which are disconnected or shut down.2. Disconnect any energized system or appliance.3. Remove deadfront covers where not accessible, or if removal could cause injury or damage to

persons or property, or remove device cover plates. 4. Operate overcurrent protection devices, or evaluate compatibility of overcurrent protection devices

with the panelboard manufacturer. 5. Examine or test smoke detectors. 6. Operate ground-fault circuit-interrupter devices by other than the manufacturer’s test button.7. Examine de-icing equipment, or private or emergency electrical supply sources, including but not

limited to: generators, windmills, photovoltaic solar collectors, or battery or electrical storage facilities.

SECTION 7 - Heating Systems

A. Items to be identified and reported: 1. Heating equipment and operation using normal user controls.2. Venting systems. 3. Combustion and ventilating air. 4. Energy source and connections. 5. Heating distribution system(s) including a representative sampling of ducting, duct insulation, outlets,

radiators, piping systems and valves.

B. The inspector is not required to: 1. Examine or evaluate condition of heat exchangers. 2. Determine uniformity, temperature, airflow or balance of heat supply to any room or building, or

examine for warming at any heating system distribution component when access would require steps or a ladder, or determine leakage in any ductwork.

3. Examine electric heater elements or heat pump fluid/gas materials, or examine below ground/slab systems, ducts, fuel tanks and related components.

4. Determine or examine thermostat calibration, heat anticipation, or automatic setbacks or clocks. 5. Examine radiant or geothermal heat pump systems. 6. Examine any solar-energy heating systems or components.7. Examine electronic air filtering systems.8. Operate heat pump systems when the ambient air temperature may damage the equipment, or

operate any heat pump system in "emergency" heat mode. 9. Examine humidity control systems and components.

SECTION 8 - Central Cooling Systems

A. Items to be identified and reported: 1. Cooling equipment and operation using normal user controls.2. Cooling distribution system(s) including a representative sampling of ducting, duct 3. insulation, outlets, piping systems and valves. 4. Energy source and connections. 5. Condensate drains.

B. The inspector is not required to: 1. Determine uniformity, temperature, airflow or balance of cool air supply to any room or building, or

examine for cooling at any cooling system distribution component when access would require steps or a ladder, or determine leakage in any ductwork.

2. Examine electrical current, coolant fluids or gases, or coolant leakage.

Page 57: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 57 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

3. Examine electronic filtering systems. 4. Determine or examine thermostat calibration, cooling anticipation, or automatic setbacks or clocks. 5. Examine any non-central cooling unit(s) or gas-fired, solar or geothermal cooling system or food, wine

or similar storage cooling system.6. Examine humidity control systems and components.

SECTION 9 - Fireplaces and Chimneys

A. Items to be identified and reported: 1. Chimneys, flues, dampers and associated components.2. Fireboxes, hearth extensions and permanently installed accessory components.3. Manufactured solid-fuel or gas-burning appliances.

B. The inspector is not required to: 1. Determine adequacy of draft, perform a smoke test, or dismantle or remove any component. 2. Examine the structural integrity of fireplaces and chimneys. 3. Examine or operate ancillary or non-permanently installed components.

SECTION 10 - Building Interior

A. Items to be identified and reported: 1. Walls, ceilings and floors. 2. Security bars, ventilation components, and a representative sampling of doors and windows. 3. Stairs, handrails, and guardrails. 4. Permanently installed cabinet and countertop surfaces. 5. Safety glazing in locations subject to human impact.

B The inspector is not required to: 1. Operate or evaluate security bar release and opening mechanisms, whether interior or exterior,

including compliance with local, state, or federal standards. 2. Determine whether a building is secure from forcible or unauthorized entry. 3. Evaluate the condition of floor, wall or ceiling finishes or coverings, or other surfaces for other than

evidence of moisture damage. 4. Examine window or door coverings or treatments. 5. Evaluate fastening of countertops, furniture or cabinets supported by floors, ceilings and/or walls. 6. Evaluate separation walls, ceilings, and floors, including, but not limited to, the fire-resistivity or

acoustical characteristics, between dwelling units. 7. Examine the interior concrete slab-on-grade when concealed by any floor coverings. 8. Operate or evaluate safety features of any garage door opener unless included as an inspection

option per Section 11.

SECTION 11 (OPTIONAL) - Other Built-In Appliances and Systems The inspector may examine any of the following at his/her discretion, as agreed with client:

Attic power vents, central vacuum, cook-tops and exhaust fans, dishwashers, food waste disposers, garage door openers, hydrotherapy tubs, ovens, microwave ovens, refrigerators, freezers, trash compactors, or whole-house fans.

A. Items to be identified and reported: 1. Optional systems, components and appliances specifically examined during the inspection.2. Basic operation of optional systems, components and appliances specifically included in the

inspection.

B. The inspector is not required to: 1. Activate any system or appliance that is shut down.

Page 58: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 58 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

2. Operate or evaluate any system, component, or appliance that does not respond to normal user controls.

3. Operate any gas appliance that requires the use of a match or other remote burner lighting device. 4. Operate any system or appliance that requires the use of special codes, keys, combinations, or

devices. 5. Operate any system, component, or appliance where damage may occur. 6. Determine thermostat(s) calibration, adequacy of heating elements, operate or evaluate self-cleaning

oven cycles, signal lights, or automatic setbacks or clocks. 7. Determine leakage from microwave ovens. 8. Determine the presence or operation of backdraft damper devices in exhaust devices. 9. Examine any sauna, steam-jenny, kiln, clothes washing or drying machine, toaster, ice-maker, coffee-

maker, can-opener, bread-warmer, blender, instant hot water dispenser, or any other similar small, ancillary or non-built-in appliances.

SECTION 12 (OPTIONAL) - Pools and Spas The inspector may examine the following at his/her discretion, as agreed with client:

A. Items to be identified and reported: 1. Location and type of pool or spa examined. 2. Conditions limiting or otherwise inhibiting inspection.3. Enclosure and related gates. 4. Hardscaping and drainage related to the inspected pool or spa. 5. Condition of visible portions of systems, structures, or components.6. Normally necessary and present equipment such as: lights, pumps, heaters, filters, and related

mechanical and electrical connections.

B. The inspector is not required to: 1. Examine any above-ground, movable, freestanding or otherwise non-permanently installed pool or

spa, or self-contained equipment. 2. Come into contact with pool or spa water to examine the system, structure, or components. 3. Determine adequacy of spa jet water force or bubble effect. 4. Determine structural integrity or leakage of any kind.5. Evaluate thermostat(s) or their calibration, heating elements, chemical dispensers, water chemistry or

conditioning devices, low voltage or computer controls, timers, sweeps or cleaners, pool or spa covers and related components.

6. Operate or evaluate filter backwash systems. 7. Examine accessories, such as, but not limited to: aerators or air-blowers, diving or jump boards,

ladders, skimmers, slides or steps.

III. LIMITATIONS, EXCEPTIONS AND EXCLUSIONS

*Note: All limitations, exceptions and exclusions apply equally to mandatory and optional Sections.

A. The inspector may exclude from the inspection any system, structure, or component of the building which is inaccessible, concealed from view, or cannot be inspected due to circumstances beyond the control of the inspector, or which the client has agreed is not to be inspected. If an inspector excludes any specific system, structure, or component of the building from the inspection, the inspector shall confirm in the report such specific system, structure, or component of the building not inspected and the reason(s) for such exclusion(s).

B. The inspector may limit the inspection to individual specific systems, structures, or components of the building. In such event, the inspector shall confirm in the report that the inspection has been limited to such individual specific systems, structures, and components of the building.

C. The following are excluded from the scope of a real estate inspection unless specifically agreed otherwise between the inspector and the client:

Page 59: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 59 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

1. Systems, structures, or components not specifically identified in these Standards. 2. Environmental hazards or conditions, including, but not limited to, toxic, reactive, combustible,

corrosive contaminants, wildfire, geologic or flood. 3. Examination of conditions related to animals, rodents, insects, wood-destroying insects, organisms,

mold, and mildew. 4. Geotechnical, engineering, structural, architectural, geological, hydrological, land surveying or soils-

related examinations.5. Certain factors relating to any systems, structures, or components of the building, including, but not

limited to: adequacy, efficiency, durability or remaining useful life, costs to repair, replace or operate, fair market value, marketability, quality, or advisability of purchase.

6. Systems, structures, or components, of the building which are not permanently installed.7. Determination of compliance with installation guidelines, manufacturers’ specifications, building

codes, ordinances, regulations, covenants, or other restrictions, including local interpretations thereof. 8. Common areas, or systems, structures, or components thereof, including, but not limited to, those of

a common interest development as defined in California Civil Code Section 1351 et seq.

D. The inspector is not required to perform any of the following as part of a real estate inspection:

1. Move any personal items or other obstruction(s) such as, but not limited to: furniture, floor or wall coverings, window coverings, snow, ice, water, debris, and foliage which may obstruct visibility or access.

2. Determine causes for the need of repair or replacement, or specify repair or replacement procedures or materials.

3. Determine existence of latent deficiencies or defects. 4. Dismantle any system, structure, or component, or perform any intrusive or destructive examination,

test or analysis. 5. Obtain or review information from any third-parties including, but not limited to: government agencies

(such as permits), component or system manufacturers (including product defects, recalls or similar notices), contractors, managers, sellers, occupants, neighbors, consultants, homeowner or similar associations, attorneys, agents or brokers.

6. Activate or operate any system or component that is shut down or does not respond to normal user controls, nor access any area or operate any component or system which may jeopardize the safety of the inspector, or any other person or thing.

7. Research the history of a property, report on its potential for alteration, modification, extendibility, or its suitability for a specific or proposed use or occupancy.

8. Offer any form of guarantee or warranty. 9. Examine or evaluate the acoustical or other nuisance characteristics of any system, structure, or

component of a building, complex, adjoining properties, or neighborhood. 10. Operate or evaluate any recreational system, structure or component.11. Operate or evaluate low voltage electrical (less than single-phase line voltage, typically 120-volts),

antennas, security systems, cable or satellite television, telephone, remote controls, radio controls, timers, intercoms, computers, photo-electric, motion sensing, or other such similar non-primary electrical power devices, components, or systems.

12. Use any special equipment to examine any system, structure, or component of a building. 13. Probe or exert pressure on any component, system or structure.14. Examine or evaluate fire-resistive qualities of any system, structure or component of the building. 15. Examine every individual component of a system or structure, where such components are typically

replicated, including, but not limited to: doors, windows, switches and receptacles. A representative sampling may be performed in order to examine such systems, structures, or components of a building.

16. Determine the age of construction or installation of any system, structure, or component of a building, or differentiate between original construction or subsequent additions, improvements, renovations or replacements thereto.

Page 60: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 60 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

IV - GLOSSARY OF TERMS

*Note: All definitions apply to derivatives of these terms when italicized in the text.

Accessible: Can be approached or entered by the inspector safely without difficulty or damage to the system, structure, or component.

Appliance: See “Component.”

Appropriate persons: An individual other than inspector herein, qualified by virtue of special knowledge, training or resources to further examine a system, structure, or component, as in the manner of a specialist.

Basic operation: The fundamental function of a component or appliance (e.g., the bake and broil elements of an oven), but not those ancillary to its use (e.g., an oven self-cleaning cycle or timer, thermostat or clock).

Building: The primary building subject of the inspection, designed and erected for the purpose of human occupancy or use (e.g. dwelling).

Built-in: See "Permanently installed."

Component: A permanently installed appliance, fixture, element, or part of a system.

Condition: The plainly visible and conspicuous state of being of a material object or thing.

Cross-connection: A connection between two otherwise separate systems, one of which is potable water and the other waste, sewage or other source of contamination.

Destructive: To demolish, damage, or probe any system, structure, or component, or to dismantle any system or component that would not be taken apart by an ordinary person in the course of normal maintenance.

Determine: To arrive at an opinion or conclusion pursuant to examination.

Disconnected: See “Shut down.”

Dismantle: See "Destructive.”

Functional Drainage: The emptying of a plumbing fixture in a reasonable amount of time, without overflow when another fixture is drained simultaneously.

Enter: See “Accessible.”

Evaluate: To assess the systems, structures, or components of a building.

Evidence: Plainly visible and conspicuous material objects or other things presented to the senses that would tend to produce conviction in the mind of an ordinary person as to the existence or non-existence of a fact.

Examine: To visually look for and identify material defects in systems, structures, or components of a building through a non-invasive, physical inspection.

Fixture: See “Component.”

Function: Performing its normal, proper and characteristic action.

Functional flow: A reasonable flow of water supply at the highest and farthest fixture from the building main when another fixture is operated simultaneously.

Further evaluation: A degree of examination beyond that of a typical and customary non-invasive physical examination.

Inspection: The act of performing a real estate inspection.

Inspector: One who performs a real estate inspection.

Intrusive: See "Destructive."

Page 61: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 61 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Malfunction: Failure to perform its normal, proper and characteristic action.

Material defect: (Refer to Section I, “Definitions and Scope” Paragraph B).

Normal user controls: Devices that would be operated by the ordinary occupants of a building, requiring no specialized skill or knowledge.

Operate: To cause systems or equipment to function with normal user controls.

Operational: Systems or components capable of being safely operated.

Permanently Installed: Fixed in place (e.g. screwed, bolted, or nailed), as distinct from components, systems, or appliances considered portable or freestanding.

Primary building: A building that an inspector has agreed to inspect, excluding all accessory buildings with the exception of the primary parking structure.

Primary parking structure: A building for the purpose of vehicle storage associated with the primary building.

Real Estate Inspection: (Refer to Section I, “Definitions and Scope” Paragraph A).

Report: The inspection report is a written document prepared for a fee and issued after a real estate inspection identifying and describing the inspected systems, structures, and components of the building and identifying material defects discovered therein.

Representative sampling: A small quantity of components of any system or structure enough like others in its class or kind to serve as an example of its class or kind.

Shut down: Turned off, inactive, not in-service, non-operational.

Special equipment: Any tools or devices other than those normally used by an inspector to perform a typical and customary non-invasive physical examination of the systems, structures, and components of a building, including, but not limited to: levels, probes, meters, video or audio devices and measuring devices.

Structure: An assemblage of various systems and components to function as a whole.

System: An assemblage of various components to function as a whole.

Technically exhaustive: A comprehensive and detailed examination beyond the scope of a real estate inspection which would include, but would not be limited to: specialized knowledge or training, special equipment, measurements, calculations, testing, research, or analysis.

Page 62: Commercial Building Inspection Report...Commercial Building Inspection Report 2148 Brush Street, Oakland, CA 94612 Inspection Date: July 5, 2017 Prepared For: Joel Lunenfeld Prepared

2148 Brush Street, Oakland, CA 94612 Page 62 of 62

This confidential report is prepared exclusively for Joel Lunenfeld © 2017 R. J. Home Inspection Services

Cost Summary INTRODUCTION

The following cost figures are order of magnitude estimates only. They pertain to some of the observations made in this report. This is not an all-inclusive list of future repair costs, nor does it address general annual maintenance. It is recommended that a budget of roughly one percent of the value of the home be set aside annually to cover unexpected repairs and annual maintenance. It is further recommended that qualified, reputable contractors be consulted for specific quotations. You may find that contractor estimates vary dramatically from these figures, and from each other. Contractors may also uncover defects not apparent at the time of the inspection, resulting in additional costs. Please proceed cautiously. Should you have any questions regarding contractor opinions or quotations, please contact our office. These approximate costs are not intended to represent or influence, in any way, the value of a property.

APPROXIMATE IMPROVEMENT COSTS

STRUCTURE Roof Structure Improvements ................................................................................. $5000 And Up ROOFING Dome Roofing Improvements ................................................................................ $6500 And Up Skylight Improvements ........................................................................................... $2500 And Up Gutter Improvements .............................................................................................. $100-300 EXTERIOR Exterior Wall Improvements .................................................................................. $2500 And Up Siding Repairs And Painting .................................................................................. $1500 And Up Window Improvements .......................................................................................... $2500 And Up PLUMBING Faucet Replacement ................................................................................................ $100 And Up (Each) INTERIOR Floor Repairs .......................................................................................................... $200 And Up Wall And Ceiling Repairs ....................................................................................... $2000 And Up