CHAPTER EIGHT Shallow Foundation – Mat Foundation 8.1 Introduction Under normal conditions, square and rectangular footings such as those described in previously are economical for supporting columns and walls. However, under certain circumstances, it may be desirable to construct a footing that supports a line of two or more columns. These footings are referred to as combined footings. When more than one line of columns is supported by a concrete slab, it is called a mat foundation. Common Types of Mat Foundations The mat foundation, which is sometimes referred to as a raft foundation. Mat foundations are sometimes preferred for soils that have low load-bearing capacities, but that will have to support high column or wall loads. Under some conditions, spread footings would have to cover more than half the building area, and mat foundations might be more economical. Several types of mat foundations are used currently. Some of the common ones are shown schematically in Figure 8.1 and include the following: 1. Flat plate (Figure 8.1a). The mat is of uniform thickness. 2. Flat plate thickened under columns (Figure 8.1b). 3. Beams and slab (Figure 8.1c). The beams run both ways, and the columns are located at the intersection of the beams. 4. Flat plates with pedestals (Figure 8.1d).
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
CHAPTER EIGHT
Shallow Foundation – Mat Foundation
8.1 Introduction Under normal conditions, square and rectangular footings such as those described in
previously are economical for supporting columns and walls. However, under certain
circumstances, it may be desirable to construct a footing that supports a line of two or
more columns. These footings are referred to as combined footings. When more than
one line of columns is supported by a concrete slab, it is called a mat foundation.
Common Types of Mat Foundations
The mat foundation, which is sometimes referred to as a raft foundation. Mat
foundations are sometimes preferred for soils that have low load-bearing capacities, but
that will have to support high column or wall loads. Under some conditions, spread
footings would have to cover more than half the building area, and mat foundations
might be more economical. Several types of mat foundations are used currently. Some
of the common ones are shown schematically in Figure 8.1 and include the following:
1. Flat plate (Figure 8.1a). The mat is of uniform thickness.
2. Flat plate thickened under columns (Figure 8.1b).
3. Beams and slab (Figure 8.1c). The beams run both ways, and the columns are located
at the intersection of the beams.
4. Flat plates with pedestals (Figure 8.1d).
Shallow Foundation – Mat Foundation
Page 2 of 25
AL-Qasim Green University College Of Water Resources Engineering
Foundation Engineering Mr. Wissam Nadir
5. Slab with basement walls as a part of the mat (Figure 8.1e). The walls act as stiffeners
for the mat.
Mats may be supported by piles, which help reduce the settlement of a structure built
over highly compressible soil. Where the water table is high, mats are often placed over
piles to control buoyancy.
Shallow Foundation – Mat Foundation
Page 3 of 25
AL-Qasim Green University College Of Water Resources Engineering
Foundation Engineering Mr. Wissam Nadir
8.2 Structural Design of Mat Foundations The structural design of mat foundations can be carried out by two conventional
methods:
The conventional rigid method
The approximate flexible method
Finite-difference and finite-element methods can also be used, but this section
covers only the basic concepts of the conventional rigid method are discussed in this
chapter.
8.3 Design Procedure for the Conventional (Rigid) Method The procedure for design a mat foundation, using the conventional method, consists of
the following steps:
Step 1. All the columns and walls are numbered and their total unfactored (working)
axial loads, moments and any overturning moment due to wind or other causes, are
calculated separately. It may be useful if a suitable table is used for this purpose.
Step 2. The line of action of the resultant R of all the axial loads and moments is
determined using statics; summing moments about two of the adjacent mat edges, and
computing the x and y moment arms of the resultant force. Then, the eccentricities ex
and ey are computed (Figure 8.2a).
Step 3- Determine the maximum contact pressure (unfactored), qmax, below one of the
mat corners using Equation below, repeated here for convenience.
𝑞 =𝑅
𝐵𝐿1 ∓
6𝑒
𝐵∓
6𝑒
𝐿
In this equation, the B and L dimensions are in x and y directions, respectively.
Step 4. Compare the computed qmax with the allowable soil pressure qa furnished by the
geotechnical engineer to check if qmax ≤ qa.
Shallow Foundation – Mat Foundation
Page 4 of 25
AL-Qasim Green University College Of Water Resources Engineering
Foundation Engineering Mr. Wissam Nadir
Step 5. Compute the contact pressure (unfactored) at selected points beneath the mat.
These selected points are corners of continuous beam strips (or combined footings with
multiple columns) to which the mat is divided in both x and y directions, as shown in
Figure 8.2b. The contact pressure q at any point below the mat is computed using
Equation:
𝑞 , =𝑅
𝐴∓
𝑀
𝐼𝑥 ∓
𝑀
𝐼𝑦
Where:
A = B × L
𝐼 = 𝐵𝐿 12⁄ , 𝐼 = 𝐿𝐵 12⁄
𝑀 = 𝑚𝑜𝑚𝑒𝑛𝑡 𝑜𝑓 𝑐𝑜𝑙𝑢𝑚𝑛 𝑙𝑜𝑎𝑑 𝑎𝑏𝑜𝑢𝑙 𝑥 − 𝑎𝑥𝑖𝑠 = 𝑅𝑒
𝑀 = 𝑚𝑜𝑚𝑒𝑛𝑡 𝑜𝑓 𝑐𝑜𝑙𝑢𝑚𝑛 𝑙𝑜𝑎𝑑 𝑎𝑏𝑜𝑢𝑙 𝑦 − 𝑎𝑥𝑖𝑠 = 𝑅𝑒
Step 6. Divide the mat into several strips in the x and y directions. (See Figure 8.2). Let
the width of any strip be B1
Step 7. Draw the shear, V, and the moment, M, diagrams for each individual strip (in the
x and y directions). For example, the average soil pressure of the bottom strip in the x
direction of Figure 8.2 a is
𝑞 =𝑞 + 𝑞
2
Where qI and qF = soil pressures at points I and F, as determined from Step 5.
The total soil reaction is equal to q B1B.
Now obtain the total column load on the strip as Q1+ Q2 + Q3 + Q4. The sum of the
column loads on the strip will not equal q B1B, because the shear between the
adjacent strips has not been taken into account. For this reason, the soil reaction and
Shallow Foundation – Mat Foundation
Page 5 of 25
AL-Qasim Green University College Of Water Resources Engineering
Foundation Engineering Mr. Wissam Nadir
the column loads need to be adjusted, or
𝑎𝑣𝑎𝑟𝑒𝑎𝑔𝑒 𝑙𝑜𝑎𝑑 =q B B + (Q1 + Q2 + Q3 + Q4)
2
Now, the modified average soil reaction becomes
𝑞 ( ) = 𝑞𝑎𝑣𝑎𝑟𝑎𝑔𝑒 𝑙𝑜𝑎𝑑
q B B
In addition, the column load modification factor is
𝐹 =𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑙𝑜𝑎𝑑
(Q1 + Q2 + Q3 + Q4)
So the modified column loads are FQ1, FQ2, FQ3 , and FQ4. This modified loading on the
strip under consideration is shown in Figure 8.2b. The shear and the moment diagram
for this strip can now be drawn, and the procedure is repeated in the x and y directions
for all strips.
Shallow Foundation – Mat Foundation
Page 6 of 25
AL-Qasim Green University College Of Water Resources Engineering
Foundation Engineering Mr. Wissam Nadir
Figure 8.2
Shallow Foundation – Mat Foundation
Page 7 of 25
AL-Qasim Green University College Of Water Resources Engineering
Foundation Engineering Mr. Wissam Nadir
Step 8. Determine the effective depth (d) of the mat by checking for diagonal tension
shear near various columns. For the critical section,
∅𝑉 ≥ 𝑉
According to ACI Code 318-14 (Section 22.6.5.2) for nonprestressed slabs and footings,
Vc shall be the smallest of the equations
ACI Table 22.6.5.2 Tow Way Shear
𝑣
Least of (a),(b) and (c)
0.33 𝜆 𝑓 𝑏°𝑑 a
0.17 1 +2
𝛽 𝜆 𝑓 𝑏°𝑑 b
0.083 2 +𝛼 𝑑
𝑏° 𝜆 𝑓 𝑏°𝑑 c
Step 9. From the moment diagrams of all strips in one direction (x or y), obtain the
maximum positive and negative moments per unit width (i.e.,Mu= M/B1).
Step 10. Determine the area of steel per unit width for positive and negative
reinforcement in the x and y directions.
Shallow Foundation – Mat Foundation
Page 8 of 25
AL-Qasim Green University College Of Water Resources Engineering
Foundation Engineering Mr. Wissam Nadir
Example: The plan of a simple mat foundation and the tabulated column working loads
are shown in the figure below. All the columns are 0.4 × 0.4 m and carry no moment of
significant value. The design soil pressure or net qa and average modulus of subgrade
reaction Ks,av, recommended by the geotechnical engineer, are 60 kPa and 7200 kN/m3,
respectively. Design the mat by the conventional rigid method, and then check if this
design method could be considered appropriate. Use:𝑓 = 24𝑀𝑃𝑎 , 𝑓𝑦 = 420𝑀𝑃𝑎
AL-Qasim Green University College Of Water Resources Engineering
Foundation Engineering Mr. Wissam Nadir
Step 2. Determine the maximum contact pressure 𝑞 .and compare with net bearing capacity.
𝑞 =𝑅
𝐵𝐿1 +
6𝑒
𝐵+
6𝑒
𝐿
𝑞 . =7230
12 × 221 +
6 × 0.17
12+
6 × 0.04
22= 30.01 𝑘𝑁 𝑚⁄
𝑞 . = 60 𝑘𝑁 𝑚⁄ > 𝑞 . = 30.01 𝑘𝑁 𝑚⁄
Step 3. Divide the the mat as continuous beam strip in both x and Y direction, then compute the unfactored contact pressure in each corner of strip.
point X (m) Y (m) q kN/m2 A 6 11 30.00 E 2.9 11 28.80 F -2.9 11 26.55 B -6 11 25.35 I 6 7.2 29.9 J -6 7.2 25.24 K 6 0 29.7 L -6 0 25.05 M 6 -7.2 29.51 N -6 -7.2 24.85 C 6 -12 29.38 G 2.9 -12 28.18 H -2.9 -12 25.93 D -6 -12 24.72
Shallow Foundation – Mat Foundation
Page 11 of 25
AL-Qasim Green University College Of Water Resources Engineering
Foundation Engineering Mr. Wissam Nadir
𝑞 , =𝑅
𝐴∓
𝑀
𝐼𝑥 ∓
𝑀
𝐼𝑦
𝑀 = 𝑅 × 𝑒 = 7230 × 0.17 = 1229.1 𝑘𝑁. 𝑚
𝑀 = 𝑅 × 𝑒 = 7230 × 0.04 = 289.2 𝑘𝑁. 𝑚
𝐼 =𝐿 𝐵
12= 3168 𝑚 , 𝐼 =
𝐵 𝐿
12= 10648 𝑚
𝑞 , =7230
12 × 22∓
1229.1
3168𝑥 ∓
289.2
10648𝑦 = 27.38 ∓ 0.388 𝑥 ∓ 0.027 𝑦
Step 4: check the equilibrium for each strip and modify the column load and contact pressure accordingly.
AL-Qasim Green University College Of Water Resources Engineering
Foundation Engineering Mr. Wissam Nadir
10 0.913 × (1.2 × 80 + 1.6 × 160) 321.376 sum 3213.75 kN Since the strip is symmetrically loaded, the factored R falls at the center and the factored contact pressure qult is assumed uniformly distributed.
Find the modification factored column load and ultimate bearing capacity
Column No. Modified ultimate load kN 3 0.897 × (1.2 × 100 + 1.6 × 200) 394.68 6 0.897 × (1.2 × 270 + 1.6 × 540) 1065.64 9 0.897 × (1.2 × 270 + 1.6 × 540) 1065.64 12 0.897 × (1.2 × 90 + 1.6 × 180) 355.212 sum 2881.17 Since the strip is unsymmetrically loaded, the factored R does not fall at the center; it has an eccentricity eL or ey, calculated as follows:
Find the modification factored column load and ultimate bearing capacity
Column No. Modified ultimate load kN 1 1.2 × (1.2 × 80 + 1.6 × 160) 422.6 2 1.2 × (1.2 × 120 + 1.6 × 240) 633.6 3 1.2 × (1.2 × 100 + 1.6 × 200) 528 sum 1584.2kN Since the strip is unsymmetrically loaded, the factored R does not fall at the center; it has an eccentricity eB or eX, calculated as follows:
�̅� =422.6 × 0.2 + 633.6 × 6 + 528 × 11.8
1584.2= 6.386 𝑚
𝑒 = 𝐵 2⁄ − �̅� = 6 − 6.386 = −0.386 < 𝐿 6⁄
𝑞 . ., =𝑅
𝐴∓
𝑒 𝑅
𝐼𝑙
Shallow Foundation – Mat Foundation
Page 15 of 25
AL-Qasim Green University College Of Water Resources Engineering
Step 7. Determine the minimum mat thickness considering punching shear (two-way or
diagonal tension shear) at critical columns.
Considering the factors which contribute to two-way shear (column load, soil reaction,
column size and length of shear perimeter at each column), by inspection, it appears
that the maximum shear occurs at column No. 4 (or column No. 7) with a three-side
shear perimeter.
Factored load = 1.2 × 320 + 1.6 × 640 = 1048kN 𝑉 = 1048 𝑘𝑁 Note that the maximum value of d is selected as the design value and it corresponds to the minimum value of Vc obtained from equations
ACI Table 22.6.5.2 Tow Way Shear
𝑣
Least of (a),(b) and (c)
0.33 𝜆 𝑓 𝑏°𝑑 a
0.17 1 +2
𝛽 𝜆 𝑓 𝑏°𝑑 b
0.083 2 +𝛼 𝑑
𝑏° 𝜆 𝑓 𝑏°𝑑 c
Shallow Foundation – Mat Foundation
Page 23 of 25