LPS series and CB series Centralised systems for emergency lighting www.daisalux.com / 902 208 108
32

Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

Aug 04, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

LPS series and CB series

Centralised systems for emergency lighting

www. d a i s a l u x . c o m / 9 0 2 2 0 8 1 0 8

Page 2: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output
Page 3: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output
Page 4: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

Table of Contents

Operation and specifications 4

Wiring diagrams 6

Reference and specifications table 7

Order forms 8

Accessories 9

Monitoring unit 10

DaisaTest System 22

Luminaires for centralised units 24

Pages

4 to 11

LPS

Page 5: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

3

Operation and specifications 12

Wiring diagrams 14

Reference and specifications table 15

Order forms 16

Accessories 19

Monitoring unit 20

DaisaTest System 22

Luminaires for centralised units 24

Pages

12 to 21

CB

Page 6: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

4

• Maximum output power 300 W·(up to 3 hours duration).

• Power factor: 0.98 when fully charged.

• 4 A output circuit with double terminal, maintained/non-maintained configuration and fuse-free dynamic short-circuit protection.

• Option of installing Daisalux beacons with dimming.

• The DBR system can also be installed in ELC-type luminaires.

• Sealed valve-regulated lead-acid battery (VRLA).

• High rate battery charge.

• Top-mounted power supply intakes and outlets.

• Control panel with graphic display and keyboard for configuration and monitoring of the central battery.

• Front-loading mini-USB for PC connection.

• Ethernet connection with PC (LPSLan accessory) or web server for DaisaTest system.

• Integration with DaisaTest system for maintenance management (EN-50172).

•Inputs:• 4 digital inputs (detector connection)

• 1 analogue input (1-10 V) for regulating Daisalux beacons

• 1 Daisalux remote control input.

•Alarms: • 4 dry contacts for failures, alarms and central battery status (EN-50171).

LPSSeries

Centralised units|Operationandspecifications

The LPS Series centralised units are designed and constructed in accordance with the EN 50171 standard for uninterruptible-type emergency lighting. They are low-power centralised wall-mounted units with an output voltage of 24 Vdc.

Cable inletand outlet Connection terminal block

Rectifierand circuitboard

Pb VRLA batteries

Control panel

Fuses for batteries

Ventilation

Wallmounting bracket

Internal operation diagram

Page 7: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output
Page 8: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

6 Centralised units|Wiringdiagrams

Connectionterminalblock

Power sourceRemote control Auxiliary inputs

Dry contacts 0-10 V beacon lighting regulation

Outputs

Each LPS unit output circuit is configured as "maintained / non-maintained”. This operating mode is assigned to all non-electric line communication (non-ELC) luminaires connected to said circuit.

If luminaires with electric line communication (ELC) are used, the "maintained / non-maintained" operating mode is individually configured on each luminaire and is independent of the circuit configuration.

The DaisaTest application (through the LPSLan communication accessory) can monitor and control an indefinite number of devices.

Ethernet (LPSLan) or USB LPSLan via web

6 outputcircuits

Maximum: 4 A per circuit

6 outputcircuits

Maximum: 4 A per circuit

Option ofmultiple units

6 outputcircuits

Maximum: 4 A per circuit

Power supply input

LPSSeries

Page 9: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

7Referenceandspecificationstable|Centralised units

LPS24-26 LPS24-65

Inputs 230V 110-127V 230V 110-127VPower source voltage 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz

Maximum cable duct diameter 2.5 mm2

Input protection 6.3 AT fuse

Analogue (Daisalux beacon regulation) 1 (0-10 Vdc)Auxiliary inputs 4Remote control 1

OutputsOutput voltage: 24 Vdc (21.6 V - 30 V)

Maximum output cable diameter 2.5 mm2

Maximum output power Duration 0.5 h 300 W 200 W 300 W 200 W 1 h 300 W 200 W 300 W 200 W 1.5 h 211 W 200 W 300 W 200 W 2 h 170 W 170 W 300 W 200 W 3 h 124 W 124 W 300 W 200 W 6 h 69 W 69 W 172 W 172 W 8 h 55 W 55 W 136 W 136 WNo. of output circuits 6

Overcurrent protection 4.1 A Overvoltage 34V Short circuit 12-24 A constant until thermal protection Self-reset (detection< 20 s) Overheating 80 ºC self-reset (detection < 20 s)Dry contacts 4 (3 fixed under EN 50171)

InteractionandconnectivityUSB Central battery front-mounted connection

Ethernet or Wifi Optional with LPSLan accessoryDisplay 160x104-dot graphic display

with central battery front-mounted keyboard

GeneralProtection class Class IDegree of protection IP20Ambient working temperature between 0 and 25 ºCNoise level < 40 dBWeight: 27 kg 56 kgBattery 24V / 26Ah Pb VRLA 24V / 65Ah Pb VRLA

SoftwareWinCBS Yes

Soft-DaisaTest Optional with ELC unit and luminaires

Page 10: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

8 Centralised units|Orderform

Orderform

Model Dimensions Battery Durationinhours(configurable)

LPS24-26 405x400x225 24V - 26 Ah 0.5 / 1 / 1.5 / 2 / 3 / 6 / 8

LPS24-65 605x400x225 24 V - 65 Ah 0.5 / 1 / 1.5 / 2 / 3 / 6 / 8

LPS24-26

Finishes

Finish Description Marking

Voltage 220-230V 50/60 Hz ---- voltage 110-127V 50/60 Hz (110-127V)

Reference Description

LPSLan Communication module Ethernet and Wifi.

DR-3 Remote three-phase/single-phase network fault detector.

Accessories

LPSSeries40

0

405

400

225 16

LPS24-65

400

225 16

600

605

Page 11: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

9Accessory|Centralised units

Web server

Communication modulesLPSLan communication module.Communication module via Ethernet connection with integrated web server.Enables monitoring of the central battery and ELC-type luminaires.

DR-3remotedetector.

Network fault detector for centralised LPS series units.

Monitors the status of the network (3 phases and neutral) which it shows by flashing a front-mounted LED (off during network downtime).

It has two contacts (NO, NC) connected to the LPS central battery auxiliary inputs and, in the event of a network fault, enables configuration of the output circuit start command.

54

45

44

50

83

35

Page 12: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

10 Centralised units|Monitoringunit

The monitoring unit controls the most critical aspects of safety (EN-50171) of the LPS units such as the status of the battery-charging rectifier, the general condition of the central battery, the status of the output circuits and runs functional, duration and battery capacity tests.

It controls the charge voltage and current of the batteries and their temperature.

General status synoptic display

A control panel with graphic LCD display enables data monitoring and performs the following configuration tasks:

• Definition of the central battery’s duration.

• Configuration of the circuits in maintained / non-maintained mode.

• Configuration of the frequency of the tests, day of the week,

test schedule, automatic/manual mode.

• Input configuration.

• Output circuit configuration.

• Display of scenarios programmed with winCBS or web server.

• Zoning of communicating luminaires (ELC)

• Operational configuration of ELC-type luminaires (maintained/non-maintained)

• Display of ELC-type luminaire status.

• Internal memory with central battery configuration log, test results and status of ELC-type luminaires.

LPSSeries

Page 13: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

11Monitoringunit|Centralised unit

Menuwindows

General condition of the central battery, batteries, rectifier and fault alarms

Configuration of functional, duration and battery capacity tests

Configuration of the inputs, output alarms, duration and web server.

Execution of actions and scenarios

General system information

Monitoring and configuration of communicating ELC circuits and luminaires.

Menu

System Test Config Outputs Actions Info

SistemaSystem Test

Config

#

Acciones

Salidas

Info

Test

Config

Actions

Outputs

Info

Page 14: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

CBSeries

• Maximum of 20 output circuits in CB800 and CB1250 units, 40 circuits in CB2500 and 60 circuits in CB5000.

• Option of configuring different autonomies for each output circuit.

• Sealed valve-regulated lead-acid battery (VRLA).

• High rate battery charge.• Top-mounted power supply intakes and outlets.

• Control panel for configuration and monitoring of the central battery.

• Front-loading mini-USB for PC connection.

• Ethernet connection with PC for DaisaTest System.

• Integration with DaisaTest system for maintenance management (EN-50172).

• The DBR system can also be installed in ELC-type luminaires.

Inputs:• 2 auxiliary inputs for remote actions.

• Communication port for EV-BUS.

• 1 x 230 V output for installation of EV-ALIM bus power source.

•Alarms: • 5 dry contacts for faults, alarms and central battery status (EN-50171).

The CB series centralised units for emergency lighting in switched mode or without breaker are designed and built in accordance with EN 50171. It is a centralised unit with 230 Vac / 24 Vdc output voltages and a maximum power output of 800 VA, 1250 VA, 2500 VA and 5000 VA. (Contact Daisalux for information about other outputs).

Power supply input and outputs

Distribution sub-rack

Rectifier(ac / dc)

Distribution cards

Pb VRLAbatteries

Ventilation

Monitoringunit

Invertor(dc / ac)

Electrical protection

Internal operation diagram

12 Centralised units|Operationandspecifications

Page 15: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output
Page 16: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

CBSeries

Connectionterminalblock

Each CB unit output circuit is configured as "maintained / non-maintained" and assign this operating mode to all luminaires without communication (non-ELC) connected to said circuits.

If the unit and luminaires are communicated (ELC), "maintained / non-maintained" operation is individually configured in each luminaire and is independent of the circuit configuration.

The DaisaTest application can monitor and control an indefinite number of units. No communication accessory is required.

CB800/1250 outputs

Power supply input

Dry contacts

Ethernet or USB

Up to20 outputcircuits

Up to 20 outputcircuits

Up to 40 outputcircuits

Up to 60 outputcircuits

Power supply input

CB800 CB1250 CB2500 CB5000

14 Centralised units |Wiringdiagrams

Page 17: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

CB800 CB1250 CB2500 CB5000

Inputs Power source voltage 230V 50/60 Hz 230/400V 50/60 HzMaximum cable duct diameter 2.5 mm2 4 mm2 4x4 mm2

Input protection 10 A 16 A 4x20 AAuxiliary inputs 2BUS-EV 1

OutputsOutput voltage 230V 50 Hz / 230V 60 HzMaximum output cable diameter 2.5 mm2

Maximum output power 800 VA 1250 VA 2500 VA 5000 VANo. of distribution sub-racks 1 1 or 2 2 or 3No. of cards per sub-rack 10

Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A

No. of output circuits up to 20 up to 40 up to 60

Output protection (fuse) 230 Vac 2 A 4 A 4 A 6.3 A 6.3 A 24 Vdc 4 A 6.3 AIsolation detector (IT) Non-interruptible and emergency modeDry contacts 5 (3 fixed under EN 50171)

InteractionandconnectivityUSB Central Battery front-mounted connectionEthernet Connection on the distribution terminal blockDisplay 160x104-dot graphic display

with central battery front-mounted keyboardSD board central battery front-mounted

GeneralProtection class Class IDegree of protection IP20Ambient working temperature between 0 and 25 ºC 24 V from 55 Ah 24 V from 75 Ah up to 150 Ah up to 150 Ah Batteries (depending on power and 24V - 200Ah with 24V from 200Ah 24V from 90Ah 24V from 250Ah required duration) additional cabinet up to 250 Ah with up to 2x250 Ah up to 4x250 Ah of batteries additional cabinet of batteries No. of rectifications 1 2 3 to 6Redundancy OptionalInvertor 1000 VA 1500 VA 3000 VA 2x3000 VAKey 5 mm double bitted (other types of key optional)

AccessoriesEV-DRY YesEV-PD YesEV-ALIM Yes

SoftwareWinCBS YesSoft-DaisaTest Optional with ELC unit and luminaires

15Referenceandspecificationstable|Centralised units

Page 18: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

16 Centralised units| Orderform

OrderformCB800

Reference Description

EV-DR Remote three phase/single phase network fault detector

EV-PD Level detector.

EV-ALIM bus power source.

Accessories

CB800-1-1- - - - - -

selectoption

Capacityof thebattery

in Ah (24V)

55657590100150200

90 Ah 1 h 150 Ah 2 h 200 Ah 3 h

selectoption

Conventionalor

communicating

---- (of series)ELC

(From0to10)

Numberof outputboards2x230Vac

(From0to10)

Number of output boards 1x230V

ac

The total number of distribution cards(sum of the four columns)

may not exceed 10.

(From0to10)

Numberof outputboards2x24Vdc

Estimation of batteries based on

duration

(From0to10)

Numberof outputboards1x24Vdc

With batteries up to 150 Ah

1935

600

400

CB800

With additional battery cabinet (200 Ah)

CBSeries

600

400

1335

Page 19: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

17Orderform|Centralised units

OrderformCB1250

Reference Description

EV-DR Remote three phase/single phase network failure detector

EV-PD Level detector.

EV-ALIM Bus power source.

Accessories

CB1250-1-1- - - - - -

selectoption

Capacityof thebattery

in Ah (24V)

7590100150200250

100 Ah 1 h 200 Ah 2 h 250 Ah 3 h

selectoption

Conventionalor

communicating

---- (of series)ELC

(From0to10)

Number of output boards 2x230V

ac

(From0to10)

Number of output boards 1x230V

ac

The total number of distribution cards(sum of the four columns)

may not exceed 10.

(From0to10)

Number of output boards 2x24Vdc

Estimation of batteries based on

duration

(From0to10)

Number of output boards 1x24Vdc

With batteries up to 150 Ah

CB1250

With additional battery cabinet (200 and 250 Ah)

600

400

1335

1935

600

400

Page 20: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

18 Centralised unit|Examplesoforder

OrderformCB2500

CB2500-1-2- - - - - -selectoption

Capacity of the battery

in Ah (24V)

901001502002502x1502x2002x250 200 Ah 1 h

2x200 Ah 2 h 2x250 Ah 3 h

selectoption

Conventionalor

communicating

---- (of series)ELC

(From0to20)

Number of output boards 2x230V

ac

(From0to20)

Numberof outputboards1x230Vac

The total number of distribution cards(sum of the four columns)

may not exceed 20.

(From0to20)

Number of output boards 2x24Vdc

Estimation of batteries based on

duration

(From0to20)

Number of output boards 1x24Vdc

CB5000

Reference Description

EV-DR Remote three phase/single phase network fault detector

EV-PD Level detector.

EV-ALIM Bus power source.

Accessories

Orderform

Reference Description

EV-DR Remote three phase/single phase network fault detector

EV-PD Level detector.

EV-ALIM Bus power source.

Accessories

CB5000-3-3- - - - - -

4x150 Ah 1 h 4x200 Ah 2 h 4x250 Ah 3 h

(From0to30)

Number of output boards 2x230 V

ac

(From0to30)

Number of output boards 1x230V

ac

The total number of distribution cards(sum of the four columns)

may not exceed 30.

(From0to30)

Number of output boards 2x24Vdc

Estimation of batteries based on

duration

(From0to30)

Number of output boards1x24 Vdc

selectoption

Capacityof thebattery

in Ah (24V)

2502x1502x2002x250 4x1504x2004x250

selectoption

Conventionalor

communicating

---- (of series)ELC

CBSeries13

35

1200

400

2135

1200

600

Page 21: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

RemoteEV-DRnetwork faultdetector• Network fault detector for CB

series centralised unit.• Monitors the status of the

network (3 phases and neutral) which it shows by flashing a front-mounted LED (off during network downtime).

• In the event of a network failure it sends a signal via the EV bus to the CB unit which enables configuration of the command to activate one or more output circuits.

• Sending signal to centralised unit via EV bus.

Leveldetector EV-PD• Level detector for CB series

centralised unit.• It has two monitoring inputs

(1-2 and 2-3) that enable configuration of activation order of one or more central battery output circuits.

• Sending signal to centralised unit via EV bus.

Buspowersource EV-ALIM• Power source for EV devices

connected to centralised CB series unit.

• It supplies the devices connected to the unit through the EV bus itself.

• The number of devices supplied depends on their distance from the power source.

• The capacity is a maximum of 10 devices at a distance of 400 m.

19Accessory|Centralised units

Accessoryconnection

90

71

1870

83

54

45

44

50

54

45

44

50

83

35

Page 22: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

20 Centralised units|Monitoringunit

The monitoring unit controls the most critical aspects of safety (EN-50171) of the CB units such as the status of

the battery-charging rectifier, the general condition of the central battery, the status of the inverter, status of

the output circuits and runs functional, duration and battery capacity tests.

It controls the charge voltage and current of the batteries

and their temperature.

A control panel with graphic LCD display enables data monitoring and performs the following configuration tasks:

• Definition of the general duration of the central battery or output circuits.

• Configuration of the output circuits as maintained / non-maintained and ELC luminaires.

• Configuration of the frequency of the tests, day of the week, test schedule, automatic/manual mode.

• Input configuration.

• Output configuration.

• Configuration of EV-DR and EV-PD detectors.

• SD card with central battery configuration log, test results and status of the ELC-type luminaires.

Generalstatussynopticdisplay

CBSeries

Page 23: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

21Monitoringunit|Centralised unit

Menuwindows

Status general of the central battery, batteries, rectifier and fault alarms

Configuration of functional, duration and battery capacity tests

Central battery configuration, dry contacts and Aux in

Execution of actions General system information

Output circuit and communicating luminaire configuration

Menu

System Test Config Devices Actions Info

SistemaSystem Test

Config

#

Acciones

Salidas

Info

Test

Config

Actions

Devices

Info

Page 24: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

22 Centralised unit|DaisaTestSystem

DaisaTestSystemA Daisatest System is a

type of emergency lighting installation capable of monitoring the status of each centralised unit and

emergency luminaire.

The system is compatible with installations due to the use of autonomous luminaires and centralised systems. It is

capable of including the two integrated systems in the same software in a single

installation.

The communication technology for centralised systems

is known as ELC (electric line communication) and

does not require a specific communication cable. The

central battery's own power cable to the luminaires also

carries the communication signal between the emergency luminaires and the system.

Based on the EN 50172 and EN 62034 (IEC 62034) standards,

the system constantly monitors and supervises the status of the installation. It runs regular operating

and duration tests on the centralised unit and

luminaires.

It makes maintenance proposals based on criteria previously set by the user.

Building and plant plan

window.A logical

plans browsing menu makes

identification of the status of the luminaires and units easy

to access.

General window of the installation.

Communication tree window. It provides

identification of the system

wiring and communication

structure.

DaisaTestSoftware

Page 25: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

Note:

Both the central battery and the luminaires must be ELC if CB series central batteries units are used with DaisaTest System.When LPS series central batteries are used, the LPSLan accessory and the emergency luminaires that must be ELC must be selected together with the central batteries.

23DaisaTestsystem|Centralised unit

Central battery specs sheet window.

Luminaire specs sheet window.Luminous flux regulation option (dimming) of luminaires and activation of the luminosity sensor (eco-permanence) configured as maintained.

Page 26: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

24 Centralised unit|Luminairesforcentralisedunits

Luminaires

S lens ESP lens ES lens HydraIzar

Myra GaliaNorma Iris Sol

Hydra-G NovaArgos-MArgos-DArgus

Orto Galia-B Galia-AD Orto-SGalia-S

AD lens EST lensBlock R lens C lens

Page 27: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

Luminairesforcentralisedunit|Centralised units 25

Vir 160x160Vir 210x210Vir 320x195Ikus 220x220

Carril Flame-proof Zenit Zenit EstancoZenit PL

Lisu

Ikus

AquaLecuAlzir-InoxAlzir Lyra

Leda Clavo

Beaconlighting

Page 28: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output
Page 29: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output
Page 30: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output
Page 31: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output
Page 32: Centralised systems for emergency lighting · 2 or 3 No. of cards per sub-rack 10 Distribution cards 230 Vac 2x1.5 A 2x2.5 A 2x2.5 A 1x5 A 1x5 A 24 Vdc 2x2.5 A 1x5 A No. of output

All the models that appear in this catalogue have been created and patented by Daisalux SAU and are for the exclusive use of this company.Daisalux reserves the right to amend the information in this catalogue without prior notice.

DOC-CENTRAL-EN / Version 1 – Review 1 - 15/04/2018

Designed andmanufactured

in

w w w . d a i s a l u x . c o m

i n f o @ d a i s a l u x . c o m