3. CENTER OF GRAVITY .......................................................................................................................................... PLFY-8
* Nominal conditions *1, *2 are referred to in the Specification sheet.
PLFY-3PLFY-P-NCMU-E/NBMU-E (Feb. 2009)
PLFY-P-NCMU-E PLFY-P-NBMU-E
Model PLFY-P08NCMU-E PLFY-P12NCMU-E PLFY-P15NCMU-EPowersource 1-phase 208-230 V 60HzCoolingcapacity*1 (Nominal)
BTU / h 8,000 12,000 15,000 kW 2.3 3.5 4.4
Powerinput kW 0.05 0.06 0.06 Current input A 0.23 0.28 0.28
Heatingcapacity*2 (Nominal)
BTU / h 9,000 13,500 17,000 kW 2.6 4.0 5.0
Powerinput kW 0.05 0.06 0.06 Current input A 0.23 0.28 0.28
Externalfinish Galvanized Steel Sheet
External dimension H x W x Din. 9-1/4 x 22-7/16 x 22-7/16 9-1/4 x 22-7/16 x 22-7/16 9-1/4 x 22-7/16 x 22-7/16mm 235 x 570 x 570 235 x 570 x 570 235 x 570 x 570
Netweight lbs (kg) 34 (15.5) 37 (17) 37 (17)
Decoration panel
Model SLP-15AAUW SLP-15AAUW SLP-15AAUWExternalfinish Munsell No. 6.4Y 8.9/0.4Dimension in. 25/32 x 25-19/32 x 25-19/32 25/32 x 25-19/32 x 25-19/32 25/32 x 25-19/32 x 25-19/32H x W x D mm 20 x 650 x 650 20 x 650 x 650 20 x 650 x 650Net Weight lbs (kg) 7(3) 7(3) 7(3)
cfm 280-320-350 320-350-390 320-350-390m3 / min 8.0-9.0-10.0 9.0-10.0-11.0 9.0-10.0-11.0L / s 133-150-167 150-167-183 150-167-183
Soundpressurelevel(Low-Mid-High) (measured in anechoic room) dB <A> 29-32-38 (208-230V) 30-34-39 (208-230V) 31-35-40(208-230V)
Insulation material PolyethylenefoamAirfilter PolypropylenehoneycombfabricProtection device FuseRefrigerantcontroldevice LEVConnectable outdoor unit R410A,R22 CITY MULTI
VentilationAir:Providingsufficientventilationairisanimportantpartofeverybuildingdesign.ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.
1. SPECIFICATIONS
Note: *1Nominalcoolingconditions *2Nominalheatingconditions Unit converter
Model PLFY-P12NBMU-E PLFY-P15NBMU-E PLFY-P18NBMU-EPowersource 1-phase 208-230 V 60HzCoolingcapacity*1 (Nominal)
BTU / h 12,000 15,000 18,000 kW 3.5 4.4 5.3
Powerinput kW 0.03 0.04 0.05 Current input A 0.22 0.29 0.36
Heatingcapacity*2 (Nominal)
BTU / h 13,500 17,000 20,000 kW 4.0 5.0 5.9
Powerinput kW 0.02 0.03 0.04 Current input A 0.14 0.22 0.29
Externalfinish Galvanized steel sheet
External dimension H x W x Din. 10-3/16 x 33-3/32 x 33-3/32 10-3/16 x 33-3/32 x 33-3/32 10-3/16 x 33-3/32 x 33-3/32mm 258 x 840 x 840 258 x 840 x 840 258 x 840 x 840
Netweight lbs (kg) 49 (22) 49 (22) 51 (23)
Decoration panel
Model PLP-40BAU PLP-40BAU PLP-40BAUExternalfinish Munsell No. (6.4Y 8.9/0.4)Dimension H x W x D
in. 1-3/8 x 37-13/32 x 37-13/32 1-3/8 x 37-13/32 x 37-13/32 1-3/8 x 37-13/32 x 37-13/32mm 35 x 950 x 950 35 x 950 x 950 35 x 950 x 950
VentilationAir:Providingsufficientventilationairisanimportantpartofeverybuildingdesign.ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.
1. SPECIFICATIONS
Note: *1Nominalcoolingconditions *2Nominalheatingconditions Unit converter
Model PLFY-P24NBMU-E PLFY-P30NBMU-E PLFY-P36NBMU-EPowersource 1-phase 208-230 V 60HzCoolingcapacity*1 (Nominal)
BTU / h 24,000 30,000 36,000 kW 7.0 8.8 10.5
Powerinput kW 0.06 0.07 0.16 Current input A 0.43 0.51 1.07
Heatingcapacity*2 (Nominal)
BTU / h 27,000 34,000 40,000 kW 7.9 10.0 11.7
Powerinput kW 0.05 0.06 0.15
Current input A 0.36 0.43 1.00
Externalfinish Galvanized steel sheet
External dimension H x W x Din. 10-3/16 x 33-3/32 x 33-3/32 10-3/16 x 33-3/32 x 33-3/32 11-3/4 x 33-3/32 x 33-3/32mm 258 x 840 x 840 258 x 840 x 840 298 x 840 x 840
Netweight lbs (kg) 51 (23) 51 (23) 60 (27)
Decoration panel
Model PLP-40BAU PLP-40BAU PLP-40BAUExternalfinish Munsell No. (6.4Y 8.9/0.4)
Dimension H x W x D
in. 1-3/8 x 37-13/32 x 37-13/32 1-3/8 x 37-13/32 x 37-13/32 1-3/8 x 37-13/32 x 37-13/32
mm 35 x 950 x 950 35 x 950 x 950 35 x 950 x 950Net Weight lbs (kg) 13 (6) 13 (6) 13 (6)
Insulation material PSAirfilter PPhoneycomb(longlifefilter,anti-bacterialtype)Protection device FuseRefrigerantcontroldevice LEVConnectable outdoor unit R410A,R22 CITY MULTI
VentilationAir:Providingsufficientventilationairisanimportantpartofeverybuildingdesign.ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.
1. SPECIFICATIONS
Note: *1Nominalcoolingconditions *2Nominalheatingconditions Unit converter
25/32~1-25/32(20~45) 33-27/32 to 35-13/16(860~910) 25/32 to 1-25/32(20~45)
31-7/8(810)
25/3
2 to
33-2
7/32
to 3
5-13
/16(
860~
910)
25/3
2
15/1
6
6-5/
16
Indoor unit/Outdoor unit connecting terminal block
ø4-29/32(ø125)
ø3-15/16(ø100)
6-7/
32
120°
120°
1 2
Note:1. As for drain pipe, please use VP-25 O.D. 1-1/4(32) PVC TUBE. Drain pump is included. Max. lifting height is 33-1/2 (850mm) from the ceiling.2. As for suspension bolt, please use M10 or W3/8. (Procured at local site)3. Electrical box may be removed for the service purpose. Make sure to slack the electrical wire little bit for control/power wires connection.4. The height of the indoor unit is able to be adjusted with the grille attached.5. For the installation of the optional high efficiency filter or optional multi-functional casement. 1 Add 5-5/16"(135mm) to the dimensions Wmarked on the figure. 2 The optional high efficiency filter becomes optional multi-functional casement and concomitant use.6. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. (It becomes the cause of dew drops/water dew.) As for necessary installation / service space, please refer to the left figure.Accessory···Drain socket(I.D.1-1/4)
FAN MOTOR (LL)DRAIN PUMP/DEW PREVENTION HEATERX1 AUX. RELAY
SYMBOL NAME
VARISTOR
INDOOR POWER BOARDP.B
ZNR
X4
I.B
CN41CN51CN52FUSE FUSE (6.3A/250V)
REMOTE INDICATIONCENTRALLY CONTROLHA TERMINAL-A
CONNECTORINDOOR CONTROLLER BOARD
[LEGEND]NAMESYMBOL
PIPE TEMPERATURE DETECTION/GASTH23
TRANSMISSIONTERMINALBLOCK
POWER SUPPLYTB5TB15
TB2
(32°F/15kΩ 77°F/5.4kΩ)THERMISTOR ROOM TEMPERATURE DETECTION
TH22
TH21
LEV LINEAR EXPANSION VALVE
MVMF
VANE MOTORFAN MOTOR (WITH THERMAL FUSE)
CAPACITOR (FAN MOTOR)C1
PIPE TEMPERATURE DETECTION/LIQUID
MA-REMOTE CONTROLLER
LED2
LED1
31 1 3CND
(POWER)
YLW21
YLW
1 3 BLU
(D+U+M)CNC
(D+HEATER) RED ORN
FUSE
ZNR
CNP
X1
RED
ORN
GRILLE
BLU
5WHTBLU
REDORNYLW
REDRED
1
10
7
236
45
89
3
5
5
5
5
C1
1 5
BLK
YLW WHTBR
N
7 9
X6 X5 X4 X7
X4 X7X5X6
MF
I.B
CN20
CN31
123
BLU
WHT
ORN
RED
YLW 6
6 5 4 3 2 1
(VANE)CN6V
GRN
RED
ORN
BLU
6 5 4 3 2 1
(LEV)CN60
WHT
WHT
YLWBRN
BLK
2 2 11
(LIQUID)(INTAKE)CN21
RED WHT
2 1
(GAS)CN29
(REM
OCON
)
WHT
13RE
D
P.B
RED
CNDK
(POWER BORD)
123
AC208-230VCNSK(RED)
TB2 L1L2GR
REDBLU
GRN/YLW
~/N 208-230V POWER SUPPLY
TRANSDC13.1VCN2S(WHT)
21
21
(POW
ER
BO
RD)
CN2D
WHT WHT
BLK
M1
12 CONTROLLER
DC8.7-13V
TO MA-REMOTE
CN2M
(M-N
ET) 1
23
1CN
3A
BLU
BLU
M2
TB15S(SHIELD)
M-NET REMOTE
TO OUTDOOR UNITBC CONTROLLERTB5
X1
TH23TH22TH21DSLEV
5
3RDDIGIT
0O
0
0N0FF
SW1
1 2 3 4 5 6 7 8 9 10
SW12 SW11
1STDIGIT
0
2NDDIGIT
SW14
CONNECTIONNo.
1 2 3 4 50FF0N
SW4SW2
654321 109876543210FF0N
SW3
MV
H2
MV
MV
MV
Notes:1.At servicing for outdoor unit,always follow the wiring diagram of outdoor unit.2.In case of using MA-Remote controller, please connect to TB15. (Remote controller wire is non-polar.)3.In case of using M-NET, please connect to TB5. (Transmisson line is non-polar.)4.Symbol[S] of TB5 is the shield wire connection.5.Symbols used in wiring diagram above are, :terminal block, :connecter.6.The setting of the SW2 dip switches differs in the capacity for the detail,refer to the fig: 1.7.Use copper supply wire.
NOTES:1.At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.2.In case of using MA-Remote controller, please connect to TB15. (Remote controller wire is non-polar.)3.In case of using M-NET, please connect to TB5. (Transmission line is non-polar.)4.Symbol [S] of TB5 is the shield wire connection.5.Symbols used in wiring diagram above are, : terminal block, : connecter.6.The setting of the SW2 dip switches differs in the capacity. For the detail, refer to fig<w1>.
[LEGEND]
LED on indoor board for service
w2.Use copper supply wires.
w2
ADDRESSCN81(RED)
ADDRESSCN42(RED)
BZ
WH
TY
LWO
RN
BLU
RE
DB
RN
LEV
LED2SW1
CNB54
MT
I-SEE SENSOR CORNER PANEL(OPTION PART)
I-SEESENSOR
TO MA-REMOTECONTROLLERDC8.7-13V
TB151BLU
BLU 2
SW2 LED1
RUW.B
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
VANE CNV(WHT)
5
0
555
MMMMMVMVMVMV
GRILLE
Pair No.
J41J42
1 3
CN32(WHT)
1
1 6
3
LED2
81 41
4
1 8
8
1
0 0
A.B
I.B
4
(RED)ADDRESS
CN43
(RED)ADDRESS
CN82
SWBSWA
SWC
3RD.DIGIT 2ND.DIGIT 1ST.DIGIT
SW14
CONNECTIONNo.
1
2
3211 2 3 4 5 6 7 8 910
234
0SW12 SW11
SW1ON
OFF
91
WIRELESSCN90(WHT)
19
4
LIQUID/PIPECN44(WHT)
TH23TH22
t°t°
1 4
FS
1 2
INTAKECN20(RED)
t°
1 2
FLOAT SWCN4F(WHT)
CN27(RED)
1 2 1 21 3
LED1
CN25(WHT)
CN24(YLW)
CN3G(BLK)
7 14
FANCNMF(WHT)
MF
MS3~
3 1
DP
M1~
M
M
D.U.MCNP(BLU)
3 1
CNAC(WHT)
U
U
ZNR02
ZNR01
DSA
1 3 5
FUSE
CND
DC311~339VRECTIFICATION
X1
2 1M-NETCN2M(BLU)
BLUBLU
M1M2
TB5
(SHIELD)
TO OUTDOOR UNITBC CONTROLLERREMOTE CONTROLLERDC24-30VS
L1L2GR
TB2REDBLU
GRN/YLW TO NEXT INDOOR UNIT
PULL BOX
FUSE(16A)
BREAKER(16A)
POWER SUPPLY~/N 208-230V 60Hz
wBe sure to turn off the power source and then disconnect fan motor connector. (Failure to do so will cause trouble in Fan motor.)TH21
Note : These figures show typical temperature distributions in the conditions above. In the actual installation, they may differfrom these figures under the influence of air temperature conditions, ceiling height, cooling/heating load,obstacles,etc.
Note : These figures show typical airflow distributions in the conditions above. In the actual installation, they may differ from these figures under the influence of air temperature conditions, ceiling height, cooling/heating load,obstacles,etc.
NOTE: Ventilation air intake amount should be 20% or less oftotal air amount to prevent condensate dripping.
Refrigerant pipeDrain pipeElectrical Box
Ventilation air intakeVentilation air intake hole diagram (Unit : inch)
3 - 1/8Burring hole
3-15/16Burring hole pitch
2-7/8(Cut out hole)
Ceiling surface
120_
120_
4-21
/32
By mounting the optional multi-function casement (PAC-SH53TM-E) to the indoor unit main body, increased ventilation air intake can be accomplished. (The mounting of the multi-function casement increase the height of the ceiling plenum by 5-5/16 [135mm].)
Knockout hole for ventilation air intake
Direct ventilation air intake into the main body is also possible.
with Multi-function Casement and Filters
7. VENTILATION AIR INTAKE AMOUNT AND STATIC PRESSURE
7-1. PLFY-P08, 12, 15NCMU-E
7-2. PLFY-P12, 15, 18, 24, 30, 36NBMU-E with Multi-function Casement and Filters
PLFY-21PLFY-P-NCMU-E/NBMU-E (Feb. 2009)
PLFY-P-NCMU-E PLFY-P-NBMU-E
2 - inlet
1 - inlet
2 - inlet
1 - inlet
2 - inlet
1 - inlet
200(0.80)
150(0.60)
100(0.40)
50(0.20)
0
0 1 2
50 100 150 200 [CFM]
3 4 5 6[CMM]
2 - inlet
1 - inlet
Airflow rate Airflow rate
Sta
tic p
ress
ure
[Pa(
in.W
.G.]
200(0.80)
150(0.60)
100(0.40)
50(0.20)
0
0 1 2
50 100 150 200 [CFM]
3 4 5 6[CMM]
Sta
tic p
ress
ure
[Pa(
in.W
.G.]
200(0.80)
150(0.60)
100(0.40)
50(0.20)
0
0 1 2
50 100 150 200 [CFM]
3 4 5 6[CMM]
Airflow rate
Sta
tic p
ress
ure
[Pa(
in.W
.G.]
200(0.80)
150(0.60)
100(0.40)
50(0.20)
0
0 2
50 100 150 200 250 [CFM]
4 8 [CMM]6
Airflow rate
Sta
tic p
ress
ure
[Pa(
in.W
.G.]
200(0.80)
150(0.60)
100(0.40)
50(0.20)
0 0
0 2
50 100 150 200 250 [CFM]
4 8 [CMM]6
Airflow rate
Sta
tic p
ress
ure
[Pa(
in.W
.G.]
200(0.80)
150(0.60)
100(0.40)
50(0.20)
0 2
50 100 150 200 250 [CFM]
4 8 [CMM]6
Airflow rate
Sta
tic p
ress
ure
[Pa(
in.W
.G.]
connection only
7. VENTILATION AIR INTAKE AMOUNT AND STATIC PRESSURE
Note:Anauxillaryfanisrequiredtobringoutsideair into the unit.
Note:Anauxillaryfanisrequiredtobringoutsideair into the unit.
High efficiency filter element PAC-SH59KF-E (MERV 10) PAC-SH53TM-E is necessary to use with filter PAC-SH59KF-E.
PLFY-P-NBMU-E
8-1. Air Outlet Shutter Plate PAC-SH51SP-E for PLFY-P-NBMU-EUsing the air outlet shutter plate to block the air outlet to modify the air-way from 4 to 3 or 2.With 1 PAC-SH51SP-E, 4 air-ways can be changed to 3;With 2 PAC-SH51SP-E, 4 air-ways can be changed to 2;Changing to 1 way is not allowed. Material: Foamed polyethylene + foamed urethane, color: Black
Item 1. Shutter plate
Quantity 2
Shape
2. Insulator
1
Detailed installation information should be referred to its Installation Manual.
8. OPTIONAL PARTS
8-1. Air Outlet Shutter Plate PAC-SH51SP-E for PLFY-P-NBMU-E
PLFY-23PLFY-P-NCMU-E/NBMU-E (Feb. 2009)
PLFY-P-NCMU-E PLFY-P-NBMU-E
8-2. High Efficiency Filter Element PAC-SH59KF-E (MERV 10) for PLFY-P-NBMU-ELife span: 2,500 hr (Dust concentration 0.15mg/m ); Colorimetric method 65% (JIS 11 class)); No re-production.3
*.The actual dust situation affects the filter life span, which should be considered at the applying site.Material: Electrostatic polyolefin fiberHigh efficiency filter element PAC-SH59KF-E must be used together with the Multi-function casement PAC-SH53TM-E. When using PAC-SH59KF-E, switching on SWC of the Indoor unit address board is needed. Details should be referred to its Installation Manual.
Quantity 1
Shape
Detailed installation information is referred in its Installation Manual.
8-3. Multi-function Casement PAC-SH53TM-E for PLFY-P-NBMU-EMulti-function casement is used for High efficiency filter element and/or ventilation air intake from outdoor.It should be used with High efficiency filter element PAC-SH59KF-E (Colorimetric method 65%).ventilation air intake on the Multi-function casement is possible from any 2 or less corners among the 4 ones.But duct and flange on the casement should be prepare locally.
Item 1. Multi-functional casement
5. Insulator A for Decorative panel 6. Insulator B for Decorative panel
2. Screw with washer (black) 3. Screw
Quantity 1 4 8
4
Shape
M5X0.8X25 M5X0.8X12
Decorative panel securing bracket
With insulator
Item
Quantity 1 1
Shape
Detailed installation information should be referred to its Installation Manual.
4.
8-2. High Efficiency Filter Element PAC-SH59KF-E (MERV 10) for PLFY-P-NBMU
8. OPTIONAL PARTS
8-3. Multi-function Casement PAC-SH53TM-E for PLFY-P-NBMU-E
PLFY-24 PLFY-P-NCMU-E/NBMU-E (Feb. 2009)
PLFY
-P-NC
MU-E
PLFY
-P-NB
MU-E
8-4. i-see Sensor Corner Panel PAC-SA1ME-E for PLFY-P-NBMU-Ei-see sensor provides comfortable space as it detects the floor temperature to prevent spotty temperature.It also enables the unit to save energy.AttentionMake sure that there are no gaps between the unit and the grille, and the grille and ceiling.It may cause condensate dripping.
Item 1. i-see sensor corner panel
Quantity 1
Shape
2. Plastic fastener
2
Detailed installation information should be referred to its Installation Manual.
8-5. Wireless Signal Receiver PAR-SF9FA-E for PLFY-P-NBMU-EUsing the wireless signal receiver to use wireles remote controller.The corner panel(the other side of refrigerant piping) is changed for the wireless signal receiver.
Item 1. Wireless signal receiver
Quantity 1
Shape
Detailed installation information should be referred to its Installation Manual.
8-4. i-see Sensor Corner Panel PAC-SA1ME-E for PLFY-P-NBMU-E
8. OPTIONAL PARTS
8-5. Wireless Signal Receiver PAR-SA9FA-E for PLFY-P-NBMU-E
PLFY-25PLFY-P-NCMU-E/NBMU-E (Feb. 2009)
PLFY-P-NCMU-E PLFY-P-NBMU-E
8-6. External Heater Adapter CN24RELAY-KIT-CM3
8. OPTIONAL PARTS
External heater adaptor CN24RELAY-KIT-CM3 is a set of special wiring parts for controlling the electric heater* with the air conditioner system.*The electric heater should be designed and prepared at the site.
A basic connection method is shown as follows:(For details, refer to its Installation Manual.)
Item External output cable Fan speed setting cablewith resistance
Quantity 2 2
Shape
Refer to the Installation Manual for wiring and installation details.
For relay X use the specifications given below Operation coilRated voltage : 12VDCPower consumption : 0.9W or less
The length of the electrical wiring for the CN24RELAY-KIT-CM3 is 2 meters (6-1/2 ft)To extend this length, use sheathed 2-core cable.
Control cable type : CVV, CVS, CPEV or equivalent.Cable size : 0.5 mm2 ~ 1.25 mm2 (16 to 22 AWG)Don't extend the cable more than 10 meters (32ft)
Recommended circuit
CN24
XX
Remote control Board Relay circuit AdapterIndoor unitcontrol board
Outdoor unitcontrol board
Ele
ctric
Hea
ter
pow
er s
ourc
e
ElectricHeater
Red 1
White 2
Preparations in the field Maximum cable lengthis 10 m (32ft)