Top Banner
ICYNENE ® AND ITS PRODUCTS ARE REGISTERED TRADEMARKS OF ICYNENE INC. CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION
26

CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION

Mar 23, 2022

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION

I C Y N E N E ® A N D I T S P R O D U C T S A R E R E G I S T E R E D T R A D E M A R K S O F I C Y N E N E I N C .

CODES EVOLUTION –

IMPACT ON SPRAY FOAM

INSULATION

Page 2: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION

THERMAL INSULATION AND MOISTURE CONTROL REQUIRMENTS

Page 3: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION

ICC Code Status

Page 4: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION

IECC Residential Code Status

Page 5: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION

IRC / IBC Climate Zones

Page 6: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION

Features of IECC 2009

• Airtightness targets introduced (7 ACH)

• Airtightness visual inspection option

• Insulation levels increased• Mechanical system trade-offs

not allowed• Insulation levels in Zones 7 &

8 contain proprietary insulation R-values (e.g. R-21 walls)

• Performance Path with Mandatory requirements

• HERS Equivalent = 85

Required R-Values

Zone Ceiling Walls Bsmt.

1 30 13 0

2 30 13 0

3 30 13 5/13

4 38 13 10/13

5 38 20 or 13+5 10/13

6 49 20 or 13+5 15/19

7 49 21 15/19

8 49 21 15/19

Page 7: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION

Effect of Moving IECC 2012

• Airtightness levels decreasing (3-5 ACH)

• Airtightness test being introduced (required on all houses)

• Insulation levels increasing• No proprietary insulation levels• Requirement for continuous

insulation in Colder Zones (Zones 6-8)

• Mechanical system trade-offs not allowed

• Performance Path with Mandatory requirements

• HERS Equivalent = 70

Required R-ValuesBuilding

Airtightness (ACH)Zone Ceiling Walls Bsmt.

1 30 13 0 5

2 30 13 0 5

3 38 20 or 13+5 5/13 3

4 49 20 or 13+5 10/13 3

5 49 20 or 13+5 15/19 3

6 49 20+5 or 13+10 15/19 3

7 49 20+5 or 13+10 15/19 3

8 49 20+5 or 13+10 15/19 3

Page 8: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION

Effect of Moving IECC 2015

• Airtightness levels unchanged (3-5 ACH)

• Airtightness testing required • Insulation levels unchanged• Performance path intact• Trade-offs allowed under Energy

Rating Compliance Alternative (Insulation = IECC 2009):

Climate Zone Energy Rating Index1/2 523 51

4 545 556 547/8 53

Required R-Values Building Airtightness

(ACH)

Zone Ceiling Walls Bsmt.

1 30 13 0 5

2 30 13 0 5

3 38 20 or 13+5 5/13 3

4 49 20 or 13+5 10/13 3

5 49 20 or 13+5 15/19 3

6 49 20+5 or 13+10 15/19 3

7 49 20+5 or 13+10 15/19 3

8 49 20+5 or 13+10 15/19 3

Page 9: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION

Commercial Code Status

Page 10: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION

COMMERCIAL 2012 IECC Requirements

• Continuous Insulation Layer

• Continuous Air Barrier (Zones 4-8)

• Air Barrier Materials deemed to comply includes Open Cell & Closed Cell Spray Foam

Required R-Values

Zone Attic Wood Framed WallsWood Framed

Walls – Group RMetal Framed

Walls

1 30 20 or 13+3.8 c.i. 20 or 13+3.8 c.i. 13+5 c.i

2 30 20 or 13+3.8 c.i. 20 or 13+3.8 c.i. 13+ 5 c.i

3 38 20 or 13+3.8 c.i. 20 or 13+3.8 c.i. 13+7.5 c.i

4 38 20 or 13+3.8 c.i. 20 or 13+3.8 c.i. 13+7.5 c.i

5 49 20 or 13+3.8 c.i.20+3.8 c.i or 13+7.5 c.i. 13+7.5 c.i

6 4920+3.8 c.i or 13+7.5 c.i.

20+3.8 c.i or 13+7.5 c.i. 13+7.5 c.i

7 4920+3.8 c.i or 13+7.5 c.i.

20+3.8 c.i or 13+7.5 c.i. 13+7.5 c.i

8 4920+10 c.i or 13+15.6 c.i.

20+10 c.i or 13+ 15.6 c.i. 13+7.5 c.i

Page 11: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION

COMMERCIAL 2015 IECC Requirements

• Insulation Levels Unchanged

• Continuous Air Barrier (Zones 1,2A,3-8)

• Air Barrier Materials deemed to comply includes Open Cell & Closed Cell Spray Foam

Required R-Values

Zone Attic Wood Framed WallsWood Framed

Walls – Group RMetal Framed

Walls

1 30 20 or 13+3.8 c.i. 20 or 13+3.8 c.i. 13+5 c.i

2 30 20 or 13+3.8 c.i. 20 or 13+3.8 c.i. 13+ 5 c.i

3 38 20 or 13+3.8 c.i. 20 or 13+3.8 c.i. 13+7.5 c.i

4 38 20 or 13+3.8 c.i. 20 or 13+3.8 c.i. 13+7.5 c.i

5 49 20 or 13+3.8 c.i.20+3.8 c.i or 13+7.5 c.i. 13+7.5 c.i

6 4920+3.8 c.i or 13+7.5 c.i.

20+3.8 c.i or 13+7.5 c.i. 13+7.5 c.i

7 4920+3.8 c.i or 13+7.5 c.i.

20+3.8 c.i or 13+7.5 c.i. 13+7.5 c.i

8 4920+10 c.i or 13+15.6 c.i.

20+10 c.i or 13+ 15.6 c.i. 13+7.5 c.i

Page 12: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION

COMMERCIAL 2015 IECC Requirements

Air Barrier Material Options include most board stock materials along with a variety of proprietary membranes, parging, spray foam, sheet steel or aluminum and other materials that have an air permeability of 0.004 cfm/ft2 (0.02 L/s) @ 75 pa. when tested to ASTM E2178. (IECC Sentence C402.5.1.2.1)

Assemblies must also test with an air leakage not greater than 0.04 cfm/ft2 (0.2 L/s) @ 75 pa. when tested to ASTM E2357, ASTM E1677, or ASTM E 283. (IECC Sentence C402.5.1.2.2)

Joints must be sealed with materials meeting IECC Sentence C402.5.1.2.2.

Page 13: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION

COMMERCIAL 2012 IBC Requirements

Section 1403.2 calls for a Water Resistive Barrier. Some building science experts refer to also refer to this as a “drainage plane” or “Weather Barrier”

Concept is relatively simple—provide a barrier system designed to prevent the ingress of wind-driven rain. In practice this requires a variety of materials, systematically lapped in a shingle fashion to keep inner walls dry and allow outer walls to drain.

Page 14: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION

VAPOR CONTROL REQUIREMENTSInternational Residential Code 2012 and 2015

Section 702.7 Vapor RetardersClass I or II vapor retarders are required on the interior side of frame walls in Zones 5,6,7,8 and Marine 4. (so not needed in Zones 1,2,3,4)Exceptions

Basement wallsBelow grade portion of any wallConstruction where moisture or its freezing will not damage the materials

Section 702.7.1 Class III Vapor RetardersClass III Vapor Retarders shall be permitted where any one of the conditions in Table R702.7.1 is met.

Page 15: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION

EXCEPTIONS TO THE VDR REQUIREMENTS

Page 16: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION

2015 VDR REQUIREMENTS

Page 17: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION
Page 18: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION

ICC-ES EVALUATION SERVICE AND TECHNICAL EVALUATION REPORTS

Page 19: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION
Page 20: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION
Page 21: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION
Page 22: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION
Page 23: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION
Page 24: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION
Page 25: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION
Page 26: CODES EVOLUTION – IMPACT ON SPRAY FOAM INSULATION

Jay Strother, Partner, Seacoast Building Solutions LLC203-339-2252

[email protected]

John Broniek, Engineering Manager, Icynene412-310-5625 (Direct Line)

800-758-7325 (Head Office Toll Free)[email protected]