For other power factor values, the total clearing integral can be calculat- ed as a multiple of the clearing integrals, the correction factor K and the correction factor X. Arc Voltage This curve gives the peak arc voltage, U L , which may appear across the fuse during its operation as a function of the applied working voltage, E g , (rms) at a power factor of 15%. Power Losses Watts loss at rated cur- rent is given in the electri- cal characteristics. The curve allows the calcula- tion of the power losses at load currents lower than the rated current . The correction factor, K p , is given as a function of the RMS load current, I b , in % of the rated current . Cut-Off Current A fuse operation relating to short-circuits only. When a fuse operates in its current-limiting range, it will clear a short-cir- cuit in less than 1 ⁄ 2 cycle. Also, it will limit the instantaneous peak let-through current to a value substantially less than that obtainable in the same circuit if that fuse were replaced with a solid conductor of equal impedance. A asymmetrical current B symmetrical current For product data sheets, visit www .cooperb ussmann.com/pr oducts/da tasheet.asp High Speed Fuses Prospective Current in Amperes RMS Peak Let-Through Current 10 2 ≈ 10 2 2 10 3 10 4 10 5 10 3 10 4 10 5 10 6 A B General applications Rated Voltage The ac voltage rating of Cooper Bussmann ® fuses is given in volts rms. Fuses tested to IEC are tested at 10% above their rated voltage. British Style BS 88 fuses are tested at 5% above its rated voltage. UL recognition tests are performed at the rated voltage. Rated Current Rated current is given in amperes rms. Cooper Bussmann fuses can continuously carry the rated current. Melting Characteristic The melting char- acteristic shows the virtual melting time in seconds as a function of the prospective current in amperes rms. The fuses are spe- cially constructed for short-circuit pro- tection against high level fault currents. Loading and opera- tion of the fuse in the non-continu- ous/dashed section of the melt curve must be avoided. The curve can also be read as the real melting time as a function of the RMS value of the pre-arc current. Clearing Integrals The total clearing I 2 t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I 2 t is found by multiplying by correction factor, K, given as a function of applied work- ing voltage, E g , (rms). 10 4 10 3 10 2 10 1 2 4 6 8 2 10 2 2 4 6 8 10 3 2 4 6 2 6 4 10 0 2 6 4 10 1 2 6 4 2 6 4 2 6 4 6 4 2 6 2 4 Prospective Current In Amperes RMS Virtual Pre-Arcing Time In Seconds 10 –4 10 –3 10 –2 10 –1 K 1.5 1.0 0.5 0.4 0.3 0.2 100 200 300 400 500 600 660 E g 1.0 0.9 0.8 0.7 0.1 0.2 0.3 0.4 0.5 COS X U L 1.4 1.2 10 3 6 8 7 9 5 4 3 200 300 400 500 600 660 Eg Kp 1.0 0.8 0.4 0.5 0.6 0.3 0.2 0.1 30 40 50 60 70 80 90 100% I b Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com 1 www.profuse.ir (021)6673 2943 , (021)6673 2945
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
For other power factorvalues, the total clearingintegral can be calculat-ed as a multiple of theclearing integrals, thecorrection factor K andthe correction factor X.
Arc Voltage
This curve gives thepeak arc voltage, UL,which may appearacross the fuse during itsoperation as a functionof the applied workingvoltage, Eg, (rms) at apower factor of 15%.
Power Losses
Watts loss at rated cur-rent is given in the electri-cal characteristics. Thecurve allows the calcula-tion of the power lossesat load currents lowerthan the rated current.The correction factor, Kp ,is given as a function ofthe RMS load current, Ib ,in % of the rated current .
Cut-Off Current
A fuse operation relating to short-circuits only. When a fuseoperates in its current-limiting range, it will clear a short-cir-cuit in less than 1⁄2 cycle. Also, it will limit the instantaneouspeak let-through current to a value substantially less thanthat obtainable in the same circuit if that fuse were replacedwith a solid conductor of equal impedance.
A asymmetrical currentB symmetrical current
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
Prospective Current in Amperes RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
102 ≈ 10
22
103
104
105
103 104 105 106
A
B
General applications
Rated Voltage
The ac voltage rating of Cooper Bussmann® fuses is given involts rms. Fuses tested to IEC are tested at 10% above theirrated voltage. British Style BS 88 fuses are tested at 5%above its rated voltage. UL recognition tests are performed atthe rated voltage.
Rated Current
Rated current is given in amperes rms. Cooper Bussmannfuses can continuously carry the rated current.
Melting Characteristic
The melting char-acteristic showsthe virtual meltingtime in seconds asa function of theprospective currentin amperes rms.The fuses are spe-cially constructedfor short-circuit pro-tection against highlevel fault currents.Loading and opera-tion of the fuse inthe non-continu-ous/dashed sectionof the melt curvemust be avoided.The curve can alsobe read as the realmelting time as afunction of theRMS value of thepre-arc current.
Clearing Integrals
The total clearing I2t atrated voltage and atpower factor of 15% aregiven in the electricalcharacteristics. Forother voltages, theclearing I2t is found bymultiplying by correctionfactor, K, given as afunction of applied work-ing voltage, Eg, (rms).
104
103
102
101 22 4 6 8 2102 2 4 6 8 103
2
46
2
64
100
2
64
101
2
64
2
64
2
64
64
2
6
2
4
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
10–4
10–3
10–2
10–1
K1.5
1.0
0.5
0.4
0.3
0.2
100 200 300 400 500 600 660
Eg
1.0
0.9
0.8
0.70.1 0.2 0.3 0.4 0.5
COS �
X
UL
1.41.2
103
6
87
9
5
4
3200 300 400 500 600 660
Eg
Kp1.00.8
0.4
0.50.6
0.3
0.2
0.130 40 50 60 70 80 90 100%
Ib
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
1 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body fuses
High Speed Fuses
High SpeedFuses
General Information
Designed and tested to:• IEC 60269: Part 4• UL Recognized
Cooper Bussmann offers a complete range of Square Bodystyle fuses and accessories. Their unique design and con-struction provide:
• Minimal energy let-through (I2t)• Low operating temperature• Low watts loss
Square Body style fuses are a very attractive solution for highpower applications which require a compact design withsuperior performance. The construction and design of SquareBody style fuses make it easy for Cooper Bussmann to manufacture custom products. Our cataloged offering provides only a sample of the wide variety of product which is available.
Each Square Body style fuse is available with a number ofdifferent end fittings. Options include:
• DIN 43 653• DIN 43 620• Flush End (Metric/U.S.)• French Style• US Style
Voltage Rating
All Cooper Bussmann® Square Body style fuses are tested toIEC 60269: Part 4. This standard requires a test voltagewhich is 5% higher than the rated voltage. In North America,fuses are required to clear only their rated voltage.
Accessories
Square Body style fuses are available with three differentopen fuse indicator systems. Options include visual indicationand indication utilizing a microswitch. Fuse blocks are alsoavailable for most applications.
Introduction
Square Body Contents
PageApplication Information 108-109Fuse Style VoltsDIN 43 653 690/700 110-121
1000 122-1271250/1300 128-135
DIN 43 620 690 136-1441000 145-146
Flush End Contact 690 147-1541000 155-1581250/1300 159-162
French Style 690/700 163-166US Style 690/700 167-170
1000 171-1741250/1300 175-178
AccessoriesIndicator System 179Fuse Bases 180
Square Body Fuse RangesAmps Volts AC DC10-7500 690 X —50-1400 1250 X —
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
2 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body applications
High Speed Fuses
Maximum Permissible Load Current
The rated current value of Cooper Bussmann® fuses is basedon the ambient temperature in the space immediately belowthe fuse of 20°C. The following graph gives correction factors(k) for a range of temperatures (–40°C to +80°C). Maximumpermissible continuous load currents can be calculated byapplying the following formula:
Ib � In � k � (1 + 0.05 V) x KbwhereIb = Maximum permissible continuous load currentIn = Rated current of fusek = Temperature correction factorv = Velocity of cooling air in m/s (max. 5 m/s).Kb = Fuse load constant 1.0
Temperature Correction Curve
The maximum permissible continuous load current Ib of afuse can be checked empirically (i.e., by satisfying the formula below) by making simple voltage and temperaturemeasurements under actual operating conditions after thefuse has been installed in its operating location and loaded at the calculated Ib value:
E2 � (0.92 + 0.004t) � NE1whereE1 = Voltage drop across fuse after 5 secondsE2 = Voltage drop across fuse after 2 hourst = Air temperature at start of test (°C)N = Constant
Fuse Rated Voltage (IEC) N690 1.51250 1.6
Body Cross SectionStandard fuse program includes barrels with different cross sections.
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
3 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body applications
High Speed Fuses
High SpeedFuses
Example Application of Square Body High Speed
Fuses Subject to Overload and Impulse Loading
Select a short-blade indicating fuse with indicator/adapter topermit the use of a single-pole microswitch for remote indica-tion and determine if the fuse selected will meet the followingapplication parameters.
Application ParametersLoad Currents ExpectedLoad Type Duration Frequency of Occurrence Amps(1) Normal Continuous — 300A
(2) Overload 60 Seconds Once Per Hour 500A
(3a) 10 Seconds 2-3 Times Per Week(3b)Overload 20 Seconds (max.) Once Per Month 700A
(4) Impulse 0.5 Seconds Less Than Once Per Month 1100A
Voltage Data(5) Voltage Applied to Fuse During Fault Conditions 400V(+10%)
Temperature Data(6) Temperature Inside Cubicle in Which Fuse is Located (Natural Convection Cooling Only)60°C
Thyrister Data(7) Thyrister Peak Voltage Withstand 1000V
(8) Thyrister I2t Withstand at 10 Milliseconds* 90,000A2s
*Note: The I2t withstand of the thyrister may be given for other impulse durations (i.e., 1.5ms, 3.5 ms, or 8.3 ms); however, the stated fuse I2t is valid for all impulse durations of 10 msor less.
Application ProcedureStep Procedure Remarks
(1) Select a short-blade fuse to 1.1 Taking into consideration only thepermit mounting of microswitch continuous load current and ambientMSW710-1S or 170H0069 temperature, from Table on page 12 of —
(2) Determine I2 t (total clearing) 2.1 See Table, page 150. Note I2t isat 44V. 105,000A2s at rated voltage of 690V.
2.2 From the figure on page 149, notethat correction factor K = 0.65.2.3 I2t660V ≈ K = I2t440V
105,000 ≈ 0.65 = 68,250
(3) Determine maximum arc voltage 3.1 From the figure on page 53, note thatat 440V maximum voltage at 440V is 900V
OK
(4) Determine maximum permissible 4.1 Per page 15 data,continuous load current Ib. Ib = In ≈ k ≈ (1 + 0.05V) ≈ Kb
—Ib = 400A ≈ 0.8 ≈ (1 + 0) ≈ 1Ib = 320A
(5) Plot a “line profile” showing the 5.0 Calculate Imax per Table, page 16,expected load and overload currents. for each overload and impulse —Determine that overload and impulse load.load currents do not exceed theirmaximum permissible values.
The tentatively selected fuse 170M3519 with microswitch 170H0069 meets all application para-meters; no further selection would be necessary.
102 10310–2
10–1
100
101
102
103
Current In Amperes
Tim
e In
Sec
onds A A
170M3669 (400A)
Pro
file
Line
1100A < 70% ≈ 1800A OKCalculation of Watt Loss
From the Table on page 154, watt loss at 400 amperes is 60watts. The continuous load current of 300A is 75% of ratedcurrent (400A). From page 154: The correction factor Kp = 0.5.Watt Loss 75% = Watt Loss 100% ≈ Kp
= 60W ≈ 0.5= 30 watts
Special Fuses
Other high speed fuses are available from CooperBussmann with voltage ratings of 380 to 10,000V and currentratings up to 10,000A in a single unit configuration. Fusescan be supplied with open fuse, “pin” indicators. Varioustypes of microswitches are also available (see page 160).
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
4 www.profuse.ir (021)6673 2943 , (021)6673 2945
Arc Voltage
This curve gives thepeak arc voltage, UL,which may appearacross the fuse duringits operation as a func-tion of the applied work-ing voltage, Eg, (rms) ata power factor of 15%.
Power Losses
Watts loss at rated cur-rent is given in the elec-trical characteristics. Thecurve allows the calcula-tion of the power lossesat load currents lowerthan the rated current.The correction factor,Kp, is given as a func-tion of the RMS loadcurrent, Ib, in % of therated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 690V/700V (IEC/UL): 10-400A
High Speed Fuses
*
690V/700V (IEC/UL) 10-400A
SpecificationsDescription: Square body DIN43-653 stud mount high speedfuses.
Dimensions: See dimensions illustration.
Ratings:Volts: — 690Vac (IEC)
— 700Vac (UL)
Amps: — 10-400A
IR: — 200kA RMS Sym.
Agency Information: CE,Designed and tested to IEC60269: Part 4, UL Recognized. ULRecognition/CSA ComponentAcceptance on Size 000.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t atrated voltage and at powerfactor of 15% are given inthe electrical characteris-tics. For other voltages, theclearing I2t is found by mul-tiplying by correction factor,K, given as a function ofapplied working voltage,Eg, (rms).
100 200 300 400 500 600
K1.5
1.0
0.5
0.4
0.3
0.2Eg
690
UL
1.41.2
103
6
87
9
5
4
3Eg
200 300 400 500 600 690
Kp
30 40 50 60 70 80 90 100%
Ib
1.00.8
0.4
0.50.6
0.3
0.2
0.1
F
100
78
D
E
G
H
K
54
Indicator
Dimensions (mm)Type -U/80, -/80, -TN/80Size D E F G H K000 40 21 20 51 8 200 51 30 28 67 10 21mm = 0.0394” / 1” = 25.4mm
* Indication for Size 00 fuses is a red pin.
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
5 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 690V/700V (IEC/UL): 10-400A
conditions. It offers a wider range of current voltage
and frequency configurations than any other facility
of its kind in the world, and is built to exceed the
short circuit capacity of today’s high power electrical
distribution systems.
Did You Know?
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
6 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 690V/700V (IEC/UL): 10-400A
High Speed Fuses
1x101 102 103 1041x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
10A
16A
20A
25A
32A
40A
50A
63A
80A
100A
125A
160A
200A
250A
315A
A
A
1x101 102 103 1041x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current in Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
25A
32A
40A
50A
63A
80A
100A
125A
160A
200A
250A
315A
350A
400A
A
A
Size 00 — 25-400A: 690VTime-Current Curve
Size 000 — 10-315A: 690VTime-Current Curve
1x101 102 103 104 1052x101
102
103
104
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
10A16A20A25A32A40A50A63A80A100A125A160A200A250A
A
B
315A
1x101 102 103 104 1052x101
102
103
104
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt 25A32A40A50A63A80A100A125A160A200A250A
315A350A400A
A
B
Peak Let-Through CurvePeak Let-Through Curve
Data Sheet: 72056310 Data Sheet: 72056312
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
7 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 690V/700V (IEC/UL):40-2000A
High Speed Fuses
High SpeedFuses
690V/700V (IEC/UL) 40-2000A
SpecificationsDescription: Square body DIN 43653 stud-mount high speed fuses.
Dimensions: See dimensionsillustration.
Ratings:Volts: — 690Vac (IEC)
— 700Vac (UL)
Amps: — 40-2000A
IR: — 200kA RMS Sym.
Agency Information: CE,Designed and tested to IEC60269: Part 4, UL Recognized.Consult Cooper Bussmann for ULRecognition/CSA ComponentAcceptance status.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t atrated voltage and at powerfactor of 15% are given in the electrical characteristics. For othervoltages, the clearing I2t isfound by multiplying by correction factor, K, givenas a function of appliedworking voltage, Eg, (rms).
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage, Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correction factor, Kp, isgiven as a function of theRMS load current, Ib, in %of the rated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
UL
1.41.2
103
6
87
9
5
4
3Eg
200 300 400 500 600 690
Kp1.00.8
0.4
0.50.6
0.3
0.2
0.1
30 40 50 60 70 80 90 100%
Ib
100 200 300 400 500 600 690
K1.5
1.0
0.5
0.4
0.3
0.2Eg
1)2)
1) Rated voltage 600V2) Rated voltage 550V
A
B
C
D
E
E
6
11
H
Dimensions (mm)Type -/80, -TN/80, -/110, -TN/110.
Size A B B** C C** D*** E H1* 50 104 134 78 108 58 45 221 50 108 138 78 108 66 53 252 50 108 138 78 108 75 61 253 51 109 139 78 108 90 76 30**Valid for fuses type -/110, -TN/110.***Microswitch.1mm = 0.0394” / 1” = 25.4mm
Cooper Bussmann® fuses
are used in all kinds of
oil-well drilling equipment
around the world.
Did You Know?
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
8 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 690V/700V (IEC/UL):40-2000A
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
9 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 690V/700V (IEC/UL):40-2000A
High Speed Fuses
High SpeedFuses
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
200A
250A
315A
350A
400A
450A
500A
550A
630A
700A
800A
900A
A A
Size 1 — 200-900A: 690VTime-Current Curve
Size 1* — 40-630A: 690VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
50A40A
63A80A
100A125A
160A200A
250A315A
350A400A450A500A550A630A
A
B
1x102 103 104 105 1062x102
103
104
105
Pea
k Le
t-T
hrou
gh C
urre
nt 200A250A
315A350A400A450A500A550A630A
700A800A
900A
A
B
Peak Let-Through CurvePeak Let-Through Curve
900 amp fuse is derated to 550V (IEC).
Data Sheet: 17056316Data Sheet: 17056314
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
10 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 690V/700V (IEC/UL):40-2000A
High Speed Fuses
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
400A
450A
500A
550A
630A
700A
800A
900A
1000
A11
00A
1250
A
A A
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
500A
550A
630A
700A
800A
900A
1000
A11
00A
1250
A14
00A
1500
A16
00A
1800
A20
00A
A A
Size 3 — 500-2000A: 690VTime-Current Curve
Size 2 — 400-1250A: 690VTime-Current Curve
1x103 104 105 106 1072x103
104
105
106
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
400A 450A500A 550A630A
700A800A900A1000A 1100A
1250A
A
B
1x103 104 105 106 1072x103
104
105
106
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
500A 550A630A
700A800A
900A1000A 1100A1250A 1400A1500A 1600A1800A 2000A
A
B
Peak Let-Through CurvePeak Let-Through Curve
1800A fuse is derated to 600V (IEC).2000A fuse is derated to 550V (IEC).
Data Sheet: 17056318 Data Sheet: 17056320
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
11 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 690V/700V (IEC/UL):40-2000A
High Speed Fuses
High SpeedFuses
1x103 104 105 1061x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current in Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
1000
A12
50A
1400
A16
00A
2000
A22
00A
2500
A30
00A
3500
A40
00A
A
A
Size 4 — 1000-4000A: 690VTime-Current Curve
1x103 104 105 106 1072x103
104
105
106
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
1000A1250A
1400A1600A
2000A 2200A2500A
3000A3500A4000A
A
B
Peak Let-Through Curve
4000A fuse is derated to 500V (IEC).
Data Sheet: 17056328
Cooper Bussmann® CustomerSatisfaction Minimizes DowntimeCaused by the 2003 North AmericanNortheast Coast Blackout
An enormous power failure blacked out population
centers from New York City to Toronto on Thursday,
August 14, 2003. As power slowly came back on,
surges and spikes began to “blow” existing fuses.
Airports reopened Friday.
The Cooper Bussmann Customer Satisfaction team
handled 11 emergency phone calls that weekend,
including:
A Michigan-based utility required a large fuse order
to protect its control switches before it could
reactivate electrical power to thousands of
customers. Ordered Friday, 8:27 p.m. Order
delivered Saturday, 12:30 p.m.
An Indiana steel mill required specialized fuses. A
Cooper Bussmann engineer was called to assist.
Ordered Sunday, 1:46 p.m. Order delivered same
day, 11:00 p.m.
A pharmaceutical plant in New Jersey needed to get
its line back up. Ordered Saturday 10:36 a.m. Order
delivered Sunday, 4:00 a.m.
An Ontario utility required more than 100 Cooper
Bussmann® Fusetron® FRN-R-200 fuses. Ordered
Saturday, 11:01 a.m.. Order delivered Sunday, 9:00
a.m. including customs processing.
Did You Know?
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
12 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
Square body DIN 43 653 — 690V/700V (IEC/UL):40-2000A
690V/700V (IEC/UL) 40-2000A
SpecificationsDescription: Square body DIN 43-653 stud-mount high speed fuses.
Dimensions: See dimensions illustration.
Ratings:Volts: — 690Vac (IEC)
— 700Vac (UL)
Amps: — 40-2000A
IR: — 200kA RMS Sym.
Agency Information: CE, Designed and tested to IEC60269: Part 4, UL Recognized. Consult Cooper Bussmann forUL Recognition/CSA Component Acceptance status.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at rated voltage and at power factor of15% are given in the elec-trical characteristics. Forother voltages, the clearingI2t is found by multiplyingby correction factor, K,given as a function ofapplied working voltage,Eg, (rms).
C
B
A
H
11
6
E
E
D
Dimensions (mm)Type -KN/80, -KN/110
Size A B B** C C** D E H1* 50 104 134 78 108 59 45 221 50 108 138 78 108 69 53 252 50 108 138 78 108 77 61 253 51 109 139 78 108 92 76 30**Valid for fuse type -KN/110.1mm = 0.0394” / 1” = 25.4mm
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage, Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correc-tion factor, Kp, is given asa function of the RMS loadcurrent, Ib, in % of therated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
Kp1.00.8
0.4
0.50.6
0.3
0.2
0.1
30 40 50 60 70 80 90 100%
Ib
UL
1.41.2
103
6
87
9
5
4
3Eg
200 300 400 500 600 690
100 200 300 400 500 600 690
K1.5
1.0
0.5
0.4
0.3
0.2Eg
1)2)
1) Rated voltage 600V.2) Rated voltage 550V
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
13 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Square body DIN 43 653 — 690V/700V (IEC/UL):40-2000A
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
14 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 690V/700V (IEC/UL):40-2000A
High Speed Fuses
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
200A
250A
315A
350A
400A
450A
500A
550A
630A
700A
800A
900A
A A
Size 1 — 200-900A: 690VTime-Current Curve
Size 1* — 40-630A: 690VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
50A40A
63A80A
100A125A
160A200A
250A315A
350A400A450A500A550A630A
A
B
1x102 103 104 105 1062x102
103
104
105
Pea
k Le
t-T
hrou
gh C
urre
nt 200A250A
315A350A400A450A500A550A630A
700A800A
900A
A
B
Peak Let-Through CurvePeak Let-Through Curve
900 amp fuse is derated to 550V (IEC).
Data Sheet: 17056314 Data Sheet: 17056316
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
15 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 690V/700V (IEC/UL):40-2000A
High Speed Fuses
High SpeedFuses
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
400A
450A
500A
550A
630A
700A
800A
900A
1000
A11
00A
1250
A
A A
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
500A
550A
630A
700A
800A
900A
1000
A11
00A
1250
A14
00A
1500
A16
00A
1800
A20
00A
A A
Size 3 — 500-2000A: 690VTime-Current Curve
Size 2 — 400-1250A: 690VTime-Current Curve
1x103 104 105 106 1072x103
104
105
106
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
400A 450A500A 550A630A
700A800A900A1000A 1100A
1250A
A
B
1x103 104 105 106 1072x103
104
105
106
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
500A 550A630A
700A800A
900A1000A 1100A1250A 1400A1500A 1600A1800A 2000A
A
B
Peak Let-Through CurvePeak Let-Through Curve
1800A fuse is derated to 600V (IEC).2000A fuse is derated to 550V (IEC).
Data Sheet: 17056318 Data Sheet: 17056320
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
16 www.profuse.ir (021)6673 2943 , (021)6673 2945
1000V (IEC) 20-315A
SpecificationsDescription: Square body DIN 43653 stud-mount high speed fuses.
Dimensions: See dimensionsillustration.
Ratings:Volts: — 1000Vac (20-250A)
— 900Vac (315A)
Amps: — 20-315A
IR: — 150kA RMS Sym.
Agency Information: CE, Designed and tested to IEC60269: Part 4, UL Recognized.
Electrical Characteristics
Total clearing I2t
The total clearing I2t at ratedvoltage and at power factorof 15% are given in the elec-trical characteristics. Forother voltages, the clearingI2t is found by multi-plying bycorrection factor, K, given asa function of applied workingvoltage, Eg, (rms).
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 1000V (IEC): 20-315A
High Speed Fuses
1,5
1,0
0,5
0,4
0,3
0,2
K
Eg 200 400 600 800 1000
*Rated voltage 900V
*
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuse dur-ing its operation as a func-tion of the applied workingvoltage Eg, (rms) at apower factor of 15%.
Power Losses
Watts loss at rated current isgiven in the electrical char-acteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correc-tion factor, Kp, is given asa function of the RMS loadcurrent, Ib, in % of therated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
2,52
1,81,61,41,2103
8765
4
3
UL
Eg 200 400 600 800 1000
0,80,70,60,5
0,4
0,3
0,2
0,15
0,1
Kp
Ib30 40 50 60 70 80 90 100%
Dimensions (mm)Type 00TN/80 – 00/80
Size Max A B C D Max E F G H00/80 54 98 78 51 30 28 1000TN/80 54 98 78 51 30 28 67 101mm = 0.0394” / 1” = 25.4mm
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
18 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 1000V (IEC): 50-1400A
High Speed Fuses
1000V (IEC) 50-1400A
SpecificationsDescription: Square body mounthigh speed fuses.
Dimensions: See dimensionsillustrations.
Ratings:
Volts: — 1000Vac.
Amps:— 50-1400A
IR: — 150kA RMS Sym.
Agency Information: CE, Designed and tested to IEC60269: Part 4, UL Recognized.
Electrical Characteristics
Total clearing I2t
The total clearing I2t atrated voltage and at powerfactor of 15% are given inthe electrical characteris-tics. For other voltages, theclearing I2t is found by mul-tiplying by correction fac-tor, K, given as a functionof applied working voltage,Eg, (rms).
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correc-tion factor, Kp, is given asa function of the RMS loadcurrent, Ib, in % of therated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
1,5
1,0
0,5
0,4
0,3
0,2
K
Eg 500 600 700 800 900 1000
*Rated voltage 900V
*
32,52
1,81,61,41,2103
8765
4
3
UL
Eg 500 600 700 800 900 1000
1,0
0,80,70,60,5
0,4
0,3
0,2
0,15
0,1
Kp
Ib30 40 50 60 70 80 90 100%
Type-TN/110
Type-KN/110
Dimensions (mm)Type –KN/110Size A B C Max D1 E G H I.1*KN/110 80 138 108 61 43 6 22 111KN/110 80 138 108 69 51 6 25 112KN/110 80 138 108 77 59 6 25 113KN/110 81 139 108 92 74 6 30 11
Type –TN/110Size A B C Max D2 E G H I1*TN/110 80 138 108 61 43 6 22 111TN/110 80 138 108 69 51 6 25 112TN/110 80 138 108 75 59 6 25 113TN/110 81 139 108 90 74 6 30 111mm = 0.0394” / 1” = 25.4mm
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
19 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
20 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 1000V (IEC): 50-1400A
High Speed Fuses
1s
10-1
10-2
10-3
10-4
Virt
ual P
re-a
rcin
g Ti
me
In S
econ
ds
Prospective Current In Ampere RMS5x101 102 103 104 5x104
50A
80A
125A
200A
315A400A
350A
63A
160A
250A
100A
105
104
103
2x102
Pea
k Le
t-T
hrou
gh C
urre
nt In
Am
pere
s
Prospective Short-Circuit Current symmetrical RMS102 103 104 105 Amp 106
400A
350A 315A
250A200A
160A
50A630A80A100A125A
Size 1* — 50-400A: 1000VTime-Current Curve
Peak Let-Through Curve
104
103
102
10
1s
10-1
10-2
10-3
10-4
Virt
ual P
re-a
rcin
g Ti
me
In S
econ
ds
Prospective Current In Ampere RMS
102 103 104 105
200A
315A400A500A630A
160A
350A
250A
450A550A
105
104
103
2x102
Pea
k Le
t-T
hrou
gh C
urre
nt In
Am
pere
s
Prospective Short-Circuit Current symmetrical RMS102 103 104 105 Amp 106
550A
500A 450A
400A 350A
315A
630A
160A200A250A
Size 1 — 160-630A: 1000VTime-Current Curve
Peak Let-Through Curve
Data Sheet: 17058564 Data Sheet: 17058566
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
21 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 1000V (IEC): 50-1400A
High Speed Fuses
High SpeedFuses
Size 2 — 250-800A: 1000VTime-Current Curve
Peak Let-Through Curve
104
103
102
10
1s
10-1
10-2
10-3
10-4
Virt
ual P
re-a
rcin
g Ti
me
In S
econ
ds
Prospective Current In Ampere RMS
102 103 104 105
250A350A
550A700A
315A
500A400A
630A800A
450A
105
104
103
2x102
Pea
k Le
t-T
hrou
gh C
urre
nt In
Am
pere
s
Prospective Short-Circuit Current symmetrical RMS102 103 104 105 Amp 106
700A800A
630A
500A550A
450A
250A315A350A
400A
104
103
102
10
1s
10-1
10-2
10-3
10-4
Virt
ual P
re-a
rcin
g Ti
me
In S
econ
ds
Prospective Current In Ampere RMS
102 103 104 105
350A450A
700A900A
315A
500A400A
630A800A
550A
1100A1400A*
1000A1250A
105
104
103
2x102
Pea
k Le
t-T
hrou
gh C
urre
nt In
Am
pere
s
Prospective Short-Circuit Current symmetrical RMS102 103 104 105 Amp 106
1250A1400A*1100A
900A1000A
800A
500A550A
630A700A
450A 400A
350A 315A
Size 3 — 315-1400A: 1000VTime-Current Curve
Peak Let-Through Curve
* 1400A fuses are derated to 900V
Data Sheet: 17058568 Data Sheet: 17058570
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
22 www.profuse.ir (021)6673 2943 , (021)6673 2945
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage, Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correc-tion factor, Kp, is given asa function of the RMS loadcurrent, Ib, in % of therated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 1250V/1300V (IEC/UL):50-1400A
High Speed Fuses
1250V/1300V (IEC/UL) 50-1400A
SpecificationsDescription: Square body DIN43 653 stud-mount high speedfuses.
Dimensions: See dimensionsillustration.
Ratings:Volts: — 1250Vac (IEC)
— 1300Vac (UL)
Amps: — 50-1400A
IR: — 100kA RMS Sym.
Agency Information: CE, Designed and tested to IEC60269: Part 4, UL Recognized. Consult Cooper Bussmann forUL Recognition/CSA Component Acceptance status.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t atrated voltage and atpower factor of 15% aregiven in the electricalcharacteristics. For othervoltages, the clearing I2tis found by multiplying bycorrection factor, K, givenas a function of appliedworking voltage, Eg,(rms).
UL32.5
8103
1.4
1.8
6
4
5
3400 600 800 1000 1200 1400
Eg
Dashed lines (- - - - - -) apply to the followingamperages:.Size Amps.1* 400A1 500-630A2 630-1000A3 800-1400A
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
23 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 1250V/1300V (IEC/UL):50-1400A
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
24 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 1250V/1300V (IEC/UL):50-1400A
High Speed Fuses
Size 1* — 50-400A:1250VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
50A63A80A100A125A160A200A250A315A350A400A
A
B
�
Peak Let-Through Curve
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Virt
ual P
re-A
rcin
g Ti
me
In S
econ
ds
A
A
160A
200A
250A
315A
350A
400A
450A
500A
550A
630A
Size 1 — 160-630A: 1250VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh In
Am
pere
s
160A200A250A315A
350A400A
450A500A
550A630A
A
B
Peak Let-Through Curve
630A fuse is derated to 1100V (IEC).
Data Sheet: 17056630 Data Sheet: 17056632
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
25 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 1250V/1300V (IEC/UL):50-1400A
High Speed Fuses
High SpeedFuses
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Virt
ual P
re-A
rcin
g Ti
me
In S
econ
ds
250A
280A
315A
350A
400A
450A
500A
550A
630A
700A
800A
900A
1000
A
A
A
Size 2 — 250-1000A: 1250VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
250A 280A315A 350A400A 450A500A 550A630A 700A800A
900A1000A
A
B
Peak Let-Through Curve
900-1000A fuses are derated to 1100V (IEC).
Size 3 — 315-1400A: 1250VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
315A350A
400A450A500A 550A
630A700A
800A 900A1000A 1100A1250A1400A
A
B
Peak Let-Through Curve
1250-1400A fuses are derated to 1100V (IEC).
Data Sheet: 17056634 Data Sheet: 17056636
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
26 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 1250V/1300V (IEC/UL):50-1400A
High Speed Fuses
1250V/1300V (IEC/UL) 50-1400A
SpecificationsDescription: Square body DIN 43653 stud-mount high speed fuses.
Dimensions: See dimensionsillustration.
Ratings:Volts: — 1250Vac (IEC)
— 1300Vac (UL)
Amps: — 50-1400A
IR: — 100kA RMS Sym.
Agency Information: CE, Designed and tested to IEC60269: Part 4, UL Recognized. Consult Cooper Bussmann forUL Recognition/CSA Component Acceptance status.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t atrated voltage and at powerfactor of 15% are given inthe electrical characteris-tics. For other voltages, theclearing I2t is found by mul-tiplying by correction factor,K, given as a function ofapplied working voltage,Eg, (rms).
C
B
A
H
11
6
E
E
D
K1.5
1.01.25
0.5
0.4
0.3
0.2
400 600 800 1000 1200 1400
Eg
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage, Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correc-tion factor, Kp, is given asa function of the RMS loadcurrent, Ib, in % of therated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
Size A B D E H1* 80 138 58 45 201 80 138 66 53 252 80 138 75 61 253 81 139 90 76 301mm = 0.0394” / 1” = 25.4mm
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
27 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 1250V/1300V (IEC/UL):50-1400A
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
28 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 1250V/1300V (IEC/UL):50-1400A
High Speed Fuses
Size 1* — 50-400A:1250VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
50A63A80A100A125A160A200A250A315A350A400A
A
B
Peak Let-Through Curve
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Virt
ual P
re-A
rcin
g Ti
me
In S
econ
ds
A
A
160A
200A
250A
315A
350A
400A
450A
500A
550A
630A
Size 1 — 160-630A: 1250VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh In
Am
pere
s
160A200A250A315A
350A400A
450A500A
550A630A
A
B
Peak Let-Through Curve
630A fuse is derated to 1100V (IEC).
Data Sheet: 17056630 Data Sheet: 17056632
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
29 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 653 — 1250V/1300V (IEC/UL):50-1400A
High Speed Fuses
High SpeedFuses
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Virt
ual P
re-A
rcin
g Ti
me
In S
econ
ds
250A
280A
315A
350A
400A
450A
500A
550A
630A
700A
800A
900A
1000
A
A
A
Size 2 — 250-1000A: 1250VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
250A 280A315A 350A400A 450A500A 550A630A 700A800A
900A1000A
A
B
Peak Let-Through Curve
900-1000A fuses are derated to 1100V (IEC).
Size 3 — 315-1400A: 1250VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
315A350A
400A450A500A 550A
630A700A
800A 900A1000A 1100A1250A1400A
A
B
Peak Let-Through Curve
1250-1400A fuses are derated to 1100V (IEC).
Data Sheet: 17056634 Data Sheet: 17056636
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
30 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 620 — 690V (IEC/UL): 10-315A
High Speed Fuses
690V (IEC/UL) 10-315A
SpecificationsDescription: Square body DIN 43620 blade style high speed fuses.
Dimensions: See dimensionsillustration.
Ratings:Volts: — 690Vac
Amps: — 10-315A
IR: — 200kA RMS Sym.
Agency Information: CE, Designed and tested to IEC60269: Part 4, UL Recognized.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t atrated voltage and at powerfactor of 15% are given inthe electrical characteris-tics. For other voltages, theclearing I2t is found by mul-tiplying by correction factor,K, given as a function ofapplied working voltage,Eg, (rms).
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage, Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correc-tion factor, Kp, is given asa function of the RMS loadcurrent, Ib, in % of therated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
UL
1.41.2
103
6
87
9
5
4
3Eg
200 300 400 500 600 690
Kp
30 40 50 60 70 80 90 100%
Ib
1.00.8
0.4
0.50.6
0.3
0.2
0.1
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
The rated current of this fuse range has been given with copper conductors that have a current density of 1.3 A/mm2
(IEC 60269-4). For conductor cross section according to IEC60269-1, the fuses with a rated current higher than 125Amust be derated. Please contact Cooper Bussmann for application assistance.
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 620 — 690V (IEC/UL): 10-315A
High Speed Fuses
High SpeedFuses
1x101 102 103 1041x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
10A
16A
20A
25A
32A
40A
50A
63A
80A
100A
125A
160A
200A
250A
315A
A
A
Size 000 — 10-315A: 690VTime-Current Curve
1x101 102 103 104 1052x101
102
103
104
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
10A16A20A25A32A40A50A63A80A100A125A160A200A250A
A
B
315A
Peak Let-Through Curve
Data Sheet: 72056310
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
32 www.profuse.ir (021)6673 2943 , (021)6673 2945
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage, Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correc-tion factor, Kp, is given asa function of the RMS loadcurrent, Ib, in % of therated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 620 — 690V/700V (IEC/UL):40-1000A
High Speed Fuses
690V/700V (IEC/UL) 40-1000A
SpecificationsDescription: Square body DIN43 620 blade style high speedfuses.
Dimensions: See dimensionsillustration.
Ratings:Volts:— 690Vac (IEC)
— 700Vac (UL)
Amps:— 40-1000A
IR:— 200kA RMS Sym.
Agency Information: CE, Designed and tested to IEC60269: Part 4, UL Recognized.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t atrated voltage and at powerfactor of 15% are given inthe electrical characteris-tics. For other voltages,the clearing I2t is found bymultiplying by correctionfactor, K, given as a func-tion of applied workingvoltage, Eg, (rms).
K1.5
1.0
0.5
0.4
0.3
0.2Eg
100 200 300 400 500 600 690
UL
1.41.2
103
6
87
9
5
4
3Eg
200 300 400 500 600 690
Kp
30 40 50 60 70 80 90 100%
Ib
1.00.8
0.4
0.50.6
0.3
0.2
0.1
A
B
D
E
F
6
H
Indicator
Dimensions (mm)Type DIN 1*, DIN 2, DIN 3
Size A B D E F H1* 69 135 58 45 40 202 69 150 71 55 48 263 68 150 88 76 60 331mm = 0.0394” / 1” = 25.4mm
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
33 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 620 — 690V/700V (IEC/UL):40-1000A
The rated current of this fuse range has been given with copper conductors that have a current density of 1.3 A/mm2
(IEC 60269-4). For conductor cross section according to IEC60269-1, the fuses must be derated. Please contact CooperBussmann for application assistance.
Size 1* — 40-630A: 690VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
50A40A
63A80A
100A125A
160A200A
250A315A
350A400A450A500A550A630A
A
B
Peak Let-Through Curve
Data Sheet: 17056314
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
34 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 620 — 690V/700V (IEC/UL):40-1000A
High Speed Fuses
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
500A
550A
630A
700A
800A
900A
1000
A11
00A
1250
A14
00A
1500
A16
00A
1800
A20
00A
A A
Size 3 — 500-2000A: 690VTime-Current Curve
1x103 104 105 106 1072x103
104
105
106
Pea
k Le
t-T
hrou
gh C
urre
nt
500A 550A630A
700A800A
900A1000A 1100A1250A 1400A1500A 1600A1800A 2000A
A
B
Peak Let-Through Curve
1800A fuse is derated to 600V (IEC).2000A fuse is derated to 550V (IEC).
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
400A
450A
500A
550A
630A
700A
800A
900A
1000
A11
00A
1250
A
A A
Size 2 — 400-1250A: 690VTime-Current Curve
1x103 104 105 106 1072x103
104
105
106
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
400A 450A500A 550A630A
700A800A900A1000A 1100A
1250A
A
B
Peak Let-Through Curve
Data Sheet: 17056318 Data Sheet: 17056320
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
35 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 620 — 690V (IEC): 10-800A
High Speed Fuses
High SpeedFuses
690V (IEC) 10-800A
SpecificationsDescription: Square body DIN43 620 blade style high speedfuses.
Dimensions: See dimensionsillustration.
Ratings:Volts: — 690Vac (IEC)
Amps: — 10-800A
IR: — 300kA RMS Sym.
Agency Information: CE, Designed and tested to IEC60269: Part 4, UL Recognized.
Electrical
Characteristics
Total clearing I2t
The total clearing I2t atrated voltage and at powerfactor of 15% are given inthe electrical characteris-tics. For other voltages, theclearing I2t is found by mul-tiplying by correction factor,K, given as a function of applied working voltage, Eg, (rms).
Arc Voltage
This curve gives thepeak arc voltage, UL,which may appearacross the fuse duringits operation as a func-tion of the appliedworking voltage Eg ,(rms) at a power factorof 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correc-tion factor, Kp, is given asa function of the RMS loadcurrent, Ib, in % of therated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
Dimensions (mm)Type DIN 00, DIN 1, DIN 2, DIN 3
Size A B Max D Max E F Min H00 49 78.5 60 30 35 151 68 135 66 52 40 202 68 150 74 60 48 253 68 150 89 75 60 321 mm = 0.0394” 1” = 25.4 mm
1,5
1,0
0,5
0,4
0,3
0,2
K
Eg 200 300 400 500 600 700
32,52
1,81,61,41,2103
8765
4
3
UL
Eg 200 300 400 500 600 700
1,0
0,80,70,60,5
0,4
0,3
0,2
0,15
0,1
Kp
Ib30 40 50 60 70 80 90 100%
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
36 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 620 — 690V (IEC): 10-800A
High Speed Fuses
Catalog NumbersCatalogNumbers
Electrical Characteristics
Type T RMS I2t (A2 Sec)Indicator Amp Clearing WattsFor Micro Size Rating* Pre-arc at 600V Loss170M2691 00 10 3.8 20 3.5170M2692 16 7.2 38 5.5170M2693 20 13 70 6170M2694 25 24 125 8170M2695 32 53 275 9170M2696 40 95 490 10170M2697 50 185 1000 11170M2698 63 345 1800 14170M2699 80 695 3600 16170M2700 100 1250 6650 19170M2701 125 2300 12000 23170M2702 160 4350 22500 29170M4176 1 50 135 705 12170M4177 63 245 1300 15170M4178 80 500 2600 17170M4179 100 950 4850 20170M4180 125 1850 9500 23170M4181 160 3450 18000 28170M4182 200 6750 34500 31170M4183 250 13500 70500 35170M4184 315 26000 135000 41170M4185 350 34000 175000 45170M4186 400 48500 250000 48170M5881 2 200 5650 29000 33170M5882 250 10000 52500 40170M5883 315 19500 105000 46170M5884 350 26000 135000 50170M5885 400 39500 205000 53170M5886 450 55500 290000 59170M5887 500 73000 375000 66170M5888 550 100000 515000 70170M5889 630 150000 770000 79170M6080 3 350 23000 120000 55170M6081 400 34000 175000 59170M6082 450 48500 250000 62170M6083 500 64000 330000 67170M6084 550 84500 435000 70170M6085 630 125000 645000 85170M6086 700 160000 840000 93170M6087 800 245000 1300000 99*The RMS amp rating of this fuse range is given with open fuse bases connected to copperconductors according to IEC 60269, Part 1, table 10. When used in enclosed fuse bases/dis-connects, derating factors have to be observed.Please contact Cooper Bussmann for application assistance.• Watts loss provided at rated current.• Microswitch ordered separately. See accessories on page 179-180.
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
37 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 620 — 690V (IEC): 10-800A
High Speed Fuses
High SpeedFuses
104
103
102
10
1s
10-1
10-2
10-3
10-4
Vir
tual
Pre
-arc
ing
Tim
e In
Sec
onds
Prospective Current In Ampere RMS
10 102 103 104
16A
25A
40A
63A
100A
160A125A
20A
80A
10A
50A
32A
105
104
103
2x102
Pea
k Le
t-T
hrou
gh C
urre
nt In
Am
pere
s
Prospective Short-Circuit Current symmetrical RMS10 102 103 104 Amp 105
160A
125A100A
80A63A
50A 40A
32A25A
20A 16A
10A
104
103
102
10
1s
10-1
10-2
10-3
10-4
Vir
tual
Pre
-arc
ing
Tim
e In
Sec
onds
Prospective Current In Ampere RMS
5x101 102 103 104 5x104
63A
100A
160A
250A350A
400A
80A
315A
50A
200A
125A
105
104
103
2x102
Pea
k Le
t-T
hrou
gh C
urre
nt In
Am
pere
s
Prospective Short-Circuit Current symmetrical RMS10 102 103 104 Amp 105
400A350A
315A250A
200A160A
125A100A
80A63A
50A
Size 00 — 10-160A: 690VTime-Current Curve
Size 1 — 50-400A: 690VTime-Current Curve
Peak Let-Through Curve Peak Let-Through Curve
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
38 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Square body DIN 43 620 — 690V (IEC): 10-800A
High Speed Fuses
104
103
102
10
1s
10-1
10-2
10-3
10-4
Vir
tual
Pre
-arc
ing
Tim
e In
Sec
onds
Prospective Current In Ampere RMS
102 103 104 105200A
315A400A500A630A
350A
250A
550A450A
105
104
103
2x102
Pea
k Le
t-T
hrou
gh C
urre
nt In
Am
pere
s
Prospective Short-Circuit Current symmetrical RMS102 103 104 105 Amp 106
630A
550A 500A
450A 100A
350A 315A
250A 200A
104
103
102
10
1s
10-1
10-2
10-3
10-4
Vir
tual
Pre
-arc
ing
Tim
e In
Sec
onds
Prospective Current In Ampere RMS
102 103 104 105
450A
350A
700A550A
800A
630A
500A
400A
105
104
103
2x102
Pea
k Le
t-T
hrou
gh C
urre
nt In
Am
pere
s
Prospective Short-Circuit Current symmetrical RMS102 103 104 105 Amp 106
800A
700A 630A
550A 00A
450A 400A
350A
Size 2 — 200-630A: 690VTime-Current Curve
Size 3 — 350-800A: 690VTime-Current Curve
Peak Let-Through CurvePeak Let-Through Curve
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
39 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correc-tion factor, Kp, is given asa function of the RMS loadcurrent, Ib, in % of therated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
Square body DIN 43 620 — 1000V (IEC): 20–225A
1000V (IEC) 20–225A
SpecificationsDescription: Square body DIN43 620 blade style high speedfuses.
Dimensions: See dimensionsillustration.
Ratings:Volts: — 1000Vac
Amps: — 20-225A
IR: — 150kA RMS Sym.
Agency Information: CE, Designed and tested to IEC60269: Part 4, UL Recognized.
Electrical Characteristics
Total clearing I2t
The total clearing I2t at ratedvoltage and at power factorof 15% are given in the elec-trical characteristics. Forother voltages, the clearingI2t is found by multiplying bycorrection factor, K, given asa function of applied workingvoltage, Eg, (rms).
1,5
1,0
0,5
0,4
0,3
0,2
K
Eg 200 400 600 800 1000
*Rated voltage 900V
*
32,52
1,81,61,41,2103
8765
4
3
UL
Eg 200 400 600 800 1000
1,0
0,80,70,60,5
0,4
0,3
0,2
0,15
0,1
Kp
Ib30 40 50 60 70 80 90 100%
Dimensions (mm)Type T
Size A B Max D Max E F G Min HDIN 00 49 78.5 60 30 35 6 151mm = 0.0394” / 1” = 25.4mm
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
40 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
Square body DIN 43 620 — 1000V (IEC): 20–225A
104
103
102
10
1s
10-1
10-2
10-3
10-4
Virt
ual P
re-a
rcin
g Ti
me
In S
econ
ds
Prospective Current In Ampere RMS
10 102 103 104
20A
32A40A
63A
100A
160A
225A*
50A
35A
25A
80A
125A
200A*
104
103
102
2x10
Pea
k Le
t-T
hrou
gh C
urre
nt In
Am
pere
s
Prospective Short-Circuit Current symmetrical RMS10 102 103 104 Amp 105
The rated current of this fuse range is given with open fusebases connected to copper conductors according to IEC60269 Part 1, table 10. When used in enclosed fusebases/disconnects, derating factors have to be observed.Please contact Cooper Bussmann for application assistance.
Data Sheet: 17058506
Cooper Bussmann Helps Ford MotorCompany Implement Electrical SafetyProgram
All of the Ford Motor Company facilities in the U.S.,
Canada and Mexico recently completed a safety
upgrade to their electrical systems using Cooper
Bussmann current limiting fuses. The automaker
initiated a proactive program to enhance worker
safety when working on electrical equipment.
The program not only included the fuse change out,
but also a short circuit current study, arc flash
hazard analysis, affixing safety labels to equipment,
and providing safety training and personal protective
equipment (PPE) to workers, as needed. By using
Cooper Bussmann® current-limiting fuses in potential
arc-flash situations the amount of electrical energy
released is considerably less, thereby helping to
reduce the risk of potential injury.
Did You Know?
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
41 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage, Egg,(rms) at a power factor of15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correction factor, Kp, isgiven as a function of theRMS load current, Ib, in %of the rated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
Square body flush end contact — 690V (IEC): 25-400A
690V (IEC) 25-400A
SpecificationsDescription: Square body flushend contact high speed fuses.
Dimensions: See dimensionsillustration.
Ratings:Volts: — 690Vac.
Amps: — 25-400A
IR: — 200kA RMS Sym.
Agency Information: CE, Designed and tested to IEC60269: Part 4, UL Recognized.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t atrated voltage and at powerfactor of 15% are given in the electrical characteristics. For othervoltages, the clearing I2t isfound by multiplying bycorrection factor, K, givenas a function of appliedworking voltage, Eg, (rms).
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
42 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
Square body flush end contact — 690V (IEC): 25-400A
Easy Internet Access to Product andTechnical Information
All of the following functions are available on-line at
www.cooperbussmann.com:
• Product cross-reference
• Product catalogs
• Technical specification sheets
• Current events/news releases
• Training seminar schedule
• Training modules
• Technical software solutions
Did You Know?
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
43 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage, Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correc-tion factor, Kp, is given asa function of the RMS loadcurrent, Ib, in % of therated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
Square body flush end contact — 690V/700V (IEC/UL):40-2000A
Kp
30 40 50 60 70 80 90 100%
Ib
1.00.8
0.4
0.50.6
0.3
0.2
0.1
690V/700V (IEC/UL) 40-2000A
SpecificationsDescription: Square body flushend contact high speed fuses.
Dimensions: See dimensionsillustrations.
Ratings:Volts: — 690Vac (IEC)
— 700Vac (UL)
Amps: — 40-2000A
IR: — 200kA RMS Sym.
Agency Information: CE, Designed and tested to IEC60269: Part 4, UL Recognized. Consult Cooper Bussmannfor UL Recognition / CSA Component Acceptance Status.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t atrated voltage and at powerfactor of 15% are given inthe electrical characteris-tics. For other voltages, theclearing I2t is found by mul-tiplying by correction fac-tor, K, given as a functionof applied working voltage,Eg, (rms).
A
B
D
E
E H
G
F
Dimensions (mm)Type -B/-, -BKN/-, -G/-, -GKN/-
Size A B D E F F** (in) G H1* 50 51 59 45 M8 5⁄16” - 18 UNC-2B 5 ø171 50 51 69 53 M8 5⁄16” - 18 UNC-2B 8 ø202 50 51 77 61 M10 3⁄8” - 16 UNC-2B 10 ø243 51 53 92 76 M12 1⁄2” - 13 UNC-2B 10 ø30**Valid for fuses type -G/- & -GKN/-.NB: B = 65 for: Size 2, 1100-1250A
Size 3, 1600-2000A1mm = 0.0394” / 1” = 25.4mm
UL
1.41.2
103
6
87
9
5
4
3Eg
200 300 400 500 600 690
K
1.5
1.0
0.5
0.4
0.3
0.2Eg
1)2)
100 200 300 400 500 600 690
1) Rated voltage 600V.2) Rated voltage 550V
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
44 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
Square body flush end contact — 690V/700V (IEC/UL):40-2000A
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
45 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Square body flush end contact — 690V/700V (IEC/UL):40-2000A
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
200A
250A
315A
350A
400A
450A
500A
550A
630A
700A
800A
900A
A A
Size 1 — 200-900A: 690VTime-Current Curve
Size 1* — 40-630A: 690VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
50A40A
63A80A
100A125A
160A200A
250A315A
350A400A450A500A550A630A
A
B
� 1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt 200A250A
315A350A400A450A500A550A630A
700A800A
900A
A
B
Peak Let-Through CurvePeak Let-Through Curve
900 amp fuse is derated to 550V (IEC).
Data Sheet: 17056314 Data Sheet: 17056316
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
46 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
Square body flush end contact — 690V/700V (IEC/UL):40-2000A
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
400A
450A
500A
550A
630A
700A
800A
900A
1000
A11
00A
1250
A
A A
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
500A
550A
630A
700A
800A
900A
1000
A11
00A
1250
A14
00A
1500
A16
00A
1800
A20
00A
A A
Size 3 — 500-2000A: 690VTime-Current Curve
Size 2 — 400-1250A: 690VTime-Current Curve
1x103 104 105 106 1072x103
104
105
106
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
400A 450A500A 550A630A
700A800A900A1000A 1100A
1250A
A
B
1x103 104 105 106 1072x103
104
105
106
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
500A 550A630A
700A800A
900A1000A 1100A1250A 1400A1500A 1600A1800A 2000A
A
B
Peak Let-Through CurvePeak Let-Through Curve
1800A fuse is derated to 600V (IEC).2000A fuse is derated to 550V (IEC).
Data Sheet: 17056318 Data Sheet: 17056320
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
47 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Arc Voltage
This curve gives the peakarc voltage, UL, whichmay appear across thefuse during its operationas a function of theapplied working voltage,Eg, (rms) at a power fac-tor of 15%.
Power Losses
Watts loss at rated cur-rent is given in the electri-cal characteristics. Thecurve allows the calcula-tion of the power lossesat load currents lowerthan the rated current.The correction factor, Kp,is given as a function ofthe RMS load current, Ib,in % of the rated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
Square body flush end contact — 690V (IEC):1000-4000A
690V (IEC) 1000-4000A
SpecificationsDescription: Square body flushend contact high speed fuses.
Dimensions: See dimensionsillustrations.
Ratings:Volts: — 690Vac
Amps: — 1000-4000A
IR: — 200kA RMS Sym.
Agency Information: CE, Designed and tested to IEC60269: Part 4, UL Recognized.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t atrated voltage and at powerfactor of 15% are given inthe electrical characteris-tics. For other voltages, theclearing I2t is found by mul-tiplying by correction fac-tor, K, given as a functionof applied working voltage,Eg, (rms).
K
1.5
1.0
0.5
0.4
0.3
0.2Eg
1)
100 200 300 400 500 600 690
Kp
30 40 50 60 70 80 90 100%
Ib
1.00.8
0.4
0.50.6
0.3
0.2
0.1
1) Rated voltage 500V
UL
1.41.2
103
6
87
9
5
4
3Eg
200 300 400 500 600 690
53
105
67
15
F
G
105
Ø4
Ø56
Dimensions (mm)Type 4B/-, 4BKN/-, 4G/-, 4GKN/-
Size F (in) G4B M10 10 deep 334G 1⁄2” -13 UNC-2B 10 deep 381mm = 0.0394” / 1” = 25.4mm
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
48 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
Square body flush end contact — 690V (IEC):1000-4000A
1x103 104 105 1061x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current in Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
1000
A12
50A
1400
A16
00A
2000
A22
00A
2500
A30
00A
3500
A40
00A
A
A
Size 4 — 1000-4000A: 690VTime-Current Curve
1x103 104 105 106 1072x103
104
105
106
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
1000A1250A
1400A1600A
2000A 2200A2500A
3000A3500A4000A
A
B
Peak Let-Through Curve
4000A fuse is derated to 500V (IEC).
Catalog NumbersCatalog Numbers
-BKN/- -GKN/-Electrical Characteristics
-B/- Type K -G/- Type K Rated Current RMS I2t (A2 Sec) Watts LossVisual Indicator Visual Indicator Norm. Liquid Clearing Norm. LiquidIndicator for Micro Indicator for Micro Size Cool. Cool. Pre-arc at 660V Cool. Cool.170M7058 170M7078 170M7098 170M7118 4 1000 1350 76000 505000 175 315170M7059 170M7079 170M7099 170M7119 1250 1700 145000 965000 195 355170M7060 170M7080 170M7100 170M7120 1400 1900 205000 1400000 205 375170M7061 170M7081 170M7101 170M7121 1600 2200 305000 2050000 220 405170M7062 170M7082 170M7102 170M7122 2000 2700 600000 3950000 245 445170M7063 170M7083 170M7103 170M7123 2500 3400 1200000 7800000 275 495170M7064 170M7084 170M7104 170M7124 3000 4100 2000000 13500000 305 555170M7065 170M7085 170M7105 170M7125 3500 4700 3250000 22000000 325 585170M7066 170M7086 170M7106 170M7126 †4000 †5400 4700000 †28000000 355 640†Rated voltage (IEC) 500V.• Watts loss provided at rated current.• Liquid Cool. = Liquid cooling. Temperature on the terminals not to exceed 60°C.• Microswitch indicator ordered separately. See accessories on pages 179-180.
Data Sheet: 17056328
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
49 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correction factor, Kp, isgiven as a function of theRMS load current, Ib, in %of the rated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
Square body flush end contact — 1000V (IEC): 50–1400A
1000V (IEC) 50–1400A
SpecificationsDescription: Square body flushend contact high speed fuses.
Dimensions: See dimensionsillustration.
Ratings:Volts: — 1000Vac.
Amps: — 50-1400A
IR: — 150kA (Est.300kA) RMS Sym.
Agency Information: CE, Designed and tested to IEC60269: Part 4, UL Recognized.
Electrical Characteristics
Total clearing I2t
The total clearing I2t atrated voltage and at powerfactor of 15% are given in the electrical characteristics. For othervoltages, the clearing I2t isfound by multiplying bycorrection factor, K, givenas a function of appliedworking voltage, Eg, (rms).
1,5
1,0
0,5
0,4
0,3
0,2
K
Eg 500 600 700 800 900 1000
*Rated voltage 900V
*
32,52
1,81,61,41,2103
8765
4
3
UL
Eg 500 600 700 800 900 1000
Dimensions (mm)Type –BKN/- and –GKN/-
Size Size A B Max D E F F** (in) Min G H1* BKN/75+GKN/75 72.5 74 61 43 M8 5⁄16” – 18 UNC-2B 5 ø17.51 BKN/75+GKN/75 73.2 74 69 52 M8 5⁄16” – 18 UNC-2B 8 ø202 BKN/75+GKN/75 73.2 74.4 77 59 M10 3⁄8” – 16 UNC-2B 10 ø243 BKN/75+GKN/75 73.3 75.4 92 74 M12 1⁄2” – 13 UNC-2B 10 ø303 BKN/90+GKN/90 80.3 91.4 92 74 M12 1⁄2” – 13 UNC-2B 10 ø30** Valid for fuses type –GKN/-.1mm = 0.0394” / 1” = 25.4mm
1,0
0,80,70,60,5
0,4
0,3
0,2
0,15
0,1
Kp
Ib30 40 50 60 70 80 90 100%
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
50 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
Square body flush end contact — 1000V (IEC): 50–1400A
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
51 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Square body flush end contact — 1000V (IEC): 50–1400A
1s
10-1
10-2
10-3
10-4
Virt
ual P
re-a
rcin
g Ti
me
In S
econ
ds
Prospective Current In Ampere RMS5x101 102 103 104 5x104
50A
80A
125A
200A
315A400A
350A
63A
160A
250A
100A
105
104
103
2x102
Pea
k Le
t-T
hrou
gh C
urre
nt In
Am
pere
s
Prospective Short-Circuit Current symmetrical RMS102 103 104 105 Amp 106
400A
350A 315A
250A200A
160A
50A630A80A100A125A
Size 1* — 50-400A: 1000VTime-Current Curve
Peak Let-Through Curve
104
103
102
10
1s
10-1
10-2
10-3
10-4
Virt
ual P
re-a
rcin
g Ti
me
In S
econ
ds
Prospective Current In Ampere RMS
102 103 104 105
200A
315A400A500A630A
160A
350A
250A
450A550A
105
104
103
2x102
Pea
k Le
t-T
hrou
gh C
urre
nt In
Am
pere
s
Prospective Short-Circuit Current symmetrical RMS102 103 104 105 Amp 106
550A
500A 450A
400A 350A
315A
630A
160A200A250A
Size 1 — 160-630A: 1000VTime-Current Curve
Peak Let-Through Curve
Data Sheet: 17058564 Data Sheet: 17058566
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
52 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
Square body flush end contact — 1000V (IEC): 50–1400A
Size 2 — 250-800A: 1000VTime-Current Curve
Peak Let-Through Curve
104
103
102
10
1s
10-1
10-2
10-3
10-4
Virt
ual P
re-a
rcin
g Ti
me
In S
econ
ds
Prospective Current In Ampere RMS
102 103 104 105
250A350A
550A700A
315A
500A400A
630A800A
450A
105
104
103
2x102
Pea
k Le
t-T
hrou
gh C
urre
nt In
Am
pere
s
Prospective Short-Circuit Current symmetrical RMS102 103 104 105 Amp 106
700A800A
630A
500A550A
450A
250A315A350A
400A
104
103
102
10
1s
10-1
10-2
10-3
10-4
Virt
ual P
re-a
rcin
g Ti
me
In S
econ
ds
Prospective Current In Ampere RMS
102 103 104 105
350A450A
700A900A
315A
500A400A
630A800A
550A
1100A1400A*
1000A1250A
105
104
103
2x102
Pea
k Le
t-T
hrou
gh C
urre
nt In
Am
pere
s
Prospective Short-Circuit Current symmetrical RMS102 103 104 105 Amp 106
1250A1400A*1100A
900A1000A
800A
500A550A
630A700A
450A 400A
350A 315A
Size 3 — 315-1400A: 1000VTime-Current Curve
Peak Let-Through Curve
* 1400A fuses are derated to 900V
Data Sheet: 17058568 Data Sheet: 17058570
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
53 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage, Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correc-tion factor, Kp, is given asa function of the RMS loadcurrent, Ib, in % of therated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
Square body flush end contact — 1250V/1300V (IEC/UL):50-1400A
1250V/1300V (IEC/UL) 50-1400A
SpecificationsDescription: Square body flushend contact high speed fuses.
Dimensions: See dimensionsillustrations.
Ratings:Volts: — 1250Vac (IEC)
— 1300Vac (UL)
Amps: — 50-1400A
IR: — 100kA RMS Sym.
Agency Information: CE, Designed and tested to IEC60269: Part 4, UL Recognized. Consult Cooper Bussmann forUL Recognition/CSA Component Acceptance status.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at ratedvoltage and at power factorof 15% are given in the elec-trical characteristics. Forother voltages, the clearingI2t is found by multiplying bycorrection factor, K, given asa function of applied workingvoltage, Eg, (rms).
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
54 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
Square body flush end contact — 1250V/1300V (IEC/UL):50-1400A
Catalog NumbersCatalog Numbers Electrical Characteristics-BKN/75 -BKN/80 -BKN/90 -GKN/75 -GKN/90 RatedType K Type K Type K Type K Type K Current I2t (A2 Sec)Indicator Indicator Indicator Indicator Indicator RMS- Clearing Clearing Wattsfor Micro for Micro for Micro for Micro for Micro Size Amps Pre-arc at 1000V at 1250V Loss170M3388 170M3438 170M3488 1* 50 135 815 1100 15170M3389 170M3439 170M3489 63 215 1300 1750 20170M3390 170M3440 170M3490 80 420 2500 3350 25170M3391 170M3441 170M3491 100 750 4450 5950 30170M3392 170M3442 170M3492 125 1450 9000 11500 35170M3393 170M3443 170M3493 160 2600 16000 21000 40170M3394 170M3444 170M3494 200 5150 31000 41000 45170M3395 170M3445 170M3495 250 9200 54500 73000 55170M3396 170M3446 170M3496 315 18500 115000 150000 60170M3397 170M3447 170M3497 350 27000 165000 220000 65
†Rated voltage (IEC) 1100V.‡Rated voltage (IEC) 1000V.¥Rated voltage (IEC) 1250V.• Watts loss provided at rated current.• Microswitch indicator ordered separately. See accessories on pages 179-180.
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
55 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Square body flush end contact — 1250V/1300V (IEC/UL):50-1400A
Size 1* — 50-400A:1250VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
50A63A80A100A125A160A200A250A315A350A400A
A
B
Peak Let-Through Curve
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Virt
ual P
re-A
rcin
g Ti
me
In S
econ
ds
A
A
160A
200A
250A
315A
350A
400A
450A
500A
550A
630A
Size 1 — 160-630A: 1250VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh In
Am
pere
s
160A200A250A315A
350A400A
450A500A
550A630A
A
B
Peak Let-Through Curve
630A fuse is derated to 1100V (IEC).
Data Sheet: 17056630 Data Sheet: 17056632
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
56 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
Square body flush end contact — 1250V/1300V (IEC/UL):50-1400A
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Virt
ual P
re-A
rcin
g Ti
me
In S
econ
ds
250A
280A
315A
350A
400A
450A
500A
550A
630A
700A
800A
900A
1000
A
A
A
Size 2 — 250-1000A: 1250VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
250A 280A315A 350A400A 450A500A 550A630A 700A800A
900A1000A
A
B
Peak Let-Through Curve
900-1000A fuses are derated to 1100V (IEC).
Size 3 — 315-1400A: 1250VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
315A350A
400A450A500A 550A
630A700A
800A 900A1000A 1100A1250A1400A
A
B
Peak Let-Through Curve
1250-1400A fuses are derated to 1100V (IEC).
Data Sheet: 17056634 Data Sheet: 17056636
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
57 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage, Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correc-tion factor, Kp, is given asa function of the RMS loadcurrent, Ib, in % of therated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
Square Body French Style — 690V/700V (IEC/UL):40-1500A
690V/700V (IEC/UL) 40-1500A
SpecificationsDescription: Square body Frenchstyle high speed fuses.
Dimensions: See dimensionsillustration.
Ratings:Volts: — 690Vac (IEC)
— 700Vac (UL)
Amps: — 40-1500A
IR: — 200kA RMS Sym.
Agency Information: CE, Designed and tested to IEC60269: Part 4, UL Recognized.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t atrated voltage and at powerfactor of 15% are given inthe electrical characteris-tics. For other voltages, theclearing I2t is found by mul-tiplying by correction factor,K, given as a function ofapplied working voltage,Eg, (rms).
A
B
C
D
EJ
E
6
H
I
Dimensions (mm)Type -E/-, -EKN/-
Size A B C D E H I J1* 50 102 76 59 45 18 9 131 50 111 86 69 53 25 11 112 50 126 91 77 61 30 13 123 51 126 91 92 76 36 13 131mm = 0.0394” / 1” = 25.4mm
K
1.5
1.0
0.5
0.4
0.3
0.2Eg
100 200 300 400 500 600 690
UL
1.41.2
103
6
87
9
5
4
3Eg
200 300 400 500 600 690
Kp1.00.8
0.4
0.50.6
0.3
0.2
0.1
30 40 50 60 70 80 90 100%
Ib
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
58 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
Square Body French Style — 690V/700V (IEC/UL):40-1500A
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
59 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Square Body French Style — 690V/700V (IEC/UL):40-1500A
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
200A
250A
315A
350A
400A
450A
500A
550A
630A
700A
800A
900A
A A
Size 1 — 200-900A: 690VTime-Current Curve
Size 1* — 40-630A: 690VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
50A40A
63A80A
100A125A
160A200A
250A315A
350A400A450A500A550A630A
A
B
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt 200A250A
315A350A400A450A500A550A630A
700A800A
900A
A
B
Peak Let-Through CurvePeak Let-Through Curve
Data Sheet: 17056314 Data Sheet: 17056316
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
60 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
Square Body French Style — 690V/700V (IEC/UL):40-1500A
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
400A
450A
500A
550A
630A
700A
800A
900A
1000
A11
00A
1250
A
A A
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
500A
550A
630A
700A
800A
900A
1000
A11
00A
1250
A14
00A
1500
A16
00A
1800
A20
00A
A A
Size 3 — 500-2000A: 690VTime-Current Curve
Size 2 — 400-1250A: 690VTime-Current Curve
1x103 104 105 106 1072x103
104
105
106
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
400A 450A500A 550A630A
700A800A900A1000A 1100A
1250A
A
B
1x103 104 105 106 1072x103
104
105
106
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
500A 550A630A
700A800A
900A1000A 1100A1250A 1400A1500A 1600A1800A 2000A
A
B
Peak Let-Through CurvePeak Let-Through Curve
1800A fuse is derated to 600V (IEC).2000A fuse is derated to 550V (IEC).
Data Sheet: 17056318 Data Sheet: 17056320
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
61 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage, Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correc-tion factor, Kp, is given asa function of the RMS loadcurrent, Ib, in % of therated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
Square Body US Style — 690V/700V (IEC):40-2000A
690V/700V (IEC) 40-2000A
SpecificationsDescription: Square body USstyle high speed fuses.
Dimensions: See dimensionsillustration.
Ratings:Volts: — 690Vac (IEC)
— 700Vac (UL)
Amps: — 40-200A
IR: — 200kA RMS Sym.
Agency Information: CE, Designed and tested to IEC60269: Part 4, UL Recognized. Consult Cooper Bussmannfor UL Recognition/ CSA Component Acceptance status.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at ratedvoltage and at power factorof 15% are given in the elec-trical characteristics. Forother voltages, the clearingI2t is found by multiplying bycorrection factor, K, given asa function of applied workingvoltage, Eg, (rms).
Size A B B** C1 C1** C2 C2** D E H I1* 50 110 148 85 123 72 110 59 45 20 101 50 136 157 104 126 78 100 69 53 25 142 50 135 159 105 125 78 99 77 61 25 143 51 135 155 106 125 77 97 92 76 36 16**Valid for fuses type -FU/115 & -FKE/115.1mm = 0.0394” / 1” = 25.4mm
K1.5
1.0
0.5
0.4
0.3
0.2
1)2)
100 200 300 400 500 600 690
UL
1.41.2
103
6
87
9
5
4
3Eg
200 300 400 500 600 690
Kp1.00.8
0.4
0.50.6
0.3
0.2
0.1
30 40 50 60 70 80 90 100%
Ib
1) Rated voltage 600V.2) Rated voltage 550V
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
62 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
63 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Square body US style — 690V/700V (IEC): 40-2000A
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
200A
250A
315A
350A
400A
450A
500A
550A
630A
700A
800A
900A
A A
Size 1 — 200-900A: 690VTime-Current Curve
Size 1* — 40-630A: 690VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
50A40A
63A80A
100A125A
160A200A
250A315A
350A400A450A500A550A630A
A
B
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt 200A250A
315A350A400A450A500A550A630A
700A800A
900A
A
B
Peak Let-Through CurvePeak Let-Through Curve
Data Sheet: 17056314 Data Sheet: 17056316
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
64 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
Square body US style — 690V/700V (IEC): 40-2000A
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
400A
450A
500A
550A
630A
700A
800A
900A
1000
A11
00A
1250
A
A A
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
500A
550A
630A
700A
800A
900A
1000
A11
00A
1250
A14
00A
1500
A16
00A
1800
A20
00A
A A
Size 3 — 500-2000A: 690VTime-Current Curve
Size 2 — 400-1250A: 690VTime-Current Curve
1x103 104 105 106 1072x103
104
105
106
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
400A 450A500A 550A630A
700A800A900A1000A 1100A
1250A
A
B
1x103 104 105 106 1072x103
104
105
106
Pea
k Le
t-T
hrou
gh C
urre
nt
500A 5630A
7800A
91000A 11250A 11500A 11800A 2
A
B
Peak Let-Through CurvePeak Let-Through Curve
1800A fuse is derated to 600V (IEC).2000A fuse is derated to 550V (IEC).
Data Sheet: 17056318 Data Sheet: 17056320
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
65 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correction factor, Kp, isgiven as a function of theRMS load current, Ib, in %of the rated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
Square body US style — 1000V (IEC): 50-1400A
1000V (IEC) 50-1400A
SpecificationsDescription: Square body USstyle high speed fuses.
Dimensions: See dimensionsillustration.
Ratings:Volts: — 1000Vac.
Amps: — 50-1400A
IR: — 150kA RMS Sym.
Agency Information: CE, Designed and tested to IEC60269: Part 4, UL Recognized.
Electrical Characteristics
Total clearing I2t
The total clearing I2t at ratedvoltage and at power factorof 15% are given in theelectrical characteristics. Forother voltages, the clearingI2t is found by multiplying bycorrection factor, K, given asa function of applied working voltage, Eg, (rms).
1,5
1,0
0,5
0,4
0,3
0,2
K
Eg 500 600 700 800 900 1000
*Rated voltage 900V
*
32,52
1,81,61,41,2103
8765
4
3
UL
Eg 500 600 700 800 900 1000
1,0
0,80,70,60,5
0,4
0,3
0,2
0,15
0,1
Kp
Ib30 40 50 60 70 80 90 100%
Dimensions (mm)Type –FKE/115
Size Type B C1 C2 D E H I1* FKE/115 156 130 101 59 45 20 101 FKE/115 160 127 102 69 53 25 142 FKE/115 160 127 102 77 61 25 143 FKE/115 159 128 101 92 76 36 161mm = 0.0394” / 1” = 25.4mm
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
66 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Cooper Bussmann® Fuse InstallationEnables Food Processor To MeetManufacturing Demand
When one of
America’s largest
retailers requested
a special packaging
size from Beech-Nut
baby foods, the
company developed
a new packaging
system with motors
and drives having state-of-the-art overcurrent
protection.
The maintenance staff required a fuse system that
was DIN-rail mountable for ease of installation with
open fuse indication and a finger-safe design. And,
the most important need was to use current-limiting
overcurrent protection to minimize the arc-flash
hazard to plant personnel in accordance with NFPA
70E guidance. The plant’s associate electrical
engineer chose the Cooper Bussmann®
CUBEFuse® compact design because it would save
time laying out and building the sub panel. He was
looking for components that were easy to wire and
would be part of a sub panel system that would be
easy to maintain over time.
The fuse panel utilizes 39 three-pole, 10A
CUBEFuse sets. The fuse holders snap onto an
easy to install 35mm DIN rail versus time-consuming
drilling and tapping mounting holes for all the fuse
holders. The panel has a total of 117 fuse
installations with expansion room up to 147 units.
Did You Know?
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
67 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Square body US style — 1000V (IEC): 50-1400A
1s
10-1
10-2
10-3
10-4
Virt
ual P
re-a
rcin
g Ti
me
In S
econ
ds
Prospective Current In Ampere RMS5x101 102 103 104 5x104
50A
80A
125A
200A
315A400A
350A
63A
160A
250A
100A
105
104
103
2x102
Pea
k Le
t-T
hrou
gh C
urre
nt In
Am
pere
s
Prospective Short-Circuit Current symmetrical RMS102 103 104 105 Amp 106
400A
350A 315A
250A200A
160A
50A630A80A100A125A
Size 1* — 50-400A: 1000VTime-Current Curve
Peak Let-Through Curve
104
103
102
10
1s
10-1
10-2
10-3
10-4
Virt
ual P
re-a
rcin
g Ti
me
In S
econ
ds
Prospective Current In Ampere RMS
102 103 104 105
200A
315A400A500A630A
160A
350A
250A
450A550A
105
104
103
2x102
Pea
k Le
t-T
hrou
gh C
urre
nt In
Am
pere
s
Prospective Short-Circuit Current symmetrical RMS102 103 104 105 Amp 106
550A
500A 450A
400A 350A
315A
630A
160A200A250A
Size 1 — 160-630A: 1000VTime-Current Curve
Peak Let-Through Curve
Data Sheet: 17058564 Data Sheet: 17058566
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
68 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
Square body US style — 1000V (IEC): 50-1400A
Size 2 — 250-800A: 1000VTime-Current Curve
Peak Let-Through Curve
104
103
102
10
1s
10-1
10-2
10-3
10-4
Virt
ual P
re-a
rcin
g Ti
me
In S
econ
ds
Prospective Current In Ampere RMS
102 103 104 105
250A350A
550A700A
315A
500A400A
630A800A
450A
105
104
103
2x102
Pea
k Le
t-T
hrou
gh C
urre
nt In
Am
pere
s
Prospective Short-Circuit Current symmetrical RMS102 103 104 105 Amp 106
700A800A
630A
500A550A
450A
250A315A350A
400A
104
103
102
10
1s
10-1
10-2
10-3
10-4
Virt
ual P
re-a
rcin
g Ti
me
In S
econ
ds
Prospective Current In Ampere RMS
102 103 104 105
350A450A
700A900A
315A
500A400A
630A800A
550A
1100A1400A*
1000A1250A
105
104
103
2x102
Pea
k Le
t-T
hrou
gh C
urre
nt In
Am
pere
s
Prospective Short-Circuit Current symmetrical RMS102 103 104 105 Amp 106
1250A1400A*1100A
900A1000A
800A
500A550A
630A700A
450A 400A
350A 315A
Size 3 — 315-1400A: 1000VTime-Current Curve
Peak Let-Through Curve
* 1400A fuses are derated to 900V
Data Sheet: 17058568 Data Sheet: 17058570
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
69 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage, Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correc-tion factor, Kp, is given asa function of the RMS loadcurrent, Ib, in % of therated current.
Features and Benefits• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss• Superior cycling capability
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
Square body US style — 1250V/1300V (IEC/UL):50-1400A
1250V/1300V (IEC/UL) 50-1400A
SpecificationsDescription: Square body USstyle high speed fuses.
Dimensions: See dimensionsillustration.
Ratings:Volts: — 1250Vac (IEC)
— 1300Vac (UL)
Amps: — 50-1400A
IR: — 100kA RMS Sym.
Agency Information: CE,Designed and tested to IEC60269: Part 4, UL Recognized.Consult Cooper Bussmann for ULRecognition/CSA ComponentAcceptance status.
Electrical
Characteristics
Total Clearing I2t
The total clearing I2t atrated voltage and at powerfactor of 15% are given inthe electrical characteris-tics. For other voltages, theclearing I2t is found by mul-tiplying by correction factor,K, given as a function ofapplied working voltage, Eg,(rms).
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
70 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
Square body US style — 1250V/1300V (IEC/UL):50-1400A
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
71 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Square body US style — 1250V/1300V (IEC/UL): 0-1400A
Size 1* — 50-400A:1250VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
50A63A80A100A125A160A200A250A315A350A400A
A
B
�
Peak Let-Through Curve
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Virt
ual P
re-A
rcin
g Ti
me
In S
econ
ds
A
A
160A
200A
250A
315A
350A
400A
450A
500A
550A
630A
Size 1 — 160-630A: 1250VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh In
Am
pere
s
160A200A250A315A
350A400A
450A500A
550A630A
A
B
Peak Let-Through Curve
630A fuse is derated to 1100V (IEC).
Data Sheet: 17056630 Data Sheet: 17056632
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
72 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
Square body US style — 1250V/1300V (IEC/UL): 0-1400A
1x102 103 104 1051x10–4
10–3
10–2
10–1
100
101
102
103
104
Prospective Current In Amperes RMS
Virt
ual P
re-A
rcin
g Ti
me
In S
econ
ds
250A
280A
315A
350A
400A
450A
500A
550A
630A
700A
800A
900A
1000
A
A
A
Size 2 — 250-1000A: 1250VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
250A 280A315A 350A400A 450A500A 550A630A 700A800A
900A1000A
A
B
Peak Let-Through Curve
900-1000A fuses are derated to 1100V (IEC).
Size 3 — 315-1400A: 1250VTime-Current Curve
1x102 103 104 105 1062x102
103
104
105
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
315A350A
400A450A500A 550A
630A700A
800A 900A1000A 1100A1250A1400A
A
B
Peak Let-Through Curve
1250-1400A fuses are derated to 1100V (IEC).
Data Sheet: 17056634 Data Sheet: 17056636
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
73 www.profuse.ir (021)6673 2943 , (021)6673 2945
DIN 43 653 DIN 43 620 French Style Flush End US StyleSize Type T Type K Type T Type K Type T Type K Type T Type K Type K000 170H0236 170H0236
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Square body fuse accessories
Indicator SystemsTypower ZILOX fuses are available with three different indicator systems.
1. Visual Indicator
The indicator situated in one cover plate is clearly visible assoon as the fuse has operated. The minimum voltage foroperating the indicator is 20V.
2. Type T Indicator
The indicator is situated on one cover plate with a coverplate tag to accommodate an auxiliary switch. The minimumvoltage for operating the indicator is 20V. A special low voltage indicator (1.5V) is available on request.
3. Type K Indicator
This indicator is situated on the fuse body. It is covered by anadapter for snap-on mounting of an auxiliary switch. Theoperating voltage of the indicator is 1.5V. As a matter of safety, the factory mounted adapter must not be removedfrom the fuse.
MicroswitchThe Typower ZILOX fuses with either type T indicator or typeK indicator can be equipped with a microswitch for remoteelectrical indication of fuse operations. All micro-switcheshave one normally open and one normally closed contact.Ratings are 2A, 250Vac.
6.3 x 0.8mm 2.8 x 0.5mm IndicatorMicroswitch Lugs Lugs Type170H0235 X T170H0236 X T170H0237 X T170H0238 X T170H0069 X K
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
74 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
Square body fuse accessories
Universal
DIN 43 653
DIN 43 653
Fuse Bases (Blocks)
DIN 43 653 Fuse Bases
For the Typower ZILOX fuses according to DIN 43 653, thefollowing fuse bases are available:
The fuse bases rated 1250A can also be used for the fuseswith higher rated current if the maximum load current is derated according to the table below:
Fuse Amp Max Amp LoadRating In Fuse Base1400 13251500 14001600 15001800 16502000 1800
Fixed Center Max Max. Fuse FuseBase Style Volts Amp Rating Size170H1007 1000 400 00, 000170H1013 660 200 0000,000UL Recognized to UL 512.
Universal Fuse Bases
For the Typower ZILOX fuses according to DIN 43 653,French style and North American style, the following fusebases are available:
Modular fuse bases are UL Recognized to UL 512 and meetthe spacing requirements of UL 347. Contact your CooperBussmann® sales representative for more complete orderinginformation.
DIN 43 620 Fuse Bases
For fuse bases used with Typower ZILOX fuses according toDIN 43 620, please contact your local Cooper Bussmannsales representative.
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
75 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
150 5-60 X X250 1-50 X X500 0.25-30 X X600 6-32 X X700 (22 x 58mm) 20-100 X —700 (14 x 51mm) 1-50 X X750 5-60 X X
1000 20-30 X X (800Vdc)1250 20-30 X X (1000Vdc)1500 8-15 X X (1000Vdc)2000 2-6 X X (1000Vdc)
General Information
Cooper Bussmann offers a full line of ferrule style (cylindricalclip-mounted) fuses, designed and tested to meet standardsand requirements in various locations around the world. Theirunique design and construction provide:
• Superior cycling capability• Low energy let-through (I2t)
Ferrule fuses provide an excellent solution for small UPS,small ac drives and other low power applications wherespace is at a premium.
Voltage Rating
All Cooper Bussmann® ferrule fuses — except 690V — havebeen tested at their rated voltage. The 690V ferrule fuse hasbeen tested to the IEC 60269 standard, which requires clearing at the rated voltage +5%.
Accessories
Ferrule fuses may be mounted in fuseclips, fuse holders,fuse blocks or fused switches. A variety of products are available. Please consult Cooper Bussmann ApplicationEngineering to discuss your requirement.
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
76 www.profuse.ir (021)6673 2943 , (021)6673 2945
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage, Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correction factor, Kp, isgiven as a function of theRMS load current, Ib, in %of the rated current.
Catalog Numbers
ElectricalCharacteristicsI2t (A2 Sec)
RatedCatalog Current Clearing WattsNumbers Size RMS-Amps Pre-arc at 150V LossFWA-5A10F 10 x 38mm 5 1.6 8 1FWA-10A10F (13⁄32” x 11⁄2”) 10 3.6 16 2.7FWA-15A10F 15 14 55 3.3FWA-20A10F 20 33 130 3.8FWA-25A10F 25 58 220 4.9FWA-30A10F 30 100 400 4.9FWA-35A21F 21 x 51mm 35 75 800 4.5FWA-40A21F (13⁄16” x 2”) 40 100 1000 5.1FWA-45A21F 45 130 1300 6FWA-50A21F 50 170 1600 7.3FWA-60A21F 60 250 2400 8.0• Watts loss provided at rated current.• See accessories on page 211.
Features and Benefits• Excellent cycling capability and dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss in a compact size• Used with finger-safe holders/blocks
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
Ferrule — FWA 150V: 5-60A
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
Dimensions - in (mm)Amp DimensionsRange A B C5-30 1.5 (38.1) 0.375 (9.5) 0.406 (10.3)35-60 2.0 (50.8) 0.625 (15.9) 0.811 (20.6)
The total clearing I2t atrated voltage and at powerfactor of 15% are given in the electrical characteristics. For othervoltages, the clearing I2t isfound by multiplying bycorrection factor, K, givenas a function of appliedworking voltage, Eg, (rms).
1501027022
1.5
1.0
0.5
0.3
0.2
0.15Eg
K
1)
2)
1) 5-30A Range2) 35-60A Range
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
77 www.profuse.ir (021)6673 2943 , (021)6673 2945
Ferrule — FWA 150V: 5-60A
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
78 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Agency Information: CE, UL Recognition 1-50A & CSAComponent Acceptance: 5-30A
Electrical
Characteristics
Total Clearing I2t
The total clearing I2t atrated voltage and at powerfactor of 15% are given in the electrical characteristics. For othervoltages, the clearing I2t isfound by multiplying bycorrection factor, K, givenas a function of appliedworking voltage, Eg, (rms).
Dimensions - mm (inches)
50.8(2.000")
15.5(0.610")
14.3(0.563")
Arc Voltage
This curve gives thepeak arc voltage, UL,which may appearacross the fuse duringits operation as a func-tion of the applied work-ing voltage, Eg, (rms) ata power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correction factor, Kp, isgiven as a function of theRMS load current, Ib, in %of the rated current.
Catalog NumbersElectrical Characteristics
Rated I2t (A2 Sec)Catalog Current Clearing WattsNumber Size RMS-Amps Pre-arc at 250V LossFWX-1A14F 14 x 51mm 1 — — —FWX-2A14F (9⁄16” x 2”) 2 — — —FWX-3A14F 3 — — —FWX-4A14F 4 — — —FWX-5A14F 5 1.6 13 1.3FWX-10A14F 10 3.6 24 3.4FWX-15A14F 15 14 83 3.8FWX-20A14F 20 33 200 4.6FWX-25A14F 25 58 300 5.3FWX-30A14F 30 100 500 5.9FWX-50A14F 50 200 1800 5.7• Watts loss provided at rated current.• (250Vdc/Interrupting rating 50kA) UL Recognition & CSA Component Acceptance on 5through 30A only. Consult Cooper Bussmann for additional ratings.• See accessories on page 211.
Features and Benefits• Excellent cycling capability and dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss in a compact size• Used with finger-safe holders/blocks
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
1.5
1.0
0.5
0.3
0.2
0.1575 125 300200 250
Eg
K
1)
2)
UL
1.41.2
103
800
600
500
400
300
20050 100 150 200 250
Eg
1)
2)
Kp1.00.8
0.4
0.50.6
0.3
0.2
0.130 40 50 60 70 80 90 100%
Ib
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
79 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Ferrule — FWX 250V (UL): 1-50A
High Speed Fuses
High SpeedFuses
Peak Let-Through Curve
FWX 1-30A: 250V (14 x 51mm)
Time-Current Curve
Data Sheet: 35785302
All-Inclusive Elevator DisconnectSimplifies Installation Plus aMultitude of Codes and Standards
When the Westin
Hotel chain reno-
vated the historic
Cupples Station in
downtown St.
Louis, the hotel’s
design-and-build
electrical contrac-
tor specified the
Cooper
Bussmann® Power Module™ elevator shunt trip
disconnect. The primary reason was the savings in
man-hours with everything in one box: the fire alarm,
control wiring and power wiring; all the parts needed
to interface with a fire alarm system in a UL 98
Listed assembly. In addition, all the codes and
standards surrounding the elevator disconnecting
means – electrical, elevator, fire alarm and the
sprinkler
system – are met, including ANSI/ASME A17.1,
NFPA 72, NEC® 620.62.
The contractor faced a unique situation when the
luxury hotel chain chose to revamp the old
warehouse versus tearing the structure down and
rebuilding. The hotel complex consists of four
buildings interconnected with walkways. A total of
eight elevators were installed with eight Power
Module switches, two per building. Each 30 HP
passenger elevator is fused with Cooper Bussmann®
Low-Peak® Class J LPJ-70SP fuses while each
40HP service elevator uses the Class J
LPJ-90SP fuses.
Did You Know?
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
80 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
*300% minimum opening current at rated voltage.**200% minimum opening current at rated voltage.• Consult Cooper Bussmann for dc ratings.• See accessories on page 211.
Features and Benefits• Excellent cycling capability and dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss in a compact size• Used with finger-safe holders/blocks
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
Application Engineering Services
Application Engineering assistance is available to all
customers. The Application Engineering team is
staffed by degreed electrical engineers and available
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
81 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Ferrule — FWH 500V: 0.25-30A
High Speed Fuses
High SpeedFuses
.2 .4 .6 .8 100 22 4 6 8 2101 2 4 6 8 2102
Prospective Current In Amperes RMS
2
46
2
64
2
64
2
64
2
64
2
64
10–1
10–2
4x10–3
100
101
102
103
104
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
FWH-002A6F
FWH-3.15A6F
FWH-005A6F
FWH-6.30A6F
FWH-001A6F
FWH-.500A6F
FWH-.250A6F
FWH-007A6F
FWH 0.25-7A: 500V (6 x 32mm)
Time-Current Curve
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
10–3
10–2
10–1
100
101
100
102
101
103
103 104102
104
FWH-12.5A6FFWH-016A6FFWH-020A6FFWH-025A6F
FWH 10-30A: 500V (6 x 32mm)Time-Current Curve
Data Sheet: 35785256 Data Sheet: 50955
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
82 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
The total clearing I2t at ratedvoltage and at power factorof 15% are given in the electrical characteristics. Forother voltages, the clearingI2t is found by multiplying bycorrection factor, K, given asa function of applied workingvoltage, Eg, (rms).
500400250100
1.5
1.0
0.5
0.3
0.2
0.15Eg
K
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuse during its operation as afunction of the applied working voltage, Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation of thepower losses at load currents lower than therated current. The correctionfactor, Kp, is given as afunction of the RMS loadcurrent, Ib, in % of the ratedcurrent.
• Watts loss provided at rated current.• See accessories on page 211.
Features and Benefits• Excellent cycling capability and dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss in a compact size• Used with finger-safe holders/blocks
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
UL
2.0
1.6
1.2
103
800
600
500
400
300100 400300200 500
Eg
�
Kp1.00.8
0.4
0.50.6
0.3
0.2
0.130 40 50 60 70 80 90 100%
Ib
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
83 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
84 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Agency Information: CE, UL Recognition: 6-32A. ULRecognition: 6-25A
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at ratedvoltage and at power factorof 15% are given in the electrical characteristics. Forother voltages, the clearingI2t is found by multiplying bycorrection factor, K, given asa function of applied workingvoltage, Eg, (rms).
Arc Voltage
This curve gives the peakarc voltage, UL, whichmay appear across thefuse during its operationas a function of theapplied working voltage,Eg, (rms) at a power factor of 15%.
Power Losses
Watts loss at rated current is given in theelectrical characteristics.The curve allows the calculation of the powerlosses at load currentslower than the rated current. The correctionfactor, Kp, is given as afunction of the RMS loadcurrent, Ib, in % of therated current.
• Watts loss provided at rated current.• See accessories on page 211.
Features and Benefits• Excellent cycling capability and dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss in a compact size• Used with finger-safe holders/blocks
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
500 600400250100
1.5
1.0
0.5
0.3
0.2
0.15Eg
K
UL
2.0
1.6
1.2
103
800
600
500
400
300400300200 500 600
Eg
�
Kp1.00.8
0.4
0.50.6
0.3
0.2
0.130 40 50 60 70 80 90 100%
Ib
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
85 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Ferrule — FWC 600V: 6-32A
High Speed Fuses
High SpeedFuses
103
104
102
10–1
10–2
10–3
10–4
101 22 4 6 8 2102 2 4 6 8 103
2
46
2
64
100
2
64
101
2
64
2
64
2
64
64
2
6
2
4
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
FWC-10A10F
FWC-30A10F & FWC-32A10F
FWC-20A10FFWC-25A10F
FWC-12A10FFWC-16A10F
FWC-8A10F FWC-6A10F
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
2
4
2
6
6
4
2
6
4
2 4 6 2 4 6 2 4 6 24 6101
102
103
104
101 102 103 104 105
FWC-6A10FFWC-8A10FFWC-10A10FFWC-12A10F
FWC-16A10FFWC-20A10FFWC-25A10F
FWC-30A10F & FWC-32A10F
Peak Let-Through Curve
FWC 6-32A: 600V (10 x 38mm)
Time-Current Curve
Data Sheet: 35785306
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
86 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
SpecificationsDescription: Ferrule style highspeed fuses with and without indicating striker.
Dimensions: See Dimensionsillustrations.
Ratings:Volts: — 690Vac (IEC)
— 700Vac (UL)
Amps: — 1-50A
IR: — 200kA RMS Sym.
— 50kA @700Vdc
Agency Information: CE, UL Recognition, CSAComponent Acceptance for versions without indicator only.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t atrated voltage and at powerfactor of 15% are given in the electrical characteristics. For othervoltages, the clearing I2t isfound by multiplying bycorrection factor, K, givenas a function of appliedworking voltage, Eg, (rms).
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage, Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correction factor, Kp, isgiven as a function of theRMS load current, Ib, in %of the rated current.
Features and Benefits• Excellent cycling capability and dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss in a compact size• Used with finger-safe holders/blocks
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
UL
1.41.2
103
6
87
9
5
4
3200 300 400 500 600 700
Eg
Kp1.00.8
0.4
0.50.6
0.3
0.2
0.130 40 50 60 70 80 90 100%
Ib
Data Sheets: E5781724 rev. B (without striker) 170K5342/43 (with striker)
K
1.41.2
1.0
0.6
0.80.7
0.9
0.5
0.4
0.3200 300 400 500 600 700
Eg
1)
2)
1) 5-30A Range2) 32-50A Range
50.8(2.000")
15.5(0.610")
14.3(0.563")
With Striker
Without Striker
FWP withstriker option.
Electrical Characteristics
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
87 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
88 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
SpecificationsDescription: Ferrule style highspeed fuses. with and withoutindicating striker.
Dimensions: See Dimensionsillustration.
Ratings:Volts: — 690Vac (IEC)
— 700Vac (UL)
Amps: — 20-100A
IR: — 200kA RMS Sym.
— 50kA @ 500Vdc
Agency Information: CE, UL Recognition
Electrical Characteristics
Total Clearing I2t
The total clearing I2t atrated voltage and at powerfactor of 15% are given in the electrical characteristics. For othervoltages, the clearing I2t isfound by multiplying bycorrection factor, K, givenas a function of appliedworking voltage, Eg, (rms).
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage, Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correction factor, Kp, isgiven as a function of theRMS load current, Ib, in %of the rated current.
Features and Benefits• Excellent cycling capability and dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss in a compact size• Used with finger-safe holders/blocks
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
K
1.41.2
1.0
0.6
0.80.7
0.9
0.5
0.4
0.3200 300 400 500 600 700
Eg
UL
1.41.2
103
6
87
9
5
4
3200 300 400 500 600 700
Eg
Kp1.00.8
0.4
0.50.6
0.3
0.2
0.130 40 50 60 70 80 90 100%
Ib
Data Sheets: E5781723 rev. B (without striker) 170K5344/45 (with striker)
58.0(2.283")
15.0(0.591")
22.2(0.875")
With Striker
Without Striker
FWP withstrikeroption.
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
89 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
90 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Ferrule — FWK 750V: 5-60A
High Speed Fuses
Dimensions - mm (inches)Fig. 1: 5-30A
146.05(5.75")
25.4(1")
20.64(0.813")
Fig. 2: 35-60A
127.0(5.000")
16.0(0.630")
20.5(0.807")
FWK 5-30A (20 x 127mm35-60A (25 x 146mm)
SpecificationsDescription: Ferrule style high speed fuses.
Features and Benefits• Excellent cycling capability and dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss in a compact size• Used with finger-safe holders/blocks
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
91 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
essential in maximizing the benefit of electronic com-
merce to the electrical distribution market. We’re
working hard to make doing business with Cooper
Bussmann easier. Some other electronic commerce
services we offer include:
• Industry Data Exchange Association (IDEA): We
are a charter member of IDEA, a foundation for
establishing standards for electronic
communications founded by members of NAED
and NEMA.
• Industry Data Warehouse (IDW)
• Electrical Industry Extranet (IDXchange)
• Socket to Socket
• Bar Coding: Cooper Bussmann product is coded
with the UCC-128 serialized shipping container bar
code to facilitate a distributor dock-to-stock and
pay from receipt process. We also offer customer-
specific bar coded shipments for distributors to
use in cross-docking and automated receiving and
stocking.
Did You Know?
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
92 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
The total clearing I2t atrated voltage and at powerfactor of 15% are given in the electrical characteristics. For othervoltages, the clearing I2t isfound by multiplying bycorrection factor, K, givenas a function of appliedworking voltage, Eg, (rms).
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage, Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correction factor, Kp, isgiven as a function of theRMS load current, Ib, in %of the rated current.
Catalog NumbersElectrical Characteristics
Rated I2t (A2 Sec)Catalog Current Clearing WattsNumbers Size RMS-Amps Pre-arc at 1000V LossFWJ-20A14F 14 x 67mm 20 25 220 9FWJ-25A14F (9⁄16” x 25⁄8”) 25 33 350 11FWJ-30A14F 30 52 450 14
• Watts loss provided at rated current.• See accessories on page 211.
Features and Benefits• Excellent cycling capability and dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss in a compact size• Used with finger-safe holders/blocks
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
1000800500200
1.5
1.0
0.5
0.3
0.2
0.15Eg
K
2000
1600
1200
800
400
200 600 1000 1400 1800
UL
Eg
Kp1.00.8
0.4
0.50.6
0.3
0.2
0.130 40 50 60 70 80 90 100%
Ib
Data Sheet: 720028
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
93 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Ferrule — FWJ 1000V: 20-30A
High Speed Fuses
High SpeedFuses
FWJ-20A14FFWJ-25A14FFWJ-30A14F
101 22 4 6 8 2102 2 4 6 8 103
2
46
2
64
2
64
2
64
2
64
2
64
64
2
6
2
4
10–4
100
101
10–1
10–2
10–3
102
103
104
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
FWJ 20-30A: 1000V (14 x 67mm)
Time-Current Curve
Pea
k Le
t-T
hrou
gh C
urre
nt
2
4
2
6
6
4
2
6
4
2 4 6 2 4 6 2 4 6 2 4 6101
102
103
104
101 102 103 104 105
FWJ-20A14FFWJ-25A14FFWJ-30A14F
2
Peak Let-Through Curve
Data Sheet: 35785315
Reduce Downtime with CooperBussmann® 24/7 Emergency After-Hours Service
When overloads or short circuits open the fuse and
there are no spares on the shelf, where do you turn
to get the production line back up, the trains running
or the elevators operating?
Customers pay only standard price for the required
circuit protection device, rush freight charges and a
$75.00 emergency fee for this door-to-door service.
No minimum order requirements.
No surcharges for drop shipments.
Call us at 314-995-1342 and we will:Set the Cooper Bussmann Customer Satisfaction
team in motion to do what it takes to satisfy your
needs.
Next flight out or next day service; your choice.
Did You Know?
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
94 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Ferrule — FWS/FWL 1000Vdc: 2-30A
High Speed Fuses
Dimensions - mm (inches)
127.0(5.000")
16.0(0.630")
20.5(0.807")
Indicating Version – Dimensions - mm (inches)
127.0(5.000")
16.0(0.630")
20.5(0.807")
2.0(0.079")
2.0
8.0(0.315")
FWL/FWS 2-30A: 1000Vdc 2-30A (20 x 127mm)
Time-Current Curve
FWS 2-15A (20 x 127mm)FWL 20-30A (20 x 127mm)
SpecificationsDescription: Ferrule style full rangefuses.
• ADD “I” to catalog number for indicating version.• Enclosed finger-safe fuse holder – CH127• Open style fuse block – 4530-OP• See accessories on page 211.
Features and Benefits• Excellent cycling capability and dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss in a compact size• Used with finger-safe holders/blocks
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters• Traction aux circuits• Capacitor protection
Data Sheet: 720040
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
95 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
Fuse Blocks
SpecificationsCatalog Symbol: J70100,
J70032
Description: Fuse blocks for 22 x 58mm & 14 x 51mmfuses.
Construction: Thermoplastic
Ratings:Volts: — 700Vac
Amps: — 32-100A
Withstand: — 200,000A RMS Sym.
Agency Information: CE, UL Recognized, Guide IZLT2,File E14853
Flammability Rating: UL 94V0
Catalog NumbersCatalog Fuse Max WireNumbers Size Amps Poles Size TerminationsJ70032-2CR 32 2 #2 Box Lug w/
J70032-3CR 32 3 #2 Retaining Clip
J70100-1CR 100 1 #2
J70100-2CR 22x58 100 2 #2
J70100-3CR 100 3 #2
Ferrule fuse accessories
Data Sheet:1151
Fuse Holders
SpecificationsCatalog Symbol: CHSeries
Description: DIN rail mountfuse holders for high speedfuses.
Agency Information: CE
North American 10 x 38Class CC: Listed UL 512,Guide IZLT, File E14853, Certified CSA Std. C22.2 No. 39,Class 6225 01, File 47235
North American 10 x 38 Midget: Recognized UL 512,Guide IZLT2, File E14853, Certified CSA Std. C22.2 No. 39,Class 6225 01, File 47235
European: 10 x 38 IEC 269-2-1, 14 x 51 IEC 269-2, 22 x 58IEC 269-2
Features and Benefits• 10 x 38 Dovetail design provides maximum flexibility in
assembling multiple poles• Finger-safe design - No exposed contacts• DIN rail mount (35mm) - Fits standard mounting rails• Optional open fuse indication lights tells fuse status at a
glance• Handle/fusepuller easily installs and removes fuses• Available in single and multi-pole configurations• Circuit marking system (P/N CH10CL and CH10CM)• Wire ready to save time as terminals are ready to accept
wires• CE marking
Typical Applications• Switchboard panel, control consoles, small motors,
transformers, and similar applications
Recommended Cooper Bussmann Fuse Types10 x 38 North American Class CC Fuses - LP-CC, FNQ-R,
KTK-R
10 x 38 North American Midget Fuses - FNQ, KTK, AGU,BAF, BAN, FNM, FWA, & FWC
14 x 51 Fuses - FWX, FWH, FWP & NON
22 x 58 Fuses - FWP
Data Sheet: 1211
Box Lug w/Retaining Clip
Web Services
www.cooperbussmann.comThe Cooper Bussmann® web site makes available
free information and other resources that include:
• Product Data Sheets for complete technical
information on Cooper Bussmann products
• Online catalogs for the latest United States and
European products
• Fuse Cross Reference to find the correct Cooper
Bussmann replacement for a competitive fuse
• Arc-Flash Calculator to determine the incident
energy level and flash protection boundary along
with the recommends the level of Personal
Protective Equipment (PPE)
Did You Know?
14x51
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
96 www.profuse.ir (021)6673 2943 , (021)6673 2945
212Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
97 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
High SpeedFuses
British BS 88 fuses
General Information
Designed and tested to:• BS 88: Part 4• IEC 269: Part 4• UL Recognized
Cooper Bussmann offers the industry’s widest range ofBritish style semiconductor fuses and accessories.
Cooper Bussmann® British style products use innovative arcquenching techniques and high grade materials to provide:
• Minimal energy let-through (I2t)• Excellent DC performance• Good surge withstand profile
British style fuses are typically found in equipment manufac-tured in the United Kingdom or British Commonwealth coun-tries. However, North American manufacturers have begun tospecify British style fuses — particularly in UPS applicationsat 240V or less — to take advantage of their size, perfor-mance and cost benefits.
Voltage Rating
All Cooper Bussmann British style fuses are tested to IEC269: Part 4. This standard requires a test voltage which is 5%higher than the rated voltage. In North America, fuses arerequired to clear only their rated voltage.
Accessories
Trip-indicator fuses are available for use in parallel with themain fuse. Indicator fuses can be attached to the associatedfuselink, or mounted separately in panel-mounted fuseclips.In addition, a push-on adapter and microswitch attachmentare available, to provide remote indication. Fuse blocks arealso available for most applications.
Introduction
British BS 88 ContentsFuse AmpVolts Range Page240 6-900 182-184690 6-710 185-188
AccessoriesIndicator System & Fuse Bases 189
British BS 88 Fuse Ranges
Amps Volts AC DC6-900 240 X —6-900 150 — X6-700 690 X —6-700 500 — X
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
98 www.profuse.ir (021)6673 2943 , (021)6673 2945
Arc Voltage
This curve gives the peakarc voltage, UL, which mayappear across the fuseduring its operation as afunction of the appliedworking voltage, Eg, (rms)at a power factor of 15%.
Power Losses
Watts loss at rated currentis given in the electricalcharacteristics. The curveallows the calculation ofthe power losses at loadcurrents lower than therated current. The correction factor, Kp, isgiven as a function of theRMS load current, Ib, in %of the rated current.
• Watts loss provided at rated current.• Note: 7LET, 10LET, 12LET and 16LET are available for replacement purposes on existingequipment.• See accessories on page 189.
Features and Benefits• Excellent cycling capability• Excellent dc performance• Low arc voltage and low
energy let-through (I2t)
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Agency Information: CE, Designed and tested to: BS 88Part 4, IEC 269 Part 4, UL Recognized. All fuses above havebeen tested at 318Vac. Consult Cooper Bussmann for specif-ic UL Recognition status.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at ratedvoltage and at power factorof 15% are given in the electrical characteristics. Forother voltages, the clearingI2t is found by multiplying bycorrection factor, K, given asa function of applied workingvoltage, Eg, (rms).
845931
83
38
25.4
13.5
10.3
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
10050 150 200 250
1)
2) Eg
K
845931
41
38.1
25.4
10.313.5
Fig. 3: LMTFig. 4: LMMT
Indicator (Optional)
1) LCT2) LET, LMT, LMMT
Kp1.00.8
0.4
0.50.6
0.3
0.2
0.130 40 50 60 70 80 90 100%
Ib
750
500
250
100 200 300
1)
2)
Eg
UL
1) LCT2) LET, LMT, LMMT
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
99 www.profuse.ir (021)6673 2943 , (021)6673 2945
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
British BS 88 — 240V: 6-900A
Peak Let-Through CurvePeak Let-Through Curve
LET 25-180A: 240V
Time-Current Curve
LCT 6-20A: 240V
Time-Current Curve
104
103
102
10–1
10–2
10–3
10–4
Prospective Current In Amperes RMS
Virt
ual P
re-A
rcin
g Ti
me
In S
econ
ds
2 4 6 8 101 22 4 6 8 2102 2 4 6 8 103
2
46
2
64
100
2
64
101
2
64
2
64
2
64
64
2
6
2
4
20LCT16LCT12LCT10LCT6LCT
104
103
102
101 22 4 6 8 2102 2 4 6 8 103
2
46
2
64
100
2
64
101
2
64
2
64
2
64
64
2
6
2
4
Prospective Current In Amperes RMS
Virt
ual P
re-A
rcin
g Ti
me
In S
econ
ds63LET50LET35LET32LET25LET
180LETa160LET125LET100LET 80LET
10–4
10–3
10–2
10–1
Prospective Short-Circuit Current Symmetrical RMS
101 1022 64 2 4 6103 2 4 6
104 2 4 6105
Pea
k Le
t-T
hrou
gh C
urre
nt
101
6
2
4
2
102
4
6
2
103
6
4
104
6
4
2
2
105
SYMMETRICAL FAULT
FULLY ASYMMETRICAL FAULT
20LCT16LCT12LCT10LCT 6LCT
25LET32LET35LET50LET63LET
80LET125 & 100LET
160LET & LMT200LMT180LET
250LMT315LMT355LMT
400 & 500LMMT450LMT
630LMMT710LMMT800LMMT900LMMT
Prospective Short-Circuit Current Symmetrical RMS
101 1022 64 2 4 6103 2 4 6
104 2 4 6105
Pea
k Le
t-T
hrou
gh C
urre
nt
101
6
2
4
2
102
4
6
2
103
6
4
104
6
4
2
2
105
SYMMETRICAL FAULT
FULLY ASYMMETRICAL FAULT
20LCT16LCT12LCT10LCT 6LCT
25LET32LET35LET50LET63LET
80LET125 & 100LET
160LET & LMT200LMT180LET
250LMT315LMT355LMT
400 & 500LMMT450LMT
630LMMT710LMMT800LMMT900LMMT
High Speed Fuses
High SpeedFuses
Data Sheet: 35785293Data Sheet: 35785296
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
British BS 88 — 240V: 6-900A
10–4
10–3
10–1
102
102 22 4 6 8 2103 2 4 6 8 104
2
46
2
64
100
2
64
101
2
64
2
64
2
64
64
2
6
2
4
104
315LMT
450LMT400LMT355LMT
250LMT200LMT160LMT
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
103
10–2
10–1
10–3
10–2
102
103
104
102 22 4 6 8 2103 2 4 6 8 104
2
46
2
64
100
2
64
101
2
64
2
64
2
64
64
2
6
2
4
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
10–4
710LMMT
900LMMT800LMMT
630LMMT500LMMT400LMMT
Prospective Short-Circuit Current Symmetrical RMS
101 1022 64 2 4 6103 2 4 6
104 2 4 6105
Pea
k Le
t-T
hrou
gh C
urre
nt
101
6
2
4
2
102
4
6
2
103
6
4
104
6
4
2
2
105
SYMMETRICAL FAULT
FULLY ASYMMETRICAL FAULT
20LCT16LCT12LCT10LCT 6LCT
25LET32LET35LET50LET63LET
80LET125 & 100LET
160LET & LMT200LMT180LET
250LMT315LMT355LMT
400 & 500LMMT450LMT
630LMMT710LMMT800LMMT900LMMT
Prospective Short-Circuit Current Symmetrical RMS
101 1022 64 2 4 6103 2 4 6
104 2 4 6105
Pea
k Le
t-T
hrou
gh C
urre
nt
101
6
2
4
2
102
4
6
2
103
6
4
104
6
4
2
2
105
SYMMETRICAL FAULT
FULLY ASYMMETRICAL FAULT
20LCT16LCT12LCT10LCT 6LCT
25LET32LET35LET50LET63LET
80LET125 & 100LET
160LET & LMT200LMT180LET
250LMT315LMT355LMT
400 & 500LMMT450LMT
630LMMT710LMMT800LMMT900LMMT
Peak Let-Through CurvePeak Let-Through Curve
LMMT 400-900A: 240V
Time-Current Curve
LMT 160-450A: 240V
Time-Current Curve
Data Sheet: 35785294 Data Sheet: 35785295
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
Agency Information: CE, Designed and tested to: BS 88Part 4, IEC 269 Part 4, UL Recognized. MT and MMT —350Vdc (IEC) rating. Consult Cooper Bussmann for ULRecognition status.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at ratedvoltage and at power factorof 15% are given in the electrical characteristics. Forother voltages, the clearingI2t is found by multiplying bycorrection factor, K, given asa function of applied workingvoltage, Eg, (rms).
This curve gives thepeak arc voltage, UL,which may appearacross the fuse during itsoperation as a functionof the applied workingvoltage, Eg, (rms) at apower factor of 15%.
Power Losses
Watts loss at rated current is given in theelectrical characteristics.The curve allows thecalculation of the powerlosses at load currentslower than the rated current. The correctionfactor, Kp, is given as afunction of the RMS loadcurrent, Ib, in % of therated current.
Features and Benefits• Excellent cycling capability• Excellent dc performance• Low arc voltage and low energy let-through (I2t)• Low watts loss
Typical Applications• DC common bus• DC drives• Power converters/rectifiers• Reduced voltage starters
1500
1000
500
200 400 600 660
Eg
UL
1)
2)
1) CT2) ET, FE, EET, FEE, FM, FMM
200 300 400 500 600 690
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1) 2)
Eg
K
1) CT, ET, EET, FE, FEE, MT, MMT2) FM, FMM
Kp1.00.8
0.4
0.50.6
0.3
0.2
0.130 40 50 60 70 80 90 100%
Ib
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
• Watts loss provided at rated current.• Note: FC, 8ET, 12ET, 15ET, 20ET, 65EET and 75EET are available for replacement purpos-es on existing equipment.• See accessories on page 189.
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
British BS 88 — 690V: 6-710A
High Speed Fuses
High SpeedFuses
103
104
102
10–1
10–2
2 4 6 8 102 22 4 6 8 2103 2 4 6 8 104
2
46
2
64
100
2
64
101
2
64
2
64
2
64
64
2
6
2
4
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
160EET140EET110EET90EET
200MT
355MT315MT280MT250MT
180MT160MT
10–4
10–3
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
2
4
2
6
6
4
2
4
6
4
2
6
4
2
6
2 4 6 2 4 6 2 4 6 2 4 6101
102
103
104
105
101 102 103 104 105 2
20CT16CT12CT10CT6CT
80ET63ET56ET45ET40ET35ET32ET25ET
710MMT630MMT560MMT500MMT450MMT
315MT 355MT 400MMT280MT 355MMT250MT 315MMT
280MMT 200MT
180MT 225MMT160MT 200MMT
180MMT
160EET140EET110EET90EET
Peak Let-Through Curve
EET 90-160A, MT 160-355A: 690V
Time-Current Curve
104
103
102
10–1
10–3
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
102 22 4 6 8 2103 2 4 6 8 104
2
46
2
64
100
2
64
101
2
64
2
64
2
64
64
2
6
2
4
280MMT
355MMT315MMT
225MMT200MMT180MMT
630MMT710MMT
560MMT500MMT450MMT400MMT
10–4
10–2
MMT 180-710A: 690V
Time-Current Curve
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
2
4
2
6
6
4
2
4
6
4
2
6
4
2
6
2 4 6 2 4 6 2 4 6 2 4 6101
102
103
104
105
101 102 103 104 105 2
20CT16CT12CT10CT6CT
80ET63ET56ET45ET40ET35ET32ET25ET
710MMT630MMT560MMT500MMT450MMT
315MT 355MT 400MMT280MT 355MMT250MT 315MMT
280MMT 200MT
180MT 225MMT160MT 200MMT
180MMT
160EET140EET110EET90EET
Peak Let-Through Curve
Data Sheet: 35785313 Data Sheet: 35785311
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High Speed Fuses
British BS 88 — 690V: 6-710A
104
103
102
10–1
10–2
10–3
10–4
102 22 4 6 8 2103 2 4 6 8 104
2
46
2
64
100
2
64
101
2
64
2
64
2
64
64
2
6
2
4
120FEE140FEE160FEE180FEE200FEE
100FEE
550FMM
700FMM630FMM
500FMM450FMM400FMM
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
FEE 100-200A & FMM 400-700A: 690V
Time-Current Curve
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
102 2 4 62
4
6
103
8
2
8
4
6
104
2
4
6
8
103 2 4 6104 2 4 6
105 2
180FEE
100FEE
120FEE
140FEE
160FEE
200FEE
400FMM
450FMM
500FMM
550FMM
630FMM
700FMM
Peak Let-Through Curve
103
102
10–1
10–2
10–4
2 4 6 8 102 22 4 6 8 2103 2 4 6 8 104
2
46
2
64
100
2
64
101
2
64
2
64
2
64
64
2
6
2
4
100FE
35FE40FE45FE50FE63FE71FE80FE90FE
350FM315FM280FM250FM220FM200FM180FM
Prospective Current In Amperes RMS
Vir
tual
Pre
-Arc
ing
Tim
e In
Sec
onds
10–3
104
FE 35-100A & FM 180-350A: 690V
Time-Current Curve
Prospective Short-Circuit Current Symmetrical RMS
Pea
k Le
t-T
hrou
gh C
urre
nt
2
4
2
6
6
4
2
6
4
2
6
4
2 4 6 2 4 6 2 4 6 2 4 6101
102
103
104
105
101 102 103 104 105 2
350FM315FM280FM250FM225FM200FM180FM
100FE90FE80FE71FE63FE50FE45FE40FE35FE
Peak Let-Through Curve
Data Sheet: 35785314 Data Sheet: 35785292
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
British BS 88 fuse accessories
Trip-indicator fuselinks are available for use in parallel withthe main fuselinks. They can either be attached to the associated fuselink or mounted separately in panel mountedfuse clips, Part No. CL1. A push-on adapter and microswitchattachment is available for use with the trip indicator to givethe facility of remote indication, reference MAI or MBI.
Fuse ratings of 20A and below cannot usually accommodatea trip fuselink in parallel.
Where trip indicator fuselinks are to be attached to the mainfuselink, an accessory pack comprising a pair of mountingclips and an appropriate trip indicator fuselink will berequired.
The ordering code references for these packs are listedbelow:
Fuse Type Order Ref. Fuse Type Order Ref.ET EC-600 FM MC-600EET EC-600 FMM MC-600FE EC-600 LMT MC-250FEE EC-600 LMMT MC-250LET EC-250
Dimensions & Fuselink Data (mm)Fuse Dim. ‘A’ Voltage Fuse Dim. ‘A’ VoltageType Max Rating Type Max RatingTI250 37.6 250 TI1100 98.4 1100TI500 47.5 500 TI1500 120.8 1500TI600 55.7 600 TI2000 147.5 2000TI700 61.8 700 TI2500 198.3 2500
6 21
A 0.8
6.35
6
2.8 2.4 3.65.2
5.2
21
3644 3.6
21
3644
9.5NC NC
NONO
Microswitch and Adapter Type MAICurrent Ratings:
ac 50/60Hz resistive load @ 250Vrms 4A
ac 50/60Hz resistive load @ 127Vrms 6A
Maximum Working Voltage:Contact-to-contact (rms) 1000V
Universal Fuse BlocksModular Max Max Fuse DataBase Voltage Amp Rating Sheet1BS101 600 100 12061BS102 600 400 12071BS103 600 400 12081BS104 600 600 1209
1mm = 0.0394” / 1” = 25.4mm
Trip Indicator
Universal and Stud Fuse Blocks
MAI or MBI
High Speed Fuses
High SpeedFuses
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
190Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
High SpeedFuses
General applications
Parallel Connection
When fuses are connected in parallel it is recommended thatthe applied voltage does not exceed 0.9 UN (the rated volt-age of the fuse). This is due to the fact that the energyreleased within the fuses may be unevenly shared betweenthe parallel connected barrels.
When fuses are connected in parallel, one must take intoaccount that the current sharing is not necessarily equal.And it must be checked, that the maximum load current isnot exceeded.
Series Connection
Fuses in series may not equally divide the applied voltage. Itis recommended that series connected fuses should only beoperated at fault currents that yield melting times less than10 ms and a recovery voltage per fuse of less than or equalto 0.9 UN (the rated voltage of the fuse).
Mounting Guidance
The recommendations below have to be followed whenmounting a Cooper Bussmann fuse with end plate threadedholes.
1. Screw in studs: 5 N•m Max, 3 N•m Min2. Attachment of the fuse to buss-bar by means of nut and
The design of Cooper Bussmann® fuses is such that theycan be operated under rather severe operating conditionsimposed by overloads (any load current in excess of themaximum permissible load current).
In applications, there will be a maximum overload current,Imax, which can be imposed on the fuse with a corresponding duration and frequency of occurrence.
Time durations fall into two categories:1. Overloads longer than one second2. Overloads less than one second termed “impulse” loads.
The following table gives general application guidelineswhich, in the expression Imax < (% factor) x It. It is the melt-ing current corresponding to the time “t” of the overload dura-tion as read from the time-current curve of the fuse. Theguidelines in the table below determine the acceptability ofthe selected fuses for a given Imax.
Frequency of Occurrence Overloads (> 1 sec) Impulse Loads (< 1 sec)Less than once per month Imax < 80% x It Imax < 70% x ItLess than twice per week Imax < 70% x It Imax < 60% x ItSeveral times per day Imax < 60% x It —
When impulse loads are an intrinsic/normal parameter of theload current either as single pulse or in trains of pulses orwhen their level is higher than the melting current at 0.01seconds (per time-current curve), contact Cooper Bussmannfor application assistance.
In addition to the parameters set forth in the preceding table,the RMS value of the load current as calculated for any period of 10 minutes or more should not exceed the maxi-mum permissible load current.
Furthermore, it is important that a fuse should not be appliedin the non-continuous/dashed portion of the associated time-current curve.
Any time-current combination point which falls in the non-continuous/dashed portion of the time-current curve isbeyond the capability of the fuse to operate properly.
DC Operation
Depending upon the short-circuit time constant and the mag-nitude of the prospective short-circuit current, the dc voltageat which a fuse can be applied may be less than its ac rating.Long time constants require a lower dc voltage. Conversely,however, higher available prospective short-circuit currentsresult in faster fuse openings and thus permit a fuse to beoperated at a higher dc voltage.
Consult Cooper Bussmann for additional information andapplication assistance when fuses have to operate under dcconditions.
Load Current Versus
Conductor Cross
Section
Reduction of permissibleload current when theconductor cross section isless than that given in IECPublication 269-1 & 4valid for CooperBussmann semiconductorfuses.
Application Assistance
If you have application problems or need a fuse outside ourstandard program, please contact the nearest CooperBussmann representative. Phone numbers are shown on theback cover.
1.0
0.9
0.8
0.5 0.6 0.7 0.8 0.9 1.0≈ (IEC cross section)
Reduction Factor