1 1.Introduction The WWD high wall mounted fan coil units delivers a high standard of air quality characteristics in many application. With the features of extremely quiet, suitable for most public buildings and private house. Units are standard equipped with remote controller and nylon filter. 2.Design Features Both EC & AC Motor Design Are Available This range can be installed either the EC motor or AC motor. Both ranges are with remote control. www.innovair.com • Air Flow:200--800CFM • 2-Pipe--2-Row • Valve Installed Inside (Optional) • 3/8” Diameter Copper Tube • EC Motor Available • Upto 800CFM Model • Project Selection Soſtware φ3/8” (9.52mm) Copper Tube Heat Exchanger Coil (Heat Exchanger) is construced of Φ3/8” seamless copper tubes. Aluminium blue fines are mechanically bonded to copper It is with much higher efficiency than triditional Φ1/4” copper tube heat exchanger and with much smaller water-resistant, not easy to get tube jam.tubes. Hi-efficiency Alu Blue Fins Φ3/8”(9.52mm) Chilled Water HighWall Mounted WWD Series
4
Embed
Chilled Water HighWall Mounted - Innovair Corporation · Chilled Water HighWall Mounted WWD Series. 2 General Data ... The motorized-valve can be installed inside the fan coil with
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
1
1.IntroductionThe WWD high wall mounted fan coil units delivers a high standard of air quality characteristics in many application. With the features of extremely quiet, suitable for most public buildings and private house. Units are standard equipped with remote controller and nylon filter.
2.Design FeaturesBoth EC & AC Motor Design Are AvailableThis range can be installed either the EC motor or AC motor.Both ranges are with remote control.
www.innovair.com
• Air Flow:200--800CFM• 2-Pipe--2-Row• Valve Installed Inside (Optional)
• 3/8” Diameter Copper Tube• EC Motor Available• Upto 800CFM Model
• Project Selection Software
φ3/8” (9.52mm) Copper Tube Heat Exchanger Coil (Heat Exchanger) is construced of Φ3/8” seamless copper tubes. Aluminium blue fines are mechanically bonded to copper It is with much higher efficiency than triditional Φ1/4” copper tube heat exchanger and with much smaller water-resistant, not easy to get tube jam.tubes.
Hi-efficiency Alu Blue Fins Φ3/8”(9.52mm)
Chilled WaterHighWall Mounted
WWD Series
2
General Data
www.innovair.com
Motorized-valve Installed InsideThe motorized-valve can be installed inside the fan coil with enough space. It can be factory fitted. Also customer can choose without valve.Customer can also install the triditional valve outside the fan coil units.
Enough Space forMotorized Valve Inside
Spec Item Unit WWD-002 WWD-003 WWD-004 WWD-005 WWD-006 WWD-008Nominal Air volume CFM 200 300 400 500 600 800
Coil
Copper tube 3/8”(9.52mm)OD seamless copper tubeFins Hi-efficiency aluminium blue fins
Fins per Inch FPI 14 14 14 14 14 14
FanFan type Cross flow, direct driven
Qty pcs 1 1 1 1 1 1
Motor
Voltage 220-240V/1Ph/50-60HZ,110-127V/1Ph/50HZ
Motor speed 3-speed AC or EC Motor
Qty pcs 1 1 1 1 1 1
Power input EC W(H/M/L) 10/8/6 13/10/8 20/13/10 30/20/13 45/24/18 55/34/22
Power input AC W(H/M/L) 26/23/21 40/34/30 42/36/29 63/47/36 75/64/45 90/72/55
Noise level at 1.0m distance
H d B(A) 37 40 42 46 47 49M d B(A) 34 37 40 43 41 45L d B(A) 31 34 37 40 38 41
Note: Air flow is tested in the condition that the fan coil heat exchanger is dry.
Chilled Water High Wall Mounted WWD Series
4
Dimension Data
Valve Package Installation(Optional)
www.innovair.com
Model A B CWWD-002 784 283 218WWD-003 784 283 218WWD-004 1050 318 237WWD-005 1050 318 237WWD-006 1050 318 237WWD-008 1178 340 250
Standard WWD series fan coil units are without valve package. Customer can choose valve package and we can help customer to make it factory fitted or customer can buy the valve and install the valve inside the fan coil by himself. The PWFC design is with enough space of installing the vaive inside the units.