© ABB - 1 Cigré 2005, SC B5 Colloquium in Calgary Preferential Subject 1 Question 7 Zoran Gajić ABB Sweden
5

Cigré 2005, SC B5 Colloquium in Calgary Preferential Subject 1 Question 7

Jan 19, 2016

Download

Documents

Rian

Cigré 2005, SC B5 Colloquium in Calgary Preferential Subject 1 Question 7. Zoran Gaji ć ABB Sweden. SC B5: PS1, Q7 Transformer Inrush Currents. EFFECT OF TRANSFORMER INRUSH CURRENTS ON PROTECTION FUNCTIONS. Where to Look, Security, Dependability. - PowerPoint PPT Presentation
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Cigré 2005, SC B5 Colloquium in Calgary Preferential Subject 1 Question 7

© A

BB

- 1

Cigré 2005, SC B5 Colloquium in Calgary Preferential Subject 1Question 7

Zoran GajićABB

Sweden

Page 2: Cigré 2005, SC B5 Colloquium in Calgary Preferential Subject 1 Question 7

© A

BB

- 2

SC B5: PS1, Q7 Transformer Inrush Currents

EFFECT OF TRANSFORMER INRUSH CURRENTS ON PROTECTION FUNCTIONS

Where to Look,

Security,

Dependability

Page 3: Cigré 2005, SC B5 Colloquium in Calgary Preferential Subject 1 Question 7

© A

BB

- 3

Transformer Inrush Currents – Where to look?

Measured in Phase Currents or in Differential Currents? 2nd harmonic

4th harmonic

5th harmonic

DC offset

Wave shape recognition

etc.

Set block level depends on position where measurement is taken

Page 4: Cigré 2005, SC B5 Colloquium in Calgary Preferential Subject 1 Question 7

© A

BB

- 4

Transformer Inrush Currents – Security?

Security? Block for all inrush cases

Not good practice to put burden on the end user to completely set this logic

15% or 7%?

Adaptive 2nd harmonic + WaveBlock good results

Correct and easy to use design is manufacturer responsibility

Page 5: Cigré 2005, SC B5 Colloquium in Calgary Preferential Subject 1 Question 7

© A

BB

- 5

Transformer Inrush Currents – Dependability?

Dependability? Trip for all internal faults

Insure that restraint level will trip in spite of CT saturation

Use of adaptive second harmonic blocking insures that

Paper in IEE DPSP 2001