Top Banner
Centrifugal Cabinet Fans Model BDF Belt Drive Duct Fan July 2007
12

Centrifugal Cabinet Fansliterature.puertoricosupplier.com/049/JU48480.pdf · 2011. 5. 30. · AMCA Seal. The ratings shown are based on tests and procedures performed in accordance

Feb 12, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • Centrifugal Cabinet FansModel BDFBelt Drive Duct Fan

    July2007

  • 2

    BDF model is listed for electrical (UL 705) with TEFC motor only. File no. E40001.

    Greenheck Fan Corporation certifies that the model BDF fans shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and Publication 311 and comply with the requirements of AMCA Certified Ratings Program. The certified ratings for model BDF are shown on pages 5 to 11.

    BDFBelt Drive Duct Fans

    Greenheck’s Belt Drive Duct Fans, Model BDF, provide the industry’s best performance and durability. Model BDF is carefully engineered for efficiency and reliability in supply, exhaust, and return air applications. The BDF is designed specifically for low sound levels in ducted applications.

    Performance ranges from 400 to 17,000 cfm (• 680 to 28,883 m3/h)

    with static pressure up to 3.0 in. wg (745 Pa).

    Available in seven sizes ranging from 80 to 200.•

    Each fan size has been tested in our AMCA Accredited •Laboratory, and all models are licensed to bear the AMCA air performance seal. Performance as cataloged is assured.

    Removable access panels provide easy •access for service.

    Rugged drive frame configuration.•

    Vibration isolation, assures long life and •quiet operation.

    UL Listed.•

    Greenheck subjects these products to •extensive life testing, assuring the fans will provide many years of reliable performance.

    Quick Delivery and Quick Build ProgramsGreenheck’s QB (Quick Build) program provides custom built to order products that ship in one, three, five, or ten days. This allows the flexibility of knowing that your fan can be made to order and shipped in as little as one day. All BDF sizes are available in three, five or ten days through our Quick Build program.

    Many products are available from our Quick Delivery (QD) program. The QD program provides same day shipment of Greenheck product from our strategically located warehouses throughout the world. These stock products can be ordered over the internet by visiting www.greenheck.com/quick

    Leading Edge Technical Support When product and IOM (Installation, Operation and Maintenance Manual) information is needed, our products are supported by the industry’s best product literature, electronic media, and Computer Aided Product Selection (CAPS) program. You’ll also find this information on our website at www.greenheck.com

    Our national and international representative organization provides personal service and expertise. To locate your nearest Greenheck representative, call 715-359-6171 or visit our website at www.greenheck.com

  • Vibration Isolation - Internal isolators support the entire drive assembly, wheel, and scroll to provide long life and quiet operation.

    Housing - The fan cabinet is constructed of galvanized steel for corrosion resistance and maintenance free operation.

    Access Panels - Two side panels are removable for inspection or servicing. Removal of either side panel, gives easy access to all the fans internal parts.

    Bearings - Permanently sealed, pillow block ball bearings are selected for a minimum L10 life in excess of 100,000 hours (L50 average life of 500,000 hours) at maximum catalogued operating conditions.

    Duct Collars - Inlet and outlet duct collars are provided for easy duct connections.

    Motor - Ball bearing motors are carefully matched to the fan load and receive the cooling benefits of being in the airstream for increased motor life.

    Wheel - Forward curved, centrifugal, galvanized steel wheel is utilized to generate high efficiency and minimal sound. Each wheel is statically and dynamically balanced for long life and quiet operation.

    Drive Frame - Heavy duty frame supports motor, scroll, and wheel to provide long life and durability.

    Drive Assembly - Belts, pulleys and keys are sized for a minimum of 150% of driven horsepower. Machined cast iron pulleys are factory set to the required RPM and adjustable for final system balancing. Belts are static free and oil resistant.

    Multi Discharge Positions - Where space between duct and ceiling is a premium, bottom horizontal and top horizontal discharge positions are available for easy installation.

    Nameplate - Permanent stamped aluminum nameplate for model and serial identification.

    Standard Construction Features

    HousingBearings

    Vibration Isolation

    Drive Assembly

    Wheel

    Duct Collars

    Drive Frame

    Filter Box Dimensions

    F

    C

    G

    B

    K

    D

    E

    H

    F

    C

    G

    B

    2(51)

    2(51)

    K*

    D

    E

    H

    FanAccessPanel

    FanAccessPanel

    Filter BoxAccessPanel

    Filter BoxAccessPanel

    BDF Size

    *K B C D E F G H Filter Size Qty.

    80 493/4

    (1264)181/2 (470)

    157/8 (403)

    153/16 (386)

    1211/16 (322)

    93/4 (248)

    87/8 (225)

    1 (25)

    16 x 20 (406 x 508)

    2

    90 547/8

    (1394)211/4 (540)

    183/4 (476)

    181/4 (464)

    157/8 (403)

    121/4 (311)

    101/2 (267)

    1 (25)

    20 x 25 (508 x 635)

    2

    100 517/8

    (1318)223/4 (578)

    203/4 (527)

    193/4 (502)

    177/8 (454)

    133/4 (349)

    117/8(302)

    1 (25)

    20 x 20 (508 x 508)

    2

    120 639/16

    (1614)271/4 (692)

    223/4 (578)

    241/8 (613)

    197/8 (505)

    16 (406)

    133/8 (340)

    11/2 (38)

    12 x 25 (533 x 635)

    4

    150 621/16

    (1576)325/8 (829)

    273/4 (705)

    285/8 (727)

    237/8 (604)

    191/8 (486)

    163/8 (416)

    1 (25)

    16 x 20 (406 x 508)

    8

    180 753/8

    (1915)413/4

    (1060)313/4 (606)

    371/2 (953)

    277/8 (708)

    221/2 (572)

    187/8 (479)

    11/2 (38)

    20 x 25 (508 x 635)

    6

    200 851/4

    (2165)491/4

    (1251)393/4

    (1010)481/8

    (1222)36

    (914)231/8 (587)

    251/4 (641)

    11/2 (38)

    16 x 25 (406 x 635)

    12

    *K is length of fan and filter box combined. All dimensions in inches (mm).

    3

    Motor

    Nameplate

  • 4

    Options & Accessories

    Sloped Filter Boxes - The double-vee configuration constructed of galvanized steel. Filters are available in 1 or 2-inch pleated disposable media or permanent washable aluminum mesh. Side access panels are standard for easy maintenance.

    Multi Discharge Positions - BDF fans have been designed for horizontal mounting and are standard with bottom horizontal discharge. Optional top horizontal discharge is also available.

    Disconnect Switches - A wide selection of NEMA rated switches are available for positive electrical shutoff and safety. This includes general, dust-tight, rainproof, and corrosion-resistant.

    Wiring Pigtail - Allows direct hook-up to the power supply externally eliminating field wiring at the fan.

    Coatings - A wide variety of protective or decorative coatings are available. Consult Greenheck’s Performance Coatings for Commercial & Industrial Fans brochure and our Product Application Guide FA/110/04R, Performance Coatings for Ventilation Products for in-depth information.

    Insulated Housing - For noise reduction and condensation control, the interior of fan housing and filter box can be lined with a fiberglass duct liner. The duct liner can be utilized to reduce radiated noise from fan housings. It is recommended for applications when fans are placed in acoustically sensitive locations. The duct liner also reduces the noise radiation from the inlet and outlet of the fan. The accompanying table depicts the reduction that can be obtained in each octave band.

    Vibration Isolators - Base and hanging isolator kits are available with either neoprene or spring isolators. Kits range in size to support either the weight of the fan alone or the weight of the fan with filter and mixing box combinations. Kits are for horizontal mounting and include mounting brackets and hardware. Knockouts are provided in the fan cabinet for ease of installation. (Hanging rods supplied by others.)

    Top Horizontal (Optional)Bottom Horizontal (Standard)

    Approximate (%) Sound Attenuation

    Octave Band 1 2 3 4 5 6 7 8 Sones

    *Lined Housing -3 -2 -3 -3 -5 -5 -5 -4 13%

    *Lined Housing shows the reduction that can be obtained in each octave band.

    Typical InstallationsAll BDF fans have been designed to be mounted horizontally. For ease of installation, knockouts are provided at each location where mounting brackets are shown. Universally adjustable brackets are available to mount the fan in hanging or base mounted positions.

    In order to assure proper fan performance, caution must be exercised in fan placement and connection. Obstructions, transitions, poorly designed elbows, etc., can cause reduced performance, excessive noise, and increase mechanical stress. For performance to be as published, the system must provide uniform and stable airflow into the fan.

    C

    C A

    AC

    C A

    AC

    Access

    Panel

    Access

    Panel

    Access

    Panel

    Access

    Panel

    BDF U

    nitFilt

    er Box

    B

    B

    A

    A

    A

    All dimensions in inches (mm).

    BDF Size A C

    80 203/4

    (527)2211/16 (576)

    90 213/4

    (552)255/8 (651)

    100 233/4

    (603)271/8 (689)

    120 301/2

    (775)315/8 (803)

    15032

    (813)35

    (889)

    180 373/8

    (949)44

    (1118)

    200 473/8

    (1203)511/2

    (1308)

    4

    Hanging Spring

    Neoprene

    Hanging Neoprene

    Standing Spring

  • 5

    Do no

    t selec

    t to t

    he le

    ft of

    this

    syst

    em c

    urve

    231/4 (591)

    ModelNumber

    FanCFM

    Static Pressure in Inches wg0.125 0.25 0.375 0.5 0.625 0.75 1 1.25 1.5 1.75

    BDF-80 300 RPM 511BHP 0.01

    Sones 4.6400 RPM 546 717

    BHP 0.02 0.03Sones 4.4 4.7

    500 RPM 610 745 881BHP 0.03 0.04 0.05

    Sones 4.2 5.0 6.1600 RPM 691 791 908 1022 1126

    BHP 0.05 0.06 0.08 0.09 0.11Sones 4.9 5.6 6.6 7.2 7.9

    700 RPM 772 857 949 1051 1149 1244BHP 0.08 0.09 0.11 0.12 0.13 0.15

    Sones 5.8 6.4 7.1 7.6 8.4 9.5800 RPM 855 937 1006 1092 1181 1269 1435

    BHP 0.11 0.13 0.14 0.16 0.17 0.19 0.23Sones 6.7 7.4 7.7 8.1 9.0 10.1 12.3

    900 RPM 939 1019 1084 1148 1224 1301 1457 1605 1738BHP 0.16 0.18 0.19 0.21 0.23 0.24 0.27 0.33 0.38

    Sones 7.7 8.3 8.6 9.0 9.7 10.8 12.9 15.2 15.51000 RPM 1024 1100 1165 1220 1280 1348 1490 1628 1762 1884

    BHP 0.21 0.23 0.25 0.27 0.28 0.31 0.34 0.38 0.44 0.50Sones 9.0 9.4 9.7 10.0 10.8 11.7 13.7 15.5 15.8 16.2

    1100 RPM 1111 1183 1246 1300 1350 1405 1526 1660 1784BHP 0.28 0.30 0.32 0.34 0.36 0.38 0.42 0.46 0.50

    Sones 10.3 10.8 11.1 11.4 12.0 12.6 14.6 15.9 16.21200 RPM 1198 1266 1327 1382 1430 1475 1582

    BHP 0.36 0.38 0.40 0.43 0.45 0.47 0.51Sones 11.9 12.5 12.7 12.7 13.2 13.8 15.7

    1300 RPM 1287 1351 1409BHP 0.45 0.48 0.50

    Sones 13.5 14.0 13.9

    BDF-80 — Belt Drive

    MAXIMUM RPM = 1885TIP SPEED = RPM x 2.356

    MAXIMUM MOTOR FRAME SIZE = 56AVERAGE OUTLET VELOCITY = CFM/0.654

    Damper Size (Outlet Side) = 93/4 x 87/8 (248 x 225)Housing Thickness = 20 ga.^Approximate Unit Weight = 70 lb. (32 kg)

    All dimensions in inches (millimeters). ^Weight shown is largest cataloged Open Drip Proof motor.

    Performance certified is for installation type D: Ducted inlet, Ducted outlet. Power rating (bhp/kW) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) from the test inlet duct in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type D: ducted inlet, ducted outlet. Ratings do not include the effects of duct end connection.

    157/8(403)

    2(51)

    5 3/8 (137)

    181/2 (470)

    93/4 (248)

    41/4 (108)

    1 (25)

    1211/16 (322)

    153/16 (386)

    87/8(226)

  • Do no

    t sele

    ct to

    the

    left

    of th

    is sy

    stem

    cur

    ve

    Damper Size (Outlet Side) = 121/4 x 101/2 (311 x 267)Housing Thickness = 20 ga.^Approximate Unit Weight = 91 lb. (41 kg)

    All dimensions in inches (millimeters). ^Weight shown is largest cataloged Open Drip Proof motor.

    ModelNumber

    FanCFM

    Static Pressure in Inches wg0.125 0.25 0.375 0.5 0.625 0.75 1 1.25 1.5 1.75

    BDF-90 800 RPM 465 584 689BHP 0.05 0.07 0.09

    Sones 3.9 4.1 5.5970 RPM 514 619 713 802

    BHP 0.08 0.10 0.12 0.15Sones 4.5 5.0 6.4 8.2

    1140 RPM 569 660 748 827 905 975BHP 0.11 0.14 0.17 0.20 0.23 0.26

    Sones 5.2 6.0 7.5 8.8 9.6 10.71310 RPM 626 708 787 863 932 1000 1125

    BHP 0.16 0.19 0.23 0.26 0.29 0.33 0.40Sones 6.6 7.3 8.9 9.4 10.2 11.2 13.5

    1480 RPM 684 761 830 901 968 1030 1150 1260BHP 0.22 0.25 0.29 0.33 0.37 0.41 0.49 0.57

    Sones 8.0 8.9 9.6 10.2 10.9 11.8 13.9 15.91650 RPM 744 817 881 943 1006 1066 1178 1285 1385

    BHP 0.30 0.34 0.38 0.42 0.46 0.50 0.59 0.68 0.77Sones 9.6 10.1 10.5 11.1 11.8 12.6 14.5 16.5 16.9

    1820 RPM 805 874 934 991 1048 1106 1213 1312 1409 1501BHP 0.39 0.44 0.47 0.52 0.57 0.61 0.71 0.80 0.90 1.00

    Sones 11.3 11.2 11.5 12.2 12.8 13.6 15.3 17.0 17.4 17.51990 RPM 872 932 990 1044 1095 1147 1250 1347 1436

    BHP 0.51 0.56 0.60 0.64 0.69 0.74 0.84 0.95 1.04Sones 12.4 12.5 12.8 13.4 14.1 14.7 16.2 17.6 18.0

    2160 RPM 940 991 1047 1098 1147 1193 1291BHP 0.64 0.69 0.74 0.78 0.83 0.89 1.00

    Sones 13.8 14.0 14.3 14.8 15.4 16.0 17.32330 RPM 1008 1051 1105 1154 1200

    BHP 0.80 0.85 0.91 0.95 1.00Sones 15.4 15.7 16.0 16.3 16.8

    2500 RPM 1077 1112BHP 0.98 1.02

    Sones 17.3 17.4

    BDF-90 — Belt Drive

    MAXIMUM RPM = 1506TIP SPEED = RPM x 2.602

    MAXIMUM MOTOR FRAME SIZE = 143TAVERAGE OUTLET VELOCITY = CFM/0.899

    Performance certified is for installation type D: Ducted inlet, Ducted outlet. Power rating (bhp/kW) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) from the test inlet duct in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type D: ducted inlet, ducted outlet. Ratings do not include the effects of duct end connection.

    241/4 (616)

    183/4(476)

    2(51)

    6 3/4 (171)

    211/4 (540)

    121/4 (311)

    41/2 (114)

    1 (25)

    157/8 (403)

    181/4 (464)

    87/8(226)

    6

  • 7

    Do no

    t sele

    ct to

    the

    left

    of th

    is sy

    stem

    cur

    ve

    ModelNumber

    FanCFM

    Static Pressure in Inches wg0.125 0.25 0.375 0.5 0.625 0.75 1 1.25 1.5 1.75

    BDF-100 800 RPM 380 501BHP 0.04 0.06

    Sones 3.6 4.81000 RPM 413 521 615

    BHP 0.06 0.09 0.12Sones 4.0 5.0 5.9

    1200 RPM 453 548 635 715 785BHP 0.09 0.13 0.16 0.19 0.23

    Sones 4.8 5.4 6.2 6.8 7.31400 RPM 498 581 660 735 804 869

    BHP 0.14 0.17 0.21 0.25 0.29 0.33Sones 6.0 6.1 6.7 7.4 7.9 8.6

    1600 RPM 548 620 691 760 825 887 1002 1104BHP 0.19 0.24 0.27 0.32 0.37 0.41 0.50 0.58

    Sones 7.6 7.4 7.4 8.1 8.7 9.7 10.9 12.51800 RPM 605 662 728 791 851 909 1020 1121 1212

    BHP 0.27 0.31 0.36 0.40 0.45 0.50 0.60 0.70 0.79Sones 9.7 8.6 8.5 8.9 9.8 10.6 11.7 13.3 14.1

    2000 RPM 666 710 768 826 882 937 1041 1139 1231 1314BHP 0.37 0.40 0.45 0.50 0.55 0.61 0.72 0.83 0.94 1.05

    Sones 10.9 9.9 9.7 10.2 11.2 11.6 12.6 13.9 14.9 15.92200 RPM 728 760 810 864 917 968 1065 1160

    BHP 0.49 0.51 0.56 0.63 0.68 0.73 0.86 0.98Sones 12.2 11.4 11.1 11.7 12.3 12.6 13.5 14.7

    2400 RPM 789 812 857 906 954 1002 1096BHP 0.63 0.65 0.69 0.76 0.83 0.88 1.01

    Sones 13.6 13.1 12.9 13.3 13.5 13.8 14.62600 RPM 851 872 907 948 995

    BHP 0.80 0.82 0.85 0.91 0.99Sones 15.1 14.7 14.7 14.6 14.9

    2800 RPM 914 933 957BHP 0.99 1.01 1.04

    Sones 16.6 16.4 16.3

    BDF-100 — Belt Drive

    Damper Size (Outlet Side) = 133/4 x 117/8 (349 x 302)Housing Thickness = 20 ga.^Approximate Unit Weight = 106 lb. (48 kg)

    All dimensions in inches (millimeters). ^Weight shown is largest cataloged Open Drip Proof motor.

    MAXIMUM RPM = 1315TIP SPEED = RPM x 2.913

    MAXIMUM MOTOR FRAME SIZE = 143TAVERAGE OUTLET VELOCITY = CFM/1.05

    Performance certified is for installation type D: Ducted inlet, Ducted outlet. Power rating (bhp/kW) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) from the test inlet duct in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type D: ducted inlet, ducted outlet. Ratings do not include the effects of duct end connection.

    261/4 (667)

    203/4(527)

    2(51)

    7 3/8 (187)

    223/4 (578)

    133/4 (349)

    41/2 (114)

    1 (25)

    177/8 (454)

    193/4 (502)

    117/8(302)

  • 8

    Do no

    t s

    elect

    to th

    e le

    ft of

    this

    syst

    em c

    urve

    ModelNumber

    FanCFM

    Static Pressure in Inches wg0.125 0.25 0.375 0.5 0.625 0.75 1 1.25 1.5 1.75

    BDF-120 1000 RPM 313 420BHP 0.05 0.08

    Sones 3.0 4.21300 RPM 338 437 518 593

    BHP 0.07 0.11 0.15 0.20Sones 3.3 5.1 5.6 5.6

    1600 RPM 370 456 535 604 666 726BHP 0.12 0.16 0.21 0.26 0.31 0.37

    Sones 4.3 6.3 6.2 6.3 7.1 8.41900 RPM 408 483 554 621 680 737 839

    BHP 0.18 0.23 0.28 0.34 0.39 0.45 0.58Sones 5.8 7.0 7.0 7.1 8.0 9.2 12.5

    2200 RPM 451 515 580 640 699 753 851 939BHP 0.26 0.31 0.37 0.43 0.50 0.56 0.70 0.84

    Sones 7.7 7.9 8.0 8.1 8.9 10.0 12.9 13.22500 RPM 504 554 608 666 719 771 866 953 1033 1110

    BHP 0.37 0.42 0.48 0.55 0.62 0.69 0.84 1.00 1.16 1.33Sones 9.4 9.6 9.0 9.2 9.9 11.0 13.3 13.6 13.9 14.1

    2800 RPM 561 592 645 694 745 793 885 969 1047BHP 0.53 0.55 0.62 0.70 0.77 0.85 1.02 1.18 1.35

    Sones 11.0 11.9 10.6 10.2 11.0 12.0 13.8 14.2 14.53100 RPM 619 635 683 727 773 819 904 988

    BHP 0.71 0.72 0.79 0.87 0.95 1.04 1.20 1.41Sones 13.2 13.2 12.5 11.7 12.1 13.2 14.3 14.8

    3400 RPM 677 689 721 766 804 847 930BHP 0.94 0.94 0.99 1.07 1.16 1.26 1.44

    Sones 14.7 14.8 14.1 13.6 13.7 14.3 15.13700 RPM 737 744 761 803 844 877

    BHP 1.21 1.21 1.22 1.32 1.41 1.50Sones 16.6 16.6 16.7 15.3 15.6 15.7

    4000 RPM 796 802 814BHP 1.52 1.53 1.54

    Sones 18.6 18.6 18.8

    BDF-120 — Belt Drive

    Damper Size (Outlet Side) = 16 x 133/8 (406 x 340)Housing Thickness = 20 ga.^Approximate Unit Weight = 142 lb. (64 kg)

    All dimensions in inches (millimeters). ^Weight shown is largest cataloged Open Drip Proof motor.

    MAXIMUM RPM = 1119TIP SPEED = RPM x 3.436

    MAXIMUM MOTOR FRAME SIZE = 182TAVERAGE OUTLET VELOCITY = CFM/1.45

    Performance certified is for installation type D: Ducted inlet, Ducted outlet. Power rating (bhp/kW) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) from the test inlet duct in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type D: ducted inlet, ducted outlet. Ratings do not include the effects of duct end connection.

    33 (838)

    223/4(578)

    2(51)

    7 7/8 (200)

    271/4 (692)

    16 (406)

    55/8 (143)

    1 (25)

    197/8 (505)

    241/8 (613)

    133/8(340)

  • 9

    ModelNumber

    FanCFM

    Static Pressure in Inches wg0.125 0.25 0.5 0.75 1 1.25 1.5 1.75 2 2.25

    BDF-150 2500 RPM 374 406 517BHP 0.27 0.29 0.42

    Sones 6.6 7.0 9.02830 RPM 411 444 527 622

    BHP 0.37 0.41 0.53 0.68Sones 8.0 8.6 9.6 13.1

    3160 RPM 449 483 544 637 714BHP 0.50 0.56 0.65 0.82 1.00

    Sones 9.6 9.7 10.5 13.5 16.03490 RPM 488 523 569 646 728 799

    BHP 0.65 0.73 0.80 0.98 1.17 1.37Sones 11.0 11.2 11.6 13.6 16.5 19.1

    3820 RPM 528 561 607 662 741 810 875BHP 0.84 0.93 1.03 1.16 1.37 1.58 1.80

    Sones 12.6 13.0 13.2 14.3 17.0 19.3 204150 RPM 570 598 645 685 749 826 886 945

    BHP 1.07 1.16 1.29 1.37 1.58 1.81 2.04 2.29Sones 14.5 14.8 15.0 15.6 17.4 19.6 20 21

    4480 RPM 611 637 685 720 770 833 902 957 1010 1071BHP 1.33 1.42 1.59 1.67 1.84 2.08 2.32 2.57 2.83 3.15

    Sones 16.3 16.5 17.1 17.5 18.3 19.9 21 22 22 234810 RPM 653 675 724 758 792 847 911 973

    BHP 1.63 1.73 1.93 2.03 2.13 2.38 2.64 2.89Sones 18.0 18.2 19.1 19.9 20 20 21 22

    5140 RPM 695 715 763 797 827 869 919BHP 1.97 2.07 2.32 2.44 2.53 2.72 2.97

    Sones 19.8 20 21 22 22 21 225470 RPM 737 756 801 836 866 893

    BHP 2.36 2.47 2.72 2.89 3.00 3.10Sones 22 22 23 24 24 23

    5800 RPM 780 797BHP 2.80 2.91

    Sones 24 24

    BDF-150 — Belt Drive

    Damper Size (Outlet Side) = 191/8 x 163/8 (486 x 416)Housing Thickness = 20 ga.^Approximate Unit Weight = 221 lb. (100 kg)

    All dimensions in inches (millimeters). ^Weight shown is largest cataloged Open Drip Proof motor.

    MAXIMUM RPM = 1071TIP SPEED = RPM x 3.927

    MAXIMUM MOTOR FRAME SIZE = 184TAVERAGE OUTLET VELOCITY = CFM/2.05

    Performance certified is for installation type D: Ducted inlet, Ducted outlet. Power rating (bhp/kW) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) from the test inlet duct in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type D: ducted inlet, ducted outlet. Ratings do not include the effects of duct end connection.

    343/4 (883)

    273/4(705)

    2(51)

    9 7/8 (251)

    325/8 (829)

    191/8 (486)

    63/4 (171)

    11/2 (38)

    237/8 (607)

    285/8 (727)

    163/8(416)

  • 10

    Do no

    t sele

    ct to

    the

    left

    of th

    is sy

    stem

    cur

    ve

    Performance certified is for installation type D: Ducted inlet, Ducted outlet. Power rating (bhp/kW) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) from the test inlet duct in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type D: ducted inlet, ducted outlet. Ratings do not include the effects of duct end connection.

    BDF-180 — Belt Drive

    ModelNumber

    FanCFM

    Static Pressure in Inches wg0.25 0.5 0.75 1 1.25 1.5 1.75 2 2.25 2.5

    BDF-180 4000 RPM 353 448 529BHP 0.48 0.68 0.91

    Sones 7.6 12.1 14.64540 RPM 375 463 540 610 673

    BHP 0.63 0.86 1.10 1.36 1.62Sones 8.9 13.6 15.2 16.1 17.0

    5080 RPM 400 479 553 621 682 738BHP 0.82 1.08 1.34 1.62 1.91 2.19

    Sones 10.8 14.9 15.8 16.8 17.4 15.55620 RPM 426 498 568 632 693 748 799

    BHP 1.05 1.34 1.62 1.90 2.22 2.55 2.85Sones 13.0 15.9 16.6 17.6 17.8 16.3 15.9

    6160 RPM 453 519 585 647 704 759 810 857 903BHP 1.31 1.63 1.94 2.26 2.56 2.93 3.28 3.62 3.98

    Sones 15.7 17.0 17.5 18.5 18.3 17.2 16.8 17.3 18.46700 RPM 480 544 603 662 718 770 821 868 912 954

    BHP 1.62 1.98 2.32 2.65 3.00 3.33 3.73 4.11 4.49 4.85Sones 17.9 18.1 18.6 19.5 18.9 18.2 17.8 18.5 19.4 21

    7240 RPM 510 568 623 680 733 784 832 879 923BHP 2.00 2.37 2.73 3.11 3.47 3.84 4.19 4.63 5.05

    Sones 18.9 19.3 19.8 20 19.9 19.3 18.9 19.6 207780 RPM 540 594 647 698 749 799 846 890

    BHP 2.44 2.81 3.22 3.61 3.99 4.40 4.79 5.17Sones 20 20 21 21 21 20 20 21

    8320 RPM 570 621 671 717 768 814BHP 2.95 3.31 3.75 4.17 4.60 5.00

    Sones 21 22 23 23 22 228860 RPM 601 648 696 741 786

    BHP 3.51 3.86 4.35 4.80 5.25Sones 23 24 24 24 24

    9400 RPM 632 675 722BHP 4.15 4.48 5.00

    Sones 24 25 26

    Damper Size (Outlet Side) = 221/2 x 187/8 (572 x 479)Housing Thickness = 20 ga.^Approximate Unit Weight = 304 lb. (138 kg)

    All dimensions in inches (millimeters). ^Weight shown is largest cataloged Open Drip Proof motor.

    MAXIMUM RPM = 958TIP SPEED = RPM x 4.843

    MAXIMUM MOTOR FRAME SIZE = 215TAVERAGE OUTLET VELOCITY = CFM/2.86

    401/4 (1022)

    313/4(806)

    2(51)

    10 1/2 (267)

    413/4 (1060)

    221/2 (572)

    95/8 (245)

    11/2 (38)

    277/8 (708)

    371/2 (953)

    187/8(480)

  • 11

    Do no

    t sel

    ect t

    o th

    e le

    ft o

    f thi

    s sy

    stem

    cur

    ve

    Performance certified is for installation type D: Ducted inlet, Ducted outlet. Power rating (bhp/kW) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) from the test inlet duct in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type D: ducted inlet, ducted outlet. Ratings do not include the effects of duct end connection.

    BDF-200 — Belt Drive

    ModelNumber

    FanCFM

    Static Pressure in Inches wg0.25 0.5 0.75 1 1.5 1.75 2 2.5 2.75 3

    BDF-200 5000 RPM 310 394 464BHP 0.57 0.84 1.09

    Sones 12.5 12.6 12.36000 RPM 340 413 480 538

    BHP 0.88 1.16 1.49 1.77Sones 13.1 13.2 13.3 14.0

    7000 RPM 374 437 498 556 656 705BHP 1.28 1.59 1.93 2.33 3.04 3.50

    Sones 14.4 14.0 14.4 15.1 16.8 18.38000 RPM 411 465 521 574 671 712 757

    BHP 1.80 2.17 2.53 2.92 3.82 4.16 4.63Sones 15.9 14.8 15.7 16.4 18.0 19.2 21

    9000 RPM 449 498 546 596 689 731 770 846 885BHP 2.45 2.87 3.26 3.70 4.65 5.15 5.63 6.52 7.11

    Sones 17.6 17.0 17.3 18.0 19.4 20 21 22 2210000 RPM 489 533 576 620 707 749 788 860 892 928

    BHP 3.26 3.71 4.19 4.60 5.56 6.15 6.71 7.77 8.15 8.71Sones 19.6 19.4 19.3 19.9 21 22 23 24 24 24

    11000 RPM 529 569 610 647 730 768 806 878 911 943BHP 4.24 4.72 5.26 5.75 6.77 7.27 7.88 9.13 9.73 10.29

    Sones 22 22 22 22 23 24 24 25 26 2612000 RPM 571 607 644 680 754 791 827 896 929 961

    BHP 5.42 5.94 6.49 7.06 8.10 8.70 9.27 10.56 11.25 11.92Sones 25 25 25 25 26 26 27 28 28 28

    13000 RPM 613 646 679 714 779 815 850 915 947 979BHP 6.81 7.34 7.91 8.56 9.70 10.27 10.93 12.14 12.87 13.63

    Sones 28 28 28 28 29 29 29 30 31 3114000 RPM 655 686 717 748 810 840 874 938 968 997

    BHP 8.42 8.97 9.59 10.25 11.57 12.14 12.74 14.14 14.79 15.44Sones 31 31 31 32 31 32 32 33 34 35

    15000 RPM 697 726 756 783 843 871 899BHP 10.30 10.80 11.50 12.20 13.60 14.30 14.90

    Sones 35 35 35 35 35 35 35

    Damper Size = 231/8 x 251/4 (587 x 638)Housing Thickness = 20 ga.^Approximate Unit Weight = 560 lb. (254 kg)

    All dimensions in inches (millimeters). ^Weight shown is largest cataloged Open Drip Proof motor.

    MAXIMUM RPM = 997TIP SPEED = RPM x 5.318

    MAXIMUM MOTOR FRAME SIZE = 256TAVERAGE OUTLET VELOCITY = CFM/3.87

    501/4 (1276)

    393/4(1010)

    2(51)

    12 1/2 (318)

    491/4 (1251)

    231/8 (588)

    13 (330)

    11/2 (38)

    36 (914)

    451/8 (1146)

    251/4(641)

  • Greenheck warrants this equipment to be free from defects in material and workmanship for a period

    of one year from the purchase date. Any units or parts which prove defective during the warranty

    period will be replaced at our option when returned to our factory, transportation prepaid. Motors are

    warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck

    prove defective during this period, they should be returned to the nearest authorized motor service

    station. Greenheck will not be responsible for any removal or installation costs.

    As a result of our commitment to continuous improvement, Greenheck reserves the right to change

    specifications without notice.

    P.O. Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com

    Building Value in Air

    Our Warranty

    Prepared to SupportGreen Building Efforts

    Catalog BDF Rev. 4 July 2007 RGCopyright © 2007 Greenheck Fan Corp.

    Specifications

    Duct mounted supply, exhaust, or return air fans shall be of the centrifugal, belt driven, inline type. The fan housing shall be of the rectangular design and constructed of heavy gauge galvanized steel, and shall include rectangular duct mounting collars on the inlet and outlet.

    Removable panels shall be provided on each side of the fan cabinet, and shall be of sufficient size to permit access for service to all of the fans internal components without further dismantling of the cabinet.

    The fan wheel shall be of the galvanized steel, forward curved, centrifugal type. Wheels shall be statically and dynamically balanced.

    Motors shall be of the heavy duty type with permanently lubricated and sealed ball bearings. The wheel shaft shall be ground and polished steel mounted in permanently sealed bearings. The bearings shall be selected for a minimum L10 life in excess of 100,000 hours (L50 average life of 500,000 hours)

    at maximum cataloged RPM. Drives shall be sized for a minimum of 150% of the driven horsepower. Pulleys shall be of the machined cast type, keyed and securely attached to the wheel and motor shafts. The motor pulley shall be adjustable for final system balancing.

    Heavy gauge galvanized steel mounting rails shall support the drive assembly, motor, wheel, and scroll.

    Fans shall have true internal vibration isolation (no metal to metal contact) of the drive assembly, motor, wheel, and scroll.

    All fans shall be tested in an AMCA Accredited Laboratory and shall be certified to bear the AMCA Certified Ratings Seal for sound and air performance.

    Fans shall be Greenheck Model BDF, manufactured by Greenheck Fan Corporation in Schofield, Wisconsin.

    Greenheck delivers value to mechanical engineers by helping them solve virtually any air quality challenges their clients face with a comprehensive selection of

    top quality, innovative air-related equipment. We offer extra value to contractors by providing easy-to-install, competitively priced, reliable products that arrive on time.

    And building owners and occupants value the energy efficiency, low maintenance and quiet dependable operation they experience long after the construction project ends.