Top Banner
CII 18 th National Award for Excellence in Energy Management - 2017 ICICI Bank Zonal Office Ambattur, Chennai August 30 & 31, 2017
24

CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

Mar 14, 2018

Download

Documents

phamdien
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

Click to add Text

CII 18th National Award for

Excellence in Energy Management - 2017

ICICI Bank Zonal Office Ambattur, Chennai

August 30 & 31, 2017

Page 2: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

2

Ambattur Tower

Year of occupation 2008

Area 14307 Sq.M.

No. of floors G + 5

No. of work stations 2375

Air cooled chillers 3 x 263 TR

Diesel Generator 2 x 625 kVA

1 x 250 kVA

UPS 2 x 120 kVA

Transformer 1000 kVA

Total connected load 950 kW

Page 3: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

3

Beginning of Journey

Description FY 2014

Annual consumption Lac kWh 18.44

Annual Cost Rs. Lac 206.70

EPI 206EPI needs

reduction

Systematic Approach – Energy Management Plan

Employee comfort is not compromised

Energy Audit

Eliminate Wastage

Optimise Capacity

Investment

Page 4: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

Type of load Working

kW

HVAC 356

IT 40

Others /

Utilities /

Pumps

160

Lighting 60

Total 616

Energy Distribution Profile

Page 5: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

5

Brainstorming and Action

Use less energy

Use energy efficiently

Use renewable energy

Active participation of

Employees and Facility

Managers

Page 6: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

Road Map

• Identification – Power Crisis

• Energy Management

• Audit and Analysis

Step 1- Identify

2014

• Establish measurement systems

• Equipment optimisation

• Low investment projects

Step 2-

Consolidate & Synergise

2015

• Continue past initiatives

• Involve mass participation

• Alternate source of energy

Step 3 -

Institutionalise

2016

• Involving business partners

• Safe and sustainable workspace culture

• Giving back to society - CSR

Step 4-

Spreading

2017

Page 7: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

7

UPS Optimisation

Units Savings:

15000 kWh / Yr

Primary UPS - 5x120 KVA

Battery Bank – 100AHx32x5

Charging battery – 100AHx32x3

Server UPS – 2x30 KVA

Battery Bank – 100AHx30x2

Before

UPS post optimisation - 2x120 KVA

Battery Bank – 100AHx32x2

After

Page 8: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

8

DG Optimisation

Units Savings:

140000 KWh / Yr

Before

After

Office Hours DG – 1x 625KVA

9am to 6pm

Post office Hours DG – 1x625KVA

6pm to 9pm

Consumption – 300 KWh

Office Hours DG – 1x 625KVA

Post office Hours DG – 1x250KVA

Consumption – 120 KWh

Page 9: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

9

Other ProjectsOptimisation of HVAC

Lighting control

Annual Savings:

20000 kWh

Annual Savings:

19000 kWh

Timing Control

Alteration of set points

Thermal performance/leakages

Filter cleaning/wet servicing

Total - 2145 2x2 40W CFL

De-lamped – 545

% de-lamped – 25%

Occupancy based lighting -

Cafeteria

Page 10: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

10

FY 14-15 FY 15-16 FY 16-17

• Inverter AC

• LED Retrofit

• HVAC

Optimisation

• Reflective

Glass

• Day light

harvesting

• Roof Top Solar

• AC Installation

• STP Integration

• UPS

Optimisation

ENCON Projects - Investment

Investment:93 Lac

Savings:290000 kWh

Investment:0.5 Lac

Savings:19000 kWh

Investment: 5.10Lac

Savings:98000 kWh

Page 11: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

11

LED Retrofit

Load Quantity Old

wattage

New

wattage

36W TL 141 5640 2820

2x18W CFL – Spot light 749 28462 11235

2x36W CFL – 2x2 fitting 2145 158730 85800

36W CFL – Street Light 36 1368 900

Total 3071 194200 100755

LPD improvement: 52%

Savings: 2.21 Lac KWh/Yr

Investment: 82.2 Lac

Payback: 30 Months

Page 12: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

12

MonitoringOctober – 2015

DATE KWAH PF MD Units Consumption EB

units

DG

Units

EB &

DG

Units

Remarks

1900 2300 700

1 4313640 0.99 655 4620 50 560 5230 696 5926

2 4318920 0.99 655 670 120 590 1380 284 1664

3 4320350 0.99 655 3980 560 530 5070 459 5529 Training

4 4325470 0.99 655 420 200 700 1320 483 1803

5 4326850 0.99 655 4530 220 680 5430 1189 6619

6 4332360 0.99 655 3640 790 70 4500 1448 5948 RBH meet

Trends in energy consumption and operating pattern

Specific area of energy wasted

Page 13: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

13

Optimisation - Air Conditioning

Inverter Star Rated ACs at

24x7 ATM and Control room

Eliminate additional load on chiller operations

Trainings extended beyond office hours / holidays

Dedicated ACs installed against 263TR chiller

5.5 TR x 1 – Duct

4 TR x 3 – Cassette

AC Replacement

Annual

Savings:

24000 kWh

Annual

Savings:

23000 kWh

Page 14: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

Specific Energy Consumption

0

1000

2000

3000

4000

5000

6000

7000

8000

9000

10000

FY13-14 FY14-15 FY15-16 FY16-17

Carpet area (Sq.m.)

0

200

400

600

800

1000

1200

1400

1600

FY13-14 FY14-15 FY15-16 FY16-17

Total no. of employees

Area and manpower increased

0

50

100

150

200

250

FY13-14 FY14-15 FY15-16 FY16-17

206184 172 160

EPI

28%

Page 15: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

Storage pit -Connecting

5 sumps

145000 Ltrs water collected

Used for gardening

Innovative Projects

Savings:

12 tanker water

Rain Water Harvesting Day Light Harvesting

Page 16: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

Internal benchmarking – EPI as on Mar-2017

0

50

100

150

200 We are

here

160

Page 17: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

Road map to achieve benchmark –

FY18

HVAC Retrofit

• Chiller pipeline replacement – 54.05 Lac

• Pumps and valves – 32.83 Lac

• Expected savings – 1.02 Lac KWh

Lighting Control

• Pulling chords

• Occupancy based lighting – Workspace

• Investment – 4 Lac

Façade Replacement

• Triple barrier semi-unitized structural glazing system

• Single glazed 6mm low heat glass

• U value – 3.85 W/Sq.m K

• SHGC – 0.45

Wind Solar Hybrid

• Clean and Green Power

• Leverage – Differential unit cost

• NIL Investment

Investment: 127 Lac

Estd. Savings: 1 Lac KWh

BEE Rating

Page 18: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

Year Scope-I Scope-II Total

FY 2013 770.11 843.98 1614.09

FY 2017 109.60 1456.40 1566.00

GHG Inventory & certification

VC facility reduced air travel –

4000 employees per year

Reduction of CO2 emission -

48 Tons

Pollution control check –

employee vehicles

Elimination of fuel

transportation losses

Page 19: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

19

Renewable Energy – Roof Top Solar

OPEX model

Capacity – 120 kWp

Annual Generation – 1.68 Lac

kWh (9%)

8% utilization during Peak hour

Average – 4.12 kWh per day /

KWp

CO2 Abatement 138 tons per

annum

Mitigates Urban Heat Island

Effect

Cost Benefit 3.8 Lac

for 6 months

Page 20: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

Best Practices

High temperature resistant

Control carbon emission

Humidity absorbent

Life span > 150 years

Restoration of green cover

Drain line channelized to

centralized STP of CAAIIUC

Water recycled, used for

Gardening plants in Ambattur

Savings in motor operation -

7800 KWh/Yr

Neem Tree Plantation

STP Integration

Page 21: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

Best Practices - Green Zone

Paper reduction

Inventory rationalisation

Image based processing

Waste paper recycling

Page 22: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

Replacement of 950 desktops with Energy star

labeled desktops and laptops

Auto switch off - Monitors

Printer with duplex printing

Recycled printer cartridges

Multifunction devices: Printer-Scanner-Photocopier

Best Practices - IT Initiatives

70% reduction in energy consumption by efficient and

optimized equipmentPhotoc

Page 23: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

Employee Training –

Involvement in Energy

Management activities

OEM/HK/Security Training -

Energy management

No cost

Awareness campaign

Training

Energy Savings through Behavioral change

Page 24: CII 18th National Award for - greenbusinesscentre.comgreenbusinesscentre.com/energyaward2017presentations/Buildings... · Click to add Text CII 18th National Award for Excellence

24

Thank you