© American Standard Inc. 2006 Chiller–Tower Optimization … Do It Right! Chiller–Tower Optimization … Do It Right! The Trane Company La Crosse, Wisconsin
24

Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

Apr 02, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

Chiller–Tower Optimization …

Do It Right!

Chiller–Tower Optimization …

Do It Right!

The Trane CompanyLa Crosse, Wisconsin

Page 2: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

chiller–tower optimizationThe Question …

“알맞은”냉각수온도는몇도인가?

Page 3: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

Simple Case(Constant Water Flow)

LoadCW TempChiller Design

Wet BulbLoadCW TempTower Design

Page 4: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

Link Is Condenser Water Temperature

CondenserWater Temp Chiller kW Tower kW Total kW

??

Page 5: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

Or Said Another Way …

0

50

100

150

200

250

300

350

72 73 74 75 76 77 78 79 80 81 82 83 84 85

Chiller kWTower kWTotal kW

Condenser Water Temperature

kW

( 29.5 C)( 22.5 C)

Page 6: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

각각의시스템구성요소보다는전체 System 관점에서생각해야한다.

Page 7: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

chiller–tower optimizationCondenser Water Control

Hot? (85°F [30°C])

Cold? (55°F [13°C])

Wet Bulb + 5°F [3°C]?

Optimized?

Page 8: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

Optimization? Optimization?

Page 9: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

a simple case …Component Models

ChillerChiller design

ARI-certified selections

Polynomials (다항식)f(Design kW, % Load)f(CW temperature)

ConstantsCondenser water flowChilled water temperature

Cooling TowerTower design

CTI-certified selections

FunctionsWet bulbHeat rejectedTower airflow

ConstantCondenser water flow

Page 10: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

Where’s The Meter?

A. On the building.

B. On the chiller.

Page 11: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

What’s The Bottom Line?

400-ton [1400 kW] chiller

0.58 kW/ton [6.06 COP]

85°-95°F [29.4°-35°C] condenser water temperature differential

78°F [25.6°C] designwet-bulb temperature

“ARI unloading” …Full load 17% of the time75% load 39% of the time50% load 33% of the time25% load 11% of the time

Economics …$0.08 per kWh$12.00 per kW1,300 equivalent full-load hours

Page 12: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

The Bottom Line … $

Minimumtempera ture

Design CW WB + 5degrees

Optimized$47,500.00

$48,000.00

$48,500.00

$49,000.00

$49,500.00

$50,000.00

$50,500.00

$51,000.00

Minimumtempera ture

Design CW WB + 5degrees

Optimized

Chiller+Tower Yearly Estimated Operating Cost OK

Page 13: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

The Bottom Line … 71°F WB

Minimumtempera ture

Design CW WB + 5degrees

Optimized$42,500.00

$43,000.00

$43,500.00

$44,000.00

$44,500.00

$45,000.00

$45,500.00

$46,000.00

$46,500.00

$47,000.00

Minimumtempera ture

Design CW WB + 5degrees

Optimized

Chiller+Tower Yearly Estimated Operating Cost OK

Page 14: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

Minimumtempera ture

Des ign CW WB + 5degrees

Optimized$39,500.00

$40,000.00

$40,500.00

$41,000.00

$41,500.00

$42,000.00

$42,500.00

$43,000.00

$43,500.00

$44,000.00

$44,500.00

Minimumtempera ture

Des ign CW WB + 5degrees

Optimized

Chiller+Tower Yearly Estimated Operating Cost OK

The Bottom Line … 65°F WB

Page 15: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

But The Chiller Must Work Harder!

Page 16: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

where’s the meter?The Only Possible Response …

On the building!On the building!

Page 17: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

chiller–tower optimizationThe REAL Bottom Line …

Our customers shouldn’t have to pay more!

Page 18: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

Plant Power vs CWS

0.0

200.0

400.0

600.0

800.0

1,000.0

1,200.0

60 62 64 66 68 70 72 74 76 78 80 82 84 86 88

Condenser Water Setpoint ( )캟

Pow

er (k

W)

Lowest condenser water temperature available from tower at this load and wet-bulb temperature

Chillers cannot meet load above this condenser water temperature

Optimal operation

1,550 tons, 65 Wet-bulb 캟

T t

1,160 tons, 59 Wet-bulb 캟

T

730 tons, 54 Wet-bulb Temperature캟

Braun, Diderrich

Hydeman, Gillespie, Kammerud

Schwedler,ASHRAE Journal

Hydeman, et. al. Pacific Gas and Electric. Used with permission.

chiller–tower optimizationIs It Real?

Page 19: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

chiller–tower optimizationHow Do You Do It?

With real-life controls!

Page 20: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

chiller–tower optimizationHow Do You Calculate Savings?

System Analyzer™

Page 21: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

chiller–tower optimizationHow Do You Calculate Savings?

TRACE® 700

Page 22: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

chiller–tower optimizationWhat Else Should You Know?

신규또는개보수시설모두적용가능

About 30 installations

최적의 set point는

냉동기 type에따라변한다

Two-speed 또는variable-speed cooling tower fan이좋은방법이다.

Page 23: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

chiller–tower optimizationIn Summary …

냉각수온도가저온일수록더이로운것은아니다.

중요한것은최적운전제어이며이를통해비용절감효과를거둘수있다.

비용절감은사실이고측정되어질수있다.

다양한제어방식이가능하다!

Page 24: Chiller-Tower Optimization Do It Right! - TRANE KOREA · 2008-06-09 · 400-ton [1400 kW] chiller 0.58 kW/ton [6.06 COP] 85°-95°F [29.4°-35°C] condenser water temperature differential

© American Standard Inc. 2006© American Standard Inc. 2006

Do it right!Chiller–Tower Optimization

Questions and answers …