COLD WEATHER MASONRY CONSTRUCTION
68
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Cold Weather Requirements for Masonry Construction

COLD WEATHER MASONRY CONSTRUCTION

Page 2: Cold Weather Requirements for Masonry Construction

BAC CONTRACTORS

IMI-TRAINED CRAFTWORKERS

International Union of Bricklayers and Allied Craftworkers

International Masonry Institute

Page 3: Cold Weather Requirements for Masonry Construction

International Masonry Institute is a registered provider with the

American Institute of Architect’s continuing education systems. Credit

earned on completion of this program will be reported to CES records

for AIA members. Certificates of completion for non-AIA members

available on request.

This program is registered with the AIA/CES for continuing professional

education. As such, it does not include content that may be deemed or

construed to be an approval or endorsement by the AIA of any material

of construction or any method or manner of handling, using,

distributing, or dealing in any material or product. Questions related to

specific materials, methods, and services will be addressed at the

conclusion of this presentation.

AIA POLICY

Page 4: Cold Weather Requirements for Masonry Construction

this presentation is protected by U.S. and international

copyright laws

reproduction, distribution, display and use of the

presentation without written permission of the speaker is

prohibited

© International Masonry Institute 2015

COPYRIGHTED MATERIALS

Page 5: Cold Weather Requirements for Masonry Construction

1. understand - code requirements for cold weather masonry construction

IBC 2012/MSJC 2011 IBC 2015/MSJC 2013

2. learn - Industry Guidelines and Common Practice 3. apply - appropriate actions for successful results 4. learn – helpful tips to plan for winter construction

LEARNING OBJECTIVES

Page 6: Cold Weather Requirements for Masonry Construction

COLD WEATHER MASONRY

CONSTRUCTION

Page 7: Cold Weather Requirements for Masonry Construction

SPECIFICATION FOR MASONRY STRUCTURES

PART 1 - GENERAL

1.5 - Submittals

1.5 B. Submit the following:

3. Construction procedures

a. Cold weather construction procedures

Page 8: Cold Weather Requirements for Masonry Construction

IBC & MSJC

BUILDING CODES

2015 IBC goes with 2013 MSJC

MSJC date will be one or two years prior to companion IBC

IBC supersedes MSJC at points of conflict

IBC: the legally adopted model code

MSJC: the referenced standard

Page 9: Cold Weather Requirements for Masonry Construction

2015 INTERNATIONAL BUILDING CODE

SECTION 2101 GENERAL

2101.2.6 Masonry Veneer

CHAPTER 21 - MASONRY

Masonry veneer shall comply

with the provisions of Chapter 14

or Chapter 6 of TMS 402/ACI

530/ASCE 5.

SECTION 2104 CONSTRUCTION

2104.1 Masonry Construction

Masonry construction shall

comply with the requirements of

Sections 2104.1.1 through

2104.4 and with TMS 402/ACI

530/ASCE 5.

Page 10: Cold Weather Requirements for Masonry Construction

CODE COMPARISONS

IBC ‘03 & ‘06 MSJC ‘02, ‘05, ’08,

’11, ‘13

PART 1 - GENERAL 1.8 – Project Conditions

1.8 C. Cold weather construction

Chapter 21: MASONRY Section 2104.3

Cold weather construction

but not ’09, ’12, ‘15

Page 11: Cold Weather Requirements for Masonry Construction

Beginning in 2009, IBC does NOT

have hot/cold weather provisions.

All are moved to the 2008 MSJC

CODE COMPARISONS

Page 12: Cold Weather Requirements for Masonry Construction

IBC 2104.3 (’06)

Cold Weather Construction ◦ The cold weather

construction provisions of ACI 530.1, (etc.) Article 1.8C OR the following procedures shall. . .when EITHER the ambient temp, OR the temp of masonry units is below 40o F.(4o C)

◦ Visible ice and snow shall be removed…

MSJC 1.8C (’08, ’11, ‘13)

Cold Weather Construction ◦ 1. Implement the following

requirements when: The ambient temperature falls

below 40oF (4.4oC) Do not lay units having either

a temp of 20oF (-6.7oC) or visible frozen

moisture

WHEN MUST COLD WEATHER PROVISION BE IMPLEMENTED?

Page 13: Cold Weather Requirements for Masonry Construction

WHY 40º ?

The temperature at which hydration of cement slows and eventually stops

Supported by research and decades of empirical evidence

Hydration is the ability of the cement to take on water and complete its chemical reaction. No hydration = no strength development

The chemical process of hydration produces heat

Page 14: Cold Weather Requirements for Masonry Construction

PERFORMANCE TARGETS

Keep the mortar between 40oF and 120oF

Don’t lay frozen units or allow the masonry to freeze before initial set

Protect the masonry from freezing after construction

Result: the masonry will perform as expected

Page 15: Cold Weather Requirements for Masonry Construction

SPECIFICALLY…

1. General Provisions

Apply to all types, all temperatures

2. Construction Provisions

Options available for how to meet targets based on job site conditions

3. Protection Provisions

Care for the masonry during and after construction

Page 16: Cold Weather Requirements for Masonry Construction

TEMPERATURE

Ambient Temperature: Current outdoor temperature at the time considered

Mean Daily Temperature: Average of the projected maximum and minimum daily temperature, midnight to midnight

Anticipated Daily Minimums: Lowest temperature forecast for the upcoming 24 hrs.

Page 17: Cold Weather Requirements for Masonry Construction

TEMPERATURE

Ambient temperature

Construction

Mean Daily Temperature

Protection, ungrouted masonry

Anticipated Daily Minimum

Protection, grouted masonry

Page 18: Cold Weather Requirements for Masonry Construction

TEMPERATURE

Mean Daily Temperature

Average of the projected

maximum and minimum daily

temperature, midnight to midnight

54º + 36º / 2 = 45º

Ambient Temperature

Current outdoor

temperature at the time

considered.

Anticipated Daily

Minimum

Lowest temp

forecast for the

upcoming 24 hrs.

considered for construction

considered for protection, ungrouted masonry

considered for protection, grouted masonry

Page 19: Cold Weather Requirements for Masonry Construction

TEMPERATURE Anticipated Daily Minimum

Lowest temp forecast for the

upcoming 24 hours

considered for protection, grouted masonry

Page 20: Cold Weather Requirements for Masonry Construction

GENERAL PROVISIONS

Keep units and other materials dry

Do not lay frozen units (units < 20o) or those with visible ice or snow

Do not overheat water or aggregates

It is not necessary to heat grout materials unless their temps are below 32o

Page 21: Cold Weather Requirements for Masonry Construction

protected not protected

Keep units and other materials dry

Do not lay frozen units or those with visible ice or snow

Page 22: Cold Weather Requirements for Masonry Construction

40o – 32o F

CONSTRUCTION PROVISIONS

Do not lay glass units below 40o

Heat sand OR water to achieve mortar temps of 40o – 120o at time of mixing

Page 23: Cold Weather Requirements for Masonry Construction

32o to 25o F

CONSTRUCTION PROVISIONS

All of the above, plus:

Heat sand AND water to achieve mortar temps of 40o – 120o at time of mixing

Maintain materials above 32oF until used

Heat grout aggregate and water to keep grout above 70oF

Page 24: Cold Weather Requirements for Masonry Construction

25o to 20o F

CONSTRUCTION PROVISIONS

All of the above, plus:

Add windbreaks or enclosures when wind is above 15 mph

Make sure masonry is above 40o before grouting

Page 25: Cold Weather Requirements for Masonry Construction

CONSTRUCTION PROVISIONS

20o F and below

All of the above, plus:

Add auxiliary heat to enclosures

Keep enclosed area above 32o F

Page 26: Cold Weather Requirements for Masonry Construction

CONSTRUCTION PROVISIONS

Heating water is the most effective technique because of its ability to retain heat and impart heat to other ingredients

Page 27: Cold Weather Requirements for Masonry Construction

Heated water used to mix mortar in the enclosure

CONSTRUCTION PROVISIONS

Page 28: Cold Weather Requirements for Masonry Construction

CONSTRUCTION PROVISIONS

Silos partially enclosed, heat provided

in mixing area

Page 29: Cold Weather Requirements for Masonry Construction

Mortar must be at least 40o at time of mixing

CONSTRUCTION PROVISIONS

Page 30: Cold Weather Requirements for Masonry Construction

Metallic surface contact thermometer

CONSTRUCTION PROVISIONS

Page 31: Cold Weather Requirements for Masonry Construction

PROTECTION REQUIREMENTS

What’s good for the masonry is also good for the mason.

Page 32: Cold Weather Requirements for Masonry Construction

Productivity and safety are improved with enclosures

Page 33: Cold Weather Requirements for Masonry Construction

IBC2104.7 Masonry

Protection

◦ The top of unfinished

masonry work shall

be covered to protect

the masonry from the

weather.

MSJC 1.8B Masonry

Protection

◦ Cover top of

unfinished masonry

work to protect it from

the weather.

Note: These provisions apply

regardless of temperature.

PROTECTION REQUIREMENTS

Page 34: Cold Weather Requirements for Masonry Construction

Barely adequate

Very good Overkill

COVER UNFINISHED WORK

Page 35: Cold Weather Requirements for Masonry Construction

IBC 2006: 2104.3.3- 2104.3.3.3.5 ◦ 6. Where mean daily

temperatures are between [all ranges down past 20oF(-7oC)], completed masonry shall be completely covered with a weather-resistant membrane for 24 hours after construction.

MSJC 2011 1.8C ◦ 7. When mean daily

temperature is between [all ranges down past 20oF (-6.7o C)], completely cover completed masonry with a weather-resistive membrane for 24 hr after construction.

Note: These are reference locations for those using

the 2006 IBC/2005 MSJC and prior. These are found

only in the MSJC from the 2005 edition forward.

PROTECTION, UNGROUTED MASONRY

Page 36: Cold Weather Requirements for Masonry Construction

Temperature Ranges for Protection Based on

“Mean daily” temperatures for ungrouted

masonry (forecast 24-hour average)

“Anticipated daily minimum” temperatures for

grouted masonry (forecast anticipated minimum)

PROTECTION REQUIREMENTS

Page 37: Cold Weather Requirements for Masonry Construction

40o – 32o F

◦Maintain glass unit masonry above 40o

for 48 hours

◦ Protect newly-laid masonry with weather-

resistant membrane for 24 hours

PROTECTION REQUIREMENTS

Page 38: Cold Weather Requirements for Masonry Construction

32o – 25o F

◦Repeats requirement

from prior temp range

– cover for 24 hours

PROTECTION REQUIREMENTS

◦ (no additional

requirements)

Page 39: Cold Weather Requirements for Masonry Construction

25o – 20o F

The above, plus

◦ For ungrouted masonry, cover

completely with insulating blankets, or

equal, for 24 hours

◦ Increase to 48 hours for grouted

masonry unless Type III cement only is

used in grout. (New in 2003 IBC)

PROTECTION REQUIREMENTS

Page 40: Cold Weather Requirements for Masonry Construction

Insulating blankets cover top of wall

INSULATING BLANKETS

Page 41: Cold Weather Requirements for Masonry Construction

20o F and below

◦ The above, plus:

◦Maintain new masonry above 32o for 24

hours with heated enclosures, lamps, etc.

◦ Increase to 48 hours for grouted masonry

unless Type III cement only is used in

grout.

PROTECTION REQUIREMENTS

Page 42: Cold Weather Requirements for Masonry Construction

Heated enclosure

PROTECTION OF MATERIALS

Enclosure on site made from scaffold framing and heavy plastic sheeting

300,000 BTU heater

Thermostat set to 50oF over the weekend

6 pallets of block and drum of water

Page 43: Cold Weather Requirements for Masonry Construction

Heated enclosure

Moving material into enclosure

PROTECTION OF MATERIALS

Page 44: Cold Weather Requirements for Masonry Construction

PROTECTION OF MATERIALS

Ambient temperature in enclosure keeps masonry units warm

Page 45: Cold Weather Requirements for Masonry Construction

Inside of enclosure

PROTECTION OF MATERIALS

Page 46: Cold Weather Requirements for Masonry Construction

In cold weather, bricks

with IRA of 25-30 may be

desirable

5-25 g/min/30 in 2 Recommendation:

INITIAL RATE OF ABSORPTION

Page 47: Cold Weather Requirements for Masonry Construction

Using a high IRA brick

reduces the risk of

freezing by more rapidly

absorbing water from

the mortar or grout.

INITIAL RATE OF ABSORPTION

If a low IRA brick is

used, water content of

the mortar should be

the minimum necessary

for workability

Page 48: Cold Weather Requirements for Masonry Construction

© 2009 INTERNATIONAL MASONRY INSTITUTE

ELEVATIONS DIAGRAM 01.410.0311 REV. 08/10/09

MORTAR JOINT MATERIAL TAKEOFF

UTILITY BRICK, RUNNING BOND MODULAR BRICK, RUNNING BOND

4 @ 12” x 3/8” = 18.000 SQ. IN. BED JOINTS

HEAD JOINTS 8 @ 2.3125” x 3/8” = 6.938 SQ. IN.

2 @ 1.3125” x 3/8” = 0.984 SQ. IN.

25.922 SQ. IN. MORTAR

3 @ 12” x 3/8” = 13.500 SQ. IN.

3 @ 3.625” x 3/8” = 4.078 SQ. IN.

17.578 SQ. IN. MORTAR

18.00% MORTAR 12.21% MORTAR

ONE SQUARE FOOT ONE SQUARE FOOT

18% 12%

Page 49: Cold Weather Requirements for Masonry Construction

MORTAR

Cold weather retards the hydration of the cement in the mortar mix.

Mortar mixed in cold weather often has lower water content, increased air content, and reduced early strength.

Mortar with lower lime content will allow the water content to decrease more rapidly

Mortar with over 6% water content will experience disruptive expansive forces if frozen, due to the increase in volume of water when it converts to ice.

Page 50: Cold Weather Requirements for Masonry Construction

Avoid scorching the sand or overheating the water, which can lead to discolored mortar and flash setting.

Avoid wide variations in mortar temps, causing variations in tooling times and possible variations in mortar color.

MORTAR

Page 51: Cold Weather Requirements for Masonry Construction

Highly

magnified,

frozen mortar

has fissures

that can

reduce

compressive

strength and

inhibit bond

MORTAR

Page 52: Cold Weather Requirements for Masonry Construction

ADMIXTURES

Accelerators are admixtures used to speed the setting time of mortar and grout.

By increasing the rate of hydration, accelerators increase the rate of early strength gain.

Avoid calcium chloride: it causes corrosion to metal accessories and possibly efflorescence.

Safer: accelerators w/ inorganic nonchloride compounds like calcium nitrite and calcium nitrate.

Avoid antifreeze: it reduces compressive and bond strength of mortar.

Page 53: Cold Weather Requirements for Masonry Construction

EFFLORESCENCE

EFFLORESCENCE

Page 54: Cold Weather Requirements for Masonry Construction

MORTAR

Bond separation

Page 55: Cold Weather Requirements for Masonry Construction

Brick & mortar leak

Wall system must address moisture penetration

MOISTURE RESISTANCE

Page 56: Cold Weather Requirements for Masonry Construction

RECESSED COURSE

MOISTURE RESISTANCE

Page 57: Cold Weather Requirements for Masonry Construction

ARCHITECTURAL EFFECT DETAIL 01.601 REV. 08/31/07

BRIC

K &

BLO

CK C

AV

ITY W

ALL

MORTAR

WASH

DETAILING MASONRY

SERIES www.imiweb.org 800-IMI-0988

International Masonry Institute

Page 58: Cold Weather Requirements for Masonry Construction

RECESSED COURSE

MOISTURE RESISTANCE

Page 59: Cold Weather Requirements for Masonry Construction

FULL HEAD JOINTS

MOISTURE RESISTANCE

Page 60: Cold Weather Requirements for Masonry Construction
Page 61: Cold Weather Requirements for Masonry Construction

PRODUCTION

If contractor figured job with pipe scaffold, (e.g. loadbearing) add 5-7% more for cold weather construction

If contractor figured job w/ hydromobile scaffold, add 15-20% for cold weather construction

If normal conditions call for 4 laborers for every 8 bricklayers, cold weather conditions call for 5 laborers

Production slows down, e.g. cut rebar into shorter pieces to work around enclosure

Page 62: Cold Weather Requirements for Masonry Construction

FACTORS AFFECTING RESULTS

Page 63: Cold Weather Requirements for Masonry Construction

Code provisions

+ Planning

+ Skilled Execution

= Successful cold weather masonry construction

FOR GOOD RESULTS

Page 64: Cold Weather Requirements for Masonry Construction

For best masonry performance in cold weather

conditions:

◦ Mason contractors: Plan ahead and submit a

plan, if required

◦ Be flexible, the weather is unpredictable

◦ Remember that top performance is the goal

and the code allows for the application of

reason and common sense.

FOR GOOD RESULTS

Page 65: Cold Weather Requirements for Masonry Construction

General Preparation and Construction Requirements: Store units and other materials in dry conditions off the ground. Do not lay frozen

units (those with temperatures below 20o F) or those with visible ice or snow. Do not heat water or aggregates above 140o F. It’s not

necessary to heat grout materials unless their temperatures are below 32o F.

TEMPERATURE

RANGES

CONSTRUCTION REQUIREMENTS

Ambient Temperatures

(During Construction)

PROTECTION REQUIREMENTS

Mean daily temps for un-grouted masonry, and

anticipated daily minimums for grouted masonry for

period following construction

40o F to 32o F Do not lay glass units.

Heat sand or water to achieve mortar

temps of 40o F to 120o F, at time of mixing.

Maintain glass unit masonry above 40o F for

48-hours.

Protect newly laid masonry with weather-resistant

membrane for 24-hours.

32o F to 25o F

Maintain materials above 32o F until used.

Heat grout aggregate & water.

Keep grout above 70o F.

No additional requirements beyond those above.

25o F to 20o F

Add windbreaks or enclosures when wind

exceeds 15 mph.

Heat masonry to 40o F prior to grouting.

Cover new masonry completely with insulating

blankets, or equal, for 24-hours.

Increase to 48-hours for grouted masonry unless

Type III cement only is used.

20o F and Below

Add auxiliary heat to enclosures.

Keep area above 32o F.

Maintain new masonry temps above 32o F for 24-

hours with heated enclosures, lamps, etc.

MSJC-13 COLD WEATHER REQUIREMENTS

Page 66: Cold Weather Requirements for Masonry Construction

IMI Tech Briefs,

Document 2.5.6

(Included in your

handouts)

BIA Technical Note #1

(www.bia.org)

NCMA Tek Note 3-1C

www.ncma.org)

NCMA Tek Note 1-2B

Portland Cement

Association (PCA)

(www.cement.org)

ADDITIONAL RESOURCES

Page 67: Cold Weather Requirements for Masonry Construction

BAC CONTRACTORS

IMI-TRAINED CRAFTWORKERS

International Union of Bricklayers and Allied Craftworkers

International Masonry Institute

Page 68: Cold Weather Requirements for Masonry Construction

COLD WEATHER MASONRY CONSTRUCTION