GE Industrial Systems Record Plus Current Limiting Molded Case Circuit Breakers INDUSTRIAL Catalog/Selection Guide
12
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Catalogo Recordplus General Electric

GE Industrial Systems

Record Plus™

Current LimitingMolded Case Circuit Breakers

INDUSTRIAL

Catalog/Selection Guide

Page 2: Catalogo Recordplus General Electric

1

F C N 3 6 TE 050 R

Frame Rating Interruption Voltage Rated

Family (Amperes) Capacity Poles Rating Type Current (A) Connection

F = Record C = 100 S = 25kA 3 = 3 Poles 4 = 480V TE = Fixed Thermal 003 – 100 R = Standard,

Plus V = 35kA 32 = 2 poles 6 = 600V Magnetic No Lugs

N = 65kA in 3-pole MH = Mag Break, R1 = Line and Load

H = 100 kA envelope 7X-20X Lugs Installed

L = 150kA ML = Mag Break, R2 = Load Lugs Installed

Y = Switch 3X-15X R3 = Line Lugs Installed

Main Standards

UL 489

IEC 947 and Associated EN Sections

Other Global Standards – Pending

BS JIS (Japan)

Bureau Vertitas KEMA

CCIB (China) NOM of Shipping

CEI RINA

CSA (Canada) UTE

Det Norske Veritas VDE

Standards

Catalog Number Structure

➊ Breaker Frame Rating

➋ Rated Voltage

➌ Breaker Frame Enclosed Rating

➍ Product Description

➎ Standards

➏ Interruption Capacity

➐ Catalog Number

➊➋ ➌

INTRODUCTION

Page 3: Catalogo Recordplus General Electric

A

B

C

D

E E

H

G F

Dimensions

2

FC 100 Amp Frame Overview

Interrupting RatingsFederal Spec C/B Class WC-375B

Trip Unit RatedCurrent (A)

Availability by Interrupting RatingsCode (see Catalog Number Structure)

Thermal Magnetic Mag Break®

3 — S,N

7 — S,N

15 S,V,N,H,L S,N

20 S,V,N,H,L —

25 S,V,N,H,L —

30 S,V,N,H,L S,N

35 S,V,N,H,L —

40 S,V,N,H,L —

45 S,V,N,H,L —

50 S,V,N,H,L S,N

60 S,V,N,H,L —

70 S,V,N,H,L —

80 S,V,N,H,L —

90 S,V,N,H,L —

100 S,V,N,H,L S,N

Trip Units

FrameA B C D E F G H

in mm in mm in mm in mm in mm in mm in mm in mm

FC 3.7 29.1 3.2 81.3 .96 24.4 3.0 76.2 1.0 25.4 6.4 162.6 5.0 127.0 1.0 25.4

Type AmpereRating

No.Poles Max AC/DC Voltage

UL Listed Interrupting Ratings - rms Symmetrical Amperes (in Thousands)

IEC Listed Interrupting Ratings, Icu, Amperes (in Thousands)

AC Voltage DC Voltage AC Voltage DC Voltage

240 480 600 250 (2p) 500 (3p) 220-240 400-415 500 250 (2p) 500 (3p)

FCS 15-100 2,3 600Vac, 500Vdc 42 25 18 22 30 36 22 14 22 30

FCV 15-100 2,3 600Vac, 500Vdc 65 35 22 25 35 50 30 18 25 35

FCN 15-100 2,3 600Vac, 500Vdc 150 65 25 30 42 85 50 22 30 42

FCH 15-100 2,3 600Vac, 500Vdc 200 100 35 42 65 100 80 36 42 65

FCL 15-100 2,3 600Vac, 500Vdc 200 150 42 65 80 200 150 50 65 80

www.GEindustrial.com

Page 4: Catalogo Recordplus General Electric

3

Record Plus, Standard Fixed Thermal Magnetic, 600 Vac, HACR Rated

Ampere Rating2-Pole 3-Pole Lug Kit ❶

Cat. No. List Price, GO-135H Cat. No. List Price, GO-135H Cat. No. List Price, GO-135H

25kA

15 FCS326TE015R2 $645.00 FCS36TE015R2 $747.00 — —20 FCS326TE020R2 645.00 FCS36TE020R2 747.00 — —25 FCS326TE025R 636.00 FCS36TE025R 738.00 FCALK13 $9.0030 FCS326TE030R 636.00 FCS36TE030R 738.00 FCALK13 9.0035 FCS326TE035R 636.00 FCS36TE035R 738.00 FCALK13 9.0040 FCS326TE040R 636.00 FCS36TE040R 738.00 FCALK13 9.0045 FCS326TE045R 636.00 FCS36TE045R 738.00 FCALK13 9.0050 FCS326TE050R 636.00 FCS36TE050R 738.00 FCALK13 9.0060 FCS326TE060R 636.00 FCS36TE060R 738.00 FCALK13 9.0070 FCS326TE070R 740.00 FCS36TE070R 840.00 FCALK14 9.0080 FCS326TE080R 740.00 FCS36TE080R 840.00 FCALK14 9.0090 FCS326TE090R 740.00 FCS36TE090R 840.00 FCALK14 9.00100 FCS326TE100R 740.00 FCS36TE100R 840.00 FCALK14 9.00

35kA

15 FCV326TE015R2 705.00 FCV36TE015R2 807.00 — —20 FCV326TE020R2 705.00 FCV36TE020R2 807.00 — —25 FCV326TE025R 696.00 FCV36TE025R 798.00 FCALK13 9.0030 FCV326TE030R 696.00 FCV36TE030R 798.00 FCALK13 9.0035 FCV326TE035R 696.00 FCV36TE035R 798.00 FCALK13 9.0040 FCV326TE040R 696.00 FCV36TE040R 798.00 FCALK13 9.0045 FCV326TE045R 696.00 FCV36TE045R 798.00 FCALK13 9.0050 FCV326TE050R 696.00 FCV36TE050R 798.00 FCALK13 9.0060 FCV326TE060R 696.00 FCV36TE060R 798.00 FCALK13 9.0070 FCV326TE070R 821.00 FCV36TE070R 921.00 FCALK14 9.0080 FCV326TE080R 821.00 FCV36TE080R 921.00 FCALK14 9.0090 FCV326TE090R 821.00 FCV36TE090R 921.00 FCALK14 9.00100 FCV326TE100R 821.00 FCV36TE100R 921.00 FCALK14 9.00

65kA

15 FCN326TE015R2 776.00 FCN36TE015R2 868.00 — —20 FCN326TE020R2 776.00 FCN36TE020R2 868.00 — —25 FCN326TE025R 757.00 FCN36TE025R 859.00 FCALK13 9.0030 FCN326TE030R 757.00 FCN36TE030R 859.00 FCALK13 9.0035 FCN326TE035R 757.00 FCN36TE035R 859.00 FCALK13 9.0040 FCN326TE040R 757.00 FCN36TE040R 859.00 FCALK13 9.0045 FCN326TE045R 757.00 FCN36TE045R 859.00 FCALK13 9.0050 FCN326TE050R 757.00 FCN36TE050R 859.00 FCALK13 9.0060 FCN326TE060R 757.00 FCN36TE060R 859.00 FCALK13 9.0070 FCN326TE070R 901.00 FCN36TE070R 1001.00 FCALK14 9.0080 FCN326TE080R 901.00 FCN36TE080R 1001.00 FCALK14 9.0090 FCN326TE090R 901.00 FCN36TE090R 1001.00 FCALK14 9.00100 FCN326TE100R 901.00 FCN36TE100R 1001.00 FCALK14 9.00

100kA

15 FCH326TE015R2 1202.00 FCH36TE015R2 1304.00 — —20 FCH326TE020R2 1202.00 FCH36TE020R2 1304.00 — —25 FCH326TE025R 1193.00 FCH36TE025R 1295.00 FCALK13 9.0030 FCH326TE030R 1193.00 FCH36TE030R 1295.00 FCALK13 9.0035 FCH326TE035R 1193.00 FCH36TE035R 1295.00 FCALK13 9.0040 FCH326TE040R 1193.00 FCH36TE040R 1295.00 FCALK13 9.0045 FCH326TE045R 1193.00 FCH36TE045R 1295.00 FCALK13 9.0050 FCH326TE050R 1193.00 FCH36TE050R 1295.00 FCALK13 9.0060 FCH326TE060R 1193.00 FCH36TE060R 1295.00 FCALK13 9.0070 FCH326TE070R 1488.00 FCH36TE070R 1588.00 FCALK14 9.0080 FCH326TE080R 1488.00 FCH36TE080R 1588.00 FCALK14 9.0090 FCH326TE090R 1488.00 FCH36TE090R 1588.00 FCALK14 9.00100 FCH326TE100R 1488.00 FCH36TE100R 1588.00 FCALK14 9.00

150kA

15 FCL326TE015R2 1638.00 FCL36TE015R2 1740.00 — —20 FCL326TE020R2 1638.00 FCL36TE020R2 1740.00 — —25 FCL326TE025R 1629.00 FCL36TE025R 1731.00 FCALK13 9.0030 FCL326TE030R 1629.00 FCL36TE030R 1731.00 FCALK13 9.0035 FCL326TE035R 1629.00 FCL36TE035R 1731.00 FCALK13 9.0040 FCL326TE040R 1629.00 FCL36TE040R 1731.00 FCALK13 9.0045 FCL326TE045R 1629.00 FCL36TE045R 1731.00 FCALK13 9.0050 FCL326TE050R 1629.00 FCL36TE050R 1731.00 FCALK13 9.0060 FCL326TE060R 1629.00 FCL36TE060R 1731.00 FCALK13 9.0070 FCL326TE070R 2075.00 FCL36TE070R 2175.00 FCALK14 9.0080 FCL326TE080R 2075.00 FCL36TE080R 2175.00 FCALK14 9.0090 FCL326TE090R 2075.00 FCL36TE090R 2175.00 FCALK14 9.00100 FCL326TE100R 2075.00 FCL36TE100R 2175.00 FCALK14 9.00

❶ Record Plus 15-20 amp circuit breakers come with load lugs factory installed.

SELECTION AND PRICING

Page 5: Catalogo Recordplus General Electric

4

Record Plus, MagBreak®, 7X-20X Pick Up, 600 Vac

Record Plus MagBreak®, 3X-15X Pick Up, 600 Vac

AmpereRating

InstantaneousAdj. Range 2-Pole 3-Pole Lug Kit (3 per kit) ❶

Low High Cat. No. List Price, GO-141H Cat. No. List Price, GO-141H Cat. No. List Price, GO-141H

25kA

3 21 60 FCS326MH003R1 $554.00 FCS36MH003R1 $656.00 — —

7 49 140 FCS326MH007R1 554.00 FCS36MH007R1 656.00 — —

15 105 300 FCS326MH015R1 554.00 FCS36MH015R1 656.00 — —

30 210 600 FCS326MH030R 536.00 FCS36MH030R 638.00 FCALK13 $9.00

50 350 1000 FCS326MH050R 536.00 FCS36MH050R 638.00 FCALK13 9.00

65kA

3 21 60 FCN326MH003R1 617.00 FCN36MH003R1 719.00 — —

7 49 140 FCN326MH007R1 617.00 FCN36MH007R1 719.00 — —

15 105 300 FCN326MH015R1 617.00 FCN36MH015R1 719.00 — —

30 210 600 FCN326MH030R 599.00 FCN36MH030R 701.00 FCALK13 9.00

50 350 1000 FCN326MH050R 599.00 FCN36MH050R 701.00 FCALK13 9.00

❶ Record Plus 3-15 amp circuit breakers come with line and load lugs factory installed.

AmpereRating

InstantaneousAdj. Range 2-Pole 3-Pole Lug Kit (3 per kit) ❶

Low High Cat. No. List Price, GO-141H Cat. No. List Price, GO-141H Cat. No. List Price, GO-141H

25kA

3 9 45 FCS326ML003R1 $481.00 FCS36ML003R1 $599.00 — —

7 21 105 FCS326ML007R1 481.00 FCS36ML007R1 599.00 — —

15 45 225 FCS326ML015R1 481.00 FCS36ML015R1 599.00 — —

30 90 450 FCS326ML030R 463.00 FCS36ML030R 581.00 FCALK13 $9.00

50 150 750 FCS326ML050R 463.00 FCS36ML050R 581.00 FCALK13 9.00

100 300 1500 FCS326ML100R 549.00 FCS36ML100R 650.00 FCALK14 9.00

65kA

3 9 45 FCN326ML003R1 554.00 FCN36ML003R1 656.00 — —

7 21 105 FCN326ML007R1 554.00 FCN36ML007R1 656.00 — —

15 45 225 FCN326ML015R1 554.00 FCN36ML015R1 656.00 — —

30 90 450 FCN326ML030R 536.00 FCN36ML030R 638.00 FCALK13 9.00

50 150 750 FCN326ML050R 536.00 FCN36ML050R 638.00 FCALK13 9.00

100 300 1500 FCN326ML100R 640.00 FCN36ML100R 742.00 FCALK14 9.00

❶ Record Plus 3-15 amp circuit breakers come with line and load lugs factory installed.

www.GEindustrial.com

Page 6: Catalogo Recordplus General Electric

5

Record Plus, Non-Automatic Circuit Breaker (Molded Case Switch), 600Vac

Internal Accessories (supplied with leads attached)Contacts – Auxiliary and Bell Alarm

Ampere Rating2-Pole 3-Pole Lug Kit (3 per kit)

Cat. No. List Price, GO-135H Cat. No. List Price, GO-135H Cat. No. List Price, GO-135H

60 FCY206D060R $345.00 FCY306D060R $445.00 FCALK13 $9.00

100 FCY206D100R 345.00 FCY306D100R 445.00 FCALK14 9.00

External AccessoriesElectrical Operator Motor Drives, Front Mounted

Voltage Cat. No. List Price, GO-135H

120V AC/125V DC FCEMF3 $710.00220/240V AC, 50/60 Hz FCEMF6 710.00

24V DC FCEMFD 710.0048V DC FCEMFF 710.00

Type Description Cat. No. List Price, GO-135H

Base Only

3 Pole - LSL - Horizontal Strap FCDDF1 $250.003 Pole - SLS - Horizontal Strap FCDDF2 250.00

3 Pole - LSL - Vertical Strap FCDDF3 250.003 Pole - SLS - Vertical Strap FCDDF4 250.00

Secondary DisconnectSecondary Disconnect Kit FCDSD 185.00

Secondary Disconnect - Base Part FCDSDP 50.00Secondary Disconnect - Breaker Part FCDSDB 50.00

Mounting Plate Mounting Plate FCDMP 40.00

Padlocking DevicesDescription Cat. No. List Price, GO-135H

Padlocking FixedToggle FC1PF $8.70

Padlocking EuserecToggle FC1PE 32.00

Plug-in Types

Accessory Ratings

Normally Open Normally Closed Form C

Cat. No. List Price, GO-135H Cat. No. List Price,

GO-135H Cat. No. List Price, GO-135H

Aux. Switch RightMounted

5A@240Vac,0.5A@125Vdc FAS10RW $149.00 FAS01RW $149.00 FASH11RW $295.00

Aux. Switch LeftMounted

5A@240Vac,0.5A@125Vdc FAS10LW 149.00 FAS01LW 149.00 FASH11LW 295.00

Aux. Switch RightMounted Gold Contacts 0.5A@30V — — — — FAS11RGW 295.00

Aux. Switch LeftMounted Gold Contacts 0.5A@30V — — — — FAS11LGW 295.00

Bell Alarm Mechanism 5A@240Vac,0.5A@125Vdc FABAM10W 154.00 FABAM01W 154.00 FABAM11W 154.00

Bell Alarm MechanismGold Contacts 0.5A@30V — — — — FABAM11GW 295.00

Releases – Shunt Trip and Undervoltage

Voltage

Shunt Trip Undervoltage Release

Rating (Inrush Power Consumption Cat. No.

List Price,GO-135H

Rating (Inrush Power Consumption Cat. No. List Price,

GO-135H

12V DC 200 mA / 2.4W FASHTBW $363.00 — — —24V AC/DC 100 mA / 3.6W FASHTDW 363.00 50 mA / 1.2W FAUVRDW $363.0048V AC/DC 60 mA / 2.88W FASHTFW 363.00 20 mA / 0.96W FAUVRFW 363.00

120V AC 40 mA / 4.8W FASHTKW 363.00 15 mA / 1.8W FAUVRKW 363.00110/130V AC/DC 40 mA / 4.8W FASHTJW 363.00 15 mA / 1.8W FAUVRJW 363.00

220/240V AC, 250V DC 20 mA / 4.6W FASHTNW 363.00 15 mA / 3.45W FAUVRNW 363.00400/480V AC 20 mA / 8.4W FASHTUW 363.00 15 mA / 6.3W FAUVRUW 363.00

SELECTION AND PRICING

Page 7: Catalogo Recordplus General Electric

6

Type Description Cat. No. List Price, GO-135H

Single Lugs for Use with Cu or Al Cables

15-20A FCAL12 $3.00

25-60A FCAL13 3.00

70-100A FCAL14 3.00

Lug Kits (Set of 3) for Use with Cu or Al Cables

15-20A FCALK12 9.00

25-60A FCALK13 9.00

70-100A FCALK14 9.00

Single Lugs for Use with Cu Cables25-60A FCO13 3.00

70-100A FCO14 3.00

Lug Kits (Set of 3) for Use with Cu Cables25-60A FCOLK13 9.00

70-100A FCOLK14 9.00

Mounting Screws for Mounting Plates with Tapped Holes (4 screws and lockwashers) 8-32 x 2 7/8 FCMSK3 6.10

Mounting Screws for Mounting Plates with Clearance Holes (4 screws, lockwashers and nuts) 8-32 x 3 FCMSK4 6.10

Nut PlatesKit of 3 FCNP3 2.10

Bulk Pack of 36 FCNPB 25.20

Back Connected StudsShort FCBCS1 28.00

Long FCBCS2 31.50Line Voltage Tab FCAL18LV 6.60

Hardware kitsFor Wire Ranges, See Page 8

Type Description Cat. No. List Price GO Schedule

STDA Flange HandleOperators

Breaker Mechanism Breaker Mechanism FCNBM $96.00 GO-144H

Flange Mounted Handle Mechanismfor Cable Operator

6 inches for NEMA 1, 3R, 12,13 FCNHM1 188.00 GO-144H 10 inches for NEMA 1, 3R, 12,13 FCNHM2 280.00 GO-144H 6 inches for NEMA 4/4X FCNHM3 258.00 GO-144H 10 inches for NEMA 4/4X FCNHM4 373.00 GO-144H

Operating Cable

3 feet SC3L 91.00 GO-144A4 feet SC4L 108.00 GO-144A5 feet SC5L 119.00 GO-144A6 feet SC6L 134.00 GO-144A7 feet SC7L 148.00 GO-144A8 feet SC8L 163.00 GO-144A9 feet SC9L 196.00 GO-144A10 feet SC10L 211.00 GO-144A

STDA FlangeHandles &Hardware Kits

Flange Handle for Variable Depth Operating Mechanism

Same as Spectra: 6-inch for NEMA 12/13 STDA1 82.50 GO-144ASame as Spectra: 10-inch for NEMA 12/13 STDA2 94.50 GO-144ASame as Spectra: 6-inch for NEMA 4/4X STDA1X 148.00 GO-144ASame as Spectra: 10-inch for NEMA 4/4X STDA2X 165.00 GO-144A

Flange Operating Mechanism Operating Mechanism Only FCNFM 67.00 GO-144H Flange Stiffener Kit Use with FCNFM TDSR 29.50 GO-144AExtender Kit Use with FCNFM TDSR 29.50 GO-144AExtended Drive Stud Use with FCNFM TDS1 29.50 GO-144ADoor Hardware Kit NEMA12/13 Door Hinged on Left, NEMA 12/13, 2-point Kit TDV1 134.00 GO-144ADoor Hardware Kit NEMA 4/4X Door Hinged on Left, NEMA 4/4X, 2-point Kit TDV1X 174.00 GO-144AThird Point Latch Kit For Use With TDV1/TDV1X Above TDV3 29.50 GO-144ADoor Hardware Kit NEMA12/13 Door Hinged on Right, NEMA 12/13 2-point Kit TDV1L 134.00 GO-144ADoor Hardware Kit NEMA 4/4X Door Hinged on Right, NEMA 4/4X, 2-point Kit TDV1LX 174.00 GO-144AThird Point Latch Kit For Use with TDV1L, TDC1LX Above TDV3L 29.50 GO-144A

Auxiliary ContactKits

DPDT for STDA Handle on Right TDAS1L2 134.00 GO-144ADPDT for STDA Handle on Left TDAS1R2 134.00 GO-144A

TDR Style RotaryHandles

Vertical Mount FCNRC 65.50 GO-144H

Horizontal Mount FCNRD 65.50 GO-144H

Door Ring Gasket Door Ring-Interlock FCFRDRCK 11.25 GO-144H

Door Gasket Kit SEFRGSK 4.00 GO-144A

TDM Style RotaryHandles

Direct Mount Complete Kit for NEMA 1, 3R, 12 FCNRN 79.00 GO-144H

Direct Through Door Complete Kit for NEMA 1, 3R, 12 FCNRT 79.00 GO-144H

Variable Mount Complete Kit for NEMA 1, 3R, 12 FCNRV 102.00 GO-144H

Operating Mechanism Only

For NEMA 1, 3R, 12, 4 and 3/16 FCNRM1 52.00 GO-144H

For NEMA 4/4X, 4 and 3/16 FCNRM2 52.00 GO-144H

For NEMA 1, 3R, 12, 6 and 1/8 - 15 FCNRM3 52.00 GO-144H

For NEMA 4/4X, 6 and 1/8 - 15 FCNRM4 52.00 GO-144H

Handle OnlyFor NEMA 1, 3R, 12 FNRH 27.00 GO-144H

For NEMA 4/4X THCH45 303.00 GO-144A

Handles and Handle Accessories

www.GEindustrial.com

Page 8: Catalogo Recordplus General Electric

7

Selection Factors

Selection Factor A. Cable SizeApplied Cable Cross Section Area as a Percent of Rated Cable Size Cross Sectional Area

Selection Factor B. Ambient Temperature

Selection Factor C. Operating Frequency

Selection Factor D. Altitude

Selection Factor E. Total Load Class ❶

❶ The total load class Factor E is the product of all the load class factors that apply to the circuit under consideration.❷ Refer to NEC Article 430, Part II and Table 430.22E for conductor and circuit breaker frame sizing.

Selection Factor F. SafetyA safety factor of 10% is equivalent to a current rating multiplier of 1.10.

Selection Factor G. Duty Rating

Duty Rating Continuous Duty (Operation at constant load formore than three hours)

Intermittent Duty (Operation at constant load forthree hours, or less)

Selection Factor G 1.25 1.00

Total Load Class Group Mounted (12 ormore Breakers)

SwitchingCapacitors

SwitchingElectromagnets

Single Motor BranchCircuit Protection

(Normal Duty)

Single Motor BranchCircuit Protection

(Heavy Duty)

All Other (NormalLoads)

Selection Factor E 1.10 1.50 1.50 1.25 ❷ 1.00

Installation AltitudeSelection Factor D

Feet Meters

-100 to 6,000 -30 to 1,800 1.00

6,001 to 10,000 1,801 to 3,000 1.04

10,000+ 3,000+ Consult GE

Circuit BreakerType

Max. RatingAmperes

Selection Factor C, Frequency at

50-60 Hz 100-120 Hz 150-180 Hz 200-240 Hz 300-360 Hz 400-415 Hz

FC 100 1.00 1.00 1.00 1.00 1.00 1.00

Frame Size

Circuit Breaker or Switch Ambient Temperature

25°C (77°F) 40°C (104°F) 50°C (122°F) 60°C (140°F) 70°C (158°F)

Factor BMin. CableInsulationRating, °C

Factor BMin. CableInsulationRating, °C

Factor BMin. CableInsulationRating, °C

Factor BMin. CableInsulationRating, °C

Factor BMin. CableInsulationRating, °C

FC 1.0 60 1.0 60 1.0 105 1.10 110 1.30 120

Percent 50 60 70 80 90 100 125 150 200

Cable Size Selection Factor A 1.40 1.25 1.15 1.07 1.03 1.00 0.99 0.97 0.97

APPLICATION INFORMATION

Page 9: Catalogo Recordplus General Electric

8

Device AmpereRating

Copper ConductorAluminum or Copper Clad Aluminum

Conductor

Paralleled Size Paralleled Size

≤15 14 AWG 12 AWG20 12 AWG 10 AWG25 10 AWG 10 AWG30 10 AWG 8 AWG35 8 AWG 8 AWG40 8 AWG 8 AWG45 8 AWG 6 AWG50 8 AWG 6 AWG60 6 AWG 4 AWG70 4 AWG 3 AWG80 4 AWG 2 AWG90 3 AWG 2 AWG100 3 AWG 1 AWG110 2 AWG 1/0 AWG125 1 AWG 2/0 AWG150 1/0 AWG 3/0 AWG175 2/0 AWG 4/0 AWG200 3/0 AWG 250 kcmil225 4/0 AWG 300 kcmil250 250 kcmil 350 kcmil275 300 kcmil 500 kcmil300 350 kcmil 500 kcmil325 400 kcmil Two 4/0 AWG350 500 kcmil Two 4/0 AWG400 Two 3/0 AWG Two 250 kcmil450 Two 4/0 AWG Two 300 kcmil500 Two 250 kcmil Two 350 kcmil550 Two 300 kcmil Two 500 kcmil600 Two 350 kcmil Two 500 kcmil

Cable & Conductor DataCable Size by Circuit Breaker or Switch Amp Rating

Wire Range & Terminal TorqueLug Catalog Number Frame Amps

Wire Range (75oC Insulated Conductor) TorqueCU AL Line Load

FCAL12 3, 7, 15, 20 #12-14 #10-#12 25-32 lb-in #12: 35 lb-inFCAL13 25-60 #10-#6 #8-#4 25-32 lb-in #10: 35 lb-in / #8: 40lb-in / #6 & #4: 45 lb-inFCAL14 70-100 #4-#1 #2-1/0 25-32 lb-in #4-1/0: 45 lb-inFCO13 25-60 #10-#6 #8-#4 25-32 lb-in #10: 35 lb-in / #8: 40lb-in / #6&#4: 45 lb-inFCO14 70-100 #4-#1 #2-1/0 25-32 lb-in #4-1/0: 45 lb-in

Properties of Conductors Rated for Use with Molded Case Circuit Breakers

AWG or kcmil Size Equivalent Cross Section (mm2) ISO Metric Cable Size (mm2)

18 0.82 0.751

16 1.3 1.514 2.1 2.512 3.3 410 5.3 68 8.4 106 13.3 164 21.2 252 33.6 35

1/0 53.5 502/0 67.4 703/0 85 954/0 107.2250 127 120300 152 150350 177 185500 253 240600 304 300

Approximate Correlation of Standard Cross Sections ofRound Copper Conductors (AWG and kcmil) versus ISOMetric Cable Sizes

www.GEindustrial.com

Size (AWGor kcmil)

AreaConductors Direct-Current Resistance at 75°C (167°F)

Stranding Overall CopperAluminum

QuantityDiameter Diameter Area Uncoated Coated

mm2 CircularMils mm in mm in mm2 in2 ohm/km ohm/kFT ohm/km ohm/kFT ohm/km ohm/kFT

14 2.08 4110 1 1.630 0.064 2.08 0.003 10.1 3.07 10.4 3.19 16.6 5.0614 2.08 4110 7 0.620 0.024 1.850 0.073 2.68 0.004 10.3 3.14 10.7 3.26 16.9 5.1712 3.31 6530 1 2.050 0.081 3.31 0.005 6.34 1.93 6.57 2.01 0.222 3.1812 3.31 6530 7 0.780 0.030 2.320 0.092 4.25 0.006 6.50 1.98 6.73 2.05 0.145 3.2510 5.261 10380 1 2.588 0.102 5.26 0.008 3.984 1.21 4.148 1.26 6.651 2.0010 5.261 10380 7 0.980 0.038 2.950 0.116 6.76 0.011 4.070 1.24 4.226 1.29 6.679 2.048 8.367 16510 1 3.264 0.128 8.37 0.013 2.506 0.764 2.579 0.786 4.125 1.268 8.367 16510 7 1.230 0.490 3.710 0.146 10.76 0.017 2.551 0.778 2.653 0.809 4.204 1.286 13.3 26240 7 1.560 0.061 4.670 0.184 17.09 0.027 1.608 0.491 1.671 0.510 2.652 0.8084 21.15 41740 7 1.960 0.077 5.890 0.232 27.19 0.042 1.010 0.308 1.053 0.321 1.666 0.5083 26.67 52620 7 2.200 0.087 6.600 0.260 34.28 0.053 0.802 0.245 0.833 0.254 1.320 0.4032 33.62 66360 7 2.470 0.097 7.420 0.292 43.23 0.067 0.634 0.194 0.661 0.201 1.045 0.3191 42.41 83690 19 1.690 0.066 8.430 0.332 55.80 0.087 0.505 0.154 0.524 0.160 0.829 0.253

1/0 53.49 105600 19 1.890 0.074 9.450 0.372 70.41 0.109 0.399 0.122 0.415 0.127 0.660 0.2012/0 67.43 133100 19 2.130 0.084 10.620 0.418 88.74 0.137 0.317 0.0967 0.329 0.101 0.523 0.1593/0 85.01 167800 19 2.390 0.094 11.940 0.470 111.90 0.173 0.2512 0.0766 0.2610 0.0797 0.413 0.1264/0 107.2 211600 19 2.680 0.106 13.410 0.528 141.10 0.219 0.1996 0.0608 0.2050 0.0626 0.328 0.100250 37 2.090 0.082 14.610 0.575 168 0.260 0.1687 0.0515 0.1753 0.0535 0.2778 0.0847300 37 2.290 0.090 16.000 0.630 201 0.312 0.1409 0.0429 0.1463 0.0446 0.2318 0.0707350 37 2.470 0.097 17.300 0.681 235 0.364 0.1205 0.0367 0.1252 0.0382 0.1984 0.0605400 37 2.640 0.104 18.490 0.728 268 0.416 0.1053 0.0321 0.1084 0.0331 0.1737 0.0529500 37 2.950 0.116 20.650 0.813 336 0.519 0.0845 0.0258 0.0869 0.0265 0.1391 0.0424600 61 2.520 0.099 22.680 0.893 404 0.626 0.0704 0.0214 0.0732 0.0223 0.1159 0.0353700 61 2.720 0.107 24.490 0.964 471 0.730 0.0603 0.0184 0.0622 0.0189 0.0994 0.0303750 61 2.820 0.111 25.350 0.998 505 0.782 0.0563 0.0171 0.0579 0.0176 0.0927 0.0282

Page 10: Catalogo Recordplus General Electric

9

Withstand RatingsNote: The maximum withstand rating is limited by the value set forth in this table or the short circuit rating of the upstream fuse or circuit breaker,whichever is less. The upstream protective device must have instantaneous trip function or element, and its rated amperage may not exceed the ratedcurrent of the switch.

Internal Accessory FunctionsUL Listed for Field Installation

Auxiliary SwitchThe auxiliary switch signals primary contact position (open or closed) to other accessories for remote indication and control applications.Switch operation is independent of the method used to open or close the breaker. Auxiliary switches do not distinguish between a trip oropen condition. Record Plus normally open switches are “early make/late break” type auxiliary switches and are normally open when thebreaker is open and normally closed when the breaker is closed.

Bell Alarm MechanismThe bell alarm mechanism (BAM) is used to signal breaker trip status to other accessories for remote indication and interlocking function.The switch operates when the breaker is tripped as a result of its protective functions, or as the result of the operation of a shunt trip orundervoltage release. The switch is not actuated as a result of normal breaker “on-off” operation.

Shunt TripThe shunt trip is used to trip (open) the circuit breaker by remote control. Record Plus shunt trips are UL listed for field installation,meeting UL requirements for operation at 55% of rated ac voltage (120 Vac shunt trip only) and 75% of rated dc voltage for use onground fault systems. Record Plus shunt trips are common to all circuit breakers and molded cases switches in the product family.These devices offer a unique combination of low power consumption and a “kiss-free” lock-out operation. When the breaker is in the“ON” position and the shunt trip is activated, the breaker will trip and its contacts will open. The device can be constantly activated atits normal voltage, allowing it to be used as a lock-out coil.

Undervoltage ReleaseThe undervoltage release trips the circuit breaker when the control voltage drops to less than 35% to 70% of rating. Optional time delay units from 100 to 250 milliseconds allow the user to minimize nuisance tripping. The time delay may be switched off to provide an instantaneous undervoltage trip. In the event an attempt is made to reclose the circuit breaker while the undervoltage condition ispresent, the undervoltage release devices will prevent the breaker contact closure. In other words, Record Plus undervoltage releasesare a “kiss-free” design.

GE Molded Case Circuit Breaker Cross-Reference SummaryBreaker Type Legacy Breakers Record Plus (Thermal magnetic trip)

Vac Maximum Ampere Rating Poles Line Version I/C Version I/C

600 ≤100 2,3 Spectra SED 18 FCS 25

600 ≤100 2,3 Spectra SEHA 25 FCS 25

600 ≤100 2,3 Spectra SEL 65 FCN 65

600 ≤100 2,3 Spectra SEP 100 FCH 100

600 ≤100 2,3 Spectra SEL 25 FCS 25

600 ≤100 2,3 Core TED 18 FCS 25

600 ≤100 2,3 Core THED 25 FCS 25

600 ≤100 3 Core TEC 10 FCS 25

600 100 3 Spectra (Switch) SED 25 FCY 150

Molded Case SwitchProtective Device Withstand Rating RMS Symmetrical Amps

(in thousands)

Fuse Circuit Breaker AC Voltage

Frame Type Rated Amperes Type Max RatingAmperes Type Max Rating

Amperes 240 480 600

FC FCY 60 or 100 RK5, J, T or L 100 MCCB, ICCB orLVPCB 100 200 150 42

APPLICATION INFORMATION

Page 11: Catalogo Recordplus General Electric

10

Time Current CurvesShift index fo r long-tim e delay only.

Temp. 25 40 50

TIM

E I

N S

EC

ON

DS

* For pri nt ing to standard scaled size, scale log-log cycle to 2.212inch per cycle for both ord inate and abscissa

*

TIM

E I

N S

EC

ON

DS

1000900800700

600

500

400

300

200

10090807060

50

40

30

20

10987

6

.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090 100

200

300

400

500

600

700

800

900

100

0

200

0

300

0

400

0

500

0

600

0

700

080

00

900

010

00

0

.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090

100

200

300

400

500

600

700

800

900

100

0

200

0

300

0

400

0

500

0

600

0

700

080

00

900

010

00

0

5

4

3

2

.9

.8

.7

.6

.5

.4

.3

.2

.1.09.08.07.06

.05

.04

.03

.02

.01

1

1000900800700

600

500

400

300

200

10090807060

50

40

30

20

10987

6

5

4

3

2

.9

.8

.7

.6

.5

.4

.3

.2

.1.09.08.07

.06

.05

.04

.03

.02

.01

1

GE Industrial Systems

GE Industrial Systems, 41 Woodford Avenue, Plainvil le, CT 06062

DES-013

DES

-013

2.2 12 inch

M olded Case Circuit Breaker

w ith Thermal-M agnet ic t rip unit

Long-t ime Delay and Instantaneous Time-Current Curves Enclosure Compensated

oCurves show enclosure compensated circuit breaker in open air, 40 C ambient,w ired with conductors of corresponding rating, no prior load.For all other ambients, use rating shift index at top of page.

AdjustmentsLong-tim e delay thermal tr ip : not adjustable.

Instantaneous magnetic trip : not adjustable.

R02-08/02

- Type FC Record PlusTM

MULTIPLES OF CURRENT RATING

MULTIPLES OF CURRENT RATING

Current limiting range, for total clearing time see above for details.2For additional data refer to Ip and I t curves DES-028 & DES-029

15, 20, 25, 30, 35AmperesCurrent Rat ings

2 pole and 3 pole

Volt age Rat ings

Frequency Rat ings Hertz

600 Vac , 500Vdc

Non-adjustable instantaneous pick-up band, AC only.For DC instantaneous pick-up band conversion multiplier refer to the circuit breaker product guide on the GE Industrial Systems website: www.GEindustrial.com

Record PlusTM

15A

35A

30A

20A

25A

30A

35A

.10

.09

.08

.07

.06

.05

.04

.03

.02

.01

.009

.008

.007

.006

.005

.004

.003

.002

.001

.10

.09

.08

.07

.06

.05

.04

.03

.02

.01

.009

.008

.007

.006

.005

.004

.003

.002

.00110 20 30 40 50 60 70 8090

100

200

300

400

500

600

700

800

900

100

0

AVAILABLE THREE-PHASE SYMMETRICAL SHORT-CIRCUIT CURRENT (KILOAMPERES)

TOTA

L C

LEA

RIN

G T

IME

IN

SE

CO

ND

S

TOTA

L C

LEA

RIN

G T

IME

IN

SE

CO

ND

S

TOTAL CLEARING TIME VS CURRENT IN KA

600 Vac

Maximum totalclearing time

Minimum totalclearing time

480 Vac

240 Vac

50/60

Shift index fo r long-tim e delay only.

Temp. 25 40 50

TIM

E I

N S

EC

ON

DS

* For pri nt ing to standard scaled size, scale log-log cycle to 2.212inch per cycle for both ord inate and abscissa

*

TIM

E I

N S

EC

ON

DS

1000900800700

600

500

400

300

200

10090807060

50

40

30

20

10987

6

.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090 100

200

300

400

500

600

700

800

900

100

0

200

0

300

0

400

0

500

0

600

0

700

080

00

900

010

00

0

.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090

100

200

300

400

500

600

700

800

900

100

0

200

0

300

0

400

0

500

0

600

0

700

080

00

900

010

00

0

5

4

3

2

.9

.8

.7

.6

.5

.4

.3

.2

.1.09.08.07.06

.05

.04

.03

.02

.01

1

1000900800700

600

500

400

300

200

10090807060

50

40

30

20

10987

6

5

4

3

2

.9

.8

.7

.6

.5

.4

.3

.2

.1.09.08.07

.06

.05

.04

.03

.02

.01

1

GE Industrial Systems

GE Industrial Systems, 41 Woodford Avenue, Plainvil le, CT 06062

DES-014

DES

-014

2.2 12 inch

M olded Case Circuit Breaker

w ith Thermal-M agnet ic t rip unit

Long-t ime Delay and Instantaneous Time-Current Curves Enclosure Compensated

oCurves show enclosure compensated circuit breaker in open air, 40 C ambient,w ired with conductors of corresponding rating, no prior load.For all other ambients, use rating shift index at top of page.

AdjustmentsLong-tim e delay thermal tr ip : not adjustable.

Instantaneous magnetic trip : not adjustable.

R02-08/02

- Type FC Record PlusTM

MULTIPLES OF CURRENT RATING

MULTIPLES OF CURRENT RATING

Current limiting range, for total clearing time see above for details.2For additional data refer to Ip and I t curves DES-028 & DES-029

40, 45, 50, 60AmperesCurrent Rat ings

2 pole and 3 pole

Volt age Rat ings

Frequency Rat ings Hertz

600 Vac , 500Vdc

Non-adjustable instantaneous pick-up band, AC only.For DC instantaneous pick-up band conversion multiplier refer to the circuit breaker product guide on the GE Industrial Systems website: www.GEindustrial.com

Record PlusTM

40A

60A

50A

45A

.10

.09

.08

.07

.06

.05

.04

.03

.02

.01

.009

.008

.007

.006

.005

.004

.003

.002

.001

.10

.09

.08

.07

.06

.05

.04

.03

.02

.01

.009

.008

.007

.006

.005

.004

.003

.002

.00110 20 30 40 50 60 70 8090

100

200

300

400

500

600

700

800

900

100

0

AVAILABLE THREE-PHASE SYMMETRICAL SHORT-CIRCUIT CURRENT (KILOAMPERES)

TOTA

L C

LEA

RIN

G T

IME

IN

SE

CO

ND

S

TOTA

L C

LEA

RIN

G T

IME

IN

SE

CO

ND

S

TOTAL CLEARING TIME VS CURRENT IN KA

50/60

600 Vac

480 Vac

240 Vac

Maximum totalclearing time

Minimum totalclearing time

Shift index fo r long-tim e delay only.

Temp. 25 40 50

TIM

E I

N S

EC

ON

DS

* For pri nt ing to standard scaled size, scale log-log cycle to 2.212inch per cycle for both ord inate and abscissa

*

TIM

E I

N S

EC

ON

DS

1000900800700

600

500

400

300

200

10090807060

50

40

30

20

10987

6

.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090 100

200

300

400

500

600

700

800

900

100

0

200

0

300

0

400

0

500

0

600

0

700

080

00

900

010

00

0

.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090

100

200

300

400

500

600

700

800

900

100

0

200

0

300

0

400

0

500

0

600

0

700

080

00

900

010

00

0

5

4

3

2

.9

.8

.7

.6

.5

.4

.3

.2

.1.09.08.07.06

.05

.04

.03

.02

.01

1

1000900800700

600

500

400

300

200

10090807060

50

40

30

20

10987

6

5

4

3

2

.9

.8

.7

.6

.5

.4

.3

.2

.1.09.08.07

.06

.05

.04

.03

.02

.01

1

GE Industrial Systems

GE Industrial Systems, 41 Woodford Avenue, Plainvil le, CT 06062

DES-015

DES

-015

2.2 12 inch

M olded Case Circuit Breaker

w ith Thermal-M agnet ic t rip unit

- Type FC

Long-t ime Delay and Instantaneous Time-Current Curves Enclosure Compensated

oCurves show enclosure compensated circuit breaker in open air, 40 C ambient,w ired with conductors of corresponding rating, no prior load.For all other ambients, use rating shift index at top of page.

AdjustmentsLong-tim e delay thermal tr ip : not adjustable.

Instantaneous magnetic trip : not adjustable.

R01 05/02

Record PlusTM

MULTIPLES OF CURRENT RATING

MULTIPLES OF CURRENT RATING

Current limiting range, for total clearing time see above for details. 2For additional data refer to Ip and I t curves DES-028 & DES-029

Non-adjustable instantaneous pick-up band, AC only.For DC instantaneous pick-up band conversion multiplier refer to the circuit breaker product guide on the GE Industrial Systems website: www.GEindustrial.com

Record PlusTM

70, 80, 90, 100AmperesCurrent Rat ings

2 pole and 3 pole

Volt age Rat ings

Frequency Rat ings50/60 Hertz

600 Vac , 500Vdc

.10

.09

.08

.07

.06

.05

.04

.03

.02

.01

.009

.008

.007

.006

.005

.004

.003

.002

.001

.10

.09

.08

.07

.06

.05

.04

.03

.02

.01

.009

.008

.007

.006

.005

.004

.003

.002

.00110 20 30 40 50 60 70 8090

100

200

300

400

500

600

700

800

900

100

0

AVAILABLE THREE-PHASE SYMMETRICAL SHORT-CIRCUIT CURRENT (KILOAMPERES)

TOTA

L C

LEA

RIN

G T

IME

IN

SE

CO

ND

S

TOTA

L C

LEA

RIN

G T

IME

IN

SE

CO

ND

S

TOTAL CLEARING TIME VS CURRENT IN KA

600 Vac

480 Vac

240 Vac

Maximum totalclearing time

Minimum totalclearing time

70A

80A

90A

100A

www.GEindustrial.com

Page 12: Catalogo Recordplus General Electric

General Electric Company41 Woodford Avenue, Plainville, CT 06062www.GEindustrial.com

©2002 General Electric CompanyDEP-122 11/02

GE Industrial Systems

Prices and data are subject to change without notice. Should further information be desired, orshould particular problems arise that are not sufficiently covered here for the purchaser’s purposes,the matter should be referred to the General Electric Company.