Ceiling Cassette TM-FFC-0515-C TECHNICAL MANUAL
Ceiling Cassette
TM-FFC-0515-CTECHNICAL MANUAL
1. Model Name .......................................................................................................... 1 2. Features ................................................................................................................ 2
3. Specifications ........................................................................................................ 3 GeneralData .............................................................................................. 3 SafetyDevices .......................................................................................... 19
4. ApplicationInformation ........................................................................................ 20 OperatingRange ...................................................................................... 20 Controllers ................................................................................................ 24
5. Installations .......................................................................................................... 31
6.WiringDiagrams .................................................................................................. 44
7. Servicing&Maintenance .................................................................................... 48
8. Troubleshooting .................................................................................................. 50
9. DimensionalData ................................................................................................ 54
10.ExplodedView&PartList ................................................................................... 57
Note:Installationandmaintenancearetobeperformedonlybyqualifiedpersonnelwhoare familiarwithlocalcodesandregulations,andexperiencedwiththistypeofequipment.
Caution:Sharpedgesandcoilsurfacesareapotentialinjuryhazard.Avoidcontactwiththem.
Warning:Movingmachineryandelectricalpowerhazard.Maycauseseverepersonnel injuryordeath.Disconnectandlockoffpowerbeforeservicingequipment.
TableofContents
1
TM-F
FC-0
515-
C
1. Model Name
FC
Type Of Air-Conditioner
FF : Ceiling Cassette (Capacity Index 10/15)FC : Ceiling Cassette (Capacity Index 20-50)
Series
C : C SeriesA2 : A2 Series
Power Supply
V1 : Single Phase, 220-240V, 50Hz
RefrigerantBlank : R22N : R410A
Capacity Index
20 : Based On Btu/hr
20 A2 V1
Indoor
R 20 C V1
Outdoor
Type Of Air-Conditioner
R : Single Split Condensing Unit
Series
F : F SeriesC : C Series
Power Supply
V1 : Single Phase, 220-240V, 50HzY1 : Three Phase, 380-415V, 50Hz
Refrigerant
Blank : R22N : R410A
Capacity Index
20 : Based On the Btu/hr
2
TM-F
FC-0
515-
C
2. Features
Ultra Slim New Stylish Design ProfileThisunitiscontemporaryindesignandmatcheventhemostuptodateinteriordecor.Theslim,(only20mmforC-series,andonly28mmforA2-series)androundprofilefrontpanelofthisunitaddsatouchofelegancetoeverydecor.
Turbo Mixed Flow FanInnovativedesignofhighlyefficientturbofanproducesanevenaircirculationinalldirection.
Built-in High Head Drain PumpTheunithasabuilt-inhighheaddrainpumpupto700mmtoprovideandensuresmoothnessdrainageofcondensatewater.
Strong and RobustTheunitisbuiltfromstrongcasingmaterialandrobustpartstoensurelonglastingreliableservice.ThedrainpanismadefromthePOLYSTYRENEwithaplasticcoatingonthesurfacetoensurenoleakingandcondensationoccur.
Friendly ServiceabilityTheairfilter,electricalparts,fan,fanmotoranddrainpumpcanallbeinspectedandreplacedfromthebottomoftheunitbysimplyremovingtheairintakegrille.ThePOLYSTYRENEdrainpanandtheheatexchangercoilscanberemovedfromtheuniteasilybyremovingthefrontpanel.
Microcomputer Remote ControllerTheincorporatedmicroprocessoroffersmoreaccuratecontrolandwiththefollowingextrafeatures:•Fanmotorspeedcanbesetathigh/medium/loworautomatic.•Timeron/off-theunitcanbepre-settoswitchonandoffautomatically.•Electronicthermostat-roomtemperatureispreciselycontrolled,resultinginenergysavingandincreasecomfort.
Wireless Remote ControllerThecompactwirelessremotecontrollermakesitpossibletooperatetheairconditioneranywherewithinthe room.
Negative Ion GeneratorBalancingtheionizationinyourhometocombattheillfeelingsassociatedwithourstressfullifestylesandcreatetherefreshingenvironmentresemblingthenature.
3
TM-F
FC-0
515-
C
3.Specifications
Specification (R22)Ceiling Cassette Type - FF-C Series
FF10CV1
R10CV1
FF15CV1
R15CV1
Btu/h 10000 13000
W 2930 3810
0.77 0.77
W 905 1190
A 3.80 5.30
Btu/hr/ W 11.05 10.92
V/Ph/Hz
kg/Ib 0.63 / 1.39 0.60 / 1.32
l/s / CFM 194 / 410 194 / 410
l/s / CFM 170 / 360 170 / 360
l/s / CFM 156 / 330 156 / 310
dBA 41 / 38 / 35 41 / 38 / 34
mm/in
mm/in
kg/Ib
mm/in
mm/in
mm/in
V/Ph/Hz
W 55 65
A 0.24 0.29
W 19 23
790 805
690 720
620 625
mm/in
mm/in
mm/in
m²/ft²
1 2
16 20
pc
LENGTH mm/in
WIDTH mm/in
THICKNESS mm/in
PANEL MATERIAL
UNIT
AIR FLOW
HIGH
EER
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE
POWER SOURCE 220 - 240 / 1/ 50
INDUCTION
IP20
316X630X630 (126X690X716) / 12.4X24.8X24.8 (5X27.2X28.2)
19.1 / 3/4
15.5 + 2 / 34 + 4
MODELINDOOR UNIT
OUTDOOR UNIT
NOMINAL COOLING CAPACITY
NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT - 1Ø [3Ø]
SENSIBLE HEAT FACTOR
TYPE
INDEX OF PROTECTION (IP)
PACKING DIMENSION (PANEL)
UNIT WEIGHT (UNIT + PANEL)
CONDENSATE DRAIN SIZE
DRIVE DIRECT
MATERIAL ABSG20
REFRIGERANT TYPE R22
REFRIGERANT CHARGE
QUANTITY
FAN
IND
OO
R U
NIT
CONTROLAIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
OPERATION WIRELESS OR WIRED REMOTE CONTROL
QUANTITY 1
THICKNESS 0.23 / 0.009
TUBE
THICKNESS 0.10 / 0.004
DIAMETER 315 / 12.4
LENGTH
TYPE WASHABLE SARANET FILTER
QUANTITY 1
TYPE
FIN
TURBO FAN
MEDIUM
LOW
SOUND PRESSURE LEVEL (H/M/L)
UNIT DIMENSION (WITH PANEL) H X W X D
H X W X D
250X570X570(295X640X640) / 9.8X22.4X22.4(11.6X25.2X25.2)
1
ROW
FIN PER INCH
FACE AREA
163 / 6.4
MATERIAL SEAMLESS INNER GROOVE COPPER
DIAMETER 7.0/0.276
MATERIAL ALUMINIUM (SLIT FIN)
INSULATION GRADE
POWER SOURCE 220 - 240 / 1/ 50
CLASS B
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES 6
AIR QUALITY FILTER
SPEED
COIL
SIZE
367.5 / 14.5
381.0 / 15.0
20.8 / 0.8
0.25
FAN MOTOR
CASINGABS
MATERIAL GALVANIZED STEEL
HIGH
RPMMEDIUM
LOW
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.
4
TM-F
FC-0
515-
C
Specification (R22)Ceiling Cassette Type - FF-C Series (Continued)
FF10CV1
R10CV1
FF15CV1
R15CV1
l/s / CFM
dBA 46 49
mm/in
mm/in
kg/Ib
mm/in
mm/in 9.52 / 3/8 12.7 / 1/2
mm/in
V/Ph/Hz
W 52 74
A 0.23 0.33
W 19 30
RPM 730 860
cm³ / fl.oz. 320 / 10.82 350 / 11.83
V/Ph/Hz
µF
W 798 1051
A 3.33 4.68
A 19 25
mm/in
mm/in
mm/in
CASING UNIT
FLARE VALVE
SIZELIQUID 6.35 / 1/4
OU
TDO
OR
UN
IT
AIR FLOW 453 / 960
SOUND PRESSURE LEVEL
UNIT DIMENSION
DIAMETER
30
401 / 15.8
MODELINDOOR UNIT
OUTDOOR UNIT
INDEX OF PROTECTION (IP) IP23
INSULATION GRADE CLASS B
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
MOTOR SPEED
INSULATION GRADE E
GALVANIZED STEELMATERIAL
MATERIAL SEAMLESS INNER GROOVE COPPER
DIAMETER 7.0 / 0.276
MATERIAL ALUMINIUMCOIL
THICKNESS 0.23 / 0.009
TUBE
THICKNESS 0.11 / 0.004
FIN PER INCH 20
FIN FACE AREA 0.35/3.82
ROW 1
FAN
QUANTITY 1
GAS
TYPE PROPELLER
DRIVE DIRECT
QUANTITY 1
MATERIAL ASG20
H X W X D 596X803X323 / 23.5X31.6X12.7
UNIT WEIGHT 28 / 61.7
PIPECONNECTION
TYPE
543X700X250 / 21.4X27.6X9.8
POWER SOURCE 220 - 240 / 1/ 50
POWER SOURCE 220 - 240 / 1/ 50
CAPACITOR
PACKING DIMENSION
H X W X D
POLES 6
COMPRESSOR
TYPE ROTARY
OIL TYPE SUNISO 4GSI/FREOL-K56
OIL AMOUNT
RATED INPUT POWER
FAN MOTOR
TYPE INDUCTION
m²/ft²
LOCKED ROTOR AMP - 1Ø [3Ø]RATED RUNNING CURRENT- 1Ø [3Ø]
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.
5
TM-F
FC-0
515-
C
Specification (R22)Ceiling Cassette Type - FC-A2 Series
R18CV1 R20CV1 R20CV1 R25CV1
Btu/h 18000 20000 22000 25000
W 5275 5862 6448 7327
0.81 0.79 0.70 0.71
W 1773 2023 2146 2809
A 7.75 8.92 9.21 12.57
Btu/hr/ W 10.15 9.89 10.25 8.90
V/Ph/Hz
kg/Ib 0.90 / 1.98 0.83 / 1.83 1.13 / 2.49 1.1 / 2.43
l/s / CFM
l/s / CFM
l/s / CFM
l/s / CFM
dBA
mm/in
mm/in
kg/Ib
mm/in
mm/in
mm/in
V/Ph/Hz
W
A
W
mm/in
mm/in
mm/in
m²/ft²
pc
LENGTH mm/in
WIDTH mm/in
THICKNESS mm/in
PANEL MATERIAL
UNIT
330
300
INNER GROOVE COPPER
7.0 / 0.28
0.23 / 0.009
ALUMINIUM (SLIT FIN)
0.1 / 0.004
0.39 / 4.20
2
330
380
R22
4 WAY AUTOMATIC LOUVER (UP & DOWN)
WIRELESS OR WIRED REMOTE CONTROL
FC25A2V1
390 / 830
42 / 39 / 35 / 32
26+4 / 57+9
290 / 615
250 / 525
200 / 430
300X916X916 (124X1016X1016) / 11.8X36.1X36.1 (4.9X40.0X40.0)
GALVANIZED STEEL
TURBO
19.1 / 3/4
1
QUANTITYAIRQUALITY
AIRFILTER
SIZE
MATERIAL
WASHABLE SARANET FILTER
NEGATIVE IONS
1
POWER SOURCE
IND
OO
R U
NIT
TYPE
FIN PER INCH
REFRIGERANT CHARGE
FANMOTOR
RPM
REFRIGERANT TYPE
AIR DISCHARGE
RATED INPUT POWER
CONTROL
INDEX OF PROTECTION (IP)
INSULATION GRADE
AIR FLOW
PACKING DIMENSION ( PANEL)
OPERATION
SOUND PRESSURE LEVEL (H/M/L/SL)
FAN
TYPE
CONDENSATE DRAIN SIZE
UNIT DIMENSION (WITH PANEL)
H X W X D
220 - 240 / 1/ 50
MODELINDOOR UNIT
OUTDOOR UNIT
NOMINAL COOLING CAPACITY
NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT - 1Ø [3Ø]
SENSIBLE HEAT FACTOR
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE
FC20A2V1
EER
POWER SOURCE
DIAMETER
THICKNESS
ROW
MATERIAL
THICKNESS
FACE AREA
COIL
SUPER LOW
CASING
TREATMENT
FIN
TYPE
MATERIAL
SUPER LOW
HIGH
LOW
UNIT WEIGHT (UNIT + PANEL)
H X W X D
MEDIUM
QUANTITY
MATERIAL
DRIVE
DIAMETER
LENGTH
RATED RUNNING CURRENT
POLES
MOTOR OUTPUT
TUBE
QUANTITY
SPEED
HIGH
MEDIUM
LOW
486 / 19.1
172 / 6.8
INDUCTION
1
IP20
B
220 - 240 / 1 / 50
161
340 / 730
39 / 36 / 33 / 28
265X820X820 (345X930X930) / 10.4X32.3X32.3 (13.6X36.6X36.6)
26+4 / 57+9
18
576 / 22.7
556 / 21.9
22 / 0.87
HIPS (PLASTIC)
ASG10
DIRECT
0.71
20
6
420
370
350 / 740
280 / 595
230 / 495
200
0.94
30
470
420
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.
6
TM-F
FC-0
515-
C
Specification (R22)Ceiling Cassette Type - FC-A2 Series (Continued)
l/s / CFM 755 / 1600
dBA 52
mm/inmm/inkg/Ib 50/110
mm/inmm/in
DIAMETER mm/in
V/Ph/HzW 121
A 0.53
W 60
RPM 840
cm³ / fl.oz.
V/Ph/HzµF 40
8
35 45
W 1535 1785 1869
7.93
2488
A 6.7 7.87 11.1
A 36 41 56
mm/inmm/in
mm/inm²/ft²
CASING UNIT
15.88 / 5/8
654X855X328 / 25.7X33.7X12.9
43 / 94.8
TYPE
INDEX OF PROTECTION (IP)
SIZE
MATERIAL
FACE AREA
MATERIAL
COMPRESSOR
MOTOR OUTPUT
POLES
LOCKED ROTOR AMP - 1Ø [3Ø]
COIL
PACKING DIMENSION
MODELINDOOR UNIT
OUTDOOR UNIT
OU
TDO
OR
UN
IT
FAN MOTOR
PIPECONNECTION
TYPE
H X W X D
AIR FLOW
UNIT DIMENSION
FAN
SOUND PRESSURE LEVEL
MATERIAL
MATERIAL
ROW
OIL AMOUNT
TYPE
DIAMETER
UNIT WEIGHT
INSULATION GRADE
H X W X D
RATED RUNNING CURRENT
OIL TYPE
POWER SOURCERATED INPUT POWER
QUANTITY
DRIVE
QUANTITY
GASLIQUID
TYPE
THICKNESS
FIN PER INCH
FIN
POWER SOURCECAPACITORRATED INPUT POWERRATED RUNNING CURRENT- 1Ø [3Ø]
TUBETHICKNESS
INSULATION GRADE
MOTOR SPEED
614 / 1300
5152
693X990X415 / 27.3X39.0X16.3
9.52 / 3/86.35 / 1/4
INDUCTION
220 - 240 / 1 / 50
FLARE VALVE
PROPELLER
1
ASG20
DIRECT
793X990X415 / 31.2X39.0X16.3
756X855X328 / 29.8X33.7X12.9
1
20
455 / 17.9
SUNISO 4GSI / FREOL K56J ATMOS NM56M / SUNISO 4GDID
ALUMINIUM
0.11 / 0.004
0.51 / 5.47
GALVANIZED STEEL
1
77
0.34
32
0.61 / 6.58
IP23
CLASS F
6
SEAMLESS INNER GROOVE COPPER
7.00 / 0.276
0.23 / 0.009
680
600 / 20.3 700 / 24
E
220 - 240 / 1/ 50
ROTARY
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.
R18CV1 R20CV1 R20CV1 R25CV1FC25A2V1FC20A2V1
7
TM-F
FC-0
515-
C
Specification (R22)Ceiling Cassette Type - FC-A2 Series
FC40A2V1R28CV1 R30CV1 R35DV1
Btu/h 28000 30000 35000W 8206 8792 10258
0.75 0.75 0.70W 2760 3200 3360A 12.42 14.32 15.79
Btu/hr/ W 10.14 9.38 10.42
V/Ph/Hz
kg/Ib 1.95 / 4.29 2.23 / 4.91 2.00 / 4.41
l/s / CFM 490 / 1030l/s / CFM 410 / 860l/s / CFM 350 / 740l/s / CFM 295 / 620
dBA 47 / 44 / 40 / 36mm/in 300X820X820(385X930X930) / 11.8X32.3X32.3 (15.2X36.6X36.6)mm/in 335X916X916(124X1016X1016) / 13.2X36.1X36.1(4.9X40.0X40.0)kg/Ib 32+4 / 71+9
mm/in
mm/inmm/in
V/Ph/HzW 176A 0.79W 60
680580510435
mm/inmm/in 0.23 / 0.009
mm/inm²/ft² 0.46 / 4.97
20
pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in
PANEL MATERIALUNIT
INNER GROOVE COPPER7.0 / 0.28
ALUMINIUM (SLIT FIN)0.1 / 0.004
0.39 / 4.10
R22
4 WAY AUTOMATIC LOUVER (UP & DOWN)WIRELESS OR WIRED REMOTE CONTROL
FC30A2V1
420 / 890
43 / 39 / 36 / 34
26+4 / 57+9300X916X916 (124X1016X1016) / 11.8X36.1X36.1 (4.9X40.0X40.0)
INDOOR CAP. TUBE
GALVANIZED STEEL
TURBO19.1 / 3/4
1
QUANTITYAIRQUALITY
AIRFILTER
SIZE
MATERIAL
WASHABLE SARANET FILTERNEGATIVE IONS
1
POWER SOURCE
IND
OO
R U
NIT
TYPE
FIN PER INCH
REFRIGERANT CHARGE
FANMOTOR
RPM
REFRIGERANT TYPE
AIR DISCHARGE
RATED INPUT POWER
CONTROL
INDEX OF PROTECTION (IP)INSULATION GRADE
AIR FLOW
PACKING DIMENSION ( PANEL)
OPERATION
SOUND PRESSURE LEVEL (H/M/L/SL)
FAN
TYPECONDENSATE DRAIN SIZE
UNIT DIMENSION (WITH PANEL)H X W X D
220 - 240 / 1 / 50
MODEL INDOOR UNITOUTDOOR UNIT
NOMINAL COOLING CAPACITY
NOMINAL TOTAL INPUT POWERNOMINAL RUNNING CURRENT - 1Ø [3Ø]
SENSIBLE HEAT FACTOR
REFRIGERANT CONTROL (EXPANSION DEVICE)EER
POWER SOURCE
DIAMETER
THICKNESS
ROW
MATERIAL
THICKNESS
FACE AREA
COIL
SUPER LOW
CASING
TREATMENT
FIN
TYPE
MATERIAL
SUPER LOW
HIGH
LOW
UNIT WEIGHT (UNIT + PANEL)
H X W X D
MEDIUM
QUANTITYMATERIALDRIVEDIAMETERLENGTH
RATED RUNNING CURRENT
POLESMOTOR OUTPUT
TUBE
QUANTITY
SPEED
HIGH MEDIUMLOW
486 / 19.1172 / 6.8
INDUCTION1
IP20 B
220 - 240 / 1 / 50
265X820X820 (345X930X930) / 10.4X32.3X32.3 (13.8X36.6X36.6)
243 / 515
3220
576 / 22.7556 / 21.922 / 0.87
HIPS (PLASTIC)
630530470415
1550.6850
368 / 780290 / 615
ASG10DIRECT
6
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.
8
TM-F
FC-0
515-
C
Specification (R22)Ceiling Cassette Type - FC-A2 Series (Continued)
l/s / CFM 808 / 1712 1605 / 3400
dBA 54 56 58
mm/in 852x1030x400 / 33.5x40.6x15.7
mm/in 1010x1180x514 / 39.8x46.5x20.2
kg/Ib 78 / 172
mm/inmm/in 19.05 / 3/4
DIAMETER mm/in 610 / 24
IP54
CLASS F
V/Ph/Hz
W 124 257
A 0.54 1.10
W 66 66 145
RPM 874 874 625
8
SCROLL
SUNISO 3GS
cm³ / fl.oz. 900 / 30 1242 / 42
B
V/Ph/HzµF 60 60 60
W 2481 2921 2927
A 11.2 13.1 13.9
A 62 66 97
mm/in 9.52 / 0.375
0.28/ 0.011mm/inALUMINIUM (CORRUGATED)
mm/inm²/ft² 0.87 / 9.36
16
CASING UNIT
15.88 / 5/8
57 / 126
TYPE
INDEX OF PROTECTION (IP)
SIZE
MATERIAL
FACE AREA
MATERIAL
COMPRESSOR
MOTOR OUTPUT
POLES
LOCKED ROTOR AMP - 1Ø [3Ø]
COIL
PACKING DIMENSION
MODELINDOOR UNIT
OUTDOOR UNIT
OU
TDO
OR
UN
IT
FANMOTOR
PIPECONNECTION
TYPE
H X W X D
AIR FLOW
UNIT DIMENSION
FAN
SOUND PRESSURE LEVEL
MATERIAL
MATERIAL
ROW
OIL AMOUNT
TYPE
DIAMETER
UNIT WEIGHT
INSULATION GRADE
H X W X D
RATED RUNNING CURRENT
OIL TYPE
POWER SOURCERATED INPUT POWER
QUANTITY
DRIVE
QUANTITY
GASLIQUID
TYPE
THICKNESS
FIN PER INCH
FIN
POWER SOURCECAPACITORRATED INPUT POWERRATED RUNNING CURRENT- 1Ø [3Ø]
TUBETHICKNESS
INSULATION GRADE
MOTOR SPEED
9.52 / 3/8
INDUCTION
220 - 240 / 1 / 50
FLARE
PROPELLER
1
ASG20
DIRECT
793x990x416 / 31.2x39.0x16.4
756x855x328 / 29.8x33.7x12.9
455 / 18
ATMOS NM32A1
ALUMINIUM (RAISE LANCE)
18
0.10 / 0.004
0.61 / 6.58
GALVANIZED STEEL
1
2 1
IP23
6
INNER GROOVE COPPER
7.00 / 0.276
0.23 / 0.009
E
220 - 240 / 1 / 50
ROTARY TWIN ROTARY
SUNISO 4GSI
1050 / 36
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.
FC40A2V1
R28CV1 R30CV1 R35DV1FC30A2V1
9
TM-F
FC-0
515-
C
Specification (R22)Ceiling Cassette Type - FC-A2 Series
Btu/h
W
W
A
Btu/hr/ W
V/Ph/Hz
kg/Ib
l/s / CFM
l/s / CFM
l/s / CFM
l/s / CFM
dBA
mm/in
mm/in
kg/Ib
mm/in
mm/inmm/in
V/Ph/HzW
A
W
mm/in
mm/in
mm/in
m²/ft²
pc
LENGTH mm/in
WIDTH mm/in
THICKNESS mm/in
PANEL MATERIALUNIT
AIR FLOW
HIGH
EER
REFRIGERANT CONTROL (EXPANSION DEVICE)
POWER SOURCE
MODELINDOOR UNIT
OUTDOOR UNIT
NOMINAL COOLING CAPACITY
NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT - 1Ø [3Ø]
SENSIBLE HEAT FACTOR
TYPE
INDEX OF PROTECTION (IP)
PACKING DIMENSION (PANEL)
UNIT WEIGHT (UNIT + PANEL)
CONDENSATE DRAIN SIZE
DRIVEMATERIAL
REFRIGERANT TYPE
REFRIGERANT CHARGE
QUANTITY
FAN
IND
OO
R U
NIT
CONTROLAIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)
OPERATION WIRELESS OR WIRED REMOTE CONTROL
QUANTITY
THICKNESS 0.23 / 0.009
TUBE
THICKNESS
DIAMETERLENGTH
TYPE WASHABLE SARANET FILTER
QUANTITY
TYPE
FIN
MEDIUM
LOW
SUPER LOW
SOUND PRESSURE LEVEL (H/M/L/SL)
UNIT DIMENSION (WITH PANEL) H X W X D
H X W X D
ROW
FIN PER INCH
FACE AREA
MATERIAL INNER GROOVE COPPER
DIAMETER 7.0 / 0.276
MATERIAL ALUMINIUM (SLIT FIN)
INSULATION GRADE
POWER SOURCERATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
POLES 6
AIR QUALITY FILTER
SPEED
COIL
SIZE
FAN MOTOR
CASINGMATERIAL
HIGH
RPMMEDIUMLOW
SUPER LOW
2.48 / 5.47 2.55 / 5.62
176 221
0.79 0.97
60 100
680 780
580 680
510 620
435 530
335X916X916(124X1016X1016) / 13.2X36.1X36.1(4.9X40.0X40.0)
300X820X820 (385X930X930) / 11.8X32.3X32.3 (15.2X36.6X36.6)
FC40A2V1
R40DY1
FC50A2V1
R50DY1
40000 50000
11723 14654
0.72 0.72
3600 4550
[6.10] [7.90]
11.11 10.99
R22
INDOOR CAP. TUBE
380 - 415 / 3 / 50
490 / 1030 570 / 1200
410 / 860 490 / 1030
350 / 740 440 / 930295 / 620 370 / 780
47 / 44 / 40 / 36 49 / 45 / 43 / 39
ASG 101
486 / 19.1
172 / 6.8
1
CLASS B
19.1 / 3/4
IP20
INDUCTION
TURBO
DIRECT
220 - 240 / 1/ 50
32+4 / 71+9
0.10 / 0.004 0.11 / 0.004
0.46 / 4.97 0.46 / 4.97
3
20
576 / 22.7
556 / 21.9
22 / 0.87
1
HIPS (PLASTIC)
GALVANIZED STEEL
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.
10
TM-F
FC-0
515-
C
Specification (R22)Ceiling Cassette Type - FC-A2 Series (Continued)
l/s / CFM
dBA
mm/in
mm/in
kg/Ib 85 / 187 88 / 194
mm/in
mm/in
V/Ph/Hz
W
A
W
RPM
cm³ /fl.oz. 1400 / 47
V/Ph/Hz
µF
W 3167 4072
A [5.47] [7.21]
A [48] [59]
mm/in
mm/in
mm/in
18
CASING UNIT
SCROLL
MINERAL OIL
0.85 / 9.15
2
7.0 / 0.276
INNER GROOVE COPPER
GAS
257
IP54
CLASS F
8
INDUCTION
PROPELLER
610 / 24
FIN PER INCH
FIN
MATERIAL
ROW
POLES
QUANTITY
MOTOR SPEED
1.10
SIZE
COIL
THICKNESS
MATERIAL
OIL AMOUNT
RATED INPUT POWER
RATED RUNNING CURRENT
MOTOR OUTPUT
1
625
0.23 / 0.009
0.10 / 0.004
ALUMINIUM (CORRUGATED)
GALVANIZED STEEL
145
INSULATION GRADE
DIAMETER
POWER SOURCE
CAPACITOR
RATED INPUT POWER
RATED RUNNING CURRENT- 1Ø [3Ø]
DRIVE
COMPRESSOR
TUBE
1
ASG 20
DIRECT
19.05 / 3/4
FLARE
PACKING DIMENSION
852X1030X400 / 33.5x40.6x15.8
1010X1180X514 / 39.8x46.5x20.24
58
9.52 / 3/8
1605 / 3400
SOUND PRESSURE LEVEL
UNIT DIMENSION H X W X D
MODELINDOOR UNIT
OUTDOOR UNIT
OU
TD
OO
R U
NIT
FAN MOTOR
FAN
FACE AREA
INDEX OF PROTECTION (IP)
LOCKED ROTOR AMP- 1Ø [3Ø]
MATERIAL
INSULATION GRADE
TYPE
OIL TYPE
THICKNESS
TYPE
DIAMETER
MATERIAL
POWER SOURCE 220 - 240 / 1/ 50
LIQUID
QUANTITY
TYPE
UNIT WEIGHT
PIPECONNECTION
TYPE
H X W X D
AIR FLOW
m²/ft²
F
380-415 / 3 / 50
N/A
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.
FC40A2V1
R40DY1
FC50A2V1
R50DY1
11
TM-F
FC-0
515-
C
Specification (R410A)Ceiling Cassette Type - FFN-C Series
FFN10CV1RN10FV1
FFN15CV1RN15FV1
Btu/h 9500 12500W 2784 3664
0.84 0.84W 950 1250A 4.26 5.6
Btu/hr/ W 10.56 10
V/Ph/Hz
kg/Ib 0.725 / 1.60 0.825 / 1.82
l/s / CFM 194 / 410 194 / 410l/s / CFM 170 / 360 170 / 360l/s / CFM 156 / 330 156 / 310
dBA 41 / 38 / 35 41 / 38 / 34mm/inmm/inkg/lb
mm/in
mm/inmm/in
V/Ph/HzW 55 65A 0.24 0.29W 19 23
790 805690 720620 625
mm/inmm/in
mm/in
1 216 20
pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in
PANEL MATERIALUNIT
MODELINDOOR UNIT
OUTDOOR UNIT
NOMINAL COOLING CAPACITY
NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT - 1Ø [3Ø]
REFRIGERANT TYPE R410A
IND
OO
R U
NIT
CONTROLAIR DISCHARGE 4 WAY AUTOMATIC LOUVER (UP & DOWN)OPERATION WIRELESS MICROCOMPUTER REMOTE CONTROL
AIR FLOWHIGH
15.5 + 2 / 34 + 4
MEDIUMLOW
SOUND PRESSURE LEVEL (H/M/L)UNIT DIMENSION (WITH PANEL) H X W X D
SENSIBLE HEAT FACTOR
QUANTITY
EERREFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBEPOWER SOURCE 220 - 240 / 1 / 50
FAN
QUANTITY 1
FAN MOTOR
PACKING DIMENSION (PANEL) H X W X D 316X630X630 (126X690X716) / 12.4X24.8X24.8 (5X27.2X28.2)UNIT WEIGHT (UNIT + PANEL)CONDENSATE DRAIN SIZE 19.1 / 3/4
TYPE TURBO FAN
DRIVE DIRECT
INDUCTION
INDEX OF PROTECTION (IP)
POLES 6
INNER GROOVE COPPER
SPEEDHIGH
RPMLOW
FILTER
GALVANIZED STEEL
1MATERIAL ABSG20
DIAMETER
WASHABLE SARANET FILTERQUANTITY 1
MATERIALDIAMETER
POWER SOURCE 220 - 240 / 1 / 50
IP20
315 / 12.4LENGTH 163 / 6.4
7.0 / 0.276
MATERIAL ALUMINIUM (SLIT FIN)
FACE AREA
INSULATION GRADE CLASS B
RATED INPUT POWERRATED RUNNING CURRENTMOTOR OUTPUT
REFRIGERANT CHARGE
MEDIUM
TYPE
250X570X570(295X640X640) / 9.8X22.4X22.4(11.6X25.2X25.2)
COIL
FIN
SIZE367.5 / 14.5381.0 /15.020.8 / 0.8
THICKNESS 0.23 / 0.009TUBE
THICKNESS 0.10 / 0.004
FIN PER INCH
0.25ROW
AIR QUALITY
TYPE
CASING ABSMATERIAL
m²/ft²
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.
12
TM-F
FC-0
515-
C
Specification (R410A)Ceiling Cassette Type - FFN-C Series (Continued)
m²/ft²
l/s / CFM 438 / 927 390 / 827
dBA 46 48
mm/inmm/in
kg/lb 28 / 61.7 29 / 63.9
mm/in
mm/in 9.52 / 3/8 12.7 / 1/2
mm/in
V/Ph/Hz
W 50 51
A 0.22 0.23
W 20
RPM 930 920
cm³ 330 320
V/Ph/HzµF 35
W 845 1134
A 3.78 5.08
A 18.00 24.50
mm/in 7 / 0.28
mm/in
mm/in0.33 / 3.55 0.32 / 3.44
2
CASING UNIT
MODELINDOOR UNIT
OUTDOOR UNIT
MOTOR SPEED
LOCKED ROTOR AMPERE - 1Ø [3Ø]
TYPE FLARE VALVE
1
GALVANIZED STEEL
MATERIAL ALUMINIUM
FACE AREA
POLES 6
MATERIAL COPPER
DIAMETER
TYPE ROTARY
OIL TYPE HAF68D1 NMOCZe -GlesRB68EP
OIL AMOUNT
RATED INPUT POWERRATED RUNNING CURRENT - 1Ø [3Ø]
POWER SOURCE 220 - 240 / 1 / 50
CAPACITOR
MATERIAL
INSULATION GRADE E
FAN MOTOR
TYPE INDUCTION
INDEX OF PROTECTION (IP) IP23
RATED RUNNING CURRENT
MOTOR OUTPUT
POWER SOURCE 220 - 240 / 1 / 50
COMPRESSOR
INSULATION GRADE CLASS B
RATED INPUT POWER
580X775X355 / 22.8X30.5X14.0
1
MATERIAL ASG 20
DIAMETER
DRIVE DIRECT
370 / 14.6
SIZELIQUID 6.35 / 1/4
GAS
TYPE PROPELLER
OU
TDO
OR
UN
IT
AIR FLOW
SOUND PRESSURE LEVEL
UNIT DIMENSION H X W X D 550X658X273 / 21.7X25.9X10.7
PACKING DIMENSION H X W X D
ROW
UNIT WEIGHT
PIPECONNECTION
THICKNESS 0.10 / 0.039
FIN PER INCH 18
FIN
COIL
FAN
QUANTITY 1
THICKNESS 0.2 / 0.0079
TUBE
QUANTITY
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.
FFN10CV1
RN10FV1
FFN15CV1
RN15FV1
13
TM-F
FC-0
515-
C
Specification (R410A)Ceiling Cassette Type - FCN-A2 Series
FCN20A2V1RN20CV1
FCN25A2V1RN25CV1
Btu/h 18000 22000W 5275 6448
0.80 0.75W 1840 2100A 8.25 9.41
Btu/hr/ W 9.78 10.48
V/Ph/Hz
kg/Ib 1.38 / 3.04 1.55 / 3.41
l/s / CFM 340 / 730 390 / 830l/s / CFM 290 / 615 350 / 740l/s / CFM 250 / 525 280 / 595l/s / CFM 200 / 430 230 / 490
dBA 39 / 36 / 33 / 28 42 / 39 / 35 / 32mm/inmm/inkg/Ib 26+4 / 57+9
mm/in
mm/inmm/in
V/Ph/HzW 161 200A 0.71 0.94W 20 30
420 470370 420330 380300 330
mm/inmm/in
mm/inm²/ft²
pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in
PANEL MATERIALUNIT
FAN
TYPE
INDEX OF PROTECTION (IP)
MATERIALCOIL
SIZEAIR QUALITY FILTER
18
CASINGMATERIAL
HIPS (PLASTIC)GALVANIZED STEEL
220 - 240 / 1 / 50
300X916X916 (124X1016X1016) / 11.8X36.1X36.1 (4.9X40.0X40.0)
CLASS B
INNER GROOVE COPPER
1
0.23 / 0.009
0.10 / 0.004
ASG 10
172 / 6.8486 / 19.1
NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT- 1Ø [3Ø]EERREFRIGERANT CONTROL (EXPANSION DEVICE)
TYPE
QUANTITYTYPE
ROW
QUANTITY
OUTDOOR CAP. TUBE
R410A
INDUCTION
MODELINDOOR UNIT
OUTDOOR UNIT
RATED RUNNING CURRENT
POLES
INSULATION GRADE
RATED INPUT POWER
DIAMETER
NOMINAL COOLING CAPACITY
LOW
IND
OO
R U
NIT
MATERIAL
AIR FLOW
SUPER LOW
H X W X D
4 WAY AUTOMATIC LOUVER (UP & DOWN)
CONDENSATE DRAIN SIZE
REFRIGERANT TYPE
UNIT DIMENSION (WITH PANEL)
UNIT WEIGHT (UNIT + PANEL)PACKING DIMENSION (PANEL) H X W X D
19.1 / 3/4
HIGH MEDIUM
SOUND PRESSURE LEVEL (H/M/L/SL)
AIR DISCHARGEOPERATION WIRELESS MICROCOMPUTER REMOTE CONTROL
265X820X820 (345X930X930) / 10.4X32.3X32.3 (13.8X36.6X36.6)
DRIVE DIRECT
MATERIAL
MOTOR OUTPUT
THICKNESSTUBE
THICKNESS
FIN PER INCH
FIN
DIAMETERLENGTH
POWER SOURCE 220 - 240 / 1 / 50
SENSIBLE HEAT FACTOR
REFRIGERANT CHARGE
QUANTITY 1
6
0.39 / 4.10
ALUMINIUM (SLIT FIN)
7.0 / 0.276
SPEED
HIGH
RPMMEDIUMLOWSUPER LOW
FAN MOTOR
POWER SOURCE
CONTROL
IP20
576 / 22.7556 / 21.922 / 0.87
FACE AREA
1
TURBO
WASHABLE SARANET FILTER
2
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.
14
TM-F
FC-0
515-
C
Specification (R410A)Ceiling Cassette Type - FCN-A2 Series (Continued)
l/s / CFM 675 / 1430 755 / 1600dBA 49 52
mm/in 654X855X328 / 25.7X33.7X12.9mm/in 693X990X415 / 27.3X39.0X16.3kg/Ib 43 / 94.8 47 / 103.6
mm/in
mm/in 12.7 / 1/2 15.88 / 5/8
mm/in
IP23
V/Ph/HzW 78 121A 0.34 0.53W 32 61
RPM 710 840
cm³ / fl.oz. 670 / 23
V/Ph/HzµFW 1601 1779A 7.2 7.94A 32
mm/inmm/in
mm/inm²/ft² 0.51 / 5.49
1
20
0.50 / 5.38
CASING UNIT
0.10 / 0.0039
ALUMINIUM
455 / 17.9
0.2 / 0.0079
TYPE
INSULATION GRADE E
POWER SOURCE 220 - 240 / 1 / 50
CAPACITORRATED INPUT POWER
ROTARY
6.35 / 1/4
CLASS F
2
GALVANIZED STEEL
INDUCTION
DIAMETER
INSULATION GRADE
6
RATED RUNNING CURRENT - 1Ø [3Ø]
SIZE
FLARE
POWER SOURCE
MODELINDOOR UNIT
OUTDOOR UNIT
TYPE
OIL TYPE
PACKING DIMENSION H X W X D
TYPE
UNIT WEIGHT
LIQUID
GAS
PIPECONNECTION
H X W X D
OU
TDO
OR
UN
IT
TYPE
SOUND PRESSURE LEVELAIR FLOW
UNIT DIMENSION
OIL AMOUNT
FAN
INDEX OF PROTECTION (IP)
LOCKED ROTOR AMP- 1Ø [3Ø]
POLES
COMPRESSOR
FAN MOTOR
MATERIAL
COPPER
7.0 / 0.276
FV50S
PROPELLER
220 - 240 / 1/ 50
FIN PER INCH
QUANTITY 1
MATERIAL ASG20
DRIVE
18
DIAMETER
FIN
QUANTITY 1
MOTOR SPEED
THICKNESSTUBE
DIRECT
RATED INPUT POWERRATED RUNNING CURRENT
ROWFACE AREA
MATERIAL
MOTOR OUTPUT
MATERIAL
50
THICKNESSCOIL
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.
FCN20A2V1RN20CV1
FCN25A2V1RN25CV1
15
TM-F
FC-0
515-
C
Specification (R410A)Ceiling Cassette Type - FCN-A2 Series
Btu/hW
WA
Btu/hr/ W
V/Ph/Hz
kg/Ib 1.80 / 3.97 2.60 / 5.73
l/s / CFMl/s / CFMl/s / CFMl/s / CFM
dBAmm/inmm/inkg/Ib
mm/in
mm/inmm/in
V/Ph/HzWAW
mm/inmm/in
mm/inm²/ft²
pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in
PANEL MATERIALUNIT
FAN
TYPE
INDEX OF PROTECTION (IP)
MATERIALCOIL
SIZEAIR QUALITY FILTER
20
CASINGMATERIAL
HIPS (PLASTIC)GALVANIZED STEEL
220 - 240 / 1 / 50
CLASS B
INNER GROOVE COPPER
1
0.23 / 0.009
0.10 / 0.004
ASG 10
172 / 6.8486 / 19.1
NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT- 1Ø [3Ø]EERREFRIGERANT CONTROL (EXPANSION DEVICE)
TYPE
QUANTITYTYPE
ROW
QUANTITY
OUTDOOR CAP. TUBE
R410A
INDUCTION
MODELINDOOR UNIT
OUTDOOR UNIT
RATED RUNNING CURRENT
POLES
INSULATION GRADE
RATED INPUT POWER
DIAMETER
NOMINAL COOLING CAPACITY
LOW
IND
OO
R U
NIT
MATERIAL
AIR FLOW
SUPER LOW
H X W X D
4 WAY AUTOMATIC LOUVER (UP & DOWN)
CONDENSATE DRAIN SIZE
REFRIGERANT TYPE
UNIT DIMENSION (WITH PANEL)
UNIT WEIGHT (UNIT + PANEL)PACKING DIMENSION (PANEL) H X W X D
19.1 / 3/4
HIGH MEDIUM
SOUND PRESSURE LEVEL (H/M/L/SL)
AIR DISCHARGEOPERATION WIRELESS MICROCOMPUTER REMOTE CONTROL
DRIVE DIRECT
MATERIAL
MOTOR OUTPUT
THICKNESSTUBE
THICKNESS
FIN PER INCH
FIN
DIAMETERLENGTH
POWER SOURCE 220 - 240 / 1 / 50
SENSIBLE HEAT FACTOR
REFRIGERANT CHARGE
QUANTITY 1
6
ALUMINIUM (SLIT FIN)
7.0 / 0.276
SPEED
HIGH
RPMMEDIUMLOWSUPER LOW
FAN MOTOR
POWER SOURCE
CONTROL
IP20
576 / 22.7556 / 21.922 / 0.87
FACE AREA
1
TURBO
WASHABLE SARANET FILTER
3050089390.76282013.7010.82
0.37 / 4.00 0.46 / 4.97318
3
FCN30A2V1RN28CV1
FCN40A2V1RN35DV1
2800082060.78283613.309.87
490 / 1030410 / 860350 / 740295 / 620
44 / 41 / 38 / 35300X820X820 (385X930X930) / 11.8X32.3X32.3 (15.2X36.6X36.6)335X916X916(124X1016X1016) / 13.2X36.1X36.1(4.9X40.0X40.0)
32+4 / 71+9
430 / 920380 / 810330 / 710290 / 610
47 / 44 / 41 / 37
26+4 / 57+9300X916X916 (124X1016X1016) / 11.8X36.1X36.1 (4.9X40.0X40.0)265X820X820 (345X930X930) / 10.4X32.3X32.3 (13.8X36.6X36.6)
1760.7960
680580510435
2411.0750
630530470415
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.
16
TM-F
FC-0
515-
C
Specification (R410A)Ceiling Cassette Type - FCN-A2 Series (Continued)
808 / 1712 1605 / 3400
54 58
852X1030X400 / 33.5X40.6X15.8
1010X1180X514 / 39.8X46.5X20.24
57 / 126 86 / 190
124 257
0.54 1.10
66 145
874 625
86
2471 2387
11.69 11.81
63 97
FLARE
756X855X328 / 29.8X33.7X12.9
793X990X415 / 31.2X39.0X16.3
SCROLL
POE OIL
15.88 / 5/8
9.52 / 3/8
1242 / 42
FV50S
1130 / 38
l/s / CFMdBA
mm/inmm/inkg/Ib
mm/in
mm/in
mm/in
IP23
CLASS FIP54
V/Ph/HzWAW
RPM
cm³ / fl.oz.
V/Ph/HzµFW
60
AA
mm/inmm/in
mm/inm²/ft²
CASING UNIT
0.11 / 0.0043
0.85 / 9.150.61 / 6.58
ALUMINIUM ALUMINIUM (CORR. FIN)
610 / 24455 / 18
0.23 / 0.009
TYPE
INSULATION GRADE E
POWER SOURCE 220 - 240 / 1 / 50
CAPACITORRATED INPUT POWER
CLASS B
2
GALVANIZED STEEL
INDUCTION
DIAMETER
INSULATION GRADE
RATED RUNNING CURRENT - 1Ø [3Ø]
SIZE
POWER SOURCE
MODELINDOOR UNIT
OUTDOOR UNIT
TYPE
OIL TYPE
PACKING DIMENSION H X W X D
TYPE
UNIT WEIGHT
LIQUID
GAS
PIPECONNECTION
H X W X D
OU
TDO
OR
UN
IT
TYPE
SOUND PRESSURE LEVELAIR FLOW
UNIT DIMENSION
OIL AMOUNT
FAN
INDEX OF PROTECTION (IP)
LOCKED ROTOR AMP- 1Ø [3Ø]
POLES
COMPRESSOR
FAN MOTOR
MATERIAL
COPPER
7.0 / 0.276
PROPELLER
220 - 240 / 1/ 50
FIN PER INCH
QUANTITY 1
MATERIAL ASG 20
DRIVE
18
DIAMETER
FIN
QUANTITY 1
MOTOR SPEED
THICKNESSTUBE
DIRECT
RATED INPUT POWERRATED RUNNING CURRENT
ROWFACE AREA
MATERIAL
MOTOR OUTPUT
MATERIAL
45
THICKNESSCOIL
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.
FCN30A2V1RN28CV1
FCN40A2V1RN35DV1
17
TM-F
FC-0
515-
C
Specification (R410A)Ceiling Cassette Type - FCN-A2 Series
FCN40A2V1RN40DY1
FCN50A2V1RN50DY1
Btu/h 40000 45000W 11723 13189
0.70 0.73W 3850 4390A [6.86] [7.8]
Btu/hr/ W 10.39 10.25
V/Ph/Hz
kg/Ib 2.10 / 4.63 2.25 / 4.96
l/s / CFM 490 / 1030 570 / 1200l/s / CFM 410 / 860 490 / 1030l/s / CFM 350 / 740 440 / 930l/s / CFM 295 / 620 370 / 780
dBA 44 / 41 / 38 / 35 47 / 44 / 43 / 39mm/inmm/inkg/lb 32 + 4 / 71 + 9
mm/in
mm/inmm/in
V/Ph/HzW 176 221A 0.79 0.97W 60 100
680 780580 680510 620435 530
mm/inmm/in
mm/inm²/ft² 0.46 / 4.97
3
pcLENGTH mm/inWIDTH mm/inTHICKNESS mm/in
PANEL MATERIALUNIT
380 - 415 / 3 / 50
POWER SOURCE 220 - 240 / 1 / 50
FAN
CLASS B
INNER GROOVE COPPER
ALUMINIUM (SLIT FIN)
7.0 / 0.276
1
6
IP20
TYPE
MATERIALCOIL
576 / 22.7
0.23 / 0.009
0.10 / 0.004
DIAMETERLENGTH
ASG 10DIRECT
486 / 19.1172 / 6.8
1
1
TURBO
INDUCTION
SENSIBLE HEAT FACTOR
REFRIGERANT CHARGE
QUANTITYMATERIALDRIVE
QUANTITY
LOW
PACKING DIMENSION (PANEL)
OUTDOOR CAP. TUBE
R410A
CONTROL
FACE AREAROW
H X W X D 335X916X916(124X1016X1016) / 13.2X36.1X36.1(5.1X40.2X39.4)
TYPE
WIRELESS MICROCOMPUTER REMOTE CONTROL
RATED INPUT POWER
UNIT WEIGHT (UNIT + PANEL)
POWER SOURCE
4 WAY AUTOMATIC LOUVER (UP & DOWN)
300X820X820 (385X930X930) / 11.8X32.3X32.3 (15.2X36.6X36.6)SOUND PRESSURE LEVEL (H/M/L/SL)
INDEX OF PROTECTION (IP)
19.1 / 3/4
MODEL INDOOR UNITOUTDOOR UNIT
UNIT DIMENSION (WITH PANEL)
NOMINAL COOLING CAPACITY
HIGH MEDIUM
AIR FLOW
NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT - 1Ø [3Ø]EERREFRIGERANT CONTROL (EXPANSION DEVICE)
H X W X D
REFRIGERANT TYPE
SUPER LOW
IND
OO
R U
NIT
TYPE
POLES
CONDENSATE DRAIN SIZE
INSULATION GRADE
QUANTITY
MATERIALDIAMETER
WASHABLE SARANET FILTER
OPERATION
RATED RUNNING CURRENTMOTOR OUTPUT
AIR DISCHARGE
SPEED
HIGH
RPMMEDIUMLOWSUPER LOW
FAN MOTOR
TUBE
FIN
SIZEAIR QUALITY FILTER
CASINGMATERIAL
THICKNESS
THICKNESS
FIN PER INCH 20
556 / 21.922 / 0.87
HIPS (PLASTIC)GALVANIZED STEEL
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.
18
TM-F
FC-0
515-
C
Specification (R410A)Ceiling Cassette Type - FCN-A2 Series (Continued)
l/s / CFM 1605 / 3400 1442 / 3056
dBA 58 60
mm/in
mm/in
kg/Ib 95 / 209 98 / 216
mm/in
mm/in
mm/in
V/Ph/Hz
W 257 276
A 1.10 1.34
W 145 145
RPM 625 625
COPELAND ULTRA 32-3 MAF
cm³ / fl.oz. 1951 / 66.0
POE OIL
1656 / 56.0
V/Ph/Hz
W
µF
3417 3893
A [6.23] [7.03]
A [64] [74]
mm/in
mm/in
mm/in
m²/ft²
CASING UNIT
POWER SOURCE 220 - 240 / 1 / 50
E
POWER SOURCE 380-415 / 3 / 50
CAPACITOR N/A
852X1030X400 / 33.5X40.6X15.7
COIL
2
THICKNESS
FIN PER INCH 18
INNER GROOVE COPPER
ALUMINIUM (CORR. FIN)
7.0 / 0.276
0.85 / 9.15
TUBE
FIN
MATERIAL
GALVANIZED STEEL
0.23 / 0.009
0.10 / 0.004
RATED INPUT POWER
LOCKED ROTOR AMP - 1Ø [3Ø]
INSULATION GRADE
MODELINDOOR UNIT
OUTDOOR UNIT
TYPE
GAS
UNIT WEIGHT
AIR FLOW
INSULATION GRADE
SOUND PRESSURE LEVEL
PROPELLER
8
SCROLL
H X W X D
OU
TD
OO
R U
NIT
QUANTITY
INDEX OF PROTECTION (IP)
UNIT DIMENSION H X W X D
TYPE
POLES
RATED RUNNING CURRENT
MOTOR OUTPUT
DIAMETER
FAN
ROW
TYPE
FACE AREA
MATERIAL
TYPEPIPECONNECTION
MATERIAL
THICKNESS
RATED INPUT POWER
PACKING DIMENSION
SIZE
COMPRESSOR
OIL TYPE
RATED RUNNING CURRENT - 1Ø [3Ø]
MOTOR SPEED
LIQUID
QUANTITY
FAN MOTOR
OIL AMOUNT
MATERIAL
DRIVE
DIAMETER
INDUCTION
DIRECT
610 / 24
ASG 20
1
CLASS F
IP54
FLARE
1010X1180X514 / 39.8X46.5X20.24
9.52 / 3/8
15.88 / 5/8
1
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW: COOLING - 27˚C DB / 19˚C WB INDOOR AND 35˚C DB / 24˚C WB OUTDOOR4) SOUND PRESSURE LEVELS ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER AS A RESULT OF AMBIENT CONDITION.5) THE CURRENT MEASURED AT SITE MAY VARY FROM THE SPECIFICATION STATED.
FCN40A2V1
RN40DY1
FCN50A2V1
RN50DY1
19
TM-F
FC-0
515-
C
Safety Devices Data - (R-22) Series
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
R35DV1 R40DV1
NC
OPEN kPa / psi 2937 / 426
CLOSE kPa / psi 2413 / 350
NC
OPEN kPa / psi 124 / 18
CLOSE kPa / psi 193 / 28
NA <YES>
°C / °F NA <130 / 266>
OPEN kPa / psi
CLOSE kPa / psi
OPEN kPa / psi
CLOSE kPa / psi
°C / °F
NC
124 / 18
193 / 28
<YES>
<130 / 266>
FC50A2V1
R50DY1
NC
2937 / 426
2413 / 350
MODELINDOOR UNIT
OUTDOOR UNIT
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE
LOW PRESSURE SWITCH
TYPE
PHASE SEQUENCER, 1Ø <3Ø>
DISCHARGE THERMOSTAT SETTING
FC40A2V1
OUTDOOR UNIT
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE
LOW PRESSURE SWITCH
DISCHARGE THERMOSTAT SETTING
TYPE
PHASE SEQUENCER, 1Ø <3Ø>
MODELINDOOR UNIT
Safety Devices Data - (R-410A) Series
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
R35DV1 RN40DY1
NC
OPEN kPa / psi 4137 / 600
CLOSE kPa / psi 3310 / 480
NC
OPEN kPa / psi 48 / 7
CLOSE kPa / psi 152 / 22
NA <YES>
°C / °F NA <130 / 266>
OPEN kPa / psi
CLOSE kPa / psi
OPEN kPa / psi
CLOSE kPa / psi
°C / °F
NC
48 / 7
152 / 22
<YES>
<130 / 266>
FCN50A2V1
RN50DY1
NC
4137 / 600
3310 / 480
PHASE SEQUENCER, 1Ø <3Ø>
DISCHARGE THERMOSTAT SETTING
PHASE SEQUENCER, 1Ø <3Ø>
DISCHARGE THERMOSTAT SETTING
MODELINDOOR UNIT
OUTDOOR UNIT
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE
LOW PRESSURE SWITCH
TYPE
MODELINDOOR UNIT
LOW PRESSURE SWITCH
TYPE
FCN40A2V1
OUTDOOR UNIT
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE
20
TM-F
FC-0
515-
C
4.ApplicationInformation
Ensure the operating temperature is in allowable range.
Cooling Only
! Caution :
The use of your air conditioner outside the range of working temperature and humidity can result in serious failure.
OutdoorDB (°C)
46
43
19
14 19 23 Indoor WB (°C)
Cooling Operation Range
Operating Range for Air Cool Direct Expansion Unit
DB = Dry Bulb WB = Wet Bulb
Operating Range
21
TM-F
FC-0
515-
C
Refrigerant Circuit Diagram
Model : (Indoor) FF10CV1, FF15CV1, FC20A2V1, FFN10CV1, FFN15CV1, FCN20A2V1, FCN25A2V1 (Outdoor) R10CV1, R15CV1, R18CV1, R20CV1, RN10FV1, RN15FV1, RN20CV1, RN25CV1
Model : (Indoor) FC25A2V1, FCN30A2V1 (Outdoor) R20CV1, R25CV1, RN28CV1
22
TM-F
FC-0
515-
C
Model : (Indoor) FC30A2V1 (Outdoor) R28CV1, R30CV1
Model : (Indoor) FC40A2V1, FC50A2V1 (Outdoor) R35DV1, R40DY1, R50DY1
23
TM-F
FC-0
515-
C
Model : (Indoor) FCN40A2V1, FCN50A2V1 (Outdoor) RN35DV1, RN40DY1, RN50DY1
24
TM-F
FC-0
515-
C
Controller
DGS01
Operating Guide
1 Transmission Source • The source where the signal will be transmitted.
2 Signal Transmission Indication • Blink to confirm that the last setting has been transmitted to the unit.
3 “ON/OFF” Button • Press once to start the air conditioner unit. • Press again to stop the unit.
4 Fan speed selection • Press the button continuously will toggle the fan speed in the following order: Low Med High Auto • Stop pressing when the desired fan speed appears on the display screen.
5 Operation mode • Press the MODE button to select the type of operating mode. • For cooling only unit, the available modes are: COOL ( ), DRY ( ) and FAN ( ).
6 Automatic air swing • Press the SWING ( ) button to activate the automatic air swing function. • To distribute the air to a specific direction, press the SWING ( ) button and wait until the louver move to the desired direction and press the button once again.
7 Turbo function • Press for fast cooling operation. • Fan speed turn to maximum speed. • Press again to deactivate the function. • Available under COOL and DRY modes only. • Any change of fan speed will deactivate this function.
TURBO QUIET
SLEEP
ON OFF
MODE
TIMER
CANCEL CANCELCLOCK
3
13
4
9
12
7
1
2
5
6
8
10
11
25
TM-F
FC-0
515-
C
7 Turbo function • Press for fast cooling operation. • Fan speed turn to maximum speed. • Press again to deactivate the function. • Available under COOL and DRY modes only. • Any change of fan speed will deactivate this function.
8 Quiet function • Press for quiet operation. • Fan speed turn to minimum speed. • Press again to deactivate the function. • Any change of fan speed will deactivate this function.
9 ON timer setting • Press the ON TIMER button will activate the on timer function. • Set the desired on time by pressing the ON TIMER button continuously. If the timer is set to 7.30am, the air conditioner will turn on at 7.30am sharp. • Press the CANCEL button to cancel the on timer setting.
10 OFF timer setting • Press the OFF TIMER button will activate the off timer function. • Set the desired off time by pressing the OFF TIMER button continuously. • Press the CANCEL button to cancel the off timer setting.
11 Clock time setting • Press and hold button to set the clock time.
12 Sleep mode setting • Press the button will activate the sleep mode function. • This is an energy saving option. When the unit is operating under cooling mode, the set temperature is increased by 0.5°C after 30 minutes, 1˚C after an hour, and 2˚C after 2 hours. • This function is available under COOL mode.
13 Temperature setting • To set the desired room temperature, press the or button to increase or decrease the set temperature. • The temperature setting range is from 16°C to 30°C. • Press both buttons and simultaneously to toggle from °C to °F setting.
26
TM-F
FC-0
515-
C
DSLM8
Operating Guide
MODETURBO
TIMEROVERRIDE
TIMER
ON OFFTIMER
SWING QUIET
SLEEP
14
5
6
23
1011
8
97
1 MODE Button Press the MODE button to switch operation from COOL, AUTO*, DRY*, FAN. Check the display to
see in which mode the control is set. *AUTO and DRY are available for selected models only.
2 TURBO Fan Speed Press the Turbo key once to activate Turbo fan speed. Turbo symbol will be shown. To disable Turbo
fan speed and back to previous fan speed, press the Turbo key once again. For the unit that does not have TURBO fan speed it will show high fan speed.
3 SWING Function Press SWING button to activate the swing function. Press it again to deactivate it.
4 QUIET Fan Speed Press the Quiet key once to activate Quiet fan speed. Quiet symbol will be shown. To disable Quiet
fan speed and back to previous fan speed, press the Quiet key once again. For the unit that does not have QUIET fan speed it will show low fan speed.
5 “▲” or “▼” Set Temperature Button Press the temperature button and set the temperature of your choice by pressing “▲” or “▼” button
once, temperature changes by 1°C or 1°F. The default temperature setting range is from 16°C to 30°C (60°F to 86°F). When the Option 20 - 30ºC is set, the temperature range limit is set to 20ºC to 30ºC (68°F to 86°F). Pressing both keys simultaneously will toggle the temperature setting between ºC and ºF.
6 SLEEP Function Press the SLEEP button to activate the sleep mode. DRY MODE and FAN MODE are not valid
during sleep function.
27
TM-F
FC-0
515-
C
7 “ON TIMER” and “OFF TIMER” The unit has 2-event timer, namely Timer 1 and Timer 2, each event has an ON TIMER and an OFF
TIMER. The key press activity for Timer ON and Timer OFF is shown on Table 1.1 Table 1.1: Timer ON and Timer OFF key press and event sequence.
All timers are event-triggered timers and can be overridden by the ON/OFF button and Override function.
Set Event 1 and Event 2 Timers
Process for Timer ON and Timer OFF is the same.1. Press and hold Timer ON/OFF key for 3 seconds to go into timer setting mode. (Icon ON 1 or OFF 1 will blink)2. Press UP or DOWN to select Timer 1 or Timer 2 to set. (‘1’ blinking indicate that Timer 1 is currently selected, ‘2’ blinking indicate that Timer 2 is currently selected)3. Press Timer ON/OFF key again to confirm. (Day will blink next)4. Press UP or DOWN to select the day.5. Press Timer ON/OFF key again to confirm the day. (Hour will blink next)4. Press UP or DOWN to change the hour.5. Press Timer ON/OFF key again to confirm the hour. (Minute will blink next)6. Press UP or DOWN to change the minute.7. Press Timer ON/OFF key again to confirm the minute.
Each timer (Timer 1 ON or Timer 1 OFF or Timer 2 ON or Timer 2 OFF) will only be set separately after all 7 steps, if there is no key operation for 5 seconds during setting the timer, it will automatically exits from setting mode and no changes will be made.
ON/OFF timer will be checked every 1 minute.It is not advisable to set ON TIMER and OFF TIMER to have same values. Shall these occur, the effective timer will be treated with priority as stated in Table 1.2.Example:ON TMR 2 settings: DAY – TUE, TIMER – 5.00pmOFF TMR 1 settings: DAY – TUE, TIMER – 5.00pmOutcome when RTC reaches 5.00pm on TUE: - when unit is on, no respond. - when unit is off, unit will trigger to on.
Table 1.2: Timer Priority
ON Timer 1 ON Timer 2 OFF Timer 1 OFF Timer 2 Deactivated Deactivated Deactivated Deactivated Activated Deactivated Activated Deactivated Deactivated Activated Deactivated Activated Activated Activated Activated Activated
TIMER ON KEY TIMER OFF KEY
Priority Timer
1 (Highest)
2
3
4 (Lowest)
ONTMR2
OFFTMR2
ONTMR1
OFFTMR1
Upon IR reception, IR wireless remote controller will override ON TIMER 2 and OFF TIMER 2 settings.
28
TM-F
FC-0
515-
C
8 OVERRIDE Function Press the OVERRIDE key once will activate the override function for 1 hour. An indicator
“OVERRIDE 1” will show on the LCD. Press the same key again will increase the setting to 2 hours. An indicator “OVERRIDE 2” will be shown. Subsequent press will deactivate the override function. After the override timer is completed, the override function is deactivated and the logo is OFF. All other timers will be resumed.
9 FAN Speed Function Fan speed can be changed via pressing the FAN key: Low > Med > High > Auto > Low >
10 ON/OFF Button Starting Operation: - Press the ON/OFF button, the LCD will show full display and the unit is turned on. Stopping Operation: - Press the ON/OFF button, the LCD will show real time clock only and the unit is turn off.
11 Real-time Clock (RTC) Display RTC is shown on screen during the unit ON or OFF except for power failure or error code.
Set RTC Setting 1. Press RTC key one time will activate RTC setting mode. (Day will blink) 2. Press UP or DOWN to select the day. 3. Press RTC again to confi rm the day. (Hour will blink next) 4. Press UP or DOWN to change the hour. 5. Press RTC again to confi rm the hour. (Minute will blink next) 6. Press UP or DOWN to change the minute. 7. Press RTC again to confi rm the minute. RTC will only be set after all 7 steps, if there is no key operation for 5 seconds during setting the
RTC, it will automatically exits from setting mode and no changes will be made on the setting.
12 Hardware Setting The unit has 4 jumpers option to control the board function. Table 2.0: Summary of Hardware Settings
OPTION
Set Temp. Range
TURBO_QUIET
Reserved
Reserved
With Jumper
Set Temp. Range from 20˚C-30˚C
Reserved
Reserved
Without Jumper
Set Temp. Range from 16˚C-30˚C(Default)
Enable turbo and quiet fan speed
Reserved
Reserved
Disable turbo and quiet fan speed(Default)
29
TM-F
FC-0
515-
C
OPERATING STATE AND FAULT TABLE
Wireless Remote Control (Universal Board)Cooling : LED Indicator Light Display
ON / ON or OFF BLINKING
Wired Remote Control (Universal Board)Cooling
POWER TIMER SLEEP
Error Code at 7 Segment Display Operation / Faulty Indication Blink E1 Room sensor contact open / short Blink E2 Indoor coil sensor contact open Blink E3 Outdoor coil sensor contact open
Blink E4 Compressor overload/ Indoor coil sensor short/Outdoor coil sensor short
Blink E5 Gas leak Blink E6 Pump faulty
POWER TIMER
1 Time
1 Time
2 Times
3 Times
2 Times
3 Times
SLEEPOperation / Faulty Indication
Cool ModeTimer OnSleep Mode On
Compressor Overload
Pump Fault
Gas Leak
Room Sensor Open or Short
Indoor Coil Sensor Open or Short
Outdoor Coil Sensor Open or Short
30
TM-F
FC-0
515-
C
Water PumpThewaterpumpwillonifcompressorisonduringcoolingcycle.Thepumpwillremainonforatleast5minutesafterthecompressorisoff.Duringmodechangefromcoolingtonon-coolingmode,thepumpwillonforminimum5minutes.Duringdefrostcycle,thepumpwillonandwillonforanother5minutesoncethedefrostcycleisterminated.
Water Level SwitchThisnormallycloseswitchistodetectfaultsinwaterpumpsystem.Itwillconfirmfor30secondsforswitchopenand60secondsforswitchclose.Onceswitchisconfirmedopen,itwillforcecompressortocutoff.Iftheswitchisclosedwithin5minutes,thecompressorisallowedtocutin.Iftheswitchdoesnotcloseformorethan5minutes,thesystemwillwarnuserregardingthefault,thecompressorisnotallowedtocutin.Iftheswitchisconfirmedopenedtwicewithin30minutes,thesystemassumestherearefaults.
Phase SequencerTheunitwithScrollCompressorcanonlyrotateinonedirection.Forthisreason,aprotectivedevice(phasesequencer)isfittedtopreventincorrectwiringoftheelectricalphases.Whenthethreephasesarenotconnectedcorrectly,thephasesequenceroperates,andtheunitwillnotstart.Thisdeviceislocatedinthecontrolboxoftheoutdoorunit.
ThefollowingtableshowstheLEDindicatorlightforphasesequencerundernormaloperationandfaultconditions.
LED_PWR(Red)
LED_S (Yellow)
LED_T (Yellow)
Normal Operation
LEDs Error Indication
On
On On
On On
-On On
-
-
-
-
- -
-
On
-
Reverse Phase Blink Blink BlinkBlink
Blink
Blink
Blink
System OffBlink
Blink
Blink
T Phase Missing S Phase Missing R Phase Missing R Phase Missing (Main Power) Overload
Sensor Missing
High Pressure
Low Pressure
Notes: 1. “-” means LED off.2. When R phase missing, no LED or buzzer will indicate the error, but relay 71 (Common) and 81(NO) will cut off.3. The unit will check the discharge sensor availability only during power up.4. All errors can only recover through manually reset.
31
TM-F
FC-0
515-
C
5.Installations
Installation GuidelineSafety Precautions
WARNING
CAUTIONPlease take note of the following important points when installing.
If gas leaks and accumulates around the unit, it may cause fire ignition.
Ensure that drainage piping is connected properly.If the drainage piping is not connected properly, it may cause water leakage which will dampen the furniture.
Do not overcharge the unit.
This unit is factory pre-charged. Overcharge will cause over-current or damage to the compressor.
Ensure that the unit’s panel is closed after service or installation.
Unsecured panels will cause the unit to operate noisily.
Sharp edges and coil surfaces are potential locations which may cause injury hazards.Avoid from being in contact with these places. Before turning off the power supply, set the remote controller’s ON/OFF switch to the “OFF” positionto prevent the nuisance tripping of the unit. If this is not done, the unit’s fans will start turning automatically when power resumes, posing a hazard to service personnel or the user. Do not operate any heating apparatus too close to the air conditioner unit. This may cause the plastic panel to melt or deform as a result of the excessive heat. Ensure the color of wires of the outdoor unit and the terminal markings are same to the indoors respectively.
IMPORTANT : DO NOT INSTALL OR USE THE AIR CONDITIONER UNIT IN A LAUNDRY ROOM.Do not use joined and twisted wires for incoming power supply.
Do not install the unit where leakage of flammable gas may occur. •
•
•
•
•
•
•
•
••
NOTICE
• Installation and maintenance should be performed by qualified persons who are familiar with local code and regulation, and experienced with this type of appliance.• All field wiring must be installed in accordance with the national wiring regulation.• Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work according to the wiring diagram.• The unit must be GROUNDED to prevent possible hazard due to insulation failure.• All electrical wiring must not touch the refrigerant piping or any moving parts of the fan motors.• Confirm that the unit has been switched OFF before installing or servicing the unit.• Disconnect from the main power supply before servicing the air conditioner unit.• DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which may result in fire hazards.• Keep the indoor and outdoor units, power cable and transmission wiring, at least 1m from TVs and radios, to prevent distorted pictures and static. {Depending on the type and source of the electrical waves, static may be heard even when more than 1m away}.
Disposal requirementsYour air conditioning product is marked with this symbol. This means that electrical and electronic products shall not be mixed with unsorted household waste.Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the refrigerant, of oil and of other parts must be done by a qualified installer in accordance with relevant local and national legislation. Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. Please contact the installer or local authority for more information.Batteries must be removed from the remote controller and disposed of separately in accordance with relevant local and national legislation.
32
TM-F
FC-0
515-
C
Installation Diagram
Indoor Unit
Drain Hose
Front Panel
Air Filter(behind the grille)
Air Intake Grille
Thermal Insulation
Air Discharge
Air Discharge Louver
Air Intake
Air Intake
Outdoor Unit
Wrap the insulated pipe with the finishing tape from bottom to top
33
TM-F
FC-0
515-
C
0.5m or more 0.5m or more
3m o
r le
ss
1m o
r m
ore
FloorObstacle
0.5m or more 0.3m
or
less
Bea
m
Preliminary Site SurveyBe sure to read this manual before installing the air-conditioner indoor unit.• Voltage supply fluctuation must not exceed +10% of rated voltage. Electricity supply lines must be
independent of welding transformers which can cause high supply fluctuation.• Ensure that the location is convenient for wiring, piping and drainage.• Do not exert pressure on the resin parts when opening the unit or when moving it after opening.• Do not move the unit from packaging while moving, until it reaches the installation site. Use safe
material or protection plates when unpacking it or lifting it to avoid damage or scratches to the unit.
• Ensure a location where:a) Drainage can be done easily.b) Convenient for wiring and piping.c) Which have enough space for installation and service work.d) Where no risk of fl ammable gas leakage.e) When free from any obstacles in path of cool air discharge and warm air return and must allow
spreading of air throughout the room (near the center of the room).f) Must be provided clearance for indoor unit from the wall and obstacles as shown in figure below.g) The installation place must be strong enough to support a load 4 times the indoor unit weight to
avoid amplifying noise and vibration.h) The installation place (hanging ceiling surface) must be assuring levelness and the height in the
ceiling is 350mm or more.i) The indoor unit must be away from heat and steam sources (avoid installing it near an entrance).
Unit Installation
Ceiling Opening Size = 875mm
Hanging rod size = 790mm
Cei
ling
Ope
ning
Siz
e =
875
mm
Han
ging
rod
siz
e =
621
mm
Unit
Piping Direction
• Measure and mark the position for the hanging rod. Drill the hole for the angle nut on the ceiling and fix the hanging rod.
• The installation template is extended according to temperature and humidity. Check on dimensions in use.• The dimensions of the installation template are the same as those of the ceiling opening dimensions.• Before ceiling laminating work is completed, be sure to fi t the installation template to the indoor unit.
Installation Of The Indoor Unit
NOTE: Be sure to discuss the ceiling drilling work with the installers concerned.
�
FF-C FC-A2
34
TM-F
FC-0
515-
C
FF-CFC-A2
Unit Hanging
Drain Piping Work
CeilingBoard
30.0mm (FF-C, FC-A2)
• Hold the unit and hang it on the hanging rod with the washer, spring washer and nut.• Adjust the unit height to 30.0mm between the indoor unit bottom surface and the ceiling surface.• Confirm with a level gauge that the unit is installed horizontally and tighten the nut and bolt to prevent
unit falling and vibration.• Open the ceiling board along the outer edge of the paper installation template.
• Avoid installing the drain pipe in upward gradient after the drain connection.
• Ensure the height of drain pipe from ceiling is 700mm or less if it is necessary to increase the height of drain pipe to prevent water leak.
• Avoid installing the drain pipe in up and down slope to prevent reversed water flow.
• During the drain pipe connection, be careful not to exert extra force on the drain connector at indoor unit.
• The outside diameter of the drain connection at the flexible drain hose is 20mm.
• Be sure to execute heat insulation (polyethylene foam with thickness more than 8.0mm) on the drain piping to avoid the condensed water dripping inside the room.
• Connect the main drain pipe to the flexible drain hose.
• Feed water from flexible drain hose to check the piping for leakage.
• When the test is completed, connect the flexible drain hose to the drain connector on the indoor unit.
Ceiling
700.
00m
m
or le
ss
Panel
Flexible Hose
Pipe Clamp
See View A
IndoorUnit
����������
Feed water
Flexible Drain Hose
Main Drain Pipe
View A
Note: This Indoor Unit uses a drain pump for condensed water drainage. Install the unit horizontally to prevent water leakage or condensation around the air outlet.
35
TM-F
FC-0
515-
C
Open
Screw
Panel Installation
• The front panel can only be fitted in one direction, follow the piping direction. (Follow piping arrow sticker on front panel)
• Be sure to remove the installation template before installing the front panel.
• Open the air intake grille by pulling back the catchers and removing it together with filter from panel.• Install the front frame panel onto the indoor unit by 4 screws and tighten it completely to prevent cool
air leakage.• Connect the LED wire and air swing wire to the indoor unit.• The air swing connector must put inside the control box after connected.
From Unit Control Box
From Front Panel
LED Wire
Air Swing Wire
Indoor UnitCool Air
Ceiling Board
Panel
Air Leak
Good Installation Bad Installation
Cool AirAir Leak
Ceiling Board
Panel
NOTE: Install the front frame panel firmly to prevent cool air leakage which will cause condensation and water dripping.
36
TM-F
FC-0
515-
C
Installation Of The Outdoor Unit
As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve maximum cooling capacity, the location selected for outdoor unit should fulfill the following requirements:
• Install the condensing (outdoor) unit in a way such that the hot air distributed by the outdoor condensing unit cannot be drawn in again (as in the case of short circuit of hot discharge air). Allow sufficient space for maintenance around the unit.
• Ensure that there is no obstruction of air flow into or out of the unit. Remove obstacles which block air intake or discharge.
• The location must be well ventilated, so that the unit can draw in and distribute plenty of air thus lowering the condensing temperature.
• A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.• A place protected from the direct sunlight. Otherwise use an awning for protection, if necessary.
• The location must not be susceptible to dust or oil mist.
Installation Clearances
Dimension
MinimumDistance,mm (in)
300
A B C D
(11.8)1000(39.4)
300(11.8)
500(19.7)
Ret
urn
air
Dis
char
ge a
ir
A
Obs
tacl
e
Obs
tacl
e
B
Obs
tacl
e
Ret
urn
air
Ser
vice
acc
ess
DC
Obs
tacl
e
• Outdoor units must be installed such that there is no short circuit of the hot discharge air or obstruction to smooth air flow. Select the coolest possible place where intake air should not be hotter than the outside temperature (Refer to operating range).
37
TM-F
FC-0
515-
C
Refrigerant Piping
Allowable Pipe Length And ElevationWhen the pipe length becomes too long, both the capacity and reliability drop. As the number of bendsincreases, system piping resistance to the refrigerant flow increases, thus lowering the cooling capacity, and as the result the compressor may become defective. Always choose the shortest path and follow the recommendation as tabulated below:
Piping Sizes (Flare Connection Type)Piping sizes are as follows:
R22
For R22
Indoor FF10CV1
R10CV1
12
5
10
FF15CV1
R15CV1
12
5
10
R18CV1
15
8
10
R20CV1
15
8
10
R20CV1
15
8
10
R25CV1
15
8
10
R28CV1
15
8
10
R30CV1
25
8
10
R35DV1
45
25
10
R40DY1
45
25
10
R50DY1
45
25
10
OutdoorModel
Maximum Length, m
Maximum Elevation, m
Maximum No. of Bends
Model R10CV1 R15CV1 R18/20CV1 R25CV1
R50DY1
Liquid (mm/in) 6.35 / 1/4 6.35 / 1/4 9.52 / 3/8 Suction (mm/in) 12.70 / 1/2 15.88 / 5/8 15.88 / 5/8
Model R28CV1 R30CV1R35DV1R40DY1
Liquid (mm/in) 9.52 / 3/8 9.52 / 3/8 9.52 / 3/8 Suction (mm/in) 15.88 / 5/8 19.05 / 3/4 19.05 / 3/4
Model RN10FV1
RN28CV1 RN35DV1 RN40DY1 RN50DY1
RN15FV1 RN20CV1 RN25CV1Liquid (mm/in) 6.35 / 1/4 6.35 / 1/4 6.35 / 1/4 Suction (mm/in) 12.70 / 1/2 12.70 / 1/2 15.88 / 5/8
Model Liquid (mm/in) 9.52 / 3/8 9.52 / 3/8 9.52 / 3/8 9.52 / 3/8 Suction (mm/in) 15.88 / 5/8 15.88 / 5/8 15.88 / 5/8 15.88 / 5/8
R410A
6.35 / 1/4 9.52 / 3/8
9.52 / 3/8 15.88 / 5/8
6.35 / 1/49.52 / 3/8
FC20A2V1 FC25A2V1 FC30A2V1 FC40A2V1 FC50A2V1
For R410A
Indoor FFN10CV1
RN10FV1
20
10
10
FFN15CV1
RN15FV1
20
10
10
RN20CV1
20
10
10
RN25CV1
20
10
10
RN28CV1
25
8
10
RN35DV1
45
25
10
RN40DY1
45
25
10
RN50DY1
45
25
10
OutdoorModel
Maximum Length, m
Maximum Elevation, m
Maximum No. of Bends
FCN20A2V1 FCN25A2V1 FCN30A2V1 FCN40A2V1 FCN50A2V1
38
TM-F
FC-0
515-
C
Piping Connection To The Units• Align the centre of the piping and tighten the flare nut sufficiently with fingers.• Finally tighten the flare nut with torque wrench unit the wrench clicks.• When tightening the flare nut with torque wrench, ensure the direction for tightening
the arrow on the wrench.
Pipe Size (mm/in) Torque (Nm) 6.35 (1/4) 18 9.52 (3/8) 42 12.70 (1/2) 55 15.88 (5/8) 65 19.05 (3/4) 78
Wiring
General Precautions• Ensure that the rated voltage of the unit corresponds to the nameplate before carrying out
proper wiring according to the wiring diagram.• Provide a power outlet to be used exclusively for each unit. A power supply disconnects and a
circuit breaker for over current protection should be provided in the exclusive line.• All wiring must be GROUNDED to prevent possible hazards due to insulation failures.• All wiring must be firmly connected.• All wiring must not come in contact with the hot refrigerant piping, compressor or any moving parts
of fan motors.
Electrical ConnectionsWiring regulations on wire diameters differ from country to country. Please refer to your LOCAL ELECTRICAL CODES for field wiring rules. Be sure that installation is complied with such rules and regulations.
39
TM-F
FC-0
515-
C
CAUTION FOR R410ADo not top-up when servicing leak, as this will reduce the unit performance. VacuumtheunitthoroughlyandthenchargetheunitwithfreshR410Aaccordingtotheamountrecommendedinthespecification.
• The precharged outdoor unit does not need any vacuuming or charging. However once it is connected,the connecting pipe line and the indoor need to be vacuumed before releasing the R22/R410A from the outdoor unit.1) Open the service port core cap.2) Connect pressure gauge to the service port.3) Connect the line to vacuum pump. Open the charging manifold valve and turn the pump on. Vacuum
to –0.1 MPa (-760mmHg) or lower. (Evacuation time varies by the pump but averagely in 1 hour).
4) After evacuation, unscrew the spindle (diagram 2) for the gas to run to indoor unit.
Note : R22: Nil R410A: Nil
Vacuuming And Charging
40
TM-F
FC-0
515-
C
Additional Charge
• The refrigerant charge has already charged into the outdoor unit. For the piping length of 7.5m, additional refrigerant charge after vacuuming is not necessary.
• When the piping length is more than 7.5m, please use the table below (unit in gram).
Example:FC25A2V1 & R25CV1 with 13m piping length, additional piping length is 5.5m. Thus,Additional Charge = 5.5 x [38g/m] = 209 [g]
* Be sure to add the proper amount of additional refrigerant. Failure to do so may result in reduced performance.
For R22
Indoor FF10CV1
R10CV1
15
FF15CV1
R15CV1
15
R18CV1
22
R20CV1
22
R20CV1
38
R25CV1
38
R28CV1
55
R30CV1
55
R35DV1
56
R40DY1
56
R50DY1
54
OutdoorModel
Additional Charge OfRefrigerant (g/m)
FC20A2V1 FC25A2V1 FC30A2V1 FC40A2V1 FC50A2V1
For R410A
Indoor FFN10CV1
RN10FV1
18
FFN15CV1
RN15FV1
18
RN20CV1
20
RN25CV1
20
RN28CV1
24
RN35DV1
27
RN40DY1
24
RN50DY1
24
OutdoorModel
Additional Charge OfRefrigerant (g/m)
FCN20A2V1 FCN25A2V1 FCN30A2V1 FCN40A2V1 FCN50A2V1
41
TM-F
FC-0
515-
C
The additional refrigerant charge amount recommended is a guideline for longer piping application. The actual charge required may be different from the guideline due to different application and variation in site conditions.
Diagram shows typical charging method:
Note : R22 - NilR410A - Nil
CAUTION FOR R410A Avoid prolong exposure of an opened compressor, or the internal part of refrigerant piping to moist air. The POE oil in the compressor and piping can absorb moisture from air.
42
TM-F
FC-0
515-
C
Special Precautions When Dealing With Refrigerant R410A Unit
(1) What is New Refrigerant R410A?R410A is a new HFC refrigerant which does not damage the ozone layer. The working pressure of this new refrigerant is 1.6 times higher than conventional refrigerant (R22), thus proper installation / servicing is essential.
(2) ComponentsMixture weight composition R32(50%) and R125(50%)
(3) Characteristic• R410A liquid and vapour components have different compositions when the fluid
evaporates of condenses. Hence, when leak occurs and only vapor leaks out, the composition of the refrigerang mixture left in the system will change and subsequently affect the system performance. DO NOT add new refrigerant to leaked system. It is recommended that the system should be evacuated thoroughly before recharging with R410A.
• When refrigerant R410A is used, the composition will differ depending on whether it is in gaseous or liquid phase. Hence when charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is to make certain that only original composition of R410A is being charged into the system.
• PVE oil is used as lubricant for R410A compressor, which is different from the mineral oil used for R22 compressor. Extra precaution must be taken not to expose the R410A system too long to moist air.
(4) Check List Before Installation / Servicing• Tubing
Refrigerant R410A is more easily affected by dust of moisture compared with R22, make sure to temporarily cover the ends of the tubing prior to installation.
• Compressor oilNo additional charge of compressor oil is permitted.
• RefrigerantNo other refrigerant other that R410A
• Tools (size of service port is different from R22 system)Tools specifically for R410A only (must not be used for R22 or other refrigerant)i) Gauge manifold and charging hoseii) Gas leak detectoriii) Refrigerant cylinder/charging cylinderiv) Vacuum pump c/w adapterv) Flare toolsvi) Refrigerant recovery machine
(5) Handling and Installation GuildelinesLike R22 system, the handling and installation of R410A system are closely similar. All precautionary measures; such as ensuring no moisture, no dirt or chips in the system, clean brazing using nitrogen, and thorough leak check and vacuuming are equally important requirements.However, due to it hydroscopic PVE oil, additional precautions must be taken to ensure optimum and trouble free system operation.
(a) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant system to moist air. Residual PVE oil in the piping and components can absorb moisture from the air.
(b) Ensure that the compressor is not exposed to open air for more than the recommended time specified by its manufacturer (typically less than 10 minutes). Removed the seal plugs only when the compressor is about to be brazed.
(c) The system should be thoroughly vacuumed to 1.0 Pa (700mmHg) or lower. This vacuuming level is more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.
43
TM-F
FC-0
515-
C
(d) When charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This isto ensure that only the original composition of R410A is being delivered into the system. The liquid composition can be different from the vapour composition.
(e) Normally, the R410A cylinder or can is being equipped with a dip pipe for liquid withdrawal. However, if the dip pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the bottom.
Overall Checking
• Ensure the following, in particular:1. The unit is mounted solidly and rigid in position.2. Piping and connections are leak proof after charging.3. Proper wiring has been done.
• Drainage check – pour some water into drain pan.• Test run
1. Conduct a test run after water drainage test and gas leakage test.2. Watch out for the following:
(a) Is the electric plug firmly inserted into the socket?(b) Is there any abnormal sound from the unit?(c) Is there any abnormal vibration with regard to the unit itself or piping?(d) Is there smooth drainage of water?
• Check that:1. Outdoor fan is running, with warm air blowing off the outdoor unit (cooling cycle).2. Indoor blower is running and discharge cool air (cooling cycle).3. Suction (low side) pressure is as per recommendations.4. The remote controller has incorporated a 3 minutes delay in the circuit. Thus, it requires
about 3 minutes before the outdoor unit can start up.
Standard Operating Condition
Ts: Dry Bulb TemperatureTh: Wet Bulb Temperature
T erutarepmeT s ºC / º T F h ºC / ºF Minimum Indoor Temperature 19.4 / 66.9 13.9 / 57.0 Maximum Indoor Temperature 26.7 / 80.1 19.4 / 66.9 Minimum Outdoor Temperature 19.4 / 66.9 13.9 / 57.0 Maximum Outdoor Temperature 46 / 114.8 24 / 75.2
44
TM-F
FC-0
515-
C
6.WiringDiagrams
Indoor UnitModel : FF10CV1, FFN10CV1, FF15CV1, FFN15CV1
Outdoor UnitModel : R10CV1, RN10FV1, R15CV1, RN15FV1
45
TM-F
FC-0
515-
C
Indoor UnitModel : FC20/25/30A2V1, FCN20/25/30A2V1
Outdoor UnitModel : R18/20/25/28/30CV1, RN20/25/28CV1
46
TM-F
FC-0
515-
C
Indoor UnitModel: FC40A2V1, FCN40A2V1
Outdoor UnitModel: R35DV1, RN35DV1
47
TM-F
FC-0
515-
C
Ind
oo
r U
nit
Mo
del
: F
C40
/50A
2V1,
FC
N40
/50A
2V1
Ou
tdo
or
Un
itM
od
el :
R40
/50D
Y1,
RN
40/5
0DY
1
48
TM-F
FC-0
515-
C
7.ServicingandMaintenance
Warning: Disconnect from main supply before servicing the air conditioner
The unit is designed to give long life operation with minimum maintenance required. However, it should be regularly checked and the following items should be given due attention.
Components Recommended Schedule Air Filter
(Indoor Unit) 1. Remove any dust adhering to the filter by using a
vacuum cleaner or wash in lukewarm water (below 40˚C) with a neutral cleaning detergent.
2. Rinse the filter well and dry before placing it back onto the unit.
3. Note: Never use gasoline, volatile substances or chemicals to clean the filter.
At least once every 2 weeks. More frequently if necessary.
Indoor Unit 1. Clean any dirt or dust on the grille or panel by wiping it with a soft cloth soaked in lukewarm water (below 40˚C) and a neutral detergent solution.
2. Note: Never use gasoline, volatile substances or chemicals to clean the indoor unit.
At least once every 2 weeks. More frequently if necessary.
Condense Drain Pan & Pipe
1. Check the cleanliness and clean it if necessary. 2. Check the condensate water flow.
Every 3 months.
Indoor Fan Check if there is any abnormal noise. If necessary. Indoor / Outdoor
Coil 1. Check and remove the dirt between the fins. 2. Check and remove any obstacles which hinder air flow
through the indoor or outdoor.
Every month.
Power Supply 1. Check the running current and voltage for indoor and outdoor unit.
2. Check the electrical wiring and tighten the wire onto the terminal block if necessary.
Every 2 months. Every year.
Compressor No maintenance needed if refrigerant circuit remains sealed. However, check for refrigerant leak at joint and fitting.
Every 6 months.
Compressor Oil Oil is factory charged. Not necessary to add oil if circuit remains sealed.
No maintenance required.
Fan Motor Oil All motors are pre-lubricated and sealed at factory. No maintenance required.
Pre Start Up Maintenance(After Extended Shut Down)
- Inspect thoroughly and clean indoor and outdoor units.- Clean or replace air filters.- Clean condensates drain line.- Clean clogged indoor and outdoor coils.- Check fan imbalance before operation.- Tighten all wiring connections and panels.- Check for refrigerant leakage.
Maintenance Procedures
!
49
TM-F
FC-0
515-
C
Caution
!
Do not charge OXYGEN, ACETYLENE OR OTHER FLAMMABLE and poisonous gases into the unit when performing a leakage test or an airtight test. These gases could cause severe explosion and damage if exposed to high temperature and pressure. It is recommended that only nitrogen or refrigerant be charged when performing the leakage or airtight test
Under normal circumstances, these outdoor units only require a check and cleaning of air intake coil surface once every 3 months. However, if a unit is installed in areas subjected to much oil mist and dust, the coils must be regularly cleaned by qualified Air Conditioner Service Technicians to ensure sufficient heat exchange and proper operation. Otherwise, the systems life span may be shortened.
The design of the R/RN outdoor series allows servicing to be carried out easily. The removal of the top, front and side panels makes almost every part accessible.
For R/RN Outdoor Models
50
TM-F
FC-0
515-
C
8.Troubleshooting
When a malfunction of the air conditioner unit is detected, immediately switch off the main power supplybefore proceeding with the following troubleshooting procedures.The following are common fault conditions and simple troubleshooting tips. If any other fault conditions whichare not listed occur, contact your nearest local dealer. DO NOT attempt to troubleshoot the unit by yourself.
snoitca evitcerroc / sesuac elbissoP snoitidnoc tluaF oN
1 The air conditioner unit will not resume after power failure.
• The auto restart function is not functioning. Please turn on the unit with the wireless / wired controller.
2 The compressor does not operate 3 minutes after the air conditioner unit is started.
• Protection against frequent starting. • Wait for 3 or 4 minutes for the compressor to start
operating by it self.
3 The airflow is too slow or room cannot be cooled sufficiently.
• The air filter is dirty. • The doors and windows are opened. • The air suction and discharge of both indoor and
outdoor units are clogged or blocked. • The regulated temperature or temperature setting
is not low enough.
4 Discharge airflow has bad odor. • Cigarettes, smoke particles, perfume and others, which might have adhered onto the coil, may cause odor.
• Contact your nearest dealer.
5 Condensation on the front air grille of the indoor unit.
• This is caused by air humidity after an extended period of operation.
• The set temperature is too low. Increase the temperature setting and operate the unit at high fan speed.
6 Water flowing out from the air conditioner. • Switch off the unit and contact your nearest dealer. This might be due to tilted installation.
7 Hissing airflow sound from the air conditioner unit during operation.
• Liquid refrigerant flowing into the evaporator coil.
8 The wireless controller display is dim. • The batteries are discharged. • The batteries are not correctly inserted. • The assembly is not good.
9 Compressor operates continuously. • Dirty air filter. Clean the air filter. • Temperature setting too low (cooling). Use higher
temperature setting.
10 No cool air comes out during cooling cycle. • Temperature setting too high (cooling). Use lower temperature setting.
51
TM-F
FC-0
515-
C
Pressure
Data
Circuit
Too
low
A li
ttle
low
Nor
mal
A li
ttle
high
Too
high
Probable cause
High side Low side
●●
1. Overcharged with refrigerant. 2. Non-condensable gases in refrigerant circuit (e.g. air) 3. Obstructed air-intake / discharge. 4. Hot air short circuiting in outdoor unit.
High side Low side
●●
1. Poor compression / no compression (compressor defective)
2. Reversing valve leaking.
High side Low side ●
● 1. Undercharged with refrigerant. 2. Refrigerant leakage. 3. Air filter clogged / dirty (indoor unit). 4. Indoor fan locked / seized.
High side Low side ●
● 1. Outdoor fan blocked (cooling). 2. Outdoor coil dirty (cooling). 3. Non-condensable gases in refrigerant circuit (e.g. air)
High side Low side
●●
1. Air intake temperature of indoor unit too high.
Diagnostic Guidelines
By means of pressure reading :
52
TM-F
FC-0
515-
C
By Means Of Diagnostic Flow Chart:Generally, there are two kinds of problems, i.e. starting failure and insufficient cooling. “Starting failure” is caused by electrical defect while improper application or defects in refrigerant circuitcauses“Insufficientcooling”.
i) Diagnosis of Electric Circuit
53
TM-F
FC-0
515-
C
ii ) Diagnosis Of Refrigerant Circuit / Application
Theremight be some causeswhere the unit starts running but does not perform satisfactorily, i.e. insufficientcooling.Judgementcouldbemadebymeasuring temperaturedifferenceof indoorunit’sintakeanddischargeairaswellasrunningcurrent.
Satisfactoryoperationwithtemperaturedifferenceofairintake&dischargeofindoorunit8°Cto13°C.*(*valueisforreferenceonly)
54
TM-F
FC-0
515-
C
9.DimensionalData
Indoor UnitModel: FF10/15CV1, FFN10/15CV1, FC20/25/30/40/50A2V1, FCN20/25/30/40/50A2V1
Outdoor UnitModel: R10/15CV1
Note : All Dimension in mm
MODEL A B C D E F G H I J
930
820 820 385 357 28
820 820 345 28 930 626 626 555
930 930 626 626 555
FF/10/15CV1FFN10/15CV1FC20/25/30A2V1FCN20/25/30A2V1FC40/50A2V1FCN40/50A2V1
640 640 408 408 364570 570 295 275
317
20
B
A
P
RS
DO
L
QN
M
NF
E
CG H
I J
LK
Dimension
Dimension
Model A B C D E F G H I J K
700 521 250 478 175 36 95 94 86 68 440
L M N O P Q R S
130 110 15 21 19 278 80 65
R10/15CV1
ModelR10/15CV1
Note : All Dimension in mm
55
TM-F
FC-0
515-
C
All dimensions are in mm
Outdoor UnitModel: RN10/15FV1
DimensionModel A B C D E F G H I J K L M N O P
RN10/15FV1 550 658 51 11 273 16 14 470 96 299 94 60 14 133 8 8
H
NJ
G
B CDE F
A
MK
L
P
O
I
56
TM-F
FC-0
515-
C
Model: R35DV1, R40/50DY1RN35DV1, RN40/50DY1
Note : All Dimension in mm
A B C D E F G H I J K L M N O P Q R S T
R18/20CV1RN20/25CV1
R25/28/30CV1RN28CV1
855 628 328 520 179 46 93 149 101 113 603 126 164 15 34 32 3 23 73 75
855 730 328 520 179 46 93 149 101 113 603 126 164 15 34 32 3 23 73 75
Note : All Dimension in mm
Model: R18/20/25/28/30CV1 RN20/25/28CV1
142 746 142
2222
448
60
40.090.0
MODEL
57
TM-F
FC-0
515-
C
10.ExplodedView&PartList
1
2
3
4
5
6
7
8
9
14
13
12
11
1015
16
17
18
19
20
21
22
1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION
1 BASE PAN
2 FAN MOTOR
3 SIDE PANEL BACK
4 FRESH AIR ADAPTOR
5 HANGER BRACKET
6 PARTITION
7 ASSY. AIR GUIDE
8 ASSY. COVER CONTROL BOX
9 ASSY. CONTROL BOX
10 LEVEL SWITCH
11 HEXAGON BOLT
12 HEXAGON BOLT
13 EVAPORATOR COIL
14 ASSY. FAN COVER
15 VALVE PLATE
16 DRAIN PUMP BUSH
17 WATER PUMP
18 ASSY. COIL BRACKET
19 BLOWER, TURBO FAN
20 ASSY. DRAIN PAN
21 COVER, WIRE A
22 COVER, WIRE B
Model: FF10/15CV1, FFN10/15CV1
58
TM-F
FC-0
515-
C
NO DESCRIPTION NO DESCRIPTION1 FRAME 11 LINKAGE COVER, MOTOR2 INTAKE GRILLE 12 ASSY., BRACKET RECEIVER3 AIR FILTER 13 AIR SWING MOTOR4 GRILLE LOCK 14 CRANK CONNECTOR5 DISCHARGE FOAM 15 LOUVER HOLDER6 DISCHARGE FOAM, LED 16 CRANK CROSS7 DISCHARGE FOAM, SHORT 17 INSULATION, LONG8 LOUVER 18 INSULATION, SHORT9 LOUVER, LED 19 INSULATION, CORNER
10 LINKAGE COVER
Panel for FF-C: BF-C
1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
59
TM-F
FC-0
515-
C
NO. PARTS DESCRIPTION NO1 ASSY. BASE PAN
13 ASSY. COVER TERMINAL
2 ASSY. COIL MAIN
14 SUPPORT, COIL B
3 ASSY. COIL BRACKET
15
4 ASSY. DRAIN PUMP MOUNTING
16 COVER, WIRE B
5 ASSY. PANEL SIDE BACK
17 BRACKET, HANGER A
6 ASSY. SIDE PANEL FRONT
18 BRACKET, HANGER B
7 MOTOR
19 BRACKET, HANGER C
8 BLOWER, TURBO FAN
20 FRESH AIR ADAPTOR
9 ASSY. DRAIN PAN
21 ASSEMBLY, VALVE PLATE
10 ASSY. FAN COVER
22 ASSY. AIR GUIDE
11 ASSY. COVER CONTROL BOX
23 ASSY. PARTITION HOLDER
12 ASSY. CONTROL BOX
24 COVER, WIRE
PARTS NOT IN THE DIAGRAML2 CONTROL MODULE
Model: FC20/25/30A2V1, FCN20/25/30A2V1
COVER, WIRE A
26 PUMP, WATER25 SWITCH WATER LEVEL DRAIN PUMP
27 HOSE, DRAIN PE
COOLING ONLY MODELSCAPACITOR
1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
PARTS DESCRIPTION
60
TM-F
FC-0
515-
C
NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY. BASE PAN
13 ASSY. COVER TERMINAL
2 ASSY. COIL
14 SUPPORT, COIL B
3 ASSY. COIL BRACKET
15
4 ASSY. DRAIN PUMP MOUNTING
16 COVER, WIRE B
5 ASSY. PANEL SIDE BACK
17 BRACKET, HANGER A
6 ASSY. SIDE PANEL FRONT
18 BRACKET, HANGER B
7 MOTOR
19 BRACKET, HANGER C
8 BLOWER, TURBO FAN
20 ASSY. FRESH AIR KIT
9 ASSY. DRAIN PAN
21 VALVE PLATE
10 ASSY. FAN COVER
22 FOAM. EPS AIR GUIDE 238*190*70mm
11 ASSY. COVER CONTROL BOX
23 ASSY. PARTITION HOLDER
12 ASSY. CONTROL BOX
24 COVER, WIRE
PARTS NOT IN THE DIAGRAML2 CONTROL MODULE
Model: FC40/50A2V1, FCN40/50A2V1
COVER, WIRE A
26 PUMP, WATER PC -04226 - OYOB25 SWITCH WATER LEVEL DRAIN PUMP
27 HOSE, DRAIN PE 18.3 x 0.5 x 315.0
COOLING ONLY MODELSCAPACITOR
1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
61
TM-F
FC-0
515-
C 1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 FRONT PANEL 7 FIX PLATE2 RECEIVER BRACKET 8 AIR INTAKE GRILLE3 SHORT LOUVER 9 GRILLE LOCK4 LOUVER 10 AIR FILTER5 LOUVER HOLDER 11 RECEIVER COVER6 LOUVER CLIP
Panel for FC-A2: BC-A2
62
TM-F
FC-0
515-
C
1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY., BASE PAN2 ASSY., OUTDOOR COIL3 VALVE BRACKET
13 RIGHT PANEL
4 COMPRESSOR
14 ASSY., FRONT PANEL
5 ASSY., PARTITION15 ASSY., CONTROL PANEL
6 SUCTION PIPE 7 DISCHARGE PIPE 8 ASSY., CAP TUBE 9 BRACKET, FAN MOTOR10
1 6 ASSY., VALVE COVER
Model : R10/15CV1
FAN MOTOR
17 ASSY., FRONT GRILLE 18 PLASTIC HANDLE 19 INSULATION PARTS NOT IN THE DIAGRAMS CAPACITOR, FAN MOTOR CAPACITOR, COMPRESSOR11 FAN BLADE
12 LEFT PANEL
63
TM-F
FC-0
515-
C
Model : RN10/15FV1
NO. DESCRIPTION NO. DESCRIPTION1 ASSY. OUTDOOR COIL
12 SUCTION PIPE2 TOP PANEL
13 ASSY. CAP TUBE3 FAN MOTOR BRACKET
14 VALVE BRACKET4 ASSY PARTITION
15 ASSY. VALVE COVER16 ASSY. CONTROL PANEL17 RIGHT PANEL
5 FAN MOTOR6 FAN BLADE7 ASSY. FRONT GRILLE8 ASSY FRONT PANEL9 ASSY BASE PAN
10 COMPRESSOR11 DISCHARGE PIPE
* DUE TO OUR POLICY OF INNOVATION, SOME SPECIFICATIONS MAY BE CHANGED WITHOUT NOTIFICATION.
17
16
15
1413121110987
6
5
4
3
2 1
64
TM-F
FC-0
515-
C
1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY., BASE PAN2 ASSY., OUTDOOR COIL3 MOTOR BRACKET
13 TERMINAL COVER PANEL
4 FAN MOTOR
14 DISCHARGE PIPE
5 FAN BLADE
15 SUCTION PIPE
6 VALVE BRACKET 7 PARTITION 8 COMPRESSOR 9 BACK PANEL, RIGHT10
16 ASSY., CAP TUBE
Model : R18/20CV1, RN20/25CV1
17 ASSY., VALVE COVER 18 ASSY., FRONT GRILLE 19 PLASTIC HANDLE 20 SERVICE PANELPARTS NOT IN THE DIAGRAMS CAPACITOR, FAN MOTOR CAPACITOR, COMPRESSOR
FRONT PANEL, LEFT11 TOP PANEL12 ASSY., CONTROL PANEL
65
TM-F
FC-0
515-
C
1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY., BASE PAN2 ASSY., OUTDOOR COIL3 MOTOR BRACKET
13 ASSY., CONTROL PANEL
4 FAN MOTOR
14 TERMINAL COVER PANEL
5 FAN BLADE15 ASSY., VALVE COVER
6 VALVE BRACKET 7 PARTITION 8 COMPRESSOR 9 BACK PANEL, RIGHT10
16 ASSY., FRONT GRILLE
Model : R25/28/30CV1, RN28CV1
17 PLASTIC HANDLE, SIDE 18 DISCHARGE PIPE 19 SUCTION PIPE 20 ASSY., CAP TUBE PARTS NOT IN THE DIAGRAMS CAPACITOR, FAN MOTOR CAPACITOR, COMPRESSOR
SERVICE PANEL11 FRONT PANEL LEFT
12 TOP PANEL
66
TM-F
FC-0
515-
C
1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
NO. PARTS DESCRIPTION NO. PARTS DESCRIPTION1 ASSY., BASE PAN2 ASSY., COIL3 PALTE, FLARE VALVE4 FLARE VALVE 3/8”5 FLARE VALVE 5/8”
16 MOTOR BRACKET17 FAN MOTOR18 ASSY., FRONT PANEL19 ASSY., CONTROL PANEL20 SERVICE PANEL21 FAN BLADE22 TOP PANEL23 PLASTIC HANDLE
6 PARTITION 7 COMPRESSOR 8 ACCUMULATOR 9 ASSY., CAPILLARY TUBE10 SUCTION PIPE11 TUBE ACCUMULATOR TO SUCTION12 DISCHARGE PIPE13 INSULATION14 BACK PANEL, RIGHT
15 SIDE PANEL, LEFT
PARTS NOT IN THE DIAGRAMS
Model : R35DV1, R40/50DY1, RN35DV1, RN40/50DY1
PHASE SEQUENCER HIGH PRESSURE SWITCH LOW PRESSURE SWITCH CAPACITOR, FAN MOTOR CAPACITOR, COMPRESSOR TXV