CENTRAL ELECTRICA MALACAS Fire Sprinkler Reports for EEPSA Prepared By: MECARTE S.A.C. PERSHING 157 MIRAFLORES (51-1) 445-3227 ABRIL, 2015
Jan 27, 2016
CENTRAL ELECTRICA MALACASFire Sprinkler Reports
for
EEPSA
Prepared By:
MECARTE S.A.C.
PERSHING 157
MIRAFLORES
(51-1) 445-3227
ABRIL, 2015
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 2
General Project Data Report
General Data
Project Title: CENTRAL ELECTRICA MALACAS Project File Name: CH-003 EEPSA TRANSFO BAT11-11UB..fiw
Designed By: Date: ABRIL, 2015Code Reference: NFPA-15 Approving Agency:Client Name: EEPSA Phone:Address: City, State Zip Code:Company Name: MECARTE S.A.C. Representative:Company Address: PERSHING 157 City And State: MIRAFLORESPhone: (51-1) 445-3227Building Name: TRANSFORMADORES
BAT11/BBT11 Building Owner:
Contact at Building: Phone at Building:Address Of Building: City, State Zip Code:
Project Data
Description Of Hazard: DELUGE SYSTEMS Sprinkler System Type: DryDesign Area Of Water Application: 500 ft² Maximum Area Per Sprinkler: 84 ft²Default Sprinkler K-Factor: 3,00 K Default Pipe Material: SCHED 40 WET STEELInside Hose Stream Allowance: 0,00 gpm Outside Hose Stream Allowance: 250,00 gpmIn Rack Sprinkler Allowance: 0,00 gpm
Sprinkler SpecificationsMake: TYCO Model: D3Size: 1/2" Temperature Rating: 0 F
Water Supply Test Data
Source Of Information:Test Hydrant ID: Date Of Test:
Hydrant Elevation: 0 ft Static Pressure: 0,00 psiTest Flow Rate: 0,00 gpm Test Residual Pressure: 0,00 psiCalculated System Flow Rate: 1496,56 gpm Calculated Inflow Residual Pressure: 88,31 psiAvailable Inflow Residual Pressure: 0 psi
Calculation Project Data
Calculation Mode: DemandHMD Minimum Residual Pressure: 60,00 psi Minimum Desired Flow Density: 0,25 gpm/ft²Number Of Active Nodes: 163Number Of Active Pipes: 167 Number Of Inactive Pipes: 0Number Of Active Sprinklers: 52 Number Of Inactive Sprinklers: 0
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 3
Fire Sprinkler Input Data
Node Input Data
Node No. Node Description Area Group SprinklerKFactor (K)
PressureEstimate (psi)
NodeElevation
(feet)
Non-SprinklerDischarge
(gpm)
1 No Discharge N/A 82,53 0,00 0,00
2 No Discharge N/A 82,25 0,00 0,00
3 No Discharge N/A 79,65 5,30 0,00
4 No Discharge N/A 78,38 7,60 0,00
5 No Discharge N/A 77,30 7,60 0,00
6 No Discharge N/A 64,45 32,33 0,00
7 No Discharge N/A 64,01 32,33 0,00
8 No Discharge N/A 67,34 23,21 0,00
9 No Discharge N/A 66,89 19,08 0,00
10 No Discharge N/A 69,83 10,55 0,00
11 No Discharge N/A 66,11 23,21 0,00
12 Sprinkler 3,00 63,63 24,68 0,00
13 No Discharge N/A 64,80 23,21 0,00
14 No Discharge N/A 64,08 23,21 0,00
15 Sprinkler 3,00 61,66 24,68 0,00
16 No Discharge N/A 63,37 23,21 0,00
17 Sprinkler 3,00 60,96 24,68 0,00
18 No Discharge N/A 62,95 23,21 0,00
19 Sprinkler 3,00 60,56 24,68 0,00
20 No Discharge N/A 62,75 23,21 0,00
21 Sprinkler 3,00 60,37 24,68 0,00
22 No Discharge N/A 62,70 23,21 0,00
23 No Discharge N/A 60,86 27,28 0,00
24 Sprinkler 3,00 60,00 27,28 0,00
25 No Discharge N/A 60,86 27,28 0,00
26 Sprinkler 3,00 60,00 27,28 0,00
27 No Discharge N/A 62,72 23,21 0,00
28 No Discharge N/A 62,76 23,21 0,00
29 Sprinkler 3,00 60,37 24,68 0,00
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 4
Fire Sprinkler Input Data
Node Input Data (cont'd)
Node No. Node Description Area Group SprinklerKFactor (K)
PressureEstimate (psi)
NodeElevation
(feet)
Non-SprinklerDischarge
(gpm)
30 No Discharge N/A 62,95 23,21 0,00
31 Sprinkler 3,00 60,56 24,68 0,00
32 No Discharge N/A 63,37 23,21 0,00
33 Sprinkler 3,00 60,97 24,68 0,00
34 No Discharge N/A 64,09 23,21 0,00
35 Sprinkler 3,00 61,67 24,68 0,00
36 No Discharge N/A 65,13 23,21 0,00
37 No Discharge N/A 66,16 23,21 0,00
38 Sprinkler 3,00 63,69 24,68 0,00
39 No Discharge N/A 65,62 19,08 0,00
40 Sprinkler 3,00 64,71 19,08 0,00
41 No Discharge N/A 64,29 19,08 0,00
42 No Discharge N/A 63,56 19,08 0,00
43 Sprinkler 3,00 62,67 19,08 0,00
44 No Discharge N/A 62,83 19,08 0,00
45 Sprinkler 3,00 61,95 19,08 0,00
46 No Discharge N/A 62,41 19,08 0,00
47 Sprinkler 3,00 61,53 19,08 0,00
48 No Discharge N/A 62,20 19,08 0,00
49 Sprinkler 3,00 61,33 19,08 0,00
50 No Discharge N/A 62,15 19,08 0,00
51 No Discharge N/A 62,10 19,08 0,00
52 Sprinkler 3,00 61,23 19,08 0,00
53 No Discharge N/A 62,10 19,08 0,00
54 Sprinkler 3,00 61,23 19,08 0,00
55 No Discharge N/A 62,20 19,08 0,00
56 No Discharge N/A 62,24 19,08 0,00
57 Sprinkler 3,00 61,36 19,08 0,00
58 No Discharge N/A 62,44 19,08 0,00
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 5
Fire Sprinkler Input Data
Node Input Data (cont'd)
Node No. Node Description Area Group SprinklerKFactor (K)
PressureEstimate (psi)
NodeElevation
(feet)
Non-SprinklerDischarge
(gpm)
59 Sprinkler 3,00 61,56 19,08 0,00
60 No Discharge N/A 62,86 19,08 0,00
61 Sprinkler 3,00 61,98 19,08 0,00
62 No Discharge N/A 63,59 19,08 0,00
63 Sprinkler 3,00 62,70 19,08 0,00
64 No Discharge N/A 64,64 19,08 0,00
65 No Discharge N/A 65,69 19,08 0,00
66 Sprinkler 3,00 64,77 19,08 0,00
67 No Discharge N/A 68,51 10,55 0,00
68 Sprinkler 3,00 67,55 10,55 0,00
69 No Discharge N/A 67,11 10,55 0,00
70 No Discharge N/A 67,89 7,60 0,00
71 No Discharge N/A 67,13 7,60 0,00
72 Sprinkler 3,00 66,19 7,60 0,00
73 No Discharge N/A 66,37 7,60 0,00
74 Sprinkler 3,00 65,44 7,60 0,00
75 No Discharge N/A 65,92 7,60 0,00
76 Sprinkler 3,00 65,00 7,60 0,00
77 No Discharge N/A 65,71 7,60 0,00
78 Sprinkler 3,00 64,79 7,60 0,00
79 No Discharge N/A 65,67 7,60 0,00
80 No Discharge N/A 64,37 10,55 0,00
81 No Discharge N/A 64,31 10,55 0,00
82 Sprinkler 3,00 63,41 10,55 0,00
83 No Discharge N/A 64,31 10,55 0,00
84 Sprinkler 3,00 63,41 10,55 0,00
85 No Discharge N/A 64,39 10,55 0,00
86 No Discharge N/A 65,69 7,60 0,00
87 No Discharge N/A 65,72 7,60 0,00
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 6
Fire Sprinkler Input Data
Node Input Data (cont'd)
Node No. Node Description Area Group SprinklerKFactor (K)
PressureEstimate (psi)
NodeElevation
(feet)
Non-SprinklerDischarge
(gpm)
88 Sprinkler 3,00 64,80 7,60 0,00
89 No Discharge N/A 65,93 7,60 0,00
90 Sprinkler 3,00 65,01 7,60 0,00
91 No Discharge N/A 66,37 7,60 0,00
92 Sprinkler 3,00 65,45 7,60 0,00
93 No Discharge N/A 67,14 7,60 0,00
94 Sprinkler 3,00 66,20 7,60 0,00
95 No Discharge N/A 68,24 7,60 0,00
96 No Discharge N/A 67,47 10,55 0,00
97 No Discharge N/A 68,57 10,55 0,00
98 Sprinkler 3,00 67,61 10,55 0,00
100 No Discharge N/A 77,27 7,60 0,00
101 No Discharge N/A 71,92 14,62 0,00
102 No Discharge N/A 71,21 14,62 0,00
103 No Discharge N/A 70,40 14,62 0,00
104 No Discharge N/A 69,68 14,62 0,00
105 No Discharge N/A 65,90 21,58 0,00
106 No Discharge N/A 65,34 21,58 0,00
107 No Discharge N/A 66,70 16,92 0,00
108 No Discharge N/A 69,68 9,21 0,00
109 No Discharge N/A 66,12 16,92 0,00
110 Sprinkler 3,00 65,20 16,92 0,00
111 No Discharge N/A 66,14 16,92 0,00
112 No Discharge N/A 65,73 16,92 0,00
113 Sprinkler 3,00 64,81 16,92 0,00
114 No Discharge N/A 65,36 16,92 0,00
115 Sprinkler 3,00 64,45 16,92 0,00
116 No Discharge N/A 65,23 16,92 0,00
117 No Discharge N/A 65,13 16,92 0,00
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 7
Fire Sprinkler Input Data
Node Input Data (cont'd)
Node No. Node Description Area Group SprinklerKFactor (K)
PressureEstimate (psi)
NodeElevation
(feet)
Non-SprinklerDischarge
(gpm)
118 Sprinkler 3,00 64,21 16,92 0,00
119 No Discharge N/A 65,10 16,92 0,00
120 Sprinkler 3,00 64,18 16,92 0,00
121 No Discharge N/A 65,10 16,92 0,00
122 No Discharge N/A 65,10 16,92 0,00
123 Sprinkler 3,00 64,19 16,92 0,00
124 No Discharge N/A 65,20 16,92 0,00
125 Sprinkler 3,00 64,28 16,92 0,00
126 No Discharge N/A 65,44 16,92 0,00
127 No Discharge N/A 65,62 16,92 0,00
128 Sprinkler 3,00 64,70 16,92 0,00
129 No Discharge N/A 69,08 9,21 0,00
130 Sprinkler 3,00 68,12 9,21 0,00
131 No Discharge N/A 69,10 9,21 0,00
132 No Discharge N/A 68,68 9,21 0,00
133 Sprinkler 3,00 67,72 9,21 0,00
134 No Discharge N/A 68,29 9,21 0,00
135 Sprinkler 3,00 67,34 9,21 0,00
136 No Discharge N/A 68,15 9,21 0,00
137 No Discharge N/A 68,04 9,21 0,00
138 Sprinkler 3,00 67,09 9,21 0,00
139 No Discharge N/A 68,01 9,21 0,00
140 Sprinkler 3,00 67,06 9,21 0,00
141 No Discharge N/A 68,02 9,21 0,00
142 No Discharge N/A 68,03 9,21 0,00
143 Sprinkler 3,00 67,08 9,21 0,00
144 No Discharge N/A 68,12 9,21 0,00
145 Sprinkler 3,00 67,17 9,21 0,00
146 No Discharge N/A 68,37 9,21 0,00
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 8
Fire Sprinkler Input Data
Node Input Data (cont'd)
Node No. Node Description Area Group SprinklerKFactor (K)
PressureEstimate (psi)
NodeElevation
(feet)
Non-SprinklerDischarge
(gpm)
147 No Discharge N/A 68,56 9,21 0,00
148 Sprinkler 3,00 67,60 9,21 0,00
201 No Discharge N/A 82,96 0,00 0,00
202 No Discharge N/A 84,94 -4,17 0,00
203 No Discharge N/A 85,13 -4,17 0,00
204 No Discharge N/A 83,50 0,00 0,00
205 No Discharge N/A 84,71 0,00 0,00
206 No Discharge N/A 87,15 -5,22 0,00
207 No Discharge N/A 87,60 -5,22 0,00
208 No Discharge N/A 85,52 0,00 0,00
209 No Discharge N/A 86,43 0,00 0,00
210 No Discharge N/A 88,15 -3,58 0,00
211 No Discharge N/A 89,41 -3,58 0,00
212 No Discharge N/A 85,64 5,58 0,00
213 No Discharge N/A 88,30 5,58 0,00
300 No Discharge N/A 82,52 0,00 0,00
301 No Discharge N/A 82,49 0,00 0,00
302 Non-Sprinkler N/A 80,75 3,90 250,00
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 9
Fire Sprinkler Input Data
Pipe Input Data
Beg.Node
End.Node Pipe Description
NominalDiameter
(inch)
TypeGroup
FittingData
NominalLength
(feet)
FittingLength
(feet)
TotalLength
(feet)
CFactor(gpm/inch-
psi)
1 2 HDPE-CLASS 200 8,000 0 7,35 0,00 27,35 150
2 3 HDPE-CLASS 200 8,000 0 E 5,30 24,20 29,50 150
3 4 SCHED 40 WET STEEL 6,000 0 G 2,30 3,00 5,30 120
4 5 SCHED 40 WET STEEL 6,000 0 E 6,43 14,00 20,43 120
5 6 SCHED 40 WET STEEL 6,000 0 EBC 24,73 56,00 80,73 120
6 7 SCHED 40 WET STEEL 6,000 0 E 2,88 14,00 16,88 120
7 8 SCHED 40 WET STEEL 6,000 0 E 9,12 14,00 23,12 120
8 9 SCHED 40 WET STEEL 4,000 0 T 4,13 20,00 24,13 120
9 10 SCHED 40 WET STEEL 4,000 0 T 8,53 20,00 28,53 120
8 11 SCHED 40 WET STEEL 2,500 0 T 4,65 12,00 16,65 120
11 12 SCHED 40 WET STEEL 1,000 0 3E 4,10 6,00 10,10 120
11 13 SCHED 40 WET STEEL 2,500 0 T 12,83 12,00 24,83 120
13 14 SCHED 40 WET STEEL 2,500 0 E 7,63 6,00 13,63 120
14 15 SCHED 40 WET STEEL 1,000 0 3E 4,10 6,00 10,10 120
14 16 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
16 17 SCHED 40 WET STEEL 1,000 0 3E 4,10 6,00 10,10 120
16 18 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
18 19 SCHED 40 WET STEEL 1,000 0 3E 4,10 6,00 10,10 120
18 20 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
20 21 SCHED 40 WET STEEL 1,000 0 3E 4,10 6,00 10,10 120
20 22 SCHED 40 WET STEEL 2,500 0 T 7,98 12,00 19,98 120
22 23 SCHED 40 WET STEEL 2,500 0 2E 16,91 12,00 28,91 120
23 24 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
23 25 SCHED 40 WET STEEL 2,500 0 T 8,47 12,00 20,47 120
25 26 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
25 27 SCHED 40 WET STEEL 2,500 0 ET 17,65 18,00 35,65 120
27 28 SCHED 40 WET STEEL 2,500 0 E 7,98 6,00 13,98 120
28 29 SCHED 40 WET STEEL 1,000 0 3E 4,10 6,00 10,10 120
28 30 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 10
Fire Sprinkler Input Data
Pipe Input Data (cont'd)
Beg.Node
End.Node Pipe Description
NominalDiameter
(inch)
TypeGroup
FittingData
NominalLength
(feet)
FittingLength
(feet)
TotalLength
(feet)
CFactor(gpm/inch-
psi)
30 31 SCHED 40 WET STEEL 1,000 0 3E 4,10 6,00 10,10 120
30 32 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
32 33 SCHED 40 WET STEEL 1,000 0 3E 4,10 6,00 10,10 120
32 34 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
34 35 SCHED 40 WET STEEL 1,000 0 3E 4,10 6,00 10,10 120
34 36 SCHED 40 WET STEEL 2,500 0 T 7,63 12,00 19,63 120
36 37 SCHED 40 WET STEEL 2,500 0 E 13,57 6,00 19,57 120
37 38 SCHED 40 WET STEEL 1,000 0 3E 4,10 6,00 10,10 120
37 8 SCHED 40 WET STEEL 2,500 0 T 3,82 12,00 15,82 120
9 39 SCHED 40 WET STEEL 2,500 0 T 4,65 12,00 16,65 120
39 40 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
39 41 SCHED 40 WET STEEL 2,500 0 T 12,83 12,00 24,83 120
41 42 SCHED 40 WET STEEL 2,500 0 E 7,63 6,00 13,63 120
42 43 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
42 44 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
44 45 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
44 46 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
46 47 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
46 48 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
48 49 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
48 50 SCHED 40 WET STEEL 2,500 0 T 7,98 12,00 19,98 120
50 51 SCHED 40 WET STEEL 2,500 0 E 12,83 6,00 18,83 120
51 52 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
51 53 SCHED 40 WET STEEL 2,500 0 2ET 9,09 24,00 33,09 120
53 54 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
53 55 SCHED 40 WET STEEL 2,500 0 2ET 14,20 24,00 38,20 120
55 56 SCHED 40 WET STEEL 2,500 0 E 7,98 6,00 13,98 120
56 57 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
56 58 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 11
Fire Sprinkler Input Data
Pipe Input Data (cont'd)
Beg.Node
End.Node Pipe Description
NominalDiameter
(inch)
TypeGroup
FittingData
NominalLength
(feet)
FittingLength
(feet)
TotalLength
(feet)
CFactor(gpm/inch-
psi)
58 59 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
58 60 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
60 61 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
60 62 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
62 63 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
62 64 SCHED 40 WET STEEL 2,500 0 T 7,63 12,00 19,63 120
64 65 SCHED 40 WET STEEL 2,500 0 E 13,57 6,00 19,57 120
65 66 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
65 9 SCHED 40 WET STEEL 2,500 0 T 3,82 12,00 15,82 120
10 67 SCHED 40 WET STEEL 2,500 0 T 4,65 12,00 16,65 120
67 68 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
67 69 SCHED 40 WET STEEL 2,500 0 T 12,83 12,00 24,83 120
69 70 SCHED 40 WET STEEL 2,500 0 E 2,95 6,00 8,95 120
70 71 SCHED 40 WET STEEL 2,500 0 E 7,63 6,00 13,63 120
71 72 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
71 73 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
73 74 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
73 75 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
75 76 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
75 77 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
77 78 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
77 79 SCHED 40 WET STEEL 2,500 0 T 3,91 12,00 15,91 120
79 80 SCHED 40 WET STEEL 2,500 0 E 2,95 6,00 8,95 120
80 81 SCHED 40 WET STEEL 2,500 0 E 12,83 6,00 18,83 120
81 82 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
81 83 SCHED 40 WET STEEL 2,500 0 T 8,47 12,00 20,47 120
83 84 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
83 85 SCHED 40 WET STEEL 2,500 0 T 13,57 12,00 25,57 120
85 86 SCHED 40 WET STEEL 2,500 0 E 2,95 6,00 8,95 120
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 12
Fire Sprinkler Input Data
Pipe Input Data (cont'd)
Beg.Node
End.Node Pipe Description
NominalDiameter
(inch)
TypeGroup
FittingData
NominalLength
(feet)
FittingLength
(feet)
TotalLength
(feet)
CFactor(gpm/inch-
psi)
86 87 SCHED 40 WET STEEL 2,500 0 E 3,91 6,00 9,91 120
87 88 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
87 89 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
89 90 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
89 91 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
91 92 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
91 93 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
93 94 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
93 95 SCHED 40 WET STEEL 2,500 0 T 7,63 12,00 19,63 120
95 96 SCHED 40 WET STEEL 2,500 0 E 2,95 6,00 8,95 120
96 97 SCHED 40 WET STEEL 2,500 0 E 13,57 6,00 19,57 120
97 98 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
97 10 SCHED 40 WET STEEL 2,500 0 T 3,82 12,00 15,82 120
1 201 PVC, CLASS 200 10,000 0 T 11,88 75,50 87,38 150
201 202 HDPE-CLASS 200 10,000 0 E 4,17 32,20 36,37 150
202 203 HDPE-CLASS 200 10,000 0 E 4,79 32,20 36,99 150
203 204 HDPE-CLASS 200 10,000 0 E 4,17 32,20 36,37 150
204 205 HDPE-CLASS 200 10,000 0 FE 196,39 48,80 245,19 150
205 206 HDPE-CLASS 200 10,000 0 E 5,22 32,20 37,42 150
206 207 HDPE-CLASS 200 10,000 0 E 58,89 32,20 91,09 150
207 208 HDPE-CLASS 200 10,000 0 E 5,22 32,20 37,42 150
208 209 HDPE-CLASS 200 10,000 0 E 151,35 32,20 183,54 150
209 210 HDPE-CLASS 200 10,000 0 E 3,58 32,20 35,78 150
210 211 HDPE-CLASS 200 10,000 0 4F2E 124,28 130,80 255,08 150
211 212 SCHED 40 WET STEEL 10,000 0 E 9,15 22,00 31,15 120
212 213 SCHED 40 WET STEEL 10,000 0 2F3EGC 265,16 148,00 413,16 120
5 100 SCHED 40 WET STEEL 6,000 0 3,95 0,00 3,95 120
100 101 SCHED 40 WET STEEL 4,000 0 EBC 7,02 44,00 51,02 120
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 13
Fire Sprinkler Input Data
Pipe Input Data (cont'd)
Beg.Node
End.Node Pipe Description
NominalDiameter
(inch)
TypeGroup
FittingData
NominalLength
(feet)
FittingLength
(feet)
TotalLength
(feet)
CFactor(gpm/inch-
psi)101 102 SCHED 40 WET STEEL 4,000 0 E 5,59 10,00 15,59 120
102 103 SCHED 40 WET STEEL 4,000 0 E 8,01 10,00 18,01 120
103 104 SCHED 40 WET STEEL 4,000 0 E 5,71 10,00 15,71 120
104 105 SCHED 40 WET STEEL 4,000 0 E 6,97 10,00 16,97 120
105 106 SCHED 40 WET STEEL 4,000 0 E 2,34 10,00 12,34 120
106 107 SCHED 40 WET STEEL 4,000 0 E 4,67 10,00 14,66 120
107 108 SCHED 40 WET STEEL 4,000 0 T 7,71 20,00 27,71 120
107 109 SCHED 40 WET STEEL 2,500 0 T 1,68 12,00 13,68 120
107 111 SCHED 40 WET STEEL 2,500 0 T 5,21 12,00 17,21 120
109 110 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
109 127 SCHED 40 WET STEEL 2,500 0 T 7,77 12,00 19,77 120
111 112 SCHED 40 WET STEEL 2,500 0 E 6,60 6,00 12,60 120
112 113 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
112 114 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
114 115 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
114 116 SCHED 40 WET STEEL 2,500 0 T 5,80 12,00 17,80 120
116 117 SCHED 40 WET STEEL 2,500 0 E 6,90 6,00 12,90 120
117 118 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
117 119 SCHED 40 WET STEEL 2,500 0 T 7,77 12,00 19,77 120
119 120 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
119 121 SCHED 40 WET STEEL 2,500 0 T 7,70 12,00 19,70 120
121 122 SCHED 40 WET STEEL 2,500 0 E 5,80 6,00 11,80 120
122 123 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
122 124 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
124 125 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
124 126 SCHED 40 WET STEEL 2,500 0 T 6,60 12,00 18,60 120
126 127 SCHED 40 WET STEEL 2,500 0 E 7,70 6,00 13,70 120
127 128 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
108 129 SCHED 40 WET STEEL 2,500 0 T 1,68 12,00 13,68 120
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 14
Fire Sprinkler Input Data
Pipe Input Data (cont'd)
Beg.Node
End.Node Pipe Description
NominalDiameter
(inch)
TypeGroup
FittingData
NominalLength
(feet)
FittingLength
(feet)
TotalLength
(feet)
CFactor(gpm/inch-
psi)129 130 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
131 132 SCHED 40 WET STEEL 2,500 0 E 6,60 6,00 12,60 120
132 133 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
132 134 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
134 135 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
134 136 SCHED 40 WET STEEL 2,500 0 T 5,80 12,00 17,80 120
136 137 SCHED 40 WET STEEL 2,500 0 E 6,90 6,00 12,90 120
137 138 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
137 139 SCHED 40 WET STEEL 2,500 0 T 7,77 12,00 19,77 120
139 140 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
139 141 SCHED 40 WET STEEL 2,500 0 3ET 13,17 30,00 43,17 120
141 142 SCHED 40 WET STEEL 2,500 0 E 5,80 6,00 11,80 120
142 143 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
142 144 SCHED 40 WET STEEL 2,500 0 T 8,53 12,00 20,53 120
144 145 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
144 146 SCHED 40 WET STEEL 2,500 0 T 6,60 12,00 18,60 120
146 147 SCHED 40 WET STEEL 2,500 0 E 7,70 6,00 13,70 120
147 148 SCHED 40 WET STEEL 1,000 0 2E 0,98 4,00 4,98 120
108 131 SCHED 40 WET STEEL 2,500 0 T 5,21 12,00 17,21 120
129 147 SCHED 40 WET STEEL 2,500 0 T 7,77 12,00 19,77 120
1 300 HDPE-CLASS 200 10,000 0 2E 25,82 64,40 90,22 150
300 301 HDPE-CLASS 200 8,000 0 EG 18,70 30,20 48,90 150
301 302 SCHED 40 WET STEEL 6,000 0 E 3,94 14,00 17,94 120
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 15
Fire Sprinkler Output Data
Overall Node Groupings Output Data
Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node ImbalanceBeg.
NodeEnd.
NodeType
GroupFlow Rate
(gpm)At Beg. Node
(gpm)Out (+)(gpm)
In (-)(gpm)
ResidualPressure (psi)
Flow At Beg.Node (gpm)
1 2 0 1246,56 0,00 0,00 0,00 82,53 0,000001 201 0 -1496,561 300 0 250,00
2 1 0 -1246,56 0,00 0,00 0,00 82,25 0,000002 3 0 1246,56
3 2 0 -1246,56 0,00 0,00 0,00 79,65 0,000003 4 0 1246,56
4 3 0 -1246,56 0,00 0,00 0,00 78,38 -0,000014 5 0 1246,56
5 4 0 -1246,56 0,00 0,00 0,00 77,30 0,000005 6 0 856,785 100 0 389,78
6 5 0 -856,78 0,00 0,00 0,00 64,45 0,000016 7 0 856,78
7 6 0 -856,78 0,00 0,00 0,00 64,01 0,000007 8 0 856,78
8 7 0 -856,78 0,00 0,00 0,00 67,34 0,000018 9 0 575,158 11 0 140,698 37 0 140,93
9 8 0 -575,15 0,00 0,00 0,00 66,89 -0,000019 10 0 291,139 39 0 142,079 65 0 141,95
10 9 0 -291,13 0,00 0,00 0,00 69,83 -0,0000410 67 0 145,4510 97 0 145,68
11 8 0 -140,69 0,00 0,00 0,00 66,11 -0,0000211 12 0 23,9311 13 0 116,76
12 11 0 -23,93 23,93 0,00 0,00 63,63 0,00009
13 11 0 -116,76 0,00 0,00 0,00 64,80 0,0000013 14 0 116,76
14 13 0 -116,76 0,00 0,00 0,00 64,08 -0,0000114 15 0 23,5614 16 0 93,21
15 14 0 -23,56 23,56 0,00 0,00 61,66 0,00007
16 14 0 -93,21 0,00 0,00 0,00 63,37 0,0000016 17 0 23,4216 18 0 69,78
17 16 0 -23,42 23,42 0,00 0,00 60,96 0,00007
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 16
Fire Sprinkler Output Data
Overall Node Groupings Output Data (cont'd)
Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node ImbalanceBeg.
NodeEnd.
NodeType
GroupFlow Rate
(gpm)At Beg. Node
(gpm)Out (+)(gpm)
In (-)(gpm)
ResidualPressure (psi)
Flow At Beg.Node (gpm)
18 16 0 -69,78 0,00 0,00 0,00 62,95 0,0000018 19 0 23,3518 20 0 46,44
19 18 0 -23,35 23,35 0,00 0,00 60,56 0,00007
20 18 0 -46,44 0,00 0,00 0,00 62,75 0,0000020 21 0 23,3120 22 0 23,13
21 20 0 -23,31 23,31 0,00 0,00 60,37 0,00006
22 20 0 -23,13 0,00 0,00 0,00 62,70 0,0000022 23 0 23,13
23 22 0 -23,13 0,00 0,00 0,00 60,86 -0,0003623 24 0 23,2423 25 0 -0,11
24 23 0 -23,24 23,24 0,00 0,00 60,00 0,00034
25 23 0 0,11 0,00 0,00 0,00 60,86 -0,0003425 26 0 23,2425 27 0 -23,35
26 25 0 -23,24 23,24 0,00 0,00 60,00 0,00041
27 25 0 23,35 0,00 0,00 0,00 62,72 0,0000027 28 0 -23,35
28 27 0 23,35 0,00 0,00 0,00 62,76 0,0000028 29 0 23,3128 30 0 -46,66
29 28 0 -23,31 23,31 0,00 0,00 60,37 0,00006
30 28 0 46,66 0,00 0,00 0,00 62,95 0,0000030 31 0 23,3530 32 0 -70,00
31 30 0 -23,35 23,35 0,00 0,00 60,56 0,00007
32 30 0 70,00 0,00 0,00 0,00 63,37 0,0000032 33 0 23,4332 34 0 -93,43
33 32 0 -23,43 23,43 0,00 0,00 60,97 0,00007
34 32 0 93,43 0,00 0,00 0,00 64,09 -0,0000134 35 0 23,5634 36 0 -116,99
35 34 0 -23,56 23,56 0,00 0,00 61,67 0,00007
36 34 0 116,99 0,00 0,00 0,00 65,13 0,0000036 37 0 -116,99
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 17
Fire Sprinkler Output Data
Overall Node Groupings Output Data (cont'd)
Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node ImbalanceBeg.
NodeEnd.
NodeType
GroupFlow Rate
(gpm)At Beg. Node
(gpm)Out (+)(gpm)
In (-)(gpm)
ResidualPressure (psi)
Flow At Beg.Node (gpm)
37 8 0 -140,93 0,00 0,00 0,00 66,16 0,0000037 36 0 116,9937 38 0 23,94
38 37 0 -23,94 23,94 0,00 0,00 63,69 0,00008
39 9 0 -142,07 0,00 0,00 0,00 65,62 -0,0000139 40 0 24,1339 41 0 117,94
40 39 0 -24,13 24,13 0,00 0,00 64,71 0,00008
41 39 0 -117,94 0,00 0,00 0,00 64,29 0,0000041 42 0 117,94
42 41 0 -117,94 0,00 0,00 0,00 63,56 0,0000042 43 0 23,7542 44 0 94,19
43 42 0 -23,75 23,75 0,00 0,00 62,67 0,00006
44 42 0 -94,19 0,00 0,00 0,00 62,83 0,0000144 45 0 23,6144 46 0 70,58
45 44 0 -23,61 23,61 0,00 0,00 61,95 0,00005
46 44 0 -70,58 0,00 0,00 0,00 62,41 0,0000646 47 0 23,5346 48 0 47,05
47 46 0 -23,53 23,53 0,00 0,00 61,53 0,00005
48 46 0 -47,05 0,00 0,00 0,00 62,20 -0,0000548 49 0 23,4948 50 0 23,56
49 48 0 -23,49 23,49 0,00 0,00 61,33 0,00006
50 48 0 -23,56 0,00 0,00 0,00 62,15 0,0000050 51 0 23,56
51 50 0 -23,56 0,00 0,00 0,00 62,10 0,0000051 52 0 23,4751 53 0 0,08
52 51 0 -23,47 23,47 0,00 0,00 61,23 0,00005
53 51 0 -0,08 0,00 0,00 0,00 62,10 0,0000053 54 0 23,4753 55 0 -23,39
54 53 0 -23,47 23,47 0,00 0,00 61,23 0,00005
55 53 0 23,39 0,00 0,00 0,00 62,20 0,0000055 56 0 -23,39
56 55 0 23,39 0,00 0,00 0,00 62,24 -0,00005
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 18
Fire Sprinkler Output Data
Overall Node Groupings Output Data (cont'd)
Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node ImbalanceBeg.
NodeEnd.
NodeType
GroupFlow Rate
(gpm)At Beg. Node
(gpm)Out (+)(gpm)
In (-)(gpm)
ResidualPressure (psi)
Flow At Beg.Node (gpm)
56 57 0 23,5056 58 0 -46,89
57 56 0 -23,50 23,50 0,00 0,00 61,36 0,00006
58 56 0 46,89 0,00 0,00 0,00 62,44 0,0000658 59 0 23,5458 60 0 -70,43
59 58 0 -23,54 23,54 0,00 0,00 61,56 0,00005
60 58 0 70,43 0,00 0,00 0,00 62,86 0,0000160 61 0 23,6260 62 0 -94,05
61 60 0 -23,62 23,62 0,00 0,00 61,98 0,00005
62 60 0 94,05 0,00 0,00 0,00 63,59 0,0000062 63 0 23,7562 64 0 -117,80
63 62 0 -23,75 23,75 0,00 0,00 62,70 0,00006
64 62 0 117,80 0,00 0,00 0,00 64,64 0,0000064 65 0 -117,80
65 9 0 -141,95 0,00 0,00 0,00 65,69 0,0000165 64 0 117,8065 66 0 24,14
66 65 0 -24,14 24,14 0,00 0,00 64,77 0,00008
67 10 0 -145,45 0,00 0,00 0,00 68,51 0,0000067 68 0 24,6667 69 0 120,79
68 67 0 -24,66 24,66 0,00 0,00 67,55 0,00007
69 67 0 -120,79 0,00 0,00 0,00 67,11 0,0000069 70 0 120,79
70 69 0 -120,79 0,00 0,00 0,00 67,89 0,0000470 71 0 120,79
71 70 0 -120,79 0,00 0,00 0,00 67,13 -0,0000471 72 0 24,4171 73 0 96,39
72 71 0 -24,41 24,41 0,00 0,00 66,19 0,00006
73 71 0 -96,39 0,00 0,00 0,00 66,37 0,0000073 74 0 24,2773 75 0 72,12
74 73 0 -24,27 24,27 0,00 0,00 65,44 0,00005
75 73 0 -72,12 0,00 0,00 0,00 65,92 0,0000075 76 0 24,19
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 19
Fire Sprinkler Output Data
Overall Node Groupings Output Data (cont'd)
Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node ImbalanceBeg.
NodeEnd.
NodeType
GroupFlow Rate
(gpm)At Beg. Node
(gpm)Out (+)(gpm)
In (-)(gpm)
ResidualPressure (psi)
Flow At Beg.Node (gpm)
75 77 0 47,93
76 75 0 -24,19 24,19 0,00 0,00 65,00 0,00005
77 75 0 -47,93 0,00 0,00 0,00 65,71 0,0000077 78 0 24,1577 79 0 23,78
78 77 0 -24,15 24,15 0,00 0,00 64,79 0,00005
79 77 0 -23,78 0,00 0,00 0,00 65,67 0,0000079 80 0 23,78
80 79 0 -23,78 0,00 0,00 0,00 64,37 0,0000080 81 0 23,78
81 80 0 -23,78 0,00 0,00 0,00 64,31 0,0000081 82 0 23,8981 83 0 -0,11
82 81 0 -23,89 23,89 0,00 0,00 63,41 0,00005
83 81 0 0,11 0,00 0,00 0,00 64,31 0,0000083 84 0 23,8983 85 0 -24,00
84 83 0 -23,89 23,89 0,00 0,00 63,41 0,00005
85 83 0 24,00 0,00 0,00 0,00 64,39 0,0000085 86 0 -24,00
86 85 0 24,00 0,00 0,00 0,00 65,69 0,0000086 87 0 -24,00
87 86 0 24,00 0,00 0,00 0,00 65,72 0,0000087 88 0 24,1587 89 0 -48,14
88 87 0 -24,15 24,15 0,00 0,00 64,80 0,00005
89 87 0 48,14 0,00 0,00 0,00 65,93 0,0000089 90 0 24,1989 91 0 -72,33
90 89 0 -24,19 24,19 0,00 0,00 65,01 0,00005
91 89 0 72,33 0,00 0,00 0,00 66,37 0,0000091 92 0 24,2791 93 0 -96,60
92 91 0 -24,27 24,27 0,00 0,00 65,45 0,00005
93 91 0 96,60 0,00 0,00 0,00 67,14 -0,0000393 94 0 24,4193 95 0 -121,01
94 93 0 -24,41 24,41 0,00 0,00 66,20 0,00006
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 20
Fire Sprinkler Output Data
Overall Node Groupings Output Data (cont'd)
Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node ImbalanceBeg.
NodeEnd.
NodeType
GroupFlow Rate
(gpm)At Beg. Node
(gpm)Out (+)(gpm)
In (-)(gpm)
ResidualPressure (psi)
Flow At Beg.Node (gpm)
95 93 0 121,01 0,00 0,00 0,00 68,24 0,0000395 96 0 -121,01
96 95 0 121,01 0,00 0,00 0,00 67,47 0,0000096 97 0 -121,01
97 10 0 -145,68 0,00 0,00 0,00 68,57 0,0000097 96 0 121,0197 98 0 24,67
98 97 0 -24,67 24,67 0,00 0,00 67,61 0,00007
100 5 0 -389,78 0,00 0,00 0,00 77,27 -0,00002100 101 0 389,78
101 100 0 -389,78 0,00 0,00 0,00 71,92 0,00000101 102 0 389,78
102 101 0 -389,78 0,00 0,00 0,00 71,21 0,00000102 103 0 389,78
103 102 0 -389,78 0,00 0,00 0,00 70,40 0,00000103 104 0 389,78
104 103 0 -389,78 0,00 0,00 0,00 69,68 0,00000104 105 0 389,78
105 104 0 -389,78 0,00 0,00 0,00 65,90 0,00000105 106 0 389,78
106 105 0 -389,78 0,00 0,00 0,00 65,34 -0,00001106 107 0 389,78
107 106 0 -389,78 0,00 0,00 0,00 66,70 -0,00003107 108 0 197,03107 109 0 103,19107 111 0 89,57
108 107 0 -197,03 0,00 0,00 0,00 69,68 0,00000108 129 0 105,40108 131 0 91,63
109 107 0 -103,19 0,00 0,00 0,00 66,12 0,00000109 110 0 24,22109 127 0 78,96
110 109 0 -24,22 24,22 0,00 0,00 65,20 0,00007
111 107 0 -89,57 0,00 0,00 0,00 66,14 0,00000111 112 0 89,57
112 111 0 -89,57 0,00 0,00 0,00 65,73 0,00000112 113 0 24,15112 114 0 65,42
113 112 0 -24,15 24,15 0,00 0,00 64,81 0,00007
114 112 0 -65,42 0,00 0,00 0,00 65,36 0,00000
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 21
Fire Sprinkler Output Data
Overall Node Groupings Output Data (cont'd)
Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node ImbalanceBeg.
NodeEnd.
NodeType
GroupFlow Rate
(gpm)At Beg. Node
(gpm)Out (+)(gpm)
In (-)(gpm)
ResidualPressure (psi)
Flow At Beg.Node (gpm)
114 115 0 24,08114 116 0 41,33
115 114 0 -24,08 24,08 0,00 0,00 64,45 0,00006
116 114 0 -41,33 0,00 0,00 0,00 65,23 0,00000116 117 0 41,33
117 116 0 -41,33 0,00 0,00 0,00 65,13 0,00000117 118 0 24,04117 119 0 17,29
118 117 0 -24,04 24,04 0,00 0,00 64,21 0,00006
119 117 0 -17,29 0,00 0,00 0,00 65,10 0,00000119 120 0 24,03119 121 0 -6,74
120 119 0 -24,03 24,03 0,00 0,00 64,18 0,00006
121 119 0 6,74 0,00 0,00 0,00 65,10 0,00000121 122 0 -6,74
122 121 0 6,74 0,00 0,00 0,00 65,10 0,00000122 123 0 24,04122 124 0 -30,78
123 122 0 -24,04 24,04 0,00 0,00 64,19 0,00006
124 122 0 30,78 0,00 0,00 0,00 65,20 0,00000124 125 0 24,05124 126 0 -54,83
125 124 0 -24,05 24,05 0,00 0,00 64,28 0,00006
126 124 0 54,83 0,00 0,00 0,00 65,44 0,00000126 127 0 -54,83
127 109 0 -78,96 0,00 0,00 0,00 65,62 0,00000127 126 0 54,83127 128 0 24,13
128 127 0 -24,13 24,13 0,00 0,00 64,70 0,00007
129 108 0 -105,40 0,00 0,00 0,00 69,08 0,00000129 130 0 24,76129 147 0 80,64
130 129 0 -24,76 24,76 0,00 0,00 68,12 0,00007
131 108 0 -91,63 0,00 0,00 0,00 69,10 0,00000131 132 0 91,63
132 131 0 -91,63 0,00 0,00 0,00 68,68 0,00000132 133 0 24,69132 134 0 66,94
133 132 0 -24,69 24,69 0,00 0,00 67,72 0,00006
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 22
Fire Sprinkler Output Data
Overall Node Groupings Output Data (cont'd)
Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node ImbalanceBeg.
NodeEnd.
NodeType
GroupFlow Rate
(gpm)At Beg. Node
(gpm)Out (+)(gpm)
In (-)(gpm)
ResidualPressure (psi)
Flow At Beg.Node (gpm)
134 132 0 -66,94 0,00 0,00 0,00 68,29 0,00000134 135 0 24,62134 136 0 42,32
135 134 0 -24,62 24,62 0,00 0,00 67,34 0,00006
136 134 0 -42,32 0,00 0,00 0,00 68,15 0,00000136 137 0 42,32
137 136 0 -42,32 0,00 0,00 0,00 68,04 0,00000137 138 0 24,57137 139 0 17,75
138 137 0 -24,57 24,57 0,00 0,00 67,09 0,00006
139 137 0 -17,75 0,00 0,00 0,00 68,01 0,00000139 140 0 24,57139 141 0 -6,82
140 139 0 -24,57 24,57 0,00 0,00 67,06 0,00006
141 139 0 6,82 0,00 0,00 0,00 68,02 0,00000141 142 0 -6,82
142 141 0 6,82 0,00 0,00 0,00 68,03 0,00000142 143 0 24,57142 144 0 -31,39
143 142 0 -24,57 24,57 0,00 0,00 67,08 0,00006
144 142 0 31,39 0,00 0,00 0,00 68,12 0,00000144 145 0 24,59144 146 0 -55,98
145 144 0 -24,59 24,59 0,00 0,00 67,17 0,00006
146 144 0 55,98 0,00 0,00 0,00 68,37 0,00000146 147 0 -55,98
147 129 0 -80,64 0,00 0,00 0,00 68,56 0,00000147 146 0 55,98147 148 0 24,67
148 147 0 -24,67 24,67 0,00 0,00 67,60 0,00006
201 1 0 1496,56 0,00 0,00 0,00 82,96 -0,00001201 202 0 -1496,56
202 201 0 1496,56 0,00 0,00 0,00 84,94 0,00000202 203 0 -1496,56
203 202 0 1496,56 0,00 0,00 0,00 85,13 0,00000203 204 0 -1496,56
204 203 0 1496,56 0,00 0,00 0,00 83,50 0,00003204 205 0 -1496,56
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 23
Fire Sprinkler Output Data
Overall Node Groupings Output Data (cont'd)
Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node ImbalanceBeg.
NodeEnd.
NodeType
GroupFlow Rate
(gpm)At Beg. Node
(gpm)Out (+)(gpm)
In (-)(gpm)
ResidualPressure (psi)
Flow At Beg.Node (gpm)
205 204 0 1496,56 0,00 0,00 0,00 84,71 -0,00003205 206 0 -1496,56
206 205 0 1496,56 0,00 0,00 0,00 87,15 0,00001206 207 0 -1496,56
207 206 0 1496,56 0,00 0,00 0,00 87,60 -0,00001207 208 0 -1496,56
208 207 0 1496,56 0,00 0,00 0,00 85,52 0,00002208 209 0 -1496,56
209 208 0 1496,56 0,00 0,00 0,00 86,43 -0,00002209 210 0 -1496,56
210 209 0 1496,56 0,00 0,00 0,00 88,15 0,00003210 211 0 -1496,56
211 210 0 1496,56 0,00 0,00 0,00 89,41 -0,00003211 212 0 -1496,56
212 211 0 1496,56 0,00 0,00 0,00 85,64 0,00004212 213 0 -1496,56
213 212 0 1496,56 0,00 0,00 -1496,56 88,30
300 1 0 -250,00 0,00 0,00 0,00 82,52 0,00000300 301 0 250,00
301 300 0 -250,00 0,00 0,00 0,00 82,49 0,00000301 302 0 250,00
302 301 0 -250,00 0,00 250,00 0,00 80,75 0,00009
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 24
Fire Sprinkler Output Data
Overall Pipe Output Data
Beg.End.
Node
NodalKFactor
(K)
Elevation(feet)
Spk/HoseDischarge
(gpm)
ResidualPressure
(psi)
Nom. Dia.Inside Dia.
C-Value
Q (gpm)Velocity
(fps)
F. L./ft(psi/ft)
FittingsType-Grp
Pipe-Len.Fit-Len.
Tot-Len.(ft)
PF-(psi)PE-(psi)PV-(psi)
1 0,00 0,00 0,00 82,53 8,00 1246,56 0,01026 27,35 0,2812 0,00 0,00 0,00 82,25 7,805 8,36 ----- 0,00 0,000
HDPE-CLASS 200 150 0 27,35 0,470
1 0,00 0,00 0,00 82,53 10,00 250,00 0,00018 25,82 0,016300 0,00 0,00 0,00 82,52 9,728 1,08 2E 64,40 0,000 HDPE-CLASS 200 150 0 90,22 0,008
2 0,00 0,00 0,00 82,25 8,00 1246,56 0,01026 5,30 0,3033 0,00 5,30 0,00 79,65 7,805 8,36 E 24,20 2,294
HDPE-CLASS 200 150 0 29,50 0,470
3 0,00 5,30 0,00 79,65 6,00 1246,56 0,05294 2,30 0,2804 0,00 7,60 0,00 78,38 6,065 13,84 G 3,00 0,994
SCHED 40 WET STEEL 120 0 5,30 1,290
4 0,00 7,60 0,00 78,38 6,00 1246,56 0,05294 6,43 1,0825 0,00 7,60 0,00 77,30 6,065 13,84 E 14,00 0,000
SCHED 40 WET STEEL 120 0 20,43 1,290
5 0,00 7,60 0,00 77,30 6,00 856,78 0,02645 24,73 2,1366 0,00 32,33 0,00 64,45 6,065 9,51 EBC 56,00 10,709
SCHED 40 WET STEEL 120 0 80,73 0,609
5 0,00 7,60 0,00 77,30 6,00 389,78 0,00616 3,95 0,024100 0,00 7,60 0,00 77,27 6,065 4,33 ----- 0,00 0,000
SCHED 40 WET STEEL 120 0 3,95 0,126
6 0,00 32,33 0,00 64,45 6,00 856,78 0,02645 2,88 0,4477 0,00 32,33 0,00 64,01 6,065 9,51 E 14,00 0,000
SCHED 40 WET STEEL 120 0 16,88 0,609
7 0,00 32,33 0,00 64,01 6,00 856,78 0,02645 9,12 0,6128 0,00 23,21 0,00 67,34 6,065 9,51 E 14,00 -3,949
SCHED 40 WET STEEL 120 0 23,12 0,609
8 0,00 23,21 0,00 67,34 4,00 575,15 0,09309 4,13 2,2469 0,00 19,08 0,00 66,89 4,026 14,50 T 20,00 -1,787
SCHED 40 WET STEEL 120 0 24,13 1,414
8 0,00 23,21 0,00 67,34 2,50 140,69 0,07442 4,65 1,23911 0,00 23,21 0,00 66,11 2,469 9,43 T 12,00 0,000
SCHED 40 WET STEEL 120 0 16,65 0,598
37 0,00 23,21 0,00 66,16 2,50 140,93 0,07465 3,82 1,1818 0,00 23,21 0,00 67,34 2,469 9,44 T 12,00 0,000
SCHED 40 WET STEEL 120 0 15,82 0,600
9 0,00 19,08 0,00 66,89 4,00 291,13 0,02641 8,53 0,75410 0,00 10,55 0,00 69,83 4,026 7,34 T 20,00 -3,694
SCHED 40 WET STEEL 120 0 28,53 0,362
9 0,00 19,08 0,00 66,89 2,50 142,07 0,07578 4,65 1,26239 0,00 19,08 0,00 65,62 2,469 9,52 T 12,00 0,000
SCHED 40 WET STEEL 120 0 16,65 0,610
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 25
Fire Sprinkler Output Data
Overall Pipe Output Data (cont'd)
Beg.End.
Node
NodalKFactor
(K)
Elevation(feet)
Spk/HoseDischarge
(gpm)
ResidualPressure
(psi)
Nom. Dia.Inside Dia.
C-Value
Q (gpm)Velocity
(fps)
F. L./ft(psi/ft)
FittingsType-Grp
Pipe-Len.Fit-Len.
Tot-Len.(ft)
PF-(psi)PE-(psi)PV-(psi)
65 0,00 19,08 0,00 65,69 2,50 141,95 0,07565 3,82 1,1979 0,00 19,08 0,00 66,89 2,469 9,51 T 12,00 0,000
SCHED 40 WET STEEL 120 0 15,82 0,609
10 0,00 10,55 0,00 69,83 2,50 145,45 0,07914 4,65 1,31867 0,00 10,55 0,00 68,51 2,469 9,75 T 12,00 0,000
SCHED 40 WET STEEL 120 0 16,65 0,639
97 0,00 10,55 0,00 68,57 2,50 145,68 0,07937 3,82 1,25610 0,00 10,55 0,00 69,83 2,469 9,76 T 12,00 0,000
SCHED 40 WET STEEL 120 0 15,82 0,641
11 0,00 23,21 0,00 66,11 1,00 23,93 0,18145 4,10 1,83312 3,00 24,68 23,93 63,63 1,049 8,88 3E 6,00 0,639
SCHED 40 WET STEEL 120 0 10,10 0,531
11 0,00 23,21 0,00 66,11 2,50 116,76 0,05271 12,84 1,30913 0,00 23,21 0,00 64,80 2,469 7,82 T 12,00 0,000
SCHED 40 WET STEEL 120 0 24,83 0,412
13 0,00 23,21 0,00 64,80 2,50 116,76 0,05271 7,63 0,71814 0,00 23,21 0,00 64,08 2,469 7,82 E 6,00 0,000
SCHED 40 WET STEEL 120 0 13,63 0,412
14 0,00 23,21 0,00 64,08 1,00 23,56 0,17623 4,10 1,78015 3,00 24,68 23,56 61,66 1,049 8,74 3E 6,00 0,639
SCHED 40 WET STEEL 120 0 10,10 0,515
14 0,00 23,21 0,00 64,08 2,50 93,21 0,03474 8,53 0,71316 0,00 23,21 0,00 63,37 2,469 6,25 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,263
16 0,00 23,21 0,00 63,37 1,00 23,42 0,17439 4,10 1,76217 3,00 24,68 23,42 60,96 1,049 8,70 3E 6,00 0,639
SCHED 40 WET STEEL 120 0 10,10 0,509
16 0,00 23,21 0,00 63,37 2,50 69,78 0,02034 8,53 0,41718 0,00 23,21 0,00 62,95 2,469 4,68 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,147
18 0,00 23,21 0,00 62,95 1,00 23,35 0,17332 4,10 1,75119 3,00 24,68 23,35 60,56 1,049 8,67 3E 6,00 0,639
SCHED 40 WET STEEL 120 0 10,10 0,505
18 0,00 23,21 0,00 62,95 2,50 46,44 0,00957 8,53 0,19720 0,00 23,21 0,00 62,75 2,469 3,11 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,065
20 0,00 23,21 0,00 62,75 1,00 23,31 0,17281 4,10 1,74621 3,00 24,68 23,31 60,37 1,049 8,65 3E 6,00 0,639
SCHED 40 WET STEEL 120 0 10,10 0,504
20 0,00 23,21 0,00 62,75 2,50 23,13 0,00264 7,98 0,05322 0,00 23,21 0,00 62,70 2,469 1,55 T 12,00 0,000
SCHED 40 WET STEEL 120 0 19,98 0,016
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 26
Fire Sprinkler Output Data
Overall Pipe Output Data (cont'd)
Beg.End.
Node
NodalKFactor
(K)
Elevation(feet)
Spk/HoseDischarge
(gpm)
ResidualPressure
(psi)
Nom. Dia.Inside Dia.
C-Value
Q (gpm)Velocity
(fps)
F. L./ft(psi/ft)
FittingsType-Grp
Pipe-Len.Fit-Len.
Tot-Len.(ft)
PF-(psi)PE-(psi)PV-(psi)
22 0,00 23,21 0,00 62,70 2,50 23,13 0,00264 16,91 0,07623 0,00 27,28 0,00 60,86 2,469 1,55 2E 12,00 1,766
SCHED 40 WET STEEL 120 0 28,91 0,016
23 0,00 27,28 0,00 60,86 1,00 23,24 0,17184 0,98 0,85624 3,00 27,28 23,24 60,00 1,049 8,63 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,501
23 0,00 27,28 0,00 60,86 2,50 0,11 0,00000 8,47 0,00025 0,00 27,28 0,00 60,86 2,469 0,01 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,47 0,000
25 0,00 27,28 0,00 60,86 1,00 23,24 0,17184 0,98 0,85626 3,00 27,28 23,24 60,00 1,049 8,63 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,501
25 0,00 27,28 0,00 60,86 2,50 23,35 0,00268 17,65 0,09627 0,00 23,21 0,00 62,72 2,469 1,56 ET 18,00 1,766
SCHED 40 WET STEEL 120 0 35,65 0,016
27 0,00 23,21 0,00 62,72 2,50 23,35 0,00268 7,98 0,03828 0,00 23,21 0,00 62,76 2,469 1,56 E 6,00 0,000
SCHED 40 WET STEEL 120 0 13,98 0,016
28 0,00 23,21 0,00 62,76 1,00 23,31 0,17282 4,10 1,74629 3,00 24,68 23,31 60,37 1,049 8,65 3E 6,00 0,639
SCHED 40 WET STEEL 120 0 10,10 0,504
28 0,00 23,21 0,00 62,76 2,50 46,66 0,00966 8,53 0,19830 0,00 23,21 0,00 62,95 2,469 3,13 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,066
30 0,00 23,21 0,00 62,95 1,00 23,35 0,17333 4,10 1,75131 3,00 24,68 23,35 60,56 1,049 8,67 3E 6,00 0,639
SCHED 40 WET STEEL 120 0 10,10 0,506
30 0,00 23,21 0,00 62,95 2,50 70,00 0,02046 8,53 0,42032 0,00 23,21 0,00 63,37 2,469 4,69 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,148
32 0,00 23,21 0,00 63,37 1,00 23,43 0,17442 4,10 1,76233 3,00 24,68 23,43 60,97 1,049 8,70 3E 6,00 0,639
SCHED 40 WET STEEL 120 0 10,10 0,509
32 0,00 23,21 0,00 63,37 2,50 93,43 0,03489 8,53 0,71634 0,00 23,21 0,00 64,09 2,469 6,26 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,264
34 0,00 23,21 0,00 64,09 1,00 23,56 0,17626 4,10 1,78035 3,00 24,68 23,56 61,67 1,049 8,75 3E 6,00 0,639
SCHED 40 WET STEEL 120 0 10,10 0,515
34 0,00 23,21 0,00 64,09 2,50 116,99 0,05290 7,63 1,03836 0,00 23,21 0,00 65,13 2,469 7,84 T 12,00 0,000
SCHED 40 WET STEEL 120 0 19,63 0,414
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 27
Fire Sprinkler Output Data
Overall Pipe Output Data (cont'd)
Beg.End.
Node
NodalKFactor
(K)
Elevation(feet)
Spk/HoseDischarge
(gpm)
ResidualPressure
(psi)
Nom. Dia.Inside Dia.
C-Value
Q (gpm)Velocity
(fps)
F. L./ft(psi/ft)
FittingsType-Grp
Pipe-Len.Fit-Len.
Tot-Len.(ft)
PF-(psi)PE-(psi)PV-(psi)
36 0,00 23,21 0,00 65,13 2,50 116,99 0,05290 13,57 1,03537 0,00 23,21 0,00 66,16 2,469 7,84 E 6,00 0,000
SCHED 40 WET STEEL 120 0 19,57 0,414
37 0,00 23,21 0,00 66,16 1,00 23,94 0,18160 4,10 1,83438 3,00 24,68 23,94 63,69 1,049 8,89 3E 6,00 0,639
SCHED 40 WET STEEL 120 0 10,10 0,532
39 0,00 19,08 0,00 65,62 1,00 24,13 0,18427 0,98 0,91840 3,00 19,08 24,13 64,71 1,049 8,96 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,540
39 0,00 19,08 0,00 65,62 2,50 117,94 0,05370 12,84 1,33441 0,00 19,08 0,00 64,29 2,469 7,90 T 12,00 0,000
SCHED 40 WET STEEL 120 0 24,83 0,420
41 0,00 19,08 0,00 64,29 2,50 117,94 0,05370 7,63 0,73242 0,00 19,08 0,00 63,56 2,469 7,90 E 6,00 0,000
SCHED 40 WET STEEL 120 0 13,63 0,420
42 0,00 19,08 0,00 63,56 1,00 23,75 0,17890 0,98 0,89243 3,00 19,08 23,75 62,67 1,049 8,82 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,523
42 0,00 19,08 0,00 63,56 2,50 94,19 0,03542 8,53 0,72744 0,00 19,08 0,00 62,83 2,469 6,31 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,268
44 0,00 19,08 0,00 62,83 1,00 23,61 0,17700 0,98 0,88245 3,00 19,08 23,61 61,95 1,049 8,77 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,517
44 0,00 19,08 0,00 62,83 2,50 70,58 0,02077 8,53 0,42646 0,00 19,08 0,00 62,41 2,469 4,73 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,151
46 0,00 19,08 0,00 62,41 1,00 23,53 0,17589 0,98 0,87747 3,00 19,08 23,53 61,53 1,049 8,74 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,514
46 0,00 19,08 0,00 62,41 2,50 47,05 0,00981 8,53 0,20148 0,00 19,08 0,00 62,20 2,469 3,15 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,067
48 0,00 19,08 0,00 62,20 1,00 23,49 0,17536 0,98 0,87449 3,00 19,08 23,49 61,33 1,049 8,72 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,512
48 0,00 19,08 0,00 62,20 2,50 23,56 0,00273 7,98 0,05450 0,00 19,08 0,00 62,15 2,469 1,58 T 12,00 0,000
SCHED 40 WET STEEL 120 0 19,98 0,017
50 0,00 19,08 0,00 62,15 2,50 23,56 0,00273 12,84 0,05151 0,00 19,08 0,00 62,10 2,469 1,58 E 6,00 0,000
SCHED 40 WET STEEL 120 0 18,83 0,017
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 28
Fire Sprinkler Output Data
Overall Pipe Output Data (cont'd)
Beg.End.
Node
NodalKFactor
(K)
Elevation(feet)
Spk/HoseDischarge
(gpm)
ResidualPressure
(psi)
Nom. Dia.Inside Dia.
C-Value
Q (gpm)Velocity
(fps)
F. L./ft(psi/ft)
FittingsType-Grp
Pipe-Len.Fit-Len.
Tot-Len.(ft)
PF-(psi)PE-(psi)PV-(psi)
51 0,00 19,08 0,00 62,10 1,00 23,47 0,17509 0,98 0,87352 3,00 19,08 23,47 61,23 1,049 8,71 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,511
51 0,00 19,08 0,00 62,10 2,50 0,08 0,00000 9,09 0,00053 0,00 19,08 0,00 62,10 2,469 0,01 2ET 24,00 0,000
SCHED 40 WET STEEL 120 0 33,09 0,000
53 0,00 19,08 0,00 62,10 1,00 23,47 0,17509 0,98 0,87354 3,00 19,08 23,47 61,23 1,049 8,71 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,511
53 0,00 19,08 0,00 62,10 2,50 23,39 0,00269 14,20 0,10355 0,00 19,08 0,00 62,20 2,469 1,57 2ET 24,00 0,000
SCHED 40 WET STEEL 120 0 38,20 0,017
55 0,00 19,08 0,00 62,20 2,50 23,39 0,00269 7,98 0,03856 0,00 19,08 0,00 62,24 2,469 1,57 E 6,00 0,000
SCHED 40 WET STEEL 120 0 13,98 0,017
56 0,00 19,08 0,00 62,24 1,00 23,50 0,17545 0,98 0,87457 3,00 19,08 23,50 61,36 1,049 8,72 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,512
56 0,00 19,08 0,00 62,24 2,50 46,89 0,00975 8,53 0,20058 0,00 19,08 0,00 62,44 2,469 3,14 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,066
58 0,00 19,08 0,00 62,44 1,00 23,54 0,17597 0,98 0,87759 3,00 19,08 23,54 61,56 1,049 8,74 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,514
58 0,00 19,08 0,00 62,44 2,50 70,43 0,02069 8,53 0,42560 0,00 19,08 0,00 62,86 2,469 4,72 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,150
60 0,00 19,08 0,00 62,86 1,00 23,62 0,17708 0,98 0,88361 3,00 19,08 23,62 61,98 1,049 8,77 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,517
60 0,00 19,08 0,00 62,86 2,50 94,05 0,03532 8,53 0,72562 0,00 19,08 0,00 63,59 2,469 6,30 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,267
62 0,00 19,08 0,00 63,59 1,00 23,75 0,17897 0,98 0,89263 3,00 19,08 23,75 62,70 1,049 8,82 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,523
62 0,00 19,08 0,00 63,59 2,50 117,80 0,05358 7,63 1,05264 0,00 19,08 0,00 64,64 2,469 7,89 T 12,00 0,000
SCHED 40 WET STEEL 120 0 19,63 0,419
64 0,00 19,08 0,00 64,64 2,50 117,80 0,05358 13,57 1,04965 0,00 19,08 0,00 65,69 2,469 7,89 E 6,00 0,000
SCHED 40 WET STEEL 120 0 19,57 0,419
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 29
Fire Sprinkler Output Data
Overall Pipe Output Data (cont'd)
Beg.End.
Node
NodalKFactor
(K)
Elevation(feet)
Spk/HoseDischarge
(gpm)
ResidualPressure
(psi)
Nom. Dia.Inside Dia.
C-Value
Q (gpm)Velocity
(fps)
F. L./ft(psi/ft)
FittingsType-Grp
Pipe-Len.Fit-Len.
Tot-Len.(ft)
PF-(psi)PE-(psi)PV-(psi)
65 0,00 19,08 0,00 65,69 1,00 24,14 0,18444 0,98 0,91966 3,00 19,08 24,14 64,77 1,049 8,96 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,541
67 0,00 10,55 0,00 68,51 1,00 24,66 0,19176 0,98 0,95668 3,00 10,55 24,66 67,55 1,049 9,15 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,564
67 0,00 10,55 0,00 68,51 2,50 120,79 0,05612 12,84 1,39469 0,00 10,55 0,00 67,11 2,469 8,09 T 12,00 0,000
SCHED 40 WET STEEL 120 0 24,83 0,441
69 0,00 10,55 0,00 67,11 2,50 120,79 0,05612 2,95 0,50270 0,00 7,60 0,00 67,89 2,469 8,09 E 6,00 -1,279
SCHED 40 WET STEEL 120 0 8,95 0,441
70 0,00 7,60 0,00 67,89 2,50 120,79 0,05612 7,63 0,76571 0,00 7,60 0,00 67,13 2,469 8,09 E 6,00 0,000
SCHED 40 WET STEEL 120 0 13,63 0,441
71 0,00 7,60 0,00 67,13 1,00 24,41 0,18817 0,98 0,93872 3,00 7,60 24,41 66,19 1,049 9,06 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,552
71 0,00 7,60 0,00 67,13 2,50 96,39 0,03696 8,53 0,75973 0,00 7,60 0,00 66,37 2,469 6,46 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,281
73 0,00 7,60 0,00 66,37 1,00 24,27 0,18620 0,98 0,92874 3,00 7,60 24,27 65,44 1,049 9,01 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,546
73 0,00 7,60 0,00 66,37 2,50 72,12 0,02161 8,53 0,44475 0,00 7,60 0,00 65,92 2,469 4,83 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,157
75 0,00 7,60 0,00 65,92 1,00 24,19 0,18505 0,98 0,92276 3,00 7,60 24,19 65,00 1,049 8,98 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,543
75 0,00 7,60 0,00 65,92 2,50 47,93 0,01015 8,53 0,20877 0,00 7,60 0,00 65,71 2,469 3,21 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,069
77 0,00 7,60 0,00 65,71 1,00 24,15 0,18451 0,98 0,92078 3,00 7,60 24,15 64,79 1,049 8,96 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,541
77 0,00 7,60 0,00 65,71 2,50 23,78 0,00278 3,91 0,04479 0,00 7,60 0,00 65,67 2,469 1,59 T 12,00 0,000
SCHED 40 WET STEEL 120 0 15,91 0,017
79 0,00 7,60 0,00 65,67 2,50 23,78 0,00278 2,95 0,02580 0,00 10,55 0,00 64,37 2,469 1,59 E 6,00 1,279
SCHED 40 WET STEEL 120 0 8,95 0,017
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 30
Fire Sprinkler Output Data
Overall Pipe Output Data (cont'd)
Beg.End.
Node
NodalKFactor
(K)
Elevation(feet)
Spk/HoseDischarge
(gpm)
ResidualPressure
(psi)
Nom. Dia.Inside Dia.
C-Value
Q (gpm)Velocity
(fps)
F. L./ft(psi/ft)
FittingsType-Grp
Pipe-Len.Fit-Len.
Tot-Len.(ft)
PF-(psi)PE-(psi)PV-(psi)
80 0,00 10,55 0,00 64,37 2,50 23,78 0,00278 12,84 0,05281 0,00 10,55 0,00 64,31 2,469 1,59 E 6,00 0,000
SCHED 40 WET STEEL 120 0 18,83 0,017
81 0,00 10,55 0,00 64,31 1,00 23,89 0,18087 0,98 0,90182 3,00 10,55 23,89 63,41 1,049 8,87 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,529
81 0,00 10,55 0,00 64,31 2,50 0,11 0,00000 8,47 0,00083 0,00 10,55 0,00 64,31 2,469 0,01 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,47 0,000
83 0,00 10,55 0,00 64,31 1,00 23,89 0,18087 0,98 0,90184 3,00 10,55 23,89 63,41 1,049 8,87 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,529
83 0,00 10,55 0,00 64,31 2,50 24,00 0,00282 13,57 0,07285 0,00 10,55 0,00 64,39 2,469 1,61 T 12,00 0,000
SCHED 40 WET STEEL 120 0 25,57 0,017
85 0,00 10,55 0,00 64,39 2,50 24,00 0,00282 2,95 0,02586 0,00 7,60 0,00 65,69 2,469 1,61 E 6,00 1,279
SCHED 40 WET STEEL 120 0 8,95 0,017
86 0,00 7,60 0,00 65,69 2,50 24,00 0,00282 3,91 0,02887 0,00 7,60 0,00 65,72 2,469 1,61 E 6,00 0,000
SCHED 40 WET STEEL 120 0 9,91 0,017
87 0,00 7,60 0,00 65,72 1,00 24,15 0,18452 0,98 0,92088 3,00 7,60 24,15 64,80 1,049 8,96 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,541
87 0,00 7,60 0,00 65,72 2,50 48,14 0,01023 8,53 0,21089 0,00 7,60 0,00 65,93 2,469 3,23 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,070
89 0,00 7,60 0,00 65,93 1,00 24,19 0,18507 0,98 0,92290 3,00 7,60 24,19 65,01 1,049 8,98 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,543
89 0,00 7,60 0,00 65,93 2,50 72,33 0,02173 8,53 0,44691 0,00 7,60 0,00 66,37 2,469 4,85 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,158
91 0,00 7,60 0,00 66,37 1,00 24,27 0,18622 0,98 0,92892 3,00 7,60 24,27 65,45 1,049 9,01 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,546
91 0,00 7,60 0,00 66,37 2,50 96,60 0,03712 8,53 0,76293 0,00 7,60 0,00 67,14 2,469 6,47 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,282
93 0,00 7,60 0,00 67,14 1,00 24,41 0,18820 0,98 0,93894 3,00 7,60 24,41 66,20 1,049 9,06 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,553
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 31
Fire Sprinkler Output Data
Overall Pipe Output Data (cont'd)
Beg.End.
Node
NodalKFactor
(K)
Elevation(feet)
Spk/HoseDischarge
(gpm)
ResidualPressure
(psi)
Nom. Dia.Inside Dia.
C-Value
Q (gpm)Velocity
(fps)
F. L./ft(psi/ft)
FittingsType-Grp
Pipe-Len.Fit-Len.
Tot-Len.(ft)
PF-(psi)PE-(psi)PV-(psi)
93 0,00 7,60 0,00 67,14 2,50 121,01 0,05631 7,63 1,10595 0,00 7,60 0,00 68,24 2,469 8,11 T 12,00 0,000
SCHED 40 WET STEEL 120 0 19,63 0,443
95 0,00 7,60 0,00 68,24 2,50 121,01 0,05631 2,95 0,50496 0,00 10,55 0,00 67,47 2,469 8,11 E 6,00 -1,279
SCHED 40 WET STEEL 120 0 8,95 0,443
96 0,00 10,55 0,00 67,47 2,50 121,01 0,05631 13,57 1,10297 0,00 10,55 0,00 68,57 2,469 8,11 E 6,00 0,000
SCHED 40 WET STEEL 120 0 19,57 0,443
97 0,00 10,55 0,00 68,57 1,00 24,67 0,19192 0,98 0,95798 3,00 10,55 24,67 67,61 1,049 9,16 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,564
100 0,00 7,60 0,00 77,27 4,00 389,78 0,04532 7,02 2,312101 0,00 14,62 0,00 71,92 4,026 9,82 EBC 44,00 3,042
SCHED 40 WET STEEL 120 0 51,02 0,649
101 0,00 14,62 0,00 71,92 4,00 389,78 0,04532 5,59 0,707102 0,00 14,62 0,00 71,21 4,026 9,82 E 10,00 0,000
SCHED 40 WET STEEL 120 0 15,59 0,649
102 0,00 14,62 0,00 71,21 4,00 389,78 0,04532 8,01 0,816103 0,00 14,62 0,00 70,40 4,026 9,82 E 10,00 0,000
SCHED 40 WET STEEL 120 0 18,01 0,649
103 0,00 14,62 0,00 70,40 4,00 389,78 0,04532 5,71 0,712104 0,00 14,62 0,00 69,68 4,026 9,82 E 10,00 0,000
SCHED 40 WET STEEL 120 0 15,71 0,649
104 0,00 14,62 0,00 69,68 4,00 389,78 0,04532 6,97 0,769105 0,00 21,58 0,00 65,90 4,026 9,82 E 10,00 3,016
SCHED 40 WET STEEL 120 0 16,97 0,649
105 0,00 21,58 0,00 65,90 4,00 389,78 0,04532 2,34 0,559106 0,00 21,58 0,00 65,34 4,026 9,82 E 10,00 0,000
SCHED 40 WET STEEL 120 0 12,34 0,649
106 0,00 21,58 0,00 65,34 4,00 389,78 0,04532 4,67 0,665107 0,00 16,92 0,00 66,70 4,026 9,82 E 10,00 -2,020
SCHED 40 WET STEEL 120 0 14,66 0,649
107 0,00 16,92 0,00 66,70 4,00 197,03 0,01283 7,71 0,355108 0,00 9,21 0,00 69,68 4,026 4,97 T 20,00 -3,338
SCHED 40 WET STEEL 120 0 27,71 0,166
107 0,00 16,92 0,00 66,70 2,50 103,19 0,04193 1,68 0,574109 0,00 16,92 0,00 66,12 2,469 6,91 T 12,00 0,000
SCHED 40 WET STEEL 120 0 13,68 0,322
107 0,00 16,92 0,00 66,70 2,50 89,57 0,03227 5,21 0,556111 0,00 16,92 0,00 66,14 2,469 6,00 T 12,00 0,000
SCHED 40 WET STEEL 120 0 17,21 0,242
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 32
Fire Sprinkler Output Data
Overall Pipe Output Data (cont'd)
Beg.End.
Node
NodalKFactor
(K)
Elevation(feet)
Spk/HoseDischarge
(gpm)
ResidualPressure
(psi)
Nom. Dia.Inside Dia.
C-Value
Q (gpm)Velocity
(fps)
F. L./ft(psi/ft)
FittingsType-Grp
Pipe-Len.Fit-Len.
Tot-Len.(ft)
PF-(psi)PE-(psi)PV-(psi)
108 0,00 9,21 0,00 69,68 2,50 105,40 0,04361 1,68 0,597129 0,00 9,21 0,00 69,08 2,469 7,06 T 12,00 0,000
SCHED 40 WET STEEL 120 0 13,68 0,336
108 0,00 9,21 0,00 69,68 2,50 91,63 0,03366 5,21 0,579131 0,00 9,21 0,00 69,10 2,469 6,14 T 12,00 0,000
SCHED 40 WET STEEL 120 0 17,21 0,254
109 0,00 16,92 0,00 66,12 1,00 24,22 0,18557 0,98 0,925110 3,00 16,92 24,22 65,20 1,049 8,99 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,544
109 0,00 16,92 0,00 66,12 2,50 78,96 0,02556 7,77 0,505127 0,00 16,92 0,00 65,62 2,469 5,29 T 12,00 0,000
SCHED 40 WET STEEL 120 0 19,77 0,188
111 0,00 16,92 0,00 66,14 2,50 89,57 0,03227 6,60 0,407112 0,00 16,92 0,00 65,73 2,469 6,00 E 6,00 0,000
SCHED 40 WET STEEL 120 0 12,60 0,242
112 0,00 16,92 0,00 65,73 1,00 24,15 0,18456 0,98 0,920113 3,00 16,92 24,15 64,81 1,049 8,97 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,541
112 0,00 16,92 0,00 65,73 2,50 65,42 0,01804 8,53 0,370114 0,00 16,92 0,00 65,36 2,469 4,38 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,129
114 0,00 16,92 0,00 65,36 1,00 24,08 0,18360 0,98 0,915115 3,00 16,92 24,08 64,45 1,049 8,94 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,538
114 0,00 16,92 0,00 65,36 2,50 41,33 0,00772 5,80 0,137116 0,00 16,92 0,00 65,23 2,469 2,77 T 12,00 0,000
SCHED 40 WET STEEL 120 0 17,80 0,052
116 0,00 16,92 0,00 65,23 2,50 41,33 0,00772 6,90 0,100117 0,00 16,92 0,00 65,13 2,469 2,77 E 6,00 0,000
SCHED 40 WET STEEL 120 0 12,90 0,052
117 0,00 16,92 0,00 65,13 1,00 24,04 0,18298 0,98 0,912118 3,00 16,92 24,04 64,21 1,049 8,92 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,536
117 0,00 16,92 0,00 65,13 2,50 17,29 0,00154 7,77 0,030119 0,00 16,92 0,00 65,10 2,469 1,16 T 12,00 0,000
SCHED 40 WET STEEL 120 0 19,77 0,009
119 0,00 16,92 0,00 65,10 1,00 24,03 0,18290 0,98 0,912120 3,00 16,92 24,03 64,18 1,049 8,92 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,536
119 0,00 16,92 0,00 65,10 2,50 6,74 0,00027 7,70 0,005121 0,00 16,92 0,00 65,10 2,469 0,45 T 12,00 0,000
SCHED 40 WET STEEL 120 0 19,70 0,001
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 33
Fire Sprinkler Output Data
Overall Pipe Output Data (cont'd)
Beg.End.
Node
NodalKFactor
(K)
Elevation(feet)
Spk/HoseDischarge
(gpm)
ResidualPressure
(psi)
Nom. Dia.Inside Dia.
C-Value
Q (gpm)Velocity
(fps)
F. L./ft(psi/ft)
FittingsType-Grp
Pipe-Len.Fit-Len.
Tot-Len.(ft)
PF-(psi)PE-(psi)PV-(psi)
121 0,00 16,92 0,00 65,10 2,50 6,74 0,00027 5,80 0,003122 0,00 16,92 0,00 65,10 2,469 0,45 E 6,00 0,000
SCHED 40 WET STEEL 120 0 11,80 0,001
122 0,00 16,92 0,00 65,10 1,00 24,04 0,18292 0,98 0,912123 3,00 16,92 24,04 64,19 1,049 8,92 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,536
122 0,00 16,92 0,00 65,10 2,50 30,78 0,00447 8,53 0,092124 0,00 16,92 0,00 65,20 2,469 2,06 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,029
124 0,00 16,92 0,00 65,20 1,00 24,05 0,18316 0,98 0,913125 3,00 16,92 24,05 64,28 1,049 8,93 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,537
124 0,00 16,92 0,00 65,20 2,50 54,83 0,01302 6,60 0,242126 0,00 16,92 0,00 65,44 2,469 3,67 T 12,00 0,000
SCHED 40 WET STEEL 120 0 18,60 0,091
126 0,00 16,92 0,00 65,44 2,50 54,83 0,01302 7,70 0,178127 0,00 16,92 0,00 65,62 2,469 3,67 E 6,00 0,000
SCHED 40 WET STEEL 120 0 13,70 0,091
127 0,00 16,92 0,00 65,62 1,00 24,13 0,18426 0,98 0,918128 3,00 16,92 24,13 64,70 1,049 8,96 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,540
129 0,00 9,21 0,00 69,08 1,00 24,76 0,19325 0,98 0,963130 3,00 9,21 24,76 68,12 1,049 9,19 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,569
129 0,00 9,21 0,00 69,08 2,50 80,64 0,02658 7,77 0,525147 0,00 9,21 0,00 68,56 2,469 5,40 T 12,00 0,000
SCHED 40 WET STEEL 120 0 19,77 0,197
131 0,00 9,21 0,00 69,10 2,50 91,63 0,03366 6,60 0,424132 0,00 9,21 0,00 68,68 2,469 6,14 E 6,00 0,000
SCHED 40 WET STEEL 120 0 12,60 0,254
132 0,00 9,21 0,00 68,68 1,00 24,69 0,19220 0,98 0,958133 3,00 9,21 24,69 67,72 1,049 9,16 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,565
132 0,00 9,21 0,00 68,68 2,50 66,94 0,01883 8,53 0,387134 0,00 9,21 0,00 68,29 2,469 4,49 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,135
134 0,00 9,21 0,00 68,29 1,00 24,62 0,19119 0,98 0,953135 3,00 9,21 24,62 67,34 1,049 9,14 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,562
134 0,00 9,21 0,00 68,29 2,50 42,32 0,00806 5,80 0,143136 0,00 9,21 0,00 68,15 2,469 2,84 T 12,00 0,000
SCHED 40 WET STEEL 120 0 17,80 0,054
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 34
Fire Sprinkler Output Data
Overall Pipe Output Data (cont'd)
Beg.End.
Node
NodalKFactor
(K)
Elevation(feet)
Spk/HoseDischarge
(gpm)
ResidualPressure
(psi)
Nom. Dia.Inside Dia.
C-Value
Q (gpm)Velocity
(fps)
F. L./ft(psi/ft)
FittingsType-Grp
Pipe-Len.Fit-Len.
Tot-Len.(ft)
PF-(psi)PE-(psi)PV-(psi)
136 0,00 9,21 0,00 68,15 2,50 42,32 0,00806 6,90 0,104137 0,00 9,21 0,00 68,04 2,469 2,84 E 6,00 0,000
SCHED 40 WET STEEL 120 0 12,90 0,054
137 0,00 9,21 0,00 68,04 1,00 24,57 0,19055 0,98 0,950138 3,00 9,21 24,57 67,09 1,049 9,12 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,560
137 0,00 9,21 0,00 68,04 2,50 17,75 0,00161 7,77 0,032139 0,00 9,21 0,00 68,01 2,469 1,19 T 12,00 0,000
SCHED 40 WET STEEL 120 0 19,77 0,010
139 0,00 9,21 0,00 68,01 1,00 24,57 0,19047 0,98 0,949140 3,00 9,21 24,57 67,06 1,049 9,12 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,560
139 0,00 9,21 0,00 68,01 2,50 6,82 0,00028 13,17 0,012141 0,00 9,21 0,00 68,02 2,469 0,46 3ET 30,00 0,000
SCHED 40 WET STEEL 120 0 43,17 0,001
141 0,00 9,21 0,00 68,02 2,50 6,82 0,00028 5,80 0,003142 0,00 9,21 0,00 68,03 2,469 0,46 E 6,00 0,000
SCHED 40 WET STEEL 120 0 11,80 0,001
142 0,00 9,21 0,00 68,03 1,00 24,57 0,19051 0,98 0,949143 3,00 9,21 24,57 67,08 1,049 9,12 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,560
142 0,00 9,21 0,00 68,03 2,50 31,39 0,00464 8,53 0,095144 0,00 9,21 0,00 68,12 2,469 2,10 T 12,00 0,000
SCHED 40 WET STEEL 120 0 20,53 0,030
144 0,00 9,21 0,00 68,12 1,00 24,59 0,19076 0,98 0,951145 3,00 9,21 24,59 67,17 1,049 9,13 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,561
144 0,00 9,21 0,00 68,12 2,50 55,98 0,01352 6,60 0,252146 0,00 9,21 0,00 68,37 2,469 3,75 T 12,00 0,000
SCHED 40 WET STEEL 120 0 18,60 0,095
146 0,00 9,21 0,00 68,37 2,50 55,98 0,01352 7,70 0,185147 0,00 9,21 0,00 68,56 2,469 3,75 E 6,00 0,000
SCHED 40 WET STEEL 120 0 13,70 0,095
147 0,00 9,21 0,00 68,56 1,00 24,67 0,19189 0,98 0,956148 3,00 9,21 24,67 67,60 1,049 9,16 2E 4,00 0,000
SCHED 40 WET STEEL 120 0 4,98 0,564
1 0,00 0,00 0,00 82,53 10,00 1496,56 0,00492 11,88 0,430201 0,00 0,00 0,00 82,96 9,728 6,46 T 75,50 0,000
HDPE-CLASS 200 150 0 87,38 0,281
201 0,00 0,00 0,00 82,96 10,00 1496,56 0,00492 4,17 0,179202 0,00 -4,17 0,00 84,94 9,728 6,46 E 32,20 1,804
HDPE-CLASS 200 150 0 36,37 0,281
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 35
Fire Sprinkler Output Data
Overall Pipe Output Data (cont'd)
Beg.End.
Node
NodalKFactor
(K)
Elevation(feet)
Spk/HoseDischarge
(gpm)
ResidualPressure
(psi)
Nom. Dia.Inside Dia.
C-Value
Q (gpm)Velocity
(fps)
F. L./ft(psi/ft)
FittingsType-Grp
Pipe-Len.Fit-Len.
Tot-Len.(ft)
PF-(psi)PE-(psi)PV-(psi)
202 0,00 -4,17 0,00 84,94 10,00 1496,56 0,00492 4,79 0,182203 0,00 -4,17 0,00 85,13 9,728 6,46 E 32,20 0,000
HDPE-CLASS 200 150 0 36,99 0,281
203 0,00 -4,17 0,00 85,13 10,00 1496,56 0,00492 4,17 0,179204 0,00 0,00 0,00 83,50 9,728 6,46 E 32,20 -1,804
HDPE-CLASS 200 150 0 36,37 0,281
204 0,00 0,00 0,00 83,50 10,00 1496,56 0,00492 196,39 1,207205 0,00 0,00 0,00 84,71 9,728 6,46 FE 48,80 0,000
HDPE-CLASS 200 150 0 245,19 0,281
205 0,00 0,00 0,00 84,71 10,00 1496,56 0,00492 5,22 0,184206 0,00 -5,22 0,00 87,15 9,728 6,46 E 32,20 2,259
HDPE-CLASS 200 150 0 37,42 0,281
206 0,00 -5,22 0,00 87,15 10,00 1496,56 0,00492 58,89 0,448207 0,00 -5,22 0,00 87,60 9,728 6,46 E 32,20 0,000
HDPE-CLASS 200 150 0 91,09 0,281
207 0,00 -5,22 0,00 87,60 10,00 1496,56 0,00492 5,22 0,184208 0,00 0,00 0,00 85,52 9,728 6,46 E 32,20 -2,259
HDPE-CLASS 200 150 0 37,42 0,281
208 0,00 0,00 0,00 85,52 10,00 1496,56 0,00492 151,35 0,903209 0,00 0,00 0,00 86,43 9,728 6,46 E 32,20 0,000
HDPE-CLASS 200 150 0 183,54 0,281
209 0,00 0,00 0,00 86,43 10,00 1496,56 0,00492 3,58 0,176210 0,00 -3,58 0,00 88,15 9,728 6,46 E 32,20 1,548
HDPE-CLASS 200 150 0 35,78 0,281
210 0,00 -3,58 0,00 88,15 10,00 1496,56 0,00492 124,28 1,255211 0,00 -3,58 0,00 89,41 9,728 6,46 4F2E 130,80 0,000
HDPE-CLASS 200 150 0 255,08 0,281
211 0,00 -3,58 0,00 89,41 10,00 1496,56 0,00644 9,15 0,201212 0,00 5,58 0,00 85,64 10,020 6,09 E 22,00 -3,963
SCHED 40 WET STEEL 120 0 31,15 0,250
212 0,00 5,58 0,00 85,64 10,00 1496,56 0,00644 265,16 2,660213 0,00 5,58 0,00 88,30 10,020 6,09 2F3EGC 148,00 0,000
SCHED 40 WET STEEL 120 0 413,16 0,250
300 0,00 0,00 0,00 82,52 8,00 250,00 0,00052 18,70 0,026301 0,00 0,00 0,00 82,49 7,805 1,68 EG 30,20 0,000
HDPE-CLASS 200 150 0 48,90 0,019
301 0,00 0,00 0,00 82,49 6,00 250,00 0,00271 3,94 0,049302 0,00 3,90 250,00 80,75 6,065 2,78 E 14,00 1,689
SCHED 40 WET STEEL 120 0 17,94 0,052
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 36
Fire Sprinkler Output Data
Overall Sprinkler Output Data
FlowingSprinkler
Node No.
Area GroupCode
SprinklerKFactor (K)
SprinklerElevation
(feet)
ResidualPressure
(psi)
Flowing Area(ft²)
FlowingDensity
(gpm/ft²)
SprinklerDischarge
(gpm)
12 3,00 24,68 63,63 84,00 0,285 23,93Sub Totals For Non-Group 84,00 0,285 23,93
15 3,00 24,68 61,66 84,00 0,280 23,56Sub Totals For Non-Group 84,00 0,280 23,56
17 3,00 24,68 60,96 84,00 0,279 23,42Sub Totals For Non-Group 84,00 0,279 23,42
19 3,00 24,68 60,56 84,00 0,278 23,35Sub Totals For Non-Group 84,00 0,278 23,35
21 3,00 24,68 60,37 84,00 0,277 23,31Sub Totals For Non-Group 84,00 0,277 23,31
24 3,00 27,28 60,00 84,00 0,277 23,24Sub Totals For Non-Group 84,00 0,277 23,24
26 3,00 27,28 60,00 84,00 0,277 23,24Sub Totals For Non-Group 84,00 0,277 23,24
29 3,00 24,68 60,37 84,00 0,277 23,31Sub Totals For Non-Group 84,00 0,277 23,31
31 3,00 24,68 60,56 84,00 0,278 23,35Sub Totals For Non-Group 84,00 0,278 23,35
33 3,00 24,68 60,97 84,00 0,279 23,43Sub Totals For Non-Group 84,00 0,279 23,43
35 3,00 24,68 61,67 84,00 0,280 23,56Sub Totals For Non-Group 84,00 0,280 23,56
38 3,00 24,68 63,69 84,00 0,285 23,94Sub Totals For Non-Group 84,00 0,285 23,94
40 3,00 19,08 64,71 84,00 0,287 24,13Sub Totals For Non-Group 84,00 0,287 24,13
43 3,00 19,08 62,67 84,00 0,283 23,75Sub Totals For Non-Group 84,00 0,283 23,75
45 3,00 19,08 61,95 84,00 0,281 23,61Sub Totals For Non-Group 84,00 0,281 23,61
47 3,00 19,08 61,53 84,00 0,280 23,53Sub Totals For Non-Group 84,00 0,280 23,53
49 3,00 19,08 61,33 84,00 0,280 23,49Sub Totals For Non-Group 84,00 0,280 23,49
52 3,00 19,08 61,23 84,00 0,279 23,47Sub Totals For Non-Group 84,00 0,279 23,47
54 3,00 19,08 61,23 84,00 0,279 23,47Sub Totals For Non-Group 84,00 0,279 23,47
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 37
Fire Sprinkler Output Data
Overall Sprinkler Output Data (cont'd)
FlowingSprinkler
Node No.
Area GroupCode
SprinklerKFactor (K)
SprinklerElevation
(feet)
ResidualPressure
(psi)
Flowing Area(ft²)
FlowingDensity
(gpm/ft²)
SprinklerDischarge
(gpm)57 3,00 19,08 61,36 84,00 0,280 23,50
Sub Totals For Non-Group 84,00 0,280 23,50
59 3,00 19,08 61,56 84,00 0,280 23,54Sub Totals For Non-Group 84,00 0,280 23,54
61 3,00 19,08 61,98 84,00 0,281 23,62Sub Totals For Non-Group 84,00 0,281 23,62
63 3,00 19,08 62,70 84,00 0,283 23,75Sub Totals For Non-Group 84,00 0,283 23,75
66 3,00 19,08 64,77 84,00 0,287 24,14Sub Totals For Non-Group 84,00 0,287 24,14
68 3,00 10,55 67,55 84,00 0,294 24,66Sub Totals For Non-Group 84,00 0,294 24,66
72 3,00 7,60 66,19 84,00 0,291 24,41Sub Totals For Non-Group 84,00 0,291 24,41
74 3,00 7,60 65,44 84,00 0,289 24,27Sub Totals For Non-Group 84,00 0,289 24,27
76 3,00 7,60 65,00 84,00 0,288 24,19Sub Totals For Non-Group 84,00 0,288 24,19
78 3,00 7,60 64,79 84,00 0,287 24,15Sub Totals For Non-Group 84,00 0,287 24,15
82 3,00 10,55 63,41 84,00 0,284 23,89Sub Totals For Non-Group 84,00 0,284 23,89
84 3,00 10,55 63,41 84,00 0,284 23,89Sub Totals For Non-Group 84,00 0,284 23,89
88 3,00 7,60 64,80 84,00 0,287 24,15Sub Totals For Non-Group 84,00 0,287 24,15
90 3,00 7,60 65,01 84,00 0,288 24,19Sub Totals For Non-Group 84,00 0,288 24,19
92 3,00 7,60 65,45 84,00 0,289 24,27Sub Totals For Non-Group 84,00 0,289 24,27
94 3,00 7,60 66,20 84,00 0,291 24,41Sub Totals For Non-Group 84,00 0,291 24,41
98 3,00 10,55 67,61 84,00 0,294 24,67Sub Totals For Non-Group 84,00 0,294 24,67
110 3,00 16,92 65,20 84,00 0,288 24,22Sub Totals For Non-Group 84,00 0,288 24,22
113 3,00 16,92 64,81 84,00 0,288 24,15Sub Totals For Non-Group 84,00 0,288 24,15
115 3,00 16,92 64,45 84,00 0,287 24,08
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 38
Fire Sprinkler Output Data
Overall Sprinkler Output Data (cont'd)
FlowingSprinkler
Node No.
Area GroupCode
SprinklerKFactor (K)
SprinklerElevation
(feet)
ResidualPressure
(psi)
Flowing Area(ft²)
FlowingDensity
(gpm/ft²)
SprinklerDischarge
(gpm)Sub Totals For Non-Group 84,00 0,287 24,08
118 3,00 16,92 64,21 84,00 0,286 24,04Sub Totals For Non-Group 84,00 0,286 24,04
120 3,00 16,92 64,18 84,00 0,286 24,03Sub Totals For Non-Group 84,00 0,286 24,03
123 3,00 16,92 64,19 84,00 0,286 24,04Sub Totals For Non-Group 84,00 0,286 24,04
125 3,00 16,92 64,28 84,00 0,286 24,05Sub Totals For Non-Group 84,00 0,286 24,05
128 3,00 16,92 64,70 84,00 0,287 24,13Sub Totals For Non-Group 84,00 0,287 24,13
130 3,00 9,21 68,12 84,00 0,295 24,76Sub Totals For Non-Group 84,00 0,295 24,76
133 3,00 9,21 67,72 84,00 0,294 24,69Sub Totals For Non-Group 84,00 0,294 24,69
135 3,00 9,21 67,34 84,00 0,293 24,62Sub Totals For Non-Group 84,00 0,293 24,62
138 3,00 9,21 67,09 84,00 0,293 24,57Sub Totals For Non-Group 84,00 0,293 24,57
140 3,00 9,21 67,06 84,00 0,292 24,57Sub Totals For Non-Group 84,00 0,292 24,57
143 3,00 9,21 67,08 84,00 0,293 24,57Sub Totals For Non-Group 84,00 0,293 24,57
145 3,00 9,21 67,17 84,00 0,293 24,59Sub Totals For Non-Group 84,00 0,293 24,59
148 3,00 9,21 67,60 84,00 0,294 24,67Sub Totals For Non-Group 84,00 0,294 24,67
Totals For All Groups 4368,00 0,285 1246,56
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 39
Fire Sprinkler Output Summary
Hydraulically Most Demanding Sprinkler Node
HMD Sprinkler Node Number: 26HMD Actual Residual Pressure: 60,00 psiHMD Actual GPM: 23,24 gpm
Sprinkler Summary
Sprinkler System Type: Dry Specified Area Of Application: 500,00 ft²Adjusted Area Of Application: 650,00 ft²Minimum Desired Density: 0,250 gpm/ft²Application Average Density: 2,493 gpm/ft²Application Adjusted Density (not required by NFPA 13): 1,918 gpm/ft²Application Average Area Per Sprinkler: 9,62 ft²Adjusted Area Per Sprinkler (not required by NFPA 13): 12,50 ft²Sprinkler Flow: 1246,56 gpmAverage Sprinkler Flow: 23,97 gpm
Flow Velocity And Imbalance Summary
Maximum Flow Velocity ( In Pipe 8 - 9 ) 14,50 ft/secMaximum Velocity Pressure ( In Pipe 8 - 9 ) 1,41 psi
Allowable Maximum Nodal Pressure Imbalance: 0,0001 psiActual Maximum Nodal Pressure Imbalance: 0,0001 psiActual Average Nodal Pressure Imbalance: 0,0000 psiActual Maximum Nodal Flow Imbalance: 0,0004 gpmActual Average Nodal Flow Imbalance: 0,0000 gpm
Overall Network Summary
Number Of Unique Pipe Sections: 167Number Of Flowing Sprinklers: 52
Pipe System Water Volume: 3836,56 gal
Sprinkler Flow: 1246,56 gpmNon-Sprinkler Flow: 250,00 gpmTotal System Demand Flow: 1496,56 gpm
Minimum Required Residual Pressure At System InflowNode: 88,31 psi
Demand Flow At System Inflow Node: 1496,56 gpm
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.CENTRAL ELECTRICA MALACASPage 40
Fire Sprinkler Output Data
Hydraulic Supply/Demand Graph
Pre
ssur
e p
si
Flowrate(x100) gpm
0000
10
20
30
40
50
60
70
80
90
100
2 4 6 8 10 12 14 16 18 20
Adjusted Hydrant DataStatic Pressure: 0 psiTest Residual Pressure: 0 psiTest Flow Rate: 0 gpm
Demand Point DataCalculated Residual Pressure: 88,30 psiCalculated Flow Rate: 1496,56 gpmExcess Available Inflow Residual Pressure: -88,3 psiPressure Required For First Sprinkler Downstream From Inflow Node To Flow: 8,27 psi