EXISTING PARKING LOT PROPOSED PARKING LOT SA SA A E1.1 1 E1.1 (E) (E) EXISTING IN GROUND JUNCTION BOX SEE DETIAL SEE DETIAL EXISTING LIGHTING CIRCUIT (TYP) C E1.1 EXISTING (2) 2-1/2"C (2) 2-1/2"C TO ROOM #2 EXISTING IN GROUND JUNCTION BOX GALEON LED AREA AND ROADWAY SA McGRAW - EDISON MANUFACTURER LUMINAIRE (2) 70 CRI, 3000k, DUAL HEAD 1A LIGHTSQUARE WITH 16 LEDS AND TYPE III OPTICS DRAWING NOTES: CONTRACTOR SHALL REMOVE EXISTING FIXTURES, POLE BASES, CONDUIT AND WIRE IN THEIR ENTIRETY WHERE INDICATED. CONDUIT AND WIRE SHALL BE REMOVED TO POINT INDICATED WITH JUNCTION BOX. FIXTURES SHALL BE TURNED OVER TO OWNER. POST HOLES AND TRENCH SHALL BE FILLED IN TO MATCH SURROUNDING AREA. COORDINATE WITH SITE CONTRACTOR. CONTRACTOR SHALL INTERCEPT EXISTING CONDUIT AND CONNECT TO JUNCTION BOX. EXISTING WIRE SHALL BE SPLICED WITH NEW WIRE TO NEW POLE. EXISTING CIRCUIT: (3) # 6, (1) # 10GRD-1-1/2"C, AS PER AS BUILT DRAWING E1. EXISTING JUNCTION BOX AND CONDUIT LOCATIONS BASED ON AS BUILT DRAWING E1. CONTRACTOR SHALL FIELD VERIFY. CONDUITS SHALL BE STUBBED UP TO LEVEL OF FINISHED GRADE AND CAPPED. 24" RED MARKER TAPE WITH METAL TRACER 6" BELOW FINISHED GRADE 6" MINIMUM STONE DUST 3" DUST OR SAND BASE OVER CONDUITS RED MARKER TAPE GRADE SCHEDULE 40 PVC CONDUIT NOTE: 1. BACKFILL TO BE COMPACTED IN 6 INCH LAYERS TO AVOID SETTLING. NO SCALE 36" UNDER ROADWAY WITH METAL TRACER WIRE. 4" PROVIDE GASKETED HEAVY DUTY COMPOSITE COVER WITH "ELECTRIC" LOGO CRUSHER RUN SUMP AREA 2" 2" COMPACTED EARTH 3000 PSI CONCRETE AROUND BOX NO SCALE NOTES: 1. SEE SITE PLAN FOR QUANTITIES & SIZES OF ELECTRICAL CONDUITS. POLE HANDHOLE W/COVER GROUND LUG BOLT COVER 1" CHAMFER 30" 6'-0" FINISHED GRADE/ PAVEMENT 18" MIN. PVC CONDUIT (TYP.) STEEL ANCHOR BOLTS QUANT., LENGTH, DIA., & PROJECTION FROM CONC. PER MANUF. RECOMMENDATIONS. &21& VERTICAL REINF. #5 REBAR @ 6" O.C. #4 REBAR @ 12" O.C. 2'-0" GROUND ROD [ CADWELD CONNECTION NO SCALE (3) #6, (1) #10 GRD- 1-1/2"C GLEON-AE-01-LED-E1- T3-GM-MA W/ 30' POLE, COOPER; SSS-6-M-30-S-G-4-2 24" RED MARKER TAPE WITH METAL TRACER 6" BELOW FINISHED GRADE 6" MINIMUM STONE DUST 3" DUST OR SAND BASE OVER CONDUITS RED MARKER TAPE GRADE SCHEDULE 40 PVC CONDUIT NOTES: 1. BACKFILL TO BE COMPACTED IN 6 INCH LAYERS TO AVOID SETTLING. CONDUITS ARE TO HAVE 2 INCHES OF HORIZONTAL SEPARATION. 2. NO SCALE 36" UNDER ROADWAY 24" RED MARKER TAPE WITH METAL TRACER 6" BELOW FINISHED GRADE 6" MINIMUM STONE DUST 3" DUST OR SAND BASE OVER CONDUITS RED MARKER TAPE GRADE SCHEDULE 40 PVC CONDUIT NOTE: 1. BACKFILL TO BE COMPACTED IN 6 INCH LAYERS TO AVOID SETTLING. NO SCALE 36" UNDER ROADWAY WITH METAL TRACER WIRE. 2-1/2"C 2-1/2"C 2-1/2"C