CODE INFORMATION APPLICABLE CODES, LAWS AND REGULATIONS 2015 INTERNATIONAL RESIDENTIAL CODE (IRC) 2015 INTERNATIONAL BUILDING CODE (IBC) 2015 INTERNATIONAL FIRE CODE (IFC) 2014 NATIONAL ELECTRICAL CODE (NEC) SHEET SATELLITE IMAGE JOB NOTES COVER SHEET PVA-0 DRAWN BY DATE DRAWN DATE CHECKED SCALE CHECKED BY 06-03-2020 EVALDEZ 06-03-2020 PROJECT LOCATION NTS 1 4 1 4 H A R B O U R W A Y S O U T H R I C H M O N D , C A 9 4 8 0 4 ( 5 1 0 ) 5 4 0 - 0 5 5 0 C O R P O R A T I O N , S Y S T E M S R E V I S I O N S SOLAR INDIVIDUAL PERMIT PACKAGE GRID-TIED PHOTOVOLTAIC SYSTEM REV DESCRIPTION DATE DB CB PROJECT OPPORTUNITY JEFF OLANDER / THERESA OLANDER 4160 STAGE STOP WAY LOT 620 WICKENBURG, ARIZONA 85390 RP-113183 8.63 kW SPRI - PHOENIX 7.88 kW MAX. OUTPUT POWER RATING TYLER BOSHARD C A L I C E N S E # 8 9 0 8 9 5 GRID-TIED PHOTOVOLTAIC SYSTEM SOLAR INDIVIDUAL PERMIT PACKAGE JEFF OLANDER / THERESA OLANDER 4160 STAGE STOP WAY LOT 620 4022187889 WICKENBURG, ARIZONA 85390 8.63 kW AHJ: TOWN OF WICKENBURG UTILITY: ARIZONA PUBLIC SERVICE CO AC MAX. CONTINUOUS POWER RATING OF (25) SPR-X21-345-E-AC = 25 x 315W = 7.88 kW PV SOLAR ARCHITECTURAL DRAWINGS SHEET INDEX PV SOLAR ELECTRICAL DRAWINGS PVE-1 ELECTRICAL THREE-LINE DIAGRAM & PVE-2 ELECTRICAL CALCULATION PVE-3 ELECTRICAL DATA & SPECIFICATIONS SPECIFICATIONS PVE-4 PVE-5 BRANCH DIAGRAM PV SOLAR STRUCTURAL DRAWINGS PVS-1 MOUNTING DETAILS PVA-0 COVER SHEET PVA-1 ARRAY LAYOUT PLACARD / EQUINOX GROUNDING DETAILS
22
Embed
CODE INFORMATION SOLAR INDIVIDUAL PERMIT …...2020/05/10 · UTILITY: ARIZONA PUBLIC SERVICE CO AC MAX. CONTINUOUS POWER RATING OF (25) SPR-X21-345-E-AC = 25 x 315W = 7.88 kW PV
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
CODE INFORMATION
APPLICABLE CODES, LAWS AND REGULATIONS
2015 INTERNATIONAL RESIDENTIAL CODE (IRC)2015 INTERNATIONAL BUILDING CODE (IBC)2015 INTERNATIONAL FIRE CODE (IFC)2014 NATIONAL ELECTRICAL CODE (NEC)
SHEET
SATELLITE IMAGE
JOB NOTES
CO
VER
SH
EET
PVA-0
DRAWN BY
DATE DRAWN
DATE CHECKED
SCALE
CHECKED BY
06-03-2020
EVALDEZ
06-03-2020
PROJECT LOCATION
NTS
1 4
1 4
H
A R
B O
U R
W
A Y
S O
U T
H
R I
C H
M O
N D
,
C A
9 4
8 0
4
( 5
1 0
) 5
4 0
- 0
5 5
0
C O
R P
O R
A T
I O
N ,
S Y
S T
E M
S
R E V I S I O N S
SO
LAR I
ND
IVID
UAL
PERM
IT P
ACKAG
E
GRID
-TIE
D P
HO
TOVO
LTAIC
SYS
TEM
REV DESCRIPTION DATE DB CB
PROJECT
OPPORTUNITY
JEFF
OLA
ND
ER /
TH
ERES
A O
LAN
DER
4160
STA
GE
STO
P W
AY
LOT
620
WIC
KEN
BU
RG
, ARIZ
ON
A 8
5390
RP-113183
8.63
kW
SPRI - PHOENIX
7.88
kW
MAX.
OU
TPU
T PO
WER
RATI
NG
TYLER BOSHARD
C A
L
I C
E N
S E
#
8 9
0 8
9 5
GRID-TIED PHOTOVOLTAIC SYSTEM
SOLAR INDIVIDUAL PERMIT PACKAGE
JEFF OLANDER / THERESA OLANDER
4160 STAGE STOP WAY LOT 6204022187889
WICKENBURG, ARIZONA 85390
8.63 kW
AHJ: TOWN OF WICKENBURGUTILITY: ARIZONA PUBLIC SERVICE CO
AC MAX. CONTINUOUS POWER RATING OF (25) SPR-X21-345-E-AC = 25 x 315W = 7.88 kW
PV SOLAR ARCHITECTURAL DRAWINGS
SHEET INDEX
PV SOLAR ELECTRICAL DRAWINGS
PVE-1 ELECTRICAL THREE-LINE DIAGRAM &
PVE-2 ELECTRICAL CALCULATIONPVE-3 ELECTRICAL DATA & SPECIFICATIONS
SPECIFICATIONS
PVE-4PVE-5 BRANCH DIAGRAM
PV SOLAR STRUCTURAL DRAWINGS
PVS-1 MOUNTING DETAILS
PVA-0 COVER SHEET
PVA-1 ARRAY LAYOUT
PLACARD / EQUINOX GROUNDING DETAILS
87'-7
"
67'-7"
ROOF ONE: 21 MODULES
5.5:12ROOF TWO: 4 MODULES
3:12
TO E
LECT
RIC
UTIL
ITY
GRID
ACD
PVM
N-LC
(E) GARAGE
ROOF ACCESSPOINT
(E) FENCE/GATE
(E) FENCE/GATE
SHEET
ARRAY
LAYO
UT
PVA-1
DRAWN BY
DATE DRAWN
DATE CHECKED
SCALE
CHECKED BY
06-03-2020
EVALDEZ
06-03-2020
ROOF TYPE
CONTRACT MODULE
MICROINVERTER
STORY
SYSTEM
ROOF PITCH
& QUANTITY
TYPE & QUANTITY
HOME TYPE
ORIENTATION
TOTALARRAY AREA
ROOF ATTACHMENTQUANTITY
SQ.FT.
FLAT TILE
5.5:12 & 3:12
1 - STORY
222°
SPR-X21-345-E-AC (240) (25)
IQ7XS-96-ACM-US (240)(25)
52
447
1/16" = 1'-0"
L E G E N D
JUNCTION BOX
EXISTING SERVICE POINTAND UTILITY METERING
PROPERTY LINE
3' WIDE ACCESS PATH
CONDUIT
ACD PV UTILITY DISCONNECT
N-LC NEW LOAD CENTER
PV METERPVM
1 4
1 4
H
A R
B O
U R
W
A Y
S O
U T
H
R I
C H
M O
N D
,
C A
9 4
8 0
4
( 5
1 0
) 5
4 0
- 0
5 5
0
C O
R P
O R
A T
I O
N ,
S Y
S T
E M
S
R E V I S I O N S
SO
LAR I
ND
IVID
UAL
PERM
IT P
ACKAG
E
GRID
-TIE
D P
HO
TOVO
LTAIC
SYS
TEM
REV DESCRIPTION DATE DB CB
PROJECT
OPPORTUNITY
JEFF
OLA
ND
ER /
TH
ERES
A O
LAN
DER
4160
STA
GE
STO
P W
AY
LOT
620
WIC
KEN
BU
RG
, ARIZ
ON
A 8
5390
RP-113183
8.63
kW
SPRI - PHOENIX
7.88
kW
MAX.
OU
TPU
T PO
WER
RATI
NG
TYLER BOSHARD
C A
L
I C
E N
S E
#
8 9
0 8
9 5
ROOF VENT
1.5' WIDE ACCESS PATH
NOTE: UTILITY HAS 24-HR UNRESTRICTEDACCESS TO ALL PHOTOVOLTAIC SYSTEMCOMPONENTS LOCATED AT SERVICEENTRANCE.
NOTE: REFERENCE SECTION 301.15 OF THEAPS ESRM FOR ELECTRIC METERSEPARATION BETWEEN WATER AND GAS.
NOTE: WORKSPACE IN FRONT OF ACELECTICAL SYSTEM COMPONENTS SHALLBE IN ACCORDANCE WITH APS AND NECREQUIREMENS. FOR APSREQUIREMENTS, REFERENCE SECTION300 OF THE APS ESRM AND SECTION 8.2OF THE APS INTERCONNECTIONREQUIREMENTS.
NOTE: NO FENCES OR GATES RESTRICTING ACCESS TO UTILITY METER AND APS EQUIPMENT.
NOTE:1. FIELD ADJUSTMENTS OF FEWER
THAN 6” MAY BE ALLOWED BASED ON SITECONDITIONS AND MEASUREMENTS.
N
FIGURE 3: MOUNTING CLAMPPOSITIONING DETAILSTABLE 2: PENETRATION GUIDE FOR INSTALL
STACKED STAGGERED FULLY STAGGERED
STACKED/STAGGEREDFULLY STAGGERED
*CHECK TABLE 1 FOR MAX.. PENETRATION SPACING AND PENETRATION PATTERN FOR EACH ARRAY.
TWO OR MORE ROWS OF MODULES
ONE ROW OF MODULES
96 CELL MODULE
·RAILS SHALL BE POSITIONED IN THE NON-CROSSHATCHED REGIONS
FIGURE 2: INVISIMOUNT WITH PEGASUS SOLAR ROOF ATTACHMENT DETAILS @ TRUSS / RAFTERS
DU222RB OR EQUIVALENTUTILITY-LOCKABLE SAFETY SWITCH 60A, 240VAC
EGC: BARE Cu #6
BRANCH CIRCUITFROM PV ARRAY TO
JUNCTION BOX
SUNPOWER PROVIDED AC MODULES EXTENSIONCABLE, LISTED AS AN ASSEMBLY #12 2
A --
1EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THENEC AND ALL APPLICABLE REQUIREMENTS OF THE SERVINGELECTRIC UTILITY COMPANY AND OF THE LOCAL AUTHORITYHAVING JURISDICTION.
2BI-DIRECTIONAL UTILITY METER TO BE INSTALLED BY UTILITYCOMPANY.
3LABEL "PHOTOVOLTAIC SYSTEM UTILITY DISCONNECT SWITCH".SWITCH COVER TO BE LOCKED AT ALL TIMES. SWITCH TO BEVISUAL OPEN AND ACCESSIBLE PER UTILITY REQUIREMENTS ANDCONFORM TO NEC 705.22
4LABEL "PHOTOVOLTAIC ARRAY DC DISCONNECT SWITCH: PERNEC 690.14(C)(2). LABEL WITH OPERATING CURRENT,OPERATING VOLTAGE MAXIMUM SYSTEM VOLTAGE, AND SHORTCIRCUIT CURRENT PER NEC 690.53 SWITCH TO BE LOCKED PERNEC 690.70(D)
5LABEL" PHOTOVOLTAIC POWER SYSTEM DEDICATED KWHMETER".METER ENCLOSURE AND SOCKET PROVIDED ANDINSTALLED BY CUSTOMER PER APS ESRM.METER PROVIDED BYCUSTOMER.
6PROVIDE WARNING SIGN PER NED 690.17 READING"WARNING-ELECTRIC SHOCK HAZARD-DO NOT TOUCHTERMINALS-TERMINALS ON BOTH LINE AND LOAD SIDES MAY BEENERGIZED IN THE OFF POSITION.
7METALLIC CONDUIT SHALL BE USED WITHIN BUILDING PER NEC690.31(E)
8LABEL "DEDICATED PHOTOVOLTAIC SYSTEM COMBINER PANEL"AND " LOADS NOT TO BE ADDED TO THIS PANEL.
9GEC TO BE INSTALLED AS REQUIRED BY MANUFACTURERINSTRUCTIONS AND NED 690.47.
10GROUNDING BUSHINGS AT EVERY ENTRY AND EXIT POINT TOENCLOSURES WITH RMC
11A PLACARD OR DIRECTORY IS INSTALLED AT THE SERVICEENTRANCE WITH EXPLICIT DIRECTIONS TO THE LOCATION OFTHE PHOTOVOLTAIC SYSTEM UTILITY DISCONNECT SWITCH ASREQUIRED BY APS.
12A PERMANENT PLACARD OR DIRECTORY IS INSTALLED PER NEC705.10
13SUPPLY SIDE CONNECTION IS INSTALLED PER NEC 230 APS,ESRM AND APS INTERCONNECTION REQUIREMENTS, LABELPHOTOVOLTAIC SYSTEM SERVICE DISCONNECT SWITCH, SWITCHCOVER TO BE LOCKED AT ALL TIMES.
14SUPPLY SIDE CONNECTIONS IS INSTALLED IN ACCORDANCEWITH MANUFACTURERS INSTRUCTIONS. DOCUMENTATION ISINCLUDED WITH THE APS INTERCONNECTION APPLICATION.ENSURE UL LISTED CONNECTORS.
15LABEL WARNING - A GENERATION SOURCE IS CONNECTED TOTHE SUPPLY (UTILITY) SIDE OF THE SERVICE OF THE SERVICEDISCONNECTING MEANS. FOLLOW PROPER LOCKOUT/ TAGOUTPROCEDURES TO ENSURE THE PHOTOVOLTAIC SYSTEM UTILITYDISCONNECT SWITCH IS OPENED PRIOR TO PERFORMING WORKON THIS DEVICE.
16EQUIPMENT SHALL BE LISTED, TESTEDAND MARKED TOWITHSTAND THE AVAILABLE SHORT CIRCUITCURRENT
AC MODULES NOTES:1. DC CIRCUIT IS ISOLATED AND INSULATED FROM GROUND AND MEETS THE REQUIREMENT OF NEC 690.35.2. SUNPOWER PROVIDED CABLES COMES WITH TWO (2) #12 AWG WIRE AND THIS IS BY DESIGN. NEUTRAL AND
ADDITIONAL GROUND WIRE IS NOT REQUIRED FOR PROVIDED TRUNK AND EXTENSION CABLES.3. SUNPOWER AC MODULES HAVE BEEN TESTED AND CERTIFIED TO UL 2703 FOR INTEGRATED GROUNDING AND
HENCE A SEPARATE GROUND WIRE IS NOT REQUIRED WITHIN THE ARRAY.4. USE ROW-TO-ROW GROUNDING CLIP PROVIDED TO GROUND ROWS OF MODULE. BOND SUB-ARRAYS BY
RUNNING #6 AWG BARE CU WIRE AND GROUND LUGS AT A SINGLE POINT ON EACH SUB-ARRAY AND THEN TOTHE JUNCTION BOX. REFER TO PVE-4 FOR ADDITIONAL DETAILS.
NOTE:BELOW ARE OPTIONAL OFFERINGS AND SHALLONLY BE INSTALLED IF THE HOMEOWNER SIGNSA SPECIFIC CONTRACT WITH SUNPOWER:· SUNPOWER MONITORING SYSTEM
ELECTRICAL NOTES:1. PROPER LISTING EXPECTED FOR CONDITIONS OF USE ON ALL LUGS, FITTINGS, CRIMPS, ETC.2. ALL CONDUIT BEND RADII TO CONFORM TO THE NEC MINIMUM BEND RADII REQUIREMENTS.3. MINIMUM CLEARANCE SHALL BE MAINTAINED PER NEC FOR ALL NEW EQUIPMENT TO BE INSTALLED.4. EXISTING GROUNDING ELECTRODE SYSTEM MUST MEET NEC AND LOCAL UTILITY REQUIREMENTS.5. COPPER CONDUCTORS SHALL BE USED UNLESS SPECIFIED.6. TYPE NM (ROMEX) CONDUCTORS ARE ALLOWED FOR INTERNAL AND ATTIC RUNS AND SHALL BE INSTALLED MEETING NEC
REQUIREMENTS.7. IF MAIN SERVICE PANEL IS TO BE UPGRADED, IT WILL BE PERMITTED AND INSTALLED BY 3RD PARTY.8. AC WIRING SHALL UPSIZE IF VOLTAGE DROP EXCEEDS 2%.9. RUN CONDUCTORS IN EXISTING CONDUIT WHEN AVAILABLE PROVIDED IT HAS NO OTHER CONDUCTORS RUNNING THROUGH IT.10. EQUIVALENT SPECIFICATION ON CABLES AND ELECTRICAL EQUIPMENT SPECIFIED ARE ACCEPTABLE.11. AS DC POWER IS INTERNAL TO THE MODULE, GROUNDING ELECTRODE CONDUCTOR (GEC) FOR THE MODULE OR ARRAY IS NOT
REQUIRED.
CHECK BOX FOR WHETHER SYSTEM IS GROUNDED ORUNGROUNDED:
GROUNDED (INCLUDE GEC)UNGROUNDED
FOR UNGROUNDED SYSTEMS:· DC OCPD DISCONNECT BOTH CONDUCTORS OF EACH
SOURCE CIRCUIT.· UNGROUNDED CONDUCTORS MUST BE IDENTIFIED PER
210.5(C). WHITE FINISHED CONDUCTORS ARE NOTPERMITTED.
TAG
1
2
3
4
5
6
7
8
9
DC / DC CONVERTERS
SOURCE CIRCUIT JUNCTION BOX
SEPARATE DC DISCONNECT
INTERNAL INVERTER DC DISCONNECT
STRING INVERTER
SOLAR LOAD CENTER
PV PRODUCTION METER
SEPARATE AC DISCONNECT
DESCRIPTION
NO
NO
YES
1
SOLAR AC MODULE / BRANCH ACM
NO
NO 1
A
DC
AC
DC
AC
DC
AC
1SUNPOWER MODULES
AC MODULEEXTENSION CABLE
AC MODULEEXTENSION CABLE
AC MODULEEXTENSION CABLE
8 AC MODULESBRANCH CIRCUIT #3
8 AC MODULESBRANCH CIRCUIT #2
9 AC MODULESBRANCH CIRCUIT #1
SPR-X21-345-E-AC (240)
GROUNDING ELECTRODEGROUND ROD
H
INCOMING SOURCE FEED
, 120/240V, 1PH, 3W
TOP FED
MCB
*MSP MAX PV BREAKER (A) = x 120% -
=
LOCATION:
MANUF: (E) UTILITYBIDIRECTIONAL
METER #:
(E) MAIN SERVICE PANEL
TO HOUSELOADS
L1L2N
GN
D
PV BREAKER: TO BEINSTALLED ON THE OPPOSITE SIDE
OF THE MAIN OCPD OF THE BUSS
225A 200A70A
225A
200A, 2P
LEFT SIDE OF HOME
SQUARE D
GA5774
50A, 2P
B
THWN-2
EGC: THWN-2
6
1
JUNCTION BOX,NEMA-3R,
3
B 3/4"EMT#10
#10
CONDUCTOR / CONDUIT SCHEDULE
DESCRIPTION &CONDUCTOR TYPE
CONDUCTOR SIZE(AWG) CONDUIT/CABLE TYPETAG CONDUIT SIZENUMBER OF
· SHALL BE LOCATED ON OR NO MORE THAN 1 M (3 FT)FROM THE SERVICE DISCONNECTING MEANS TO WHICHTHE PV SYSTEMS ARE CONNECTED.
32.75 A
240 V
1. MATERIAL USED FOR THE SIGNAGE SHALL BE REFLECTIVE,WEATHER RESISTANT AND SUITABLE FOR THEENVIRONMENT.
2. ALL SIGNAGE SHALL HAVE ALL CAPITAL LETTERS WITHMINIMUM 38" LETTER HEIGHT.
3. MAIN SERVICE DISCONNECT MARKING SHALL BE PLACEDADJACENT TO MAIN SERVICE DISCONNECT IN A LOCATIONCLEARLY VISIBLE FROM THE LOCATION WHERE THE LEVER ISOPERATED.
4. MARKING IS REQUIRED ON ALL INTERIOR AND EXTERIOR DCCONDUIT, RACEWAYS, ENCLOSURES, CABLE ASSEMBLIES,AND JUNCTION BOXES TO ALERT THE FIRE SERVICE TOAVOID CUTTING THEM. MARKINGS SHALL BE PLACED EVERY10', AT TURNS AND ABOVE AND/OR BELOW PENETRATIONS,AND AT ALL DC COMBINER AND JUNCTION BOXES.
5. DO NOT USE SCREWS FOR SIGNAGE ATTACHMENT. USEONLY APPROVED ADHESIVE.
SIGNAGE NOTES
ELECTRICAL DATA & SPECIFICATIONS
PHOTOVOLTAIC SYSTEM EQUIPPEDWITH RAPID SHUTDOWN
AMPS
VOLTS
PHOTOVOLTAIC POINT OFINTERCONNECTION
WARNING: DUAL POWER SOURCE.SECOND SOURCE IS PHOTOVOLTAIC
SYSTEM
SIGNAGE LOCATIONS:
· MAIN SERVICE PANEL· INDOOR / OUTDOOR SUBPANEL
MAXIMUM RATED AC OUTPUT CURRENT:
MAXIMUM OPERATING AC VOLTAGE:
SIGNAGE LOCATIONS:
· MAIN SERVICE PANEL
PV SOLAR BREAKERDO NOT RELOCATE THISOVERCURRENT DEVICE
SIGNAGE LOCATIONS:
· MAIN SERVICE PANEL· NEW INDOOR / OUTDOOR LOAD CENTER· INDOOR / OUTDOOR SUBPANEL
32.75 A
240 V
SHEET
ELEC
TRIC
AL
DATA
& S
PECIF
ICATI
ON
S
PVE-3
DRAWN BY
DATE DRAWN
DATE CHECKED
SCALE
CHECKED BY
06-03-2020
EVALDEZ
06-03-2020
NTS
1 4
1 4
H
A R
B O
U R
W
A Y
S O
U T
H
R I
C H
M O
N D
,
C A
9 4
8 0
4
( 5
1 0
) 5
4 0
- 0
5 5
0
C O
R P
O R
A T
I O
N ,
S Y
S T
E M
S
R E V I S I O N S
SO
LAR I
ND
IVID
UAL
PERM
IT P
ACKAG
E
GRID
-TIE
D P
HO
TOVO
LTAIC
SYS
TEM
REV DESCRIPTION DATE DB CB
PROJECT
OPPORTUNITY
JEFF
OLA
ND
ER /
TH
ERES
A O
LAN
DER
4160
STA
GE
STO
P W
AY
LOT
620
WIC
KEN
BU
RG
, ARIZ
ON
A 8
5390
RP-113183
8.63
kW
SPRI - PHOENIX
7.88
kW
MAX.
OU
TPU
T PO
WER
RATI
NG
TYLER BOSHARD
C A
L
I C
E N
S E
#
8 9
0 8
9 5
ACD
PVM
N-LC
FIGURE 1: SUNPOWER EQUINOX GROUNDING DETAILS
FILE: RP-113183-IP-PLSOLAR-PVE-4.dwg, USER: erwvaldez, DATE/TIME: Jun 05, 2020 - 9:48am
SHEET
PVE-4
DRAWN BY
DATE DRAWN
DATE CHECKED
SCALE
CHECKED BY
06-03-2020
EVALDEZ
06-03-2020
NTS
POWER TO THIS BUILDING IS ALSOSUPPLIED FROM THE FOLLOWINGSOURCES WITH DISCONNECT(S)
LOCATED AS SHOWN:
CAUTION:
ACDISCONNECT
PHOTOVOLTAICARRAY ON ROOF
SERVICE POINT &UTILITY METERING
SOLAR LOADCENTER
PV METER
FIGURE 2: PLACARD IDENTIFYING LOCATION OF DISCONNECTS AND POWER SOURCES