-
Edition: Feb. 2013C53000-L2040-C370-2
SIPROTECCommunication ModuleIEC 60870-5-104
Communication Profile
Preface
com_T104_profile_us.book Page 1 Tuesday, February 19, 2013 3:17
PMContents
Characteristic of the IEC 60870-5-104 Module 1Configuration in
DIGSI 4 2Scaling and Thresholds for Transmission 3Time
Synchronization 4IEC 60870-5-104 Diagnosis for EN100+ 5Redundancy
IEC 60870-5-104 6Technical Data 7Index
-
NOTEFor your own safety, please observe the warnings and safety
instructions contained in this document.
com_T104_profile_us.book Page 2 Tuesday, February 19, 2013 3:17
PMDisclaimer of Liability
This document has been subjected to rigorous technical review
before being published. It is revised at regular intervals, and any
modifications and amendments are included in the subsequent issues.
The content of this document has been compiled for information
purposes only. Although Siemens AG has made best efforts to keep
the document as precise and up-to-date as possible, Siemens AG
shall not assume any liability for defects and damage which result
through use of the information contained herein.
This content does not form part of a contract or of business
relations; nor does it change these. All obligations of Siemens AG
are stated in the relevant contractual agreements.
Siemens AG reserves the right to revise this document from time
to time.
Document Release: C53000-L2040-C370-2Edition: 02.2013Product
version: V1.00
Copyright
Copyright Siemens AG 2013. All rights reserved. The disclosure,
duplication, distribution and editing of this document, or
utilization and communication of the content are not permitted,
unless authorized in writing. All rights, including rights created
by patent grant or registration of a utility model or a design, are
reserved.
Registered Trademarks
SIMATIC, SIMATIC NET, SIPROTEC, DIGSI, SICAM, SIMEAS, SINAUT ,
OSCOP, and DAKON are registered trademarks of SIEMENS AG. An
unauthorized use is illegal.
All other designations in this document can be trademarks whose
use by third parties for their own purposes can infringe the rights
of the owner.
-
com_T104_profile_us.book Page 3 Tuesday, February 19, 2013 3:17
PMPreface
Purpose of this manual
This manual describes the communication profile of the SIPROTEC
Communication Module with IEC 60870-5-104.
Target group
Protection engineers, commissioning engineers, persons who are
involved in setting, testing and service of protection, automation,
and control devices, as well as operation personnel in electrical
plants and power sta-tions.
Scope of validity of this manual
This manual is valid for the SIPROTEC Communication Module with
IEC 60870-5-104.
Further support
Should further information be desired or should particular
problems arise which are not covered sufficiently for the
purchaser's purpose, the matter should be referred to the local
Siemens representative.
Hotline
Our Customer Support Center provides around-the-clock
support.
Phone: +49 (180) 524-8437Fax: +49 (180) 524-2471Internet:
http://www.siprotec.come-mail: [email protected]
Training courses
If you are interested in our current training program, please
contact our training center:
Siemens AGSiemens Power Academy TD
Humboldtstr. 59
D-90459 NurembergGermany
Phone: +49 (911) 433-7415Fax: +49 (911) 433-5482e-mail:
[email protected]:
www.siemens.com/poweracademy3SIPROTEC, Communication Module,
Communication ProfileC53000-L2040-C370-2, Edition 02.2013
-
Preface
com_T104_profile_us.book Page 4 Tuesday, February 19, 2013 3:17
PM4 SIPROTEC, Communication Module, Communication Profile
Notes On Safety
This document is not a complete index of all safety measures
required for operation of the equipment (module, device). However,
it comprises important information that must be noted for purposes
of personal safety, as well as in order to avoid material damage.
Information is highlighted and illustrated as follows according to
the degree of danger:
DANGERDANGER means that death or severe injury will result if
the measures specified are not taken.
Comply with all instructions, in order to avoid death or severe
injuries
WARNINGWARNING means that death or severe injury can result if
the measures specified are not taken.
Comply with all instructions, in order to avoid death or severe
injuries.
CAUTIONCAUTION means that medium-severe or slight injuries can
result if the measures specified are not taken.
Comply with all instructions, in order to avoid medium-severe or
slight injuries.
NOTICENOTICE means that material damage can result if the
measures specified are not taken.
Comply with all instructions, in order to avoid material
damage.
NOTEImportant information about the product, product handling,
or a certain section of the documentation, which must be given
particular attention.C53000-L2040-C370-2, Edition 02.2013
-
Preface
com_T104_profile_us.book Page 5 Tuesday, February 19, 2013 3:17
PM5SIPROTEC, Communication Module, Communication Profile
Qualified Personnel
Commissioning and operation of the equipment (module, device)
described in this manual must be performed by qualified personnel
only. As used in the safety notes contained in this manual,
qualified personnel are those persons who are authorized to
commission, release, ground and tag devices, systems, and
electrical circuits in accordance with safety standards.
Use as Prescribed
The equipment (device, module) must not be used for any other
purposes than those described in the Catalog and the Technical
Description. If it is used together with third-party devices and
components, these must be recommended or approved by Siemens.
Correct and safe operation of the product requires adequate
transportation, storage, installation, and mounting as well as
appropriate use and maintenance.
During the operation of electrical equipment, it is unavoidable
that certain parts of this equipment will carry dan-gerous
voltages. Severe injury or damage to property can occur if the
appropriate measures are not taken:
Before making any connections at all, ground the equipment at
the PE terminal.
Hazardous voltages can be present on all switching components
connected to the power supply.
Even after the supply voltage has been disconnected, hazardous
voltages can still be present in the equip-ment (capacitor
storage).
Equipment with current transformer circuits must not be operated
while open.
The limit values indicated in the manual or the operating
instructions must not be exceeded; this also refers to testing and
commissioningC53000-L2040-C370-2, Edition 02.2013
-
Preface
com_T104_profile_us.book Page 6 Tuesday, February 19, 2013 3:17
PM6 SIPROTEC, Communication Module, Communication Profile
C53000-L2040-C370-2, Edition 02.2013
-
com_T104_profile_us.book Page 7 Tuesday, February 19, 2013 3:17
PMContents
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 3
1 Characteristic of the IEC 60870-5-104 Module . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 9
1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . 10
1.2 Identification of Module and Firmware . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 12
1.3 Supported IEC 60870-5-104 Object Types. . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 14
1.4 Table of Parameters . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 17
1.5 Buffered Events . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . 19
1.6 File Transfer . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . 20
1.6.1 Reading of Fault Records . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . 20
1.6.2 Reading of Parameter File . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . 25
1.7 Further Ethernet Services and Protocols . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . 27
1.7.1 Services . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . 27
1.7.2 IEC 60870-5-104 with IEC 61850 and GOOSE . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
2 Configuration in DIGSI 4 . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 31
2.1 Inserting and Adjusting of a New Project . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . 32
2.2 Setting the Interfaces . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 38
2.3 Customization of the Allocations. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . 40
3 Scaling and Thresholds for Transmission . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 53
3.1 Measured Value Scaling. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 54
3.2 Measured Value Threshold Processing . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 56
3.3 Counter Value Scaling . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . 57
4 Time Synchronization . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 59
4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . 60
4.2 Time Synchronization with IEC 60870-5-104 . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 60
5 IEC 60870-5-104 Diagnosis for EN100+ . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . 63
5.1 HTML Page. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . 64
5.2 SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . 68
5.3 IEC 60870-5-104 Error Indication . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . 69
6 Redundancy IEC 60870-5-104. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 71
6.1 General Introduction and Requirements. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 72
6.2 Configuration in DIGSI . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . 737SIPROTEC, Communication Module, Communication
ProfileC53000-L2040-C370-2, Edition 02.2013
7 Technical Data . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 75
7.1 Technical Data of EN100+ . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . 76
-
Contents
com_T104_profile_us.book Page 8 Tuesday, February 19, 2013 3:17
PM8 SIPROTEC, Communication Module, Communication Profile
Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . 77C53000-L2040-C370-2,
Edition 02.2013
-
com_T104_profile_us.book Page 9 Tuesday, February 19, 2013 3:17
PM1 Characteristic of the IEC 60870-5-104 Module
1.1 General 10
1.2 Identification of Module and Firmware 12
1.3 Supported IEC 60870-5-104 Object Types 14
1.4 Table of Parameters 17
1.5 Buffered Events 19
1.5 Buffered Events 19
1.6 File Transfer 20
1.7 Further Ethernet Services and Protocols 279SIPROTEC,
Communication Module, Communication ProfileC53000-L2040-C370-2,
Edition 02.2013
-
1 Characteristic of the IEC 60870-5-104 Module
1.1 General
com_T104_profile_us.book Page 10 Tuesday, February 19, 2013 3:17
PM10 SIPROTEC, Communication Module, Communication Profile
1.1 GeneralWith the EN100+ module firmware IEC 60870-5-104 from
version V1.00, the Ethernet-based IEC 60870-5-104 protocol is
implemented in addition to other transmission protocols (e.g. IEC
61850 and GOOSE, see chapter 1.7) in the 100 Mbit Ethernet module
EN100+.
The required settings are made by using the DIGSI 4
parameterization software from version 4.87.
Detailed information on the EN100+ module and the IEC 61850
engineering is given in the manuals:
German edition: Handbuch Ethernetmodul EN100+, Bestellnr.
C53000-G1100-C167-x
US-english edition: Manual Ethernet Module EN100+, order no.
C53000-G1140-C167-x
Abbreviations are used in the following text:
for 100-MBit Ethernet module EN100+: EN100+
for IEC 60870-5-104 over the internet protocol suite: IEC
60870-5-104
NOTERefer to your device manual to find out whether the device
you are using supports the IEC 60870-5-104 pro-tocol.The protocol
is available for the electrical and optical module.
NOTEFor the configuration of IEC 60870-5-104 a DIGSI 4 package
is required with IEC 61850 station
configurator.C53000-L2040-C370-2, Edition 02.2013
-
1 Characteristic of the IEC 60870-5-104 Module
1.1 General
com_T104_profile_us.book Page 11 Tuesday, February 19, 2013 3:17
PM11SIPROTEC, Communication Module, Communication Profile
Application
Figure 1-1 shows an application example of the SIPROTEC devices
with IEC 60870-5-104 and GOOSE in an installation where IEC
60870-5-104 is used for communication to a substation controller
and GOOSE for inter-device data exchange.
Fig. 1-1 Application Communication Example
Bus Mapping Documents
You can download the bus mapping document for each device type
at the following address:
http://siemens.siprotec.de/download_neu/index_e.htm
The bus mapping documents describe the data objects available
via IEC 60870-5-104.
Example: Manual SIPROTEC Feeder Automation Controller 7SC80,
order number C53000-L2040-C353
Accessories
EN100+ supports electrical and optical interface in different
variants. Please refer to Chapter 3.1 Getting Start-ed in
Commissioning in the Device in the manual of SIPROTEC4 Ethernet
Module EN100 for IEC 61850 with electrical/optical 100 MBit
Interface, for the technical specification of the cables needed for
electrical or optical connection.
To order these cables, please refer to SIPROTEC price list
available from your Siemens representative or sup-port
hotline.C53000-L2040-C370-2, Edition 02.2013
-
1 Characteristic of the IEC 60870-5-104 Module
1.2 Identification of Module and Firmware
com_T104_profile_us.book Page 12 Tuesday, February 19, 2013 3:17
PM12 SIPROTEC, Communication Module, Communication Profile
1.2 Identification of Module and Firmware
Modulinfo Menu
Available on HMI display or via WebMonitor:
Select Enter Test/Diagnosis Modulinfo Port F This shows e.g.
module type, communication protocol, network settings
Fig. 1-2 Modulinfo
Module type: EN100_E+ - EN100+ module with electrical Ethernet
interface
EN100_O+ - EN100+ module with fiber-optical Ethernet
interface
Communication protocol: IEC61850 - IEC61850/GOOSE
IEC 60870-5-104 - IEC 60870-5-104 with IEC61850/GOOSE option
(see chapter 1.7.2)
MLFB/Version Menu
Available on HMI display or via WebMonitor:
Select Enter Settings Setup/Extras MLFB/Version, then scroll
down twiceThis shows the version number of the firmware on EN100+
moduleC53000-L2040-C370-2, Edition 02.2013
-
1 Characteristic of the IEC 60870-5-104 Module
1.2 Identification of Module and Firmware
com_T104_profile_us.book Page 13 Tuesday, February 19, 2013 3:17
PM13SIPROTEC, Communication Module, Communication Profile
Fig. 1-3 MLFB/Version
HTML Page of the EN100+ Module
Refer to chapter 5.1.
If IEC 60870-5-104 firmware is loaded then the menu IEC
60870-5-104 is available in the navigation pane.
The firmware version is shown on the bottom of the homepage.
NOTEAlways the firmware identifcation IEC61850 is shown here,
also when IEC 60870-5-104 firmware is loaded. C53000-L2040-C370-2,
Edition 02.2013
-
1 Characteristic of the IEC 60870-5-104 Module
1.3 Supported IEC 60870-5-104 Object Types
com_T104_profile_us.book Page 14 Tuesday, February 19, 2013 3:17
PM14 SIPROTEC, Communication Module, Communication Profile
1.3 Supported IEC 60870-5-104 Object Types
Table 1-1 IEC 60870-5-104 Object Types
TI No. Type Identification
COT( Cause Of Transmission )
1 2 3 4 5 6 7 8 9 10 11 12 13 20to36
37to41
Description
M_SP_NA_1 X X X Single-point information
M_DP_NA_1 X X X Double-point infor-mation
M_ST_NA_1 X X X X Step position infor-mation
M_BO_NA_1 X Bitstring of 32 bit
M_ME_NC_1 X X X Measured value, short floating point value
M_IT_NA_1 X Integrated totals
M_SP_TB_1 X X X Single-point infor-mation with time tag
CP56Time2a
M_DP_TB_1 X X X Double-point infor-mation with time tag
CP56Time2a
M_ST_TB_1 X X X Step position infor-mation with time tag
CP56Time2a
M_ME_TF_1 X Measured value, short floating point value with time
tag CP56Time2a
M_IT_TB_1 X Integrated totals with time tag CP56Time2a
M_EP_TD_1 X Event of protection equipment with time tag
CP56Time2a
C_SC_NA_1 X X X X X Single command
C_DC_NA_1 X X X X X Double commandC53000-L2040-C370-2, Edition
02.2013
-
1 Characteristic of the IEC 60870-5-104 Module
1.3 Supported IEC 60870-5-104 Object Types
com_T104_profile_us.book Page 15 Tuesday, February 19, 2013 3:17
PM15SIPROTEC, Communication Module, Communication Profile
C_RC_NA_1 X X X X X Regulating step command
M_EI_NA_1 X End of initialization
C_IC_NA_1 X X X Interrogation command
C_CI_NA_1 X X X Counter interroga-tion command
C_RD_NA_1 X Read command
C_CS_NA_1 X X X Clock synchroniza-tion command (option see
7.6)
C_RP_NA_1 X X Reset process command
F_SC_NA_1 X X Call directory, select file, call file, call
section
F_AF_NA_1 X Ack file, ack section
F_DR_TA_1 X X Directory {blank or X, only available in monitor
(standard) direction}
Table 1-1 IEC 60870-5-104 Object Types (cont.)
TI No. Type Identification
COT( Cause Of Transmission )
1 2 3 4 5 6 7 8 9 10 11 12 13 20to36
37to41
DescriptionC53000-L2040-C370-2, Edition 02.2013
-
1 Characteristic of the IEC 60870-5-104 Module
1.3 Supported IEC 60870-5-104 Object Types
com_T104_profile_us.book Page 16 Tuesday, February 19, 2013 3:17
PM16 SIPROTEC, Communication Module, Communication Profile
Table 1-2 IEC 60870-5-104-Specific Parameters
COT Number Description
1 Periodic, cycilic
2 Background scan
3 Spontaneous
4 Initialized
5 Request or requested
6 Activation
7 Activation confirmation
8 Deactivation
9 Deactivation confirmation
10 Activation termination
11 Return info caused by a remote cmd
12 Return info caused by a local cmd
13 File transfer
20 to 36 Interrogated by group
37 to 41 Request by group counter request
44 Unknown type identification
45 Unknown cause of transmission
46 Unknown common address of ASDU
47 Unknown information object addressC53000-L2040-C370-2,
Edition 02.2013
-
1 Characteristic of the IEC 60870-5-104 Module
1.4 Table of Parameters
com_T104_profile_us.book Page 17 Tuesday, February 19, 2013 3:17
PM17SIPROTEC, Communication Module, Communication Profile
1.4 Table of ParametersThe following IEC 60870-5-104-specific
configuration parameters are available in the SIPROTEC device (i.e.
in the IEC 60870-5-104 mapping file, see chapter 2).
Table 1-3 IEC 60870-5-104-Specific Parameters
Parameter DefaultSetting
SettingRange
Description
OutstationAddress 1 1 to 250 IEC 60870-5-104 station address of
the device
MasterAddress1 0.0.0.0, 0.0.0.0
0.0.0.0 to 255.255.255.254
Addresses of the IEC 60870-5-104 masters
MasterAddress2
TcpPortNumber1TcpPortNumber2
2404, 2405
1000 to 65535TcpPortNumber1=2404TcpPortNumber2=2405
The TCP ports to listen on
Enable104TimeSynch 0 0,10 = device does not ex-pect time
synchronization from IEC 60870-5-104 master1 = device expect time
synchronization from IEC 60870-5-104 master
Determines whether the IEC 60870-5-104 outstation expect and
evalu-ates time synchronization from IEC 60870-5-104 master
EnableRedundancy 0 0,10 = no redundancy1 = redundancy
support-ed
Determines whether the IEC 60870-5-104 outstation supports the
redun-dancy
t1AckPeriod_1/2 15 1 to 255 (in seconds) Determines the Time-out
of send or test APDUs for connection with the master 1 or master
2
t2SFramePeriod_1/2 10 1 to 255 (in seconds) Determines the
Time-out for ac-knowledges in case of no data mes-sages(t2 < t1)
for connection with the master 1 or master 2
t3TestPeriod_1/2 20 1 to 255 (in seconds) Determines the
Time-out for sending test frames in case of a long idle state for
connection with the master 1 or master 2
TransMeasurements 0 0,1,2,30 = not assigned 1 = cyclic2 =
general interrogation3 = cyclic and general in-terrogation
Choice of the measured values transmission (in addition to
events)C53000-L2040-C370-2, Edition 02.2013
-
1 Characteristic of the IEC 60870-5-104 Module
1.4 Table of Parameters
com_T104_profile_us.book Page 18 Tuesday, February 19, 2013 3:17
PM18 SIPROTEC, Communication Module, Communication Profile
.
CyclicTime 60 0, 1 to 65535 (in seconds)0 = swiched off
Time for sending cyclical data (in seconds) only valid if
transmission of measuremens is cyclic or cyclic and general
interrogation
MeasureTimeStamp 1 0, 10 = no time stamp1 = with time stamp
Determines wether the measured value events are sent with time
stamp or not
MeasureDelay 1000 0, 1 to 10000 (in miliisec-onds)0 = no
delay
Determines the delay time when sending spontaneous measure-ments
(in milliseconds)
Table 1-3 IEC 60870-5-104-Specific Parameters (cont.)
Parameter DefaultSetting
SettingRange
Description
NOTEThe settings above are valid for all TCP connections in the
same way; they are not configurable individually per TCP connection
or connected IEC 60870-5-104 master.
During startup of the Ethernet module it is checked whether all
IEC 60870-5-104 parameters are configured in their valid ranges
given in table 1-4 and table 1-3. If a parameter value is detected
outside the valid range, an error log entry is issued on the EN100+
module and the parameter is set to its default value (see figure
5-2).C53000-L2040-C370-2, Edition 02.2013
-
1 Characteristic of the IEC 60870-5-104 Module
1.5 Buffered Events
com_T104_profile_us.book Page 19 Tuesday, February 19, 2013 3:17
PM19SIPROTEC, Communication Module, Communication Profile
1.5 Buffered EventsWhen a SOE(Sequence of Event) happened, this
event will be transmitted to the master, if the transmission is
successful this event will be cleared up in the buffer, otherwise
the event will be stored in the buffer and wait for the next
transmission try. The max event entries are 100 items for each type
of indication including SP (Sin-gle Point indication), DP (Double
Point indication) and Counter Value. The latest event will replace
the oldest one when buffered event reaches maximum
amount.C53000-L2040-C370-2, Edition 02.2013
-
1 Characteristic of the IEC 60870-5-104 Module
1.6 File Transfer
com_T104_profile_us.book Page 20 Tuesday, February 19, 2013 3:17
PM20 SIPROTEC, Communication Module, Communication Profile
1.6 File Transfer
1.6.1 Reading of Fault RecordsFault records from the device can
be read using the file transfer feature of IEC 60870-5-104. The
fault records are converted on the EN100+ module to Comtrade
format.
For reading a fault record, the following steps must be
executed:
Open the directory file of available fault records which are
available using IEC 60870-5-104 TI122(call directo-ry), COT 5
(request), e.g.:
The IEC 60870-5-104 outstation responds with IEC 60870-5-104
TI126, COT5 (response).
If no fault records are available, the returned object is zero,
otherwise it is different from zero, e.g.
With this response, a file handle is returned
Object:11010001).
In the IEC 60870-5-104 master the file selection after directory
read could look like this:
NOTEASE2000 version 2 is used as IEC 60870-5-104 test master for
the examples.C53000-L2040-C370-2, Edition 02.2013
-
1 Characteristic of the IEC 60870-5-104 Module
1.6 File Transfer
com_T104_profile_us.book Page 21 Tuesday, February 19, 2013 3:17
PM21SIPROTEC, Communication Module, Communication Profile
Fig. 1-4 Select File Name on Remote Device to Read
NOTEThe file named with 11xxxxxx can be saved as a *.dat file,
and the file named with 12xxxxxx can be saved as a *.cfg file. The
file named with 13xxxxxx can be saved as a *.txt
file.C53000-L2040-C370-2, Edition 02.2013
-
1 Characteristic of the IEC 60870-5-104 Module
1.6 File Transfer
com_T104_profile_us.book Page 22 Tuesday, February 19, 2013 3:17
PM22 SIPROTEC, Communication Module, Communication Profile
Read the file(s) of interest, e.g. the file "11010001": Read
file use TI 122 COT 13 SCQ 01 to request and use TI 120 COT 13 to
response:C53000-L2040-C370-2, Edition 02.2013
-
1 Characteristic of the IEC 60870-5-104 Module
1.6 File Transfer
com_T104_profile_us.book Page 23 Tuesday, February 19, 2013 3:17
PM23SIPROTEC, Communication Module, Communication Profile
Read section use TI122 COT 13 SCQ 02 to request and use TI 121
COT 13 to response: C53000-L2040-C370-2, Edition 02.2013
-
1 Characteristic of the IEC 60870-5-104 Module
1.6 File Transfer
com_T104_profile_us.book Page 24 Tuesday, February 19, 2013 3:17
PM24 SIPROTEC, Communication Module, Communication Profile
Call section use TI 122 COT 13 SCQ 06 to request and use TI 125
COT 13 to response:
When one section is transmitted, the outstation will send last
section TI 123 COT 13 to the master:C53000-L2040-C370-2, Edition
02.2013
-
1 Characteristic of the IEC 60870-5-104 Module
1.6 File Transfer
com_T104_profile_us.book Page 25 Tuesday, February 19, 2013 3:17
PM25SIPROTEC, Communication Module, Communication Profile
Then, the master can call the next section as the same.
When all the sections are transmitted, the master will send ACK
TI 124 COT 13 to the outstation.
The read file now is available in the IEC 60870-5-104 master and
the next file can be read.
After that, the fault record Comtrade file can be evaluated,
e.g. with the "SIGRA 4 - Fault Evaluation Software" from
Siemens.
1.6.2 Reading of Parameter FileParameter file from the device
can be read using the file transfer feature of IEC 60870-5-104 as
well. The op-eration is nearly the same as reading of fault record
file. Please refer to chapter 1.7.1.C53000-L2040-C370-2, Edition
02.2013
-
1 Characteristic of the IEC 60870-5-104 Module
1.6 File Transfer
com_T104_profile_us.book Page 26 Tuesday, February 19, 2013 3:17
PM26 SIPROTEC, Communication Module, Communication Profile
The file looks like figure 1-5:
Fig. 1-5 Parameter File
The following table gives a reference for understanding the
parameter file.
Table 1-4 Reference for Parameter File
Unit ID Description
1 Dimensionless
5 A (amperer)
23 C (degree centigrade)
29 V (volt)
33 Hz ((hertz))
61 VA
62 W (watt)
63 var
72 Wh
73 varh
Multipier ID Description
3 k (kilo)
6 M (mega)C53000-L2040-C370-2, Edition 02.2013
-
1 Characteristic of the IEC 60870-5-104 Module
1.7 Further Ethernet Services and Protocols
com_T104_profile_us.book Page 27 Tuesday, February 19, 2013 3:17
PM27SIPROTEC, Communication Module, Communication Profile
1.7 Further Ethernet Services and ProtocolsThe following
additional services and protocols are supported on the EN100+
module. With DIGSI 4 these ser-vices can be switched ON or OFF.
Unused services shall be switched OFF for security reason.
1.7.1 Services Module homepage (HTTP)
Firmware upgrade (HTTP)
DIGSI 4 over EN100+
SNMP V2 (see chapter 5.2)
IEC 61850 and GOOSE
SNTP (see chapter 4.2)
For more information, please refer to the following manual:
Ethernet Module EN100+ for IEC 61850 with electrical/optical 100
Mbit Interface,Order number C53000-G1140-C167
1.7.2 IEC 60870-5-104 with IEC 61850 and GOOSEThe communication
IEC 60870-5-104 with IEC 61850 and GOOSE is represented in the
following figure:
NOTEIn order to make sure the GOOSE service runs smoothly, it is
recommended that the maximum GOOSE set-tings from sending or
receiving sides are less than 100.C53000-L2040-C370-2, Edition
02.2013
-
1 Characteristic of the IEC 60870-5-104 Module
1.7 Further Ethernet Services and Protocols
com_T104_profile_us.book Page 28 Tuesday, February 19, 2013 3:17
PM28 SIPROTEC, Communication Module, Communication Profile
Fig. 1-6 IEC 60870-5-104 with IEC 61850 and GOOSE
IEC61850: 2 process clients maximum in the system
GOOSE: Publisher: 12 GOOSE applications/dataset maximum per
device, with 120 data objects in total Subscriber: 100 GOOSE
dataset per device, with 1000 data objects in total
Set minimum monitoring >= 10 ms (use standard settings of
communication profile PriorityLow in GOOSE pa-rameters of the IEC
61850 System Configurator)
The above mentioned recommendations are not fixed, the system
allows configuring more GOOSE applica-tions and more data objects
as source and destination. Higher GOOSE load may lead to delayed
transmission. Please test and verify the needed transmission times
for indications in your specified application.C53000-L2040-C370-2,
Edition 02.2013
-
com_T104_profile_us.book Page 31 Tuesday, February 19, 2013 3:17
PM2 Configuration in DIGSI 4
2.1 Inserting and Adjusting of a New Project 32
2.2 Setting the Interfaces 38
2.3 Customization of the Allocations 4031SIPROTEC, Communication
Module, Communication ProfileC53000-L2040-C370-2, Edition
02.2013
-
2 Configuration in DIGSI 4
2.1 Inserting and Adjusting of a New Project
com_T104_profile_us.book Page 32 Tuesday, February 19, 2013 3:17
PM32 SIPROTEC, Communication Module, Communication Profile
2.1 Inserting and Adjusting of a New Project
Open DIGSI Manager.
Click File New...
Fig. 2-1 New Project Dialog
NOTEIn order to configure the IEC 60870-5-104 protocol, the
device functions must be parameterized correctly. For detailed
information in this context, please see chapter 1.1 (Prerequisites
at DIGSI 4) of the DIGSI 4 manual.
NOTEThe following configuration is shown for the 7SC80.
C53000-L2040-C370-2, Edition 02.2013
-
2 Configuration in DIGSI 4
2.1 Inserting and Adjusting of a New Project
com_T104_profile_us.book Page 33 Tuesday, February 19, 2013 3:17
PM33SIPROTEC, Communication Module, Communication Profile
Enter a name for the new project (7SC80_XX in the example) and
select the storage location (path). Next click OK.
Fig. 2-2 DIGSI Manager with a New Project
Right-click Folder and open the Device Catalog via Insert New
Object SIPROTEC device.
Fig. 2-3 DIGSI Manager with an Object
SelectedC53000-L2040-C370-2, Edition 02.2013
-
2 Configuration in DIGSI 4
2.1 Inserting and Adjusting of a New Project
com_T104_profile_us.book Page 34 Tuesday, February 19, 2013 3:17
PM34 SIPROTEC, Communication Module, Communication Profile
Select the desired device in the Device Catalog (7SC feeder
automation/7SC802/V4.0 in the example) and copy the object into the
Folder of the DIGSI Manager window via Drag&Drop.
Fig. 2-4 Device Catalog
The MLFB tab of Properties - SIPROTEC device dialog opens (see
figure 2-5 ).
Configure the order number (MLFB) of your device in the
Properties - SIPROTEC device dialog and press the OK button.
Fig. 2-5 Configuring the Order Number (MLFB)
If you have retrofitted the device or if you want to install the
IEC 60870-5-104 protocol afterwards, you have to activate the IEC
60870-5-104 protocol on the tab Communication modules List item 11.
Port C53000-L2040-C370-2, Edition 02.2013
-
2 Configuration in DIGSI 4
2.1 Inserting and Adjusting of a New Project
com_T104_profile_us.book Page 35 Tuesday, February 19, 2013 3:17
PM35SIPROTEC, Communication Module, Communication Profile
F (Communication Interface) Selection L:.. Additional
Information dialog.
Fig. 2-6 Activating the IEC 60870-5-104 Protocol
Click the OK button.
Right-click Folder and insert an IEC61850 station via Insert New
Object IEC61850 station.An IEC61850 station is inserted in DIGSI
Manager.
Fig. 2-7 Inserting an IEC61850 Station
In DIGSI Manager, right-click IEC61850 station and select the
Object properties menu item.
Select a device from the Available IEC61850 devices in the
Properties - IEC61850 station dialog Communicator tab and click
Add.The selected device is moved from the Available IEC61850
devices window into the IEC61850 station communicator
window.C53000-L2040-C370-2, Edition 02.2013
-
2 Configuration in DIGSI 4
2.1 Inserting and Adjusting of a New Project
com_T104_profile_us.book Page 36 Tuesday, February 19, 2013 3:17
PM36 SIPROTEC, Communication Module, Communication Profile
Fig. 2-8 Select Device into IEC61850 Station Communicator
Click the OK button.
Double-click the SIPROTEC device in DIGSI Manager.The Open
device dialog opens.
Activate the option Offline in the Connection type section and
confirm with OK.
Fig. 2-9 Opening the SIPROTEC DeviceC53000-L2040-C370-2, Edition
02.2013
-
2 Configuration in DIGSI 4
2.1 Inserting and Adjusting of a New Project
com_T104_profile_us.book Page 37 Tuesday, February 19, 2013 3:17
PM37SIPROTEC, Communication Module, Communication Profile
After initialization the following window opens:
Fig. 2-10 Select FunctionsC53000-L2040-C370-2, Edition
02.2013
-
2 Configuration in DIGSI 4
2.2 Setting the Interfaces
com_T104_profile_us.book Page 38 Tuesday, February 19, 2013 3:17
PM38 SIPROTEC, Communication Module, Communication Profile
2.2 Setting the Interfaces Double-click the function
Settings.
The following windows opens.
Fig. 2-11 Settings
Double-click the function Interfaces.The Interface Settings
dialog opens.
Select the Additional protocols at device tab.
Fig. 2-12 Mapping File Selection and Module-specific
SettingsC53000-L2040-C370-2, Edition 02.2013
-
2 Configuration in DIGSI 4
2.2 Setting the Interfaces
com_T104_profile_us.book Page 39 Tuesday, February 19, 2013 3:17
PM39SIPROTEC, Communication Module, Communication Profile
List Box Mapping File
If no mapping file is currently assigned to the SIPROTEC device
then the following entries are available in the list box Mapping
file:
The following entries can be selected at an already existing
mapping file assignment:
If the mapping file assignment was changed for a SIPROTEC
device, then this is in general connected with a change of the
routing of the SIPROTEC objects to the system interface.
Please, check after choice of a new mapping file the allocations
to column Destination or Source in the DIGSI configuration
matrix.
To activate and change the protocol IEC 60870-5-104 , proceed as
follows:
Activate the mapping file IEC 60870-5-104 standard mapping 3-1
in the list box Mapping file. If necessary, change the entries in
the Module-specific settings edit area according to your device
configuration.
Click the OK button.
Table 2-1 Selection without Module-specific Settings
Selection Meaning
No mapping file is assigned to the device.
IEC60870-5-104 standard mapping 3-1 toIEC60870-5-104 standard
mapping 3-n
Selection of a mapping file 3-1 to 3-n (n = device type
dependent number of standard mappings).
Table 2-2 Selection with Module-specific Settings
Selection Meaning
No mapping file is assigned to the device.
This selection indicates the device will use the current content
in the edit area Module-specific settings, which can have the
updated bus specific parameters upon specific requirement.
IEC60870-5-104 standard mapping 3-1 toIEC60870-5-104 standard
mapping 3-n
New Selection of a mapping file 3-1 to 3-n(n = device type
dependent number of standardmappings). All bus specific parameters
are reset todefault values.
NOTEThe mapping file is factory-set, but you can adapt it to
your device configuration.
NOTEPlease, edit only the numbers in the rows which do not start
with // and note the semicolons at the end of the line.
Editing anything else in the Module-specific settings may cause
an error when closing the Interface Settings
dialog.C53000-L2040-C370-2, Edition 02.2013
-
2 Configuration in DIGSI 4
2.3 Customization of the Allocations
com_T104_profile_us.book Page 40 Tuesday, February 19, 2013 3:17
PM40 SIPROTEC, Communication Module, Communication Profile
2.3 Customization of the Allocations Double-click the function
Masking I/O (Configuration Matrix) in the dialog Settings acc. to
Figure 2-11.
The windows Setting Masking I/O opens:
Fig. 2-13 DIGSI 4 Configuration Matrix with Columns for System
Interface Routing
Move the cursor in the columns Source and Destination over port
F and determine the column assigned to IEC 60870-5-104 (marked in
red in Figure 2-13).
The used protocol is displayed (text in a yellow box) if you
stop for a short while on the letter F.
If necessary, adapt the default routing in the configuration
matrix to your SIPROTEC device/installation as follows. If you do
not want to change anything in the DIGSI routing matrix, continue
with the section Time Synchronization.
If you want to delete all default routings to set new default
routings, right-click the corresponding port F or the system
interface S in Source or Destination. Then, click the query Delete
configurations at Port F or Delete configurations at System
Interface.A dialog appears with the information that a deletion is
not possible or with the confirmation about how many entries can be
deleted or cannot be deleted. Confirm this information with OK:
NOTEAnother port instead of port F can be displayed as Source
and Destination of the system interface, for exam-ple, port B for
SIPROTEC 4 devices.
NOTEIf you do not want to display all columns and rows in the
configuration matrix for the setting of the system in-terface or
for your information, you can minimize these columns and rows by
double-clicking the corresponding button. If you want to enter
values to the minimized columns, you can maximize these columns
again by dou-ble-clicking the corresponding
button.C53000-L2040-C370-2, Edition 02.2013
-
2 Configuration in DIGSI 4
2.3 Customization of the Allocations
com_T104_profile_us.book Page 41 Tuesday, February 19, 2013 3:17
PM41SIPROTEC, Communication Module, Communication Profile
Fig. 2-14 Indications for Deletion
The identification whether an information is routed on system
interface (IEC 60870-5-104) is shown in the col-umns Source and
Destination, port F, system interface S in the DIGSI configuration
matrix.
A cross ('X') in this column indicates the associated
information as "routed on system interface"(see Figure 2-13).
Source System Interface
The SIPROTEC object can be controlled via IEC 60870-5-104. This
is possible for the following information types (column Type in
configuration matrix): IntSP Internal single-point indication
(tagging)
IntDP Internal double-point indication (tagging)
SC/DC Single control/Double control without feedback from
process
SF/DF Single control/Double control with feedback from
process
Destination System Interface
The value of the SIPROTEC object is transmitted to the IEC
60870-5-104 master. This is possible for the fol-lowing information
types:
SP Single-point indication
DP Double-point indication
Out Output annunciation
IntSP Internal single-point indication (tagging)
IntDP Internal double-point indication (tagging)
MV Measured value
MVMV Power meter (metered measurand, source is a measured
value)
PMV Pulse (metered measurand, source is a pulsed binary
input)C53000-L2040-C370-2, Edition 02.2013
-
2 Configuration in DIGSI 4
2.3 Customization of the Allocations
com_T104_profile_us.book Page 42 Tuesday, February 19, 2013 3:17
PM42 SIPROTEC, Communication Module, Communication Profile
To add or remove an information to Source or Destination of
system interface set/reset the cross ('X') in the associated column
of the DIGSI configuration matrix (pop-up menu when pressing the
right mouse button).
Fig. 2-15 Pop-up Menu in Column Destination F/S
Fig. 2-16 Error Message
NOTE The maximum number ( see Table 2-3) of routable objects of
an information type varies according to the
chosen mapping file. If e.g. a measured value not routed in the
mapping file per default shall be transferred via IEC 60870-5-104,
then first a measured value already routed has to be removed from
system interface so that the position gets available in the IEC
60870-5-104 message.
The maximum number of user defined objects mapping to IEC 61850
system interface is recommended not more than 100. Otherwise, it
may cause the MMS disabled.
An error message (see Figure 2-16) is shown if all routing
possibilities of an information type are occupied and if it is
nevertheless tried to route an information of this type.
Table 2-3 The Maximum Number
Info Types Maximum Number
Comments
Measured Values 59 Include 5 user defined values
Counter Value 12 Include 5 user defined values
Single Point 108 Include 14 user defined values
Double Point 5 Include 2 user defined values
Step Position 5 5 user defined values
Single Commands 9 Include 4 user defined commands
Double Commands 5 Include 2 user defined commands
Step Position Commands 5 5 user defined
commandsC53000-L2040-C370-2, Edition 02.2013
-
2 Configuration in DIGSI 4
2.3 Customization of the Allocations
com_T104_profile_us.book Page 43 Tuesday, February 19, 2013 3:17
PM43SIPROTEC, Communication Module, Communication Profile
Adding an Allocation
Adding an allocation requires (in addition to the identification
in the system interface column of the DIGSI con-figuration matrix)
the selection of the position of the information in the IEC
60870-5-104 message as well as the definition of scaling values for
measured values (scaling of measured values see chapter 3 Scaling
and Thresholds for Transmission).
Therefore after adding the allocation, the Object properties
dialog window which is used to define the mes-sage position of the
information is opened automatically (property sheets for source:
Protocol info - Source F; property sheets for destination: Protocol
info - Destination F and Measured value - Destination F).
Fig. 2-17 Definition of the Position of an Information in the
IEC 60870-5-104 Message
Change of an Existing Allocation
If the information already routed on system interface shall get
another (empty) position in the IEC 60870-5-104 message, then the
Object properties dialog (see Figure 2-17) has to be selected
(Properties ... in the pop-up menu when pressing the right mouse
button in one of the columns Display text, Long text or Type of
the
NOTE The information type of double commands for routing as
Source system interface depends on the infor-
mation type of the associated checkback indication.
Only double commands with a double-point indication as checkback
indication can be routed to the positions in the IEC 60870-5-104
message which are reserved for double commands according to the bus
mapping.
Double commands with a single-point indication as checkback
indication or without checkback indication are treated via IEC
60870-5-104 like single commands and must be routed to the
positions reserved for single commands.
Commands without checkback indication can not be routed to
Destination of system interface. Reading the state of these command
types is not possible via IEC 60870-5-104.C53000-L2040-C370-2,
Edition 02.2013
-
2 Configuration in DIGSI 4
2.3 Customization of the Allocations
com_T104_profile_us.book Page 44 Tuesday, February 19, 2013 3:17
PM44 SIPROTEC, Communication Module, Communication Profile
DIGSI configuration matrix in the row which is associated to the
information).
Fig. 2-18 Change of an Existing Allocation
Depending on the information type the following parameters are
to select in the property sheetProtocol info - Source F, Protocol
info - Destination F or Measured value - Destination F of the
Object properties dialog:
Table 2-4 Protocol Info Source
Parameter Comments Info Types
Obj Address The index indicates the address of this object.
IntSP, IntDP, SC/DC, SF/DF
Flags Command properties (Latch ON/OFF, ... - depending on the
object info type)
Table 2-5 Protocol Info Destination
Parameter Comments Info Types
Obj Address The index indicates the address of this object. SP,
DP, Out, IntSP, IntDP, MV, MVMV, PMV
Type The index indicates the types that this object can be
mapped to.
SP,IntSP,OutC53000-L2040-C370-2, Edition 02.2013
-
2 Configuration in DIGSI 4
2.3 Customization of the Allocations
com_T104_profile_us.book Page 45 Tuesday, February 19, 2013 3:17
PM45SIPROTEC, Communication Module, Communication Profile
Measurement Conversion
Before transmission of a measured value via IEC 60870-5-104 a
measurement conversion (scaling) must be executed in the SIPROTEC
device.
Scaling
Scaling of a measured value to the format for the transmission
via IEC 60870-5-104 means the definition of:
Type
Scaling factor
Zero offset
Type
Decision, whether the measured value is transmitted as
percentage value or whether a conversion shall take place into
primary or secondary value before (depending on the measured value
not all of these three possibil-ities are available, e.g. no
secondary values for power values).
Threshold value
Changes of measured values are transmitted using IEC 60870-5-104
object 32 (Analog Change Event) only if the accumulated change
differences of the 16-bit analog input exceed the threshold
value.
Scaling factor
The measured value in the SIPROTEC device (floating-point
format) is multiplied by the scaling factor before transformation
to an integer value. With that it is possible to transfer
fractional digits by multiplication by a mul-tiple of 10 in the
integer value.
Zero offset
The Zero offset is added to the result of the multiplication of
the measured value in the SIPROTEC device (float-ing-point format)
by the scaling factor.
The measured value in the integer format for transmission via
IEC 60870-5-104 is calculated summarizing ac-cording to the
following formula:
Measured valueInteger = Measured valueFloat * Scaling factor +
Zero offset
in which "Measured valueFloat" is a percentage value or, if
necessary, changed into primary value or secondary value before
(according to the definition of type).C53000-L2040-C370-2, Edition
02.2013
-
2 Configuration in DIGSI 4
2.3 Customization of the Allocations
com_T104_profile_us.book Page 46 Tuesday, February 19, 2013 3:17
PM46 SIPROTEC, Communication Module, Communication Profile
Time Synchronization
If the device requires time synchronization with NTP or IEC
60870-5-104, double-click Time Synchronization.The Time
Synchronization & Time Format dialog opens.
Select Ethernet NTP as the source in the field Source of time
synchronization and set the desired parameters.
Fig. 2-19 Setting theTime Synchronization
Confirm with OK.
Close the SIPROTEC device and confirm that you want to save the
modified data.
Close the Report window.
Double-click IEC61850 station in DIGSI Manager. The DIGSI system
configurator opens with the IEC61850 station application and
Subnet1.C53000-L2040-C370-2, Edition 02.2013
-
2 Configuration in DIGSI 4
2.3 Customization of the Allocations
com_T104_profile_us.book Page 47 Tuesday, February 19, 2013 3:17
PM47SIPROTEC, Communication Module, Communication Profile
Fig. 2-20 DIGSI System Configurator - Subnet
If necessary, change the name for Subnet1 in the Properties
window (right window) and the parameters (e.g. IP start address,
Subnet mask, Standard gateway).
Click the SIPROTEC device and change its parameters in the
Properties window (right window) (e.g. IP address, Subnet mask,
Standard gateway).
Fig. 2-21 DIGSI System Configurator - SIPROTEC Device
Close the DIGSI system configurator and confirm saving the
IEC61850 station settings with OK. C53000-L2040-C370-2, Edition
02.2013
-
2 Configuration in DIGSI 4
2.3 Customization of the Allocations
com_T104_profile_us.book Page 48 Tuesday, February 19, 2013 3:17
PM48 SIPROTEC, Communication Module, Communication Profile
The following steps only have to be carried out if time
synchronization via NTP or IEC 60870-5-104 is required; in case of
time synchronization via NTP with a second redundant NTP server,
these steps have to be carried out for two NTP servers:
Right-click Folder and open the Import device dialog via Insert
New Object Other IEC61850 communicator.
Search for the file sntp.icd in the DIGSI 4 folder and click
OK.(Example (x = hard drive directory):
x:\DIGSI4\Utilities\IEC61850\ICD\sntp.icd)
TEMPLATE is inserted in the DIGSI Manager window.
Rename TEMPLATE to NTP Server. In DIGSI Manager, right-click
IEC61850 station and select the menu item Object properties...
Select a device from the Available IEC61850 devices in the
Properties - IEC61850 station dialog
Communicator tab and click Add.The selected device is moved from
the Available IEC61850 devices window into the IEC61850 station
communicator window and click OK.
Double-click on IEC61850 station in DIGSI Manager.The DIGSI
system configurator opens with the IEC61850 station
application.
Drag & Drop the NTP server entered under New devices (1)
into the Subnet1 folder.
Fig. 2-22 Integrating the NTP Server in Subnet1
Click on NTP server and enter the IP address under Parameter in
the Properties window (right window). If necessary, change
subsequently the Subnet mask and the Standard gateway.
Close the DIGSI system configurator and confirm saving the IEC
61850 station settings with OK.Please refer to chapter 4 Time
Synchronization .
Parameterizing the Device Functions
Open the SIPROTEC device from the DIGSI 4 user
interface.C53000-L2040-C370-2, Edition 02.2013
-
2 Configuration in DIGSI 4
2.3 Customization of the Allocations
com_T104_profile_us.book Page 49 Tuesday, February 19, 2013 3:17
PM49SIPROTEC, Communication Module, Communication Profile
Enter all desired settings (see Figure 2-11).
Save the parameter set and subsequently close the device on the
DIGSI 4 user interface.
Update the Parameter Sets of IEC 61850
In DIGSI Manager, right-click IEC61850 station and select the
menu item Object properties...
In the Properties - IEC61850 station dialog box select the
Update tab and update the parameter set using the Update all
parameter sets button.
Close the Report window and the Properties - IEC61850 station
dialog box.
Initializing the SIPROTEC Device
Right-click the SIPROTEC device in DIGSI Manager.
Click Initialize device.... in the menu that opens.
Fig. 2-23 Click Initialize Device in the Menu
NOTEThese settings, e.g. protection settings, CFC charts and
routing to binary inputs/outputs or LEDs, are described in the
DIGSI 4 manual.
NOTETo activate the modified parameters, you have to update the
parameter set after each time you have changed the settings in
DIGSI Manager.
NOTEThe SIPROTEC device only has to be initialized once when a
new device has been added.C53000-L2040-C370-2, Edition 02.2013
-
2 Configuration in DIGSI 4
2.3 Customization of the Allocations
com_T104_profile_us.book Page 50 Tuesday, February 19, 2013 3:17
PM50 SIPROTEC, Communication Module, Communication Profile
Adapt again the device settings in DIGSI 4 or the IEC
60870-5-104 settings in the mapping file if necessary.
To transmit the device settings modified in DIGSI Manager to the
SIPROTEC device, right-click the SIPROTEC device.
Click DIGSI -> Device... in the menu that opens.
Fig. 2-24 Click DIGSI -> Device in the
MenuC53000-L2040-C370-2, Edition 02.2013
-
2 Configuration in DIGSI 4
2.3 Customization of the Allocations
com_T104_profile_us.book Page 51 Tuesday, February 19, 2013 3:17
PM51SIPROTEC, Communication Module, Communication Profile
Select the Connection type and the device in the Transfer the
parameter set dialog.
Fig. 2-25 Select the Connection type
Fig. 2-26 Transfer the parameter setC53000-L2040-C370-2, Edition
02.2013
-
2 Configuration in DIGSI 4
2.3 Customization of the Allocations
com_T104_profile_us.book Page 52 Tuesday, February 19, 2013 3:17
PM52 SIPROTEC, Communication Module, Communication Profile
C53000-L2040-C370-2, Edition 02.2013
-
com_T104_profile_us.book Page 53 Tuesday, February 19, 2013 3:17
PM3 Scaling and Thresholds for Transmission
3.1 Measured Value Scaling 54
3.2 Measured Value Threshold Processing 56
3.3 Counter Value Scaling 5753SIPROTEC, Communication Module,
Communication ProfileC53000-L2040-C370-2, Edition 02.2013
-
3 Scaling and Thresholds for Transmission
3.1 Measured Value Scaling
com_T104_profile_us.book Page 54 Tuesday, February 19, 2013 3:17
PM54 SIPROTEC, Communication Module, Communication Profile
3.1 Measured Value ScalingDepending on the rated values of the
primary equipment of the installation (Vrated, Irated), the scaling
of the measured values has to be adapted in order to ensure a
correct transmission of these values in integer format ( 32767)
including implicit fractional digits.
Example with rated current: 120 A
Primary current values in SIPROTEC are then displayed in A.
For transmission with implicit one fractional digit a scaling
factor of 10 must be used:
120 A then is transmitted as: 120 * 10 = 1200
Example with rated current: 1500 A
Primary current values in SIPROTEC are then displayed in kA.
For transmission with implicit 3 fractional digit a scaling
factor of 1000 must be used:
1.5 kA then is transmitted as: 1.5 * 1000 = 1500
In addition to the scaling factor it has to be determined
whether the measured value shall be transmitted as primary value,
secondary value or percentage value (i.e. the measured value
type).
For the scaling of a measured value, a scaling index in the
conversion table has to be selected which is a com-bination of
scaling value, threshold value and measured value type as shown in
the following table with the de-fault entries:
NOTEBy default, only primary values are used with IEC
60870-5-104.
Table 3-1 Conversion Table for Measured Values with Default
Entries
Scaling Index Scaling Factor Measured Value Type
Threshold Value (in%)
By Default Used for
0 10 Primary value 5 AC currents
1 100 Primary value 3 AC voltages
2 100 Primary value 10 Power
3 1000 Primary value 5 Power factor
4 100 Primary value 0.1 Frequency
5 10 Primary value 2 DC voltages
6 10 Primary value 2 Temperatures
7 100 Primary value 10 -C53000-L2040-C370-2, Edition 02.2013
-
3 Scaling and Thresholds for Transmission
3.1 Measured Value Scaling
com_T104_profile_us.book Page 55 Tuesday, February 19, 2013 3:17
PM55SIPROTEC, Communication Module, Communication Profile
The scaling index also determines the threshold value for
measured values.
Threshold value: Changes of measured values are transmitted
using object 32 (Analog Change Event) only if the accumulated
change differences of the 16-bit Analog Input exceed the threshold
value.
8 100 Percentage value 10 -
9 100 Percentage value 10 -
10 10 Secondary value 10 -
11 100 Secondary value 10 -
Table 3-1 Conversion Table for Measured Values with Default
Entries (cont.)
Scaling Index Scaling Factor Measured Value Type
Threshold Value (in%)
By Default Used forC53000-L2040-C370-2, Edition 02.2013
-
3 Scaling and Thresholds for Transmission
3.2 Measured Value Threshold Processing
com_T104_profile_us.book Page 56 Tuesday, February 19, 2013 3:17
PM56 SIPROTEC, Communication Module, Communication Profile
3.2 Measured Value Threshold ProcessingThreshold processing is
executed based on a combined fixed and integrated threshold method
and based on relative thresholds related to the last transmitted
value.
Relative thresholds related to the last transmitted valueThe
threshold values are given in percent.
The absolute size of the threshold value in units of the
measured value depends on the value last transmitted to the master
and is smaller for smaller values than for larger values.
Example for Configured Threshold Value: 10 %
Last transmitted value: 100 V
Current threshold in units: 10 V
If the last transmitted value was zero, a measured value change
is transmitted immediately.
NOTEThis is independent if the last value has been transmitted
by a change event or by a value request from the IEC 60870-5-104
master, e.g. for General Interrogation.C53000-L2040-C370-2, Edition
02.2013
-
3 Scaling and Thresholds for Transmission
3.3 Counter Value Scaling
com_T104_profile_us.book Page 57 Tuesday, February 19, 2013 3:17
PM57SIPROTEC, Communication Module, Communication Profile
3.3 Counter Value Scaling
Scaling
The scaling of the metered measurands, which are derived from
measured values, refers to:
60,000 impulses per hour for V = Vprim and I = Iprim
Vprim = Full Scale Voltage
(parameter address = 1101)
Iprim = Full Scale Current
(parameter address = 1102)
Example
The following is configured in the parameter set:
Iprim = 1000 A and Vprim = 400.0 kV
60,000 impulses correspond so that:
1 h * 1000 A * 400 kV * = 692.82 MWh3
NOTE The type of the update (cyclic, with or without deletion)
and the update interval must be programmed for
the metered measurands with the parametrization software DIGSI
4.
The scaling of the metered measurands at binary inputs Wp(puls)
and Wq(puls) depends on the externally connected pulse
generator.C53000-L2040-C370-2, Edition 02.2013
-
3 Scaling and Thresholds for Transmission
3.3 Counter Value Scaling
com_T104_profile_us.book Page 58 Tuesday, February 19, 2013 3:17
PM58 SIPROTEC, Communication Module, Communication Profile
C53000-L2040-C370-2, Edition 02.2013
-
com_T104_profile_us.book Page 59 Tuesday, February 19, 2013 3:17
PM4 Time Synchronization
4.1 General 60
4.2 Time Synchronization with IEC 60870-5-104 6059SIPROTEC,
Communication Module, Communication ProfileC53000-L2040-C370-2,
Edition 02.2013
-
4 Time Synchronization
4.1 General
com_T104_profile_us.book Page 60 Tuesday, February 19, 2013 3:17
PM60 SIPROTEC, Communication Module, Communication Profile
4.1 GeneralDuring operation, SIPROTEC devices need the date and
time for all time-relevant processes. The time syn-chronization is
required to guarantee a uniform time basis for the communication
with other devices and time stamping of the process data.
Chapter 2 describes the configuration of the time
synchronization with IEC 60870-5-104 .
4.2 Time Synchronization with IEC 60870-5-104IEC 60870-5-104
offers an own time synchronization from the master to the
outstations.
During configuration of the SIPROTEC device in DIGSI 4, set the
time synchronization parameters for time syn-chronization via IEC
60870-5-104 in same manner as for NTP (see figure 2-20 ):
Source of time synchronization: Ethernet NTP
Further time synchronization parameters (see figure 4-1 )
Fig. 4-1 IEC 60870-5-104 Synchronization Parameters
The following IEC 60870-5-104-specific parameters are relevant
for time synchronization via :
Table 4-1 IEC 60870-5-104-specific Parameters
Parameter Description
Enable104TimeSynch Determines whether the IEC 60870-5-104
outstation expects and evaluates time synchronization from IEC
60870-5-104 master.
NOTEFor time synchronization with NTP or IEC 60870-5-104, at
least one NTP server must be configured in the IEC 61850 System
Configurator (see figure 2-22)C53000-L2040-C370-2, Edition
02.2013
-
4 Time Synchronization
4.2 Time Synchronization with IEC 60870-5-104
com_T104_profile_us.book Page 61 Tuesday, February 19, 2013 3:17
PM61SIPROTEC, Communication Module, Communication Profile
If IEC 60870-5-104 time synchronization is enabled, the
IEC60870-5-104 master shall perform time synchro-nization to the
outstation periodically every 55 s to 61 s, because the time
control algorithm in the SIPROTEC devices is based on a cyclical
synchronization within this time period.
The accuracy of the time synchronization via IEC60870-5-104
protocol is 10 ms when time telegrams are being received
continuously in the interval stated above.
If two masters are connected to the device, the connecting one
will be the time master.
The IEC 60870-5-104-specific parameter Enable T104 Time Synch
determines whether NTP or IEC60870-5-104 is used for time
synchronization:
IEC 60870-5-104 time objects contain the number of milliseconds
from the IEC60870-5-104 time epoch, which is defined as 1970-01-01
00:00:00.000 UTC. Before transmitting internally from the EN100+ to
the SIPROTEC device, the local time correction factor that is
configured for NTP time synchronization (and which contains the
time zone and daylight saving time factors, see figure 2-19) is
added;
Table 4-2 Time Synchronization Sources
Source Time Synchronization Selection in DIGSI 4
NTP Server isConfigured inStation Configurator
SettingEnable T104TimeSynch
Result
Ethernet NTP Yes = 0: NTP is used Device is synchronized from
NTP (no time requests with IIN1.4 to a IEC 60870-5-104 master and
time telegrams from IEC60870-5-104 master are rejected)
= 1: IEC60870-5-104 is used
Device is synchronized from IEC60870-5-104
Ethernet NTP No Not relevant No time synchronization(no time
requests with IIN1.4 to a IEC 60870-5-104 master and time telegrams
from IEC60870-5-104 master are rejected)
Other thanEthernet NTP(e.g. IRIG B, GPS)
Not relevant Device is synchronized from the selected source (no
time requests with IIN1.4 to a IEC 60870-5-104 master and time
telegrams from IEC60870-5-104 master are
rejected)C53000-L2040-C370-2, Edition 02.2013
-
4 Time Synchronization
4.2 Time Synchronization with IEC 60870-5-104
com_T104_profile_us.book Page 62 Tuesday, February 19, 2013 3:17
PM62 SIPROTEC, Communication Module, Communication Profile
C53000-L2040-C370-2, Edition 02.2013
-
com_T104_profile_us.book Page 63 Tuesday, February 19, 2013 3:17
PM5 IEC 60870-5-104 Diagnosis for EN100+
5.1 HTML Page 64
5.2 SNMP 68
5.3 IEC 60870-5-104 Error Indication 6963SIPROTEC, Communication
Module, Communication ProfileC53000-L2040-C370-2, Edition
02.2013
-
5 IEC 60870-5-104 Diagnosis for EN100+
5.1 HTML Page
com_T104_profile_us.book Page 64 Tuesday, February 19, 2013 3:17
PM64 SIPROTEC, Communication Module, Communication Profile
5.1 HTML PageEN100+ has a homepage which you can open by
entering the IP address of the device.
To open the HTML page, proceed as follows:
Enter the IP address of the device in the browser according to
the following rule:http://IP address/home
Example: http://192.168.0.186/home
The EN100+ homepage opens.
Fig. 5-1 EN100+ Homepage
In the navigation pane (menu on the left), click the entry
IEC60870-5-104.The IEC 60870-5-104 diagnosis page
opens.C53000-L2040-C370-2, Edition 02.2013
-
5 IEC 60870-5-104 Diagnosis for EN100+
5.1 HTML Page
com_T104_profile_us.book Page 65 Tuesday, February 19, 2013 3:17
PM65SIPROTEC, Communication Module, Communication Profile
Fig. 5-2 IEC 60870-5-104 Diagnosis HTML Page
This page offers statistic data that are useful for
communication diagnosis (e.g. telegram and error counters as well
as the IP of the connected IEC 60870-5-104 master). Additionally,
the main protocol-specific settings made during IEC 60870-5-104
configuration in the mapping file are shown and an overview is
given with which para-meters IEC 60870-5-104 is running on the
module.
The parameters displayed on the diagnosis page correspond to the
IEC 60870-5-104-specific parameters(see table 1-3) and the IEC
60870-5-104 networking parameters (see table 1-4).
Additional Remarks to Links
Clear statistics (link) Clicking this link resets all statistic
values (telegram and error counters) to zero.C53000-L2040-C370-2,
Edition 02.2013
-
5 IEC 60870-5-104 Diagnosis for EN100+
5.1 HTML Page
com_T104_profile_us.book Page 66 Tuesday, February 19, 2013 3:17
PM66 SIPROTEC, Communication Module, Communication Profile
Update statistics (link) The HTML page is not updated
automatically. Click this link to up-date the statistic values (all
values will then be read again from the EN100+ module)
Additional Remarks to Statistics and Parameters
Connected It is shown whether a IEC 60870-5-104 client is
connected to this IEC 60870-5-104 server - yes or no- and
additionally if time synchro-nization via IEC 60870-5-104 is
executed, the text Time synch. shows which client acts as time
master.
IEC 60870-5-104 Client IP address:Port
IP address and TCP port number of the client which is currently
con-nected to the server or was last connected to the server.
Enable IEC 60870-5-104 time synchronization
- no: Enable IEC 60870-5-104 time synchronization = no
- yes: Enable IEC 60870-5-104 time synchronization = yes and NTP
server is configured
- (yes): Enable IEC 60870-5-104 time synchronization = yes but
no NTP server is configuredC53000-L2040-C370-2, Edition 02.2013
-
5 IEC 60870-5-104 Diagnosis for EN100+
5.1 HTML Page
com_T104_profile_us.book Page 67 Tuesday, February 19, 2013 3:17
PM67SIPROTEC, Communication Module, Communication Profile
Fig. 5-3 EN100+ Module - Connection/Security Log
NOTEThe entry Connection / Security log in the navigation pane
(see figure 5-1) is also relevant for IEC 60870-5-104.
The following events are entered:
Establishing a new connection with a client (IEC 60870-5-104
master)
Closing a connection
Rejecting a connection (unknown IP address or server already
connected)C53000-L2040-C370-2, Edition 02.2013
-
5 IEC 60870-5-104 Diagnosis for EN100+
5.2 SNMP
com_T104_profile_us.book Page 68 Tuesday, February 19, 2013 3:17
PM68 SIPROTEC, Communication Module, Communication Profile
5.2 SNMPAll statistic data shown in the IEC 60870-5-104
diagnosis HTML page (see figure 5-2) are also available via SNMP. A
special MIB file with the name SipT104.mib exists for this purpose
and is delivered together with the other MIB files for the EN100+
module. The SipT104.mib is contained in the IEC61850 SNMP MIB
V1.XX.
MIB files package for SIPROTEC devices with EN100+ can be
downloaded from:
http://siemens.siprotec.de/download_neu/index_e.htm All
Documents for Communication IEC 61850 - General information and
descriptions Tools and MIB-FilesC53000-L2040-C370-2, Edition
02.2013
-
5 IEC 60870-5-104 Diagnosis for EN100+
5.3 IEC 60870-5-104 Error Indication
com_T104_profile_us.book Page 69 Tuesday, February 19, 2013 3:17
PM69SIPROTEC, Communication Module, Communication Profile
5.3 IEC 60870-5-104 Error Indication
Display in DIGSI 4
For the IEC 60870-5-104 error indication the SysIntErr (Error
System Interface) indication in the device is used. In the DIGSI
Configuration Matrix this indication is available in the Protocol
group.
Fig. 5-4 IEC 60870-5-104 Error Indication - Group Protocol in
DIGSI 4
The following table shows the values and causes of the IEC
60870-5-104 error indication:
Table 5-1 Indication SysIntErr in DIGSI 4
Indication After Startup/Restart
Change ON to OFF Change OFF to ON
SysIntErr ON Changes to OFF when a client is connected to the
IEC 60870-5-104 servers with its config-ured TCP port numbers.
Changes to ON when no clients are connected to the IEC
60870-5-104 servers more.C53000-L2040-C370-2, Edition 02.2013
-
5 IEC 60870-5-104 Diagnosis for EN100+
5.3 IEC 60870-5-104 Error Indication
com_T104_profile_us.book Page 70 Tuesday, February 19, 2013 3:17
PM70 SIPROTEC, Communication Module, Communication Profile
Display in DIGSI 4 for EN100+
Further general EN100+ indications show the startup state of the
EN100+ module as well as Ethernet link sta-tus information:
Fig. 5-5 IEC 60870-5-104 Error Indication - EN100+
Table 5-2 Indication SysIntErr from EN100+
Indication After Startup/Restart
Change ON to OFF Change OFF to ON
Failure Modul ON Module is ready to work, startup sequence via
DPR successfully processed
Device or module reset/restart
Fail Ch1 ON Ethernet link on Ch1/Ch2 is es-tablished
Ethernet link on Ch1/Ch2 is lost
Fail Ch2 ONC53000-L2040-C370-2, Edition 02.2013
-
com_T104_profile_us.book Page 71 Tuesday, February 19, 2013 3:17
PM6 Redundancy IEC 60870-5-104
6.1 General Introduction and Requirements 72
6.2 Configuration in DIGSI 7371SIPROTEC, Communication Module,
Communication ProfileC53000-L2040-C370-2, Edition 02.2013
-
6 Redundancy IEC 60870-5-104
6.1 General Introduction and Requirements
com_T104_profile_us.book Page 72 Tuesday, February 19, 2013 3:17
PM72 SIPROTEC, Communication Module, Communication Profile
6.1 General Introduction and Requirements
Redundant communication in a system using IEC 60870-5-104 can be
achieved by providing the possibility to establish more than one
logical connections between two stations.
The station that performs the connection establishment is in
either case referred to as the controlling station (station A) in
the subsequent description, while the partner station is referred
to as the controlled station (station B).
The following general rules apply to this clause concerning
redundant connections:
1) The controlling and controlled station shall be able to
handle multiple (N) logical connections.
2) The N logical connections represent one redundancy group.
3) Only one logical connection is in the started state and
sending/receiving user data at a time for one redun-dancy
group.
4) The controlling station decides which one of the N
connections is in started state.
5) All logical connections of a redundancy group shall be
supervised by test frames as described in 60870-5-104
Ed_2_57_812e_FDIS 5.2.
6) A redundancy group shall rely upon only one process image
(database/event buffer).C53000-L2040-C370-2, Edition 02.2013
-
6 Redundancy IEC 60870-5-104
6.2 Configuration in DIGSI
com_T104_profile_us.book Page 73 Tuesday, February 19, 2013 3:17
PM73SIPROTEC, Communication Module, Communication Profile
6.2 Configuration in DIGSI
During configuration of the SIPROTEC device in DIGSI 4, 3
parameters need setting in mapping file (see figure 6-1):
Fig. 6-1 IEC 60870-5-104 redundancy setting
The following IEC 60870-5-104-specific parameters are relevant
for redundancy via :
Table 6-1 IEC 60870-5-104-specific Parameters
Parameter Parameter
EnableRedundancy Determines whether the IEC 60870-5-104
outstation support the redundancy.
TcpPortNumber Determines the TCP ports to listen on
MasterIPAddress List of IP address to accept connections from
mastersC53000-L2040-C370-2, Edition 02.2013
-
6 Redundancy IEC 60870-5-104
6.2 Configuration in DIGSI
com_T104_profile_us.book Page 74 Tuesday, February 19, 2013 3:17
PM74 SIPROTEC, Communication Module, Communication Profile
Table 6-2 IEC 60870-5-104 redundancy description
Redundancy Disable/ Enable
IP address setting
Action
IEC 60870-5-104 redundancy Disable (Only port number 2404 is
available
Master1 IP address *.*.*.* (by default) Any IEC 60870-5-104
master can com-municate with the device. After the con-nection of
master1is interrupted, the master2 can communicate with the device
without device restarts.
Master2 IP address *.*.*.* (by default)
Master1 IP address *.*.*.* (by default) Only master2 can
communicate with the device
Master2 IP address 192.168.0.12 (e.g)
Master1 IP address 192.168.0.11(e.g) Only master1 can
communicate with the device
Master2 IP address *.*.*.* (by default)
Master1 IP address 192.168.0.11 (e.g) Both of them can
communicate with the device.But only one can communicate with the
device at one time. After the con-nection is interrupted, the
device does not need to restart.
Master2 IP address 192.168.0.12 (e.g)
IEC 60870-5-104 redundancy Enable (port number 2404 and 2405 are
all avail-able)
Master1 IP address *.*.*.*(by default) Any IEC 60870-5-104
master can com-municate with the device. If the first master
communicates with the device via port2404/2405, the next one can
only communicate via another port 2405/2404.
Master2 IP address *.*.*.*(by default)
Master1 IP address *.*.*.*(by default) The two scenarios are
forbidden to con-figure in DIGSI. If the customer makes a defect to
configure like this. The redun-dancy will be switched off. That
means no redundancy. Only the master with fixed ip address can
communicate via port 2404. Port 2405 is unavailable.
Master2 IP address 192.168.0.12 (e.g)
Master1 IP address 192.168.0.11 (e.g)
Master2 IP address *.*.*.* (by default)
Master1 IP address 192.168.0.11 (e.g) Only these two masters can
communi-cate with the device.If the first master communicates with
the device via port2404/2405, the next one can only communicate via
another port 2405/2404
Master2 IP address 192.168.0.12 (e.g)C53000-L2040-C370-2,
Edition 02.2013
-
com_T104_profile_us.book Page 75 Tuesday, February 19, 2013 3:17
PM7 Technical Data
7.1 Technical Data of EN100+ 7675SIPROTEC, Communication Module,
Communication ProfileC53000-L2040-C370-2, Edition 02.2013
-
7 Technical Data
7.1 Technical Data of EN100+
com_T104_profile_us.book Page 76 Tuesday, February 19, 2013 3:17
PM76 SIPROTEC, Communication Module, Communication Profile
7.1 Technical Data of EN100+The following manuals contain a
detailed list of the technical data of the EN100+:
German edition: Handbuch Ethernetmodul EN100+, Bestellnr.
C53000-G1100-C167-10
US-english edition: Manual Ethernet Module EN100+, order no.
C53000-G1140-C167-10
Since EN100+ modules are installed in SIPROTECT 4 devices, both
the technical data of the EN100+ and the technical data of the
SIPROTEC 4 device can apply.C53000-L2040-C370-2, Edition
02.2013
-
com_T104_profile_us.book Page 77 Tuesday, February 19, 2013 3:17
PMIndex
AApplication 11
BBuffered Events 19Bus Mapping Documents 11
CConfiguration in DIGSI 4 31Counter Value Scaling 57
EEthernet Services and Protocols 27
FFile Transfer 20File Transfer/Reading of Fault Records 20
HHTML Page 64
IIEC 60870-5-104 Diagnosis for EN100+ Module 63IEC 60870-5-104
with IEC 61850 and GOOSE 27Initializing the SIPROTEC 4 device
49
MMeasured Value Scaling 54Measured Value Threshold Processing
56
PParameterizing the device functions 48Parameters 17
RReading of Fault Records 20Redundant IEC 60870-5-104 71
SScaling for Transmission 53SNMP 68
Thresholds for Transmission 53Time Synchronization 59Time
Synchronization with IEC 60870-5-104 60
UUpdate the Parameter Sets of IEC 61850 4977SIPROTEC,
Communication Module, Communication ProfileC53000-L2040-C370-2,
Edition 02.2013
TTechnical Data of EN100+ 76
-
Index
com_T104_profile_us.book Page 78 Tuesday, February 19, 2013 3:17
PM78 SIPROTEC, Communication Module, Communication Profile
C53000-L2040-C370-2, Edition 02.2013
Preface1 Characteristic of the IEC 60870-5-104 Module1.1
General1.2 Identification of Module and Firmware1.3 Supported IEC
60870-5-104 Object Types1.4 Table of Parameters1.5 Buffered
Events1.6 File Transfer1.6.1 Reading of Fault Records1.6.2 Reading
of Parameter File
1.7 Further Ethernet Services and Protocols1.7.1 Services1.7.2
IEC 60870-5-104 with IEC 61850 and GOOSE
2 Configuration in DIGSI 42.1 Inserting and Adjusting of a New
Project2.2 Setting the Interfaces2.3 Customization of the
Allocations
3 Scaling and Thresholds for Transmission3.1 Measured Value
Scaling3.2 Measured Value Threshold Processing3.3 Counter Value
Scaling
4 Time Synchronization4.1 General4.2 Time Synchronization with
IEC 60870-5-104
5 IEC 60870-5-104 Diagnosis for EN100+5.1 HTML Page5.2 SNMP5.3
IEC 60870-5-104 Error Indication
6 Redundancy IEC 60870-5-1046.1 General Introduction and
Requirements6.2 Configuration in DIGSI
7 Technical Data7.1 Technical Data of EN100+
IndexABCEFHIMPRSTU