Code Compliance Research Report CCRR-0145 Issue Date: 11-15-2016 Renewal Date: 11-18-2017 130 Derry Court • York, PA 17406 www.intertek.com/building/ PCA-125 DIVISION: 05 - Metals Section: 05 50 00 – Metal Fabrications MARSHALL STAMPING COMPANY 355 Glade Mills Road Valencia, Pennsylvania 16059 www.marshallstamping.com REPORT SUBJECT: Marshall Extend-O-Column Marshall Fixed Length Column 1.0 SCOPE OF EVALUATION 1.1. This research report addresses compliance with the following Codes: 2015 International Building Code® (IBC) 2015 International Residential Code® (IRC) 1.2. Marshall Extend-O-Column and Marshall Fixed Length Columns has been evaluated for the following properties (see Table 1): Structural Corrosion Protection 1.3. Marshall Extend-O-Column and Marshall Fixed Length Columns have been evaluated for use in supporting loads in wood frame and light steel frame construction. 2.0 STATEMENT OF COMPLIANCE 2.1. Marshall Extend-O-Column and Marshall Fixed Length Columns comply with the Codes listed in Section 1.1, for the properties stated in Section 1.2 and uses stated in Section 1.3, when installed as described in this report, including the Conditions of Use stated in section 5. 3.0 DESCRIPTION 3.1. Marshall Extend-O-Column and Marshall Fixed Length Columns are adjustable and fixed columns, respectively, constructed of carbon steel. 3.2. The posts are fabricated from the steel grade listed below: Tube - ASTM A 500 Grade B Carbon Steel Flange - ASTM A 36 Hot-Rolled Carbon Steel Screw - AISI 1117 Carbon Steel 3.3. Corrosion protection - All Marshall Stamping steel column sections are protected with a rust inhibiting enamel applied to all surfaces including the inside of the column. 3.4. Column sizes recognized in this report are listed in Table A through H for standard measurements and Tables A(M) through H(M) for metric equivalents. Refer to Figure 1 for column details. 3.4.1. The columns, both fixed length and adjustable, are produced in three diameters – 3.0" (76 mm), 3.5" (89 mm), and 4.0" (102 mm) – with either an 11 gauge or 0.216 inch (5.5 mm) thickness. 3.4.2. The adjustable columns are available in lengths from six feet (1829 mm) to twelve feet, four inches (3759 mm). 3.4.3. The fixed length columns are available in lengths from five feet, nine inches (1753 mm) to twelve feet (3658 mm). 4.0 INSTALLATION Marshall Extend-O-Column and Marshall Fixed Length Columns must be installed in accordance with the manufacturer’s published installation instructions, the applicable Code and this Research Report. A copy of the manufacturer’s instructions must be available on the jobsite during installation. 4.1. The Marshall Extend-O-Column must be installed with the adjustable screw mechanism on the bottom. The entire adjustment mechanism, including the entire collar nut, shall be encased in minimum 3500 psi (24.1 MPa) concrete.
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Code Compliance Research Report CCRR-0145
Issue Date: 11-15-2016
Renewal Date: 11-18-2017
130 Derry Court • York, PA 17406 www.intertek.com/building/
1.1. This research report addresses compliance with the following Codes:
2015 International Building Code® (IBC)
2015 International Residential Code® (IRC)
1.2. Marshall Extend-O-Column and Marshall Fixed Length Columns has been evaluated for the following properties (see Table 1):
Structural
Corrosion Protection
1.3. Marshall Extend-O-Column and Marshall Fixed Length Columns have been evaluated for use in supporting loads in wood frame and light steel frame construction.
2.0 STATEMENT OF COMPLIANCE
2.1. Marshall Extend-O-Column and Marshall Fixed Length Columns comply with the Codes listed in Section 1.1, for the properties stated in Section 1.2 and uses stated in Section 1.3, when installed as described in this report, including the Conditions of Use stated in section 5.
3.0 DESCRIPTION
3.1. Marshall Extend-O-Column and Marshall Fixed Length Columns are adjustable and fixed columns, respectively, constructed of carbon steel.
3.2. The posts are fabricated from the steel grade listed below:
Tube - ASTM A 500 Grade B Carbon Steel
Flange - ASTM A 36 Hot-Rolled Carbon Steel
Screw - AISI 1117 Carbon Steel
3.3. Corrosion protection - All Marshall Stamping steel column sections are protected with a rust inhibiting enamel applied to all surfaces including the inside of the column.
3.4. Column sizes recognized in this report are listed in Table A through H for standard measurements and Tables A(M) through H(M) for metric equivalents. Refer to Figure 1 for column details.
3.4.1. The columns, both fixed length and adjustable, are produced in three diameters – 3.0" (76 mm), 3.5" (89 mm), and 4.0" (102 mm) – with either an 11 gauge or 0.216 inch (5.5 mm) thickness.
3.4.2. The adjustable columns are available in lengths from six feet (1829 mm) to twelve feet, four inches (3759 mm).
3.4.3. The fixed length columns are available in lengths from five feet, nine inches (1753 mm) to twelve feet (3658 mm).
4.0 INSTALLATION
Marshall Extend-O-Column and Marshall Fixed Length Columns must be installed in accordance with the manufacturer’s published installation instructions, the applicable Code and this Research Report. A copy of the manufacturer’s instructions must be available on the jobsite during installation.
4.1. The Marshall Extend-O-Column must be installed with the adjustable screw mechanism on the bottom. The entire adjustment mechanism, including the entire collar nut, shall be encased in minimum 3500 psi (24.1 MPa) concrete.
CCRR-0145 Code Compliance Research Report Page 2 of 12
130 Derry Court • York, PA 17406 www.intertek.com/building/
PCA-125
5.0 CONDITIONS OF USE
5.1. Installation must comply with this Research Report, the manufacturer’s published installation instructions and the applicable Code. In the event of a conflict, this report governs.
5.2. The steel columns identified in this report are deemed to comply with the referenced building codes subject to the following conditions.
5.3. Steel column structural elements shall be designed to safely support applicable loads and load combinations in accordance with Chapter 16 of the IBC.
5.4. Design Strengths are applicable to American Institute of Steel Construction (AISC) 360-10, Specification for Structural Steel Buildings (ASD) as identified in Tables A through H for standard measurements and Tables A(M) through H(M) for metric equivalents.
5.5. Use of Marshall Stamping columns shall be accompanied by structural calculations. These calculations shall be signed and sealed by a registered design professional authorized to provide services in the jurisdiction where the project is located. The calculations shall address the following:
5.5.1. The transfer of design loads from the structure to the bearing surface below.
5.5.2. The ability of the column bearing surface to carry the design loads.
5.6. Allowable loads shall be limited to vertical, concentric loadings. The use of these columns to resist lateral loads is outside the scope of this report.
5.7. When Marshall Extend-O-Columns are used, the threaded adjustment rod shall not extend more than four inches (102 mm) from the minimum height.
5.8. Jobsite manufacturing of Marshall Stamping columns is outside the scope of this report.
5.9. Installation outside of the building envelope is outside the scope of this report.
5.10. The Marshall Stamping columns identified in this report are manufactured in Valencia, Pennsylvania in accordance with the manufacturer's approved quality control system with inspections by Architectural Testing (IAS AA-676).
5.11. The Marshall Extend-O-Column and Marshall Fixed Length Column are manufactured under a quality program with inspections by Intertek ATI Inc. (IAS AA-676).
6.0 SUPPORTING EVIDENCE
6.1. Manufacturer's drawings and installation instructions.
6.2. Engineering calculations in accordance with American Institute of Steel Construction (AISC) 360-10, Specification for Structural Steel Buildings.
6.3. Reports of load testing in accordance with ASTM E 72, as referenced by ICC-ES AC335, Acceptance Criteria for Adjustable Steel Columns, revised March 2014.
6.4. Quality control manual in accordance with ICC-ES AC10, Acceptance Criteria for Quality Documentation, dated June 2014.
7.0 IDENTIFICATION
7.1. Marshall Stamping columns produced in accordance with this report shall be identified with labeling that includes the following information:
7.1.1. The manufacturer's name and/or logo
7.1.2. The product name and model number
7.1.3. Design Thickness of the column
7.1.4. Material Grade, i.e. 42 ksi
7.1.5. The Intertek Mark as shown below, and the code compliance Research Report number (CCRR-0145).
CCRR-0145 Code Compliance Research Report Page 3 of 12
130 Derry Court • York, PA 17406 www.intertek.com/building/
PCA-125
9.0 CODE COMPLIANCE RESEARCH REPORT USE
9.1. Approval of building products and/or materials can only be granted by a building official having legal authority in the specific jurisdiction where approval is sought.
9.2. Code Compliance Research Reports shall not be used in any manner that implies an endorsement of the product by Intertek.
9.3. Reference to the Intertek website address: whdirectory.intertek.com is recommended to ascertain the current version and status of this report.
This Code Compliance Research Report (“Report”) is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Report. Only the Client is authorized to permit copying or distribution of this Report and then only in its entirety, and the Client shall not use the Report in a misleading manner. Client further agrees and understands that reliance upon the Report is limited to the representations made therein. The Report is not an endorsement or recommendation for use of the subject and/or product described herein. This Report is not the Intertek Listing Report covering the subject product and utilized for Intertek Certification and this Report does not represent authorization for the use of any Intertek certification marks. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek.