03/19/2014 HPL-ED2014 V2.13 EN 1 / 12 Contactor, 3p, 30kW/400V/AC3 Part no. DILM65(220V50HZ,240V60HZ) Article no. 277893 Catalog No. XTCE065D00B Delivery programme Product range Contactors Application Contactors for Motors Subrange Contactors up to 170 A, 3 pole Utilization category AC-1: Non-inductive or slightly inductive loads, resistance furnaces AC-3: Squirrel-cage motors: starting, switching off during running AC-4: Squirrel-cage motors: starting, plugging, reversing, inching Connection technique Screw terminals Pole 3 pole Rated operational current AC-3 380 V 400 V I e A 65 AC-1 Conventional free air thermal current, 3 pole, 50 - 60 Hz Open at 40 °C I th =I e A 98 enclosed I th A 72 Conventional free air thermal current, 1 pole open I th A 200 enclosed I th A 180 Max. rating for three-phase motors, 50 - 60 Hz AC-3 220 V 230 V P kW 20 380 V 400 V P kW 30 660 V 690 V P kW 35 AC-4 220 V 230 V P kW 7 380 V 400 V P kW 12 660 V 690 V P kW 17 Contact sequence Instructions Contacts to EN 50 012. Can be combined with auxiliary contact DILM150-XHI(V).. DILM1000-XHI(V).. Voltage AC/DC AC operation Approvals Product Standards IEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking UL File No. E29096 UL Category Control No. NLDX CSA File No. 012528 CSA Class No. 2411-03, 3211-04 North America Certification UL listed, CSA certified Specially designed for North America No General Standards IEC/EN 60947, VDE 0660, UL, CSA Lifespan, mechanical AC operated Operations x 10 6 10 DC operated Operations x 10 6 10 Operating frequency, mechanical AC operated Operations/ h 5000 DC operated Operations/ h 5000 Climatic proofing Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
DeliveryprogrammeProduct range ContactorsApplication Contactors for MotorsSubrange Contactors up to 170 A, 3 poleUtilization category AC-1: Non-inductive or slightly
inductive loads, resistance furnacesAC-3: Squirrel-cage motors: starting,switching off during runningAC-4: Squirrel-cage motors: starting,plugging, reversing, inching
Connection technique Screw terminalsPole 3 poleRated operational current
enclosed Ith A 72Conventional free air thermalcurrent, 1 pole
open Ith A 200enclosed Ith A 180
Max. rating for three-phase motors, 50- 60 Hz
AC-3 220 V 230 V P kW 20380 V 400 V P kW 30660 V 690 V P kW 35
AC-4 220 V 230 V P kW 7380 V 400 V P kW 12660 V 690 V P kW 17
Contact sequence
Instructions Contacts to EN 50 012. Can be combined with auxiliary contact DILM150-XHI(V)..
DILM1000-XHI(V)..Voltage AC/DC AC operation
ApprovalsProduct Standards IEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE markingUL File No. E29096UL Category Control No. NLDXCSA File No. 012528CSA Class No. 2411-03, 3211-04North America Certification UL listed, CSA certifiedSpecially designed for North America No
Main cable Pozidriv screwdriver Size 2Standard screwdriver mm 0.8 x 5.5
1 x 6Control circuit cables
Pozidriv screwdriver Size 2Standard screwdriver mm 0.8 x 5.5
1 x 6Terminal capacity control circuit cables
Solid mm2 1 x (0.75 - 2.5)2 x (0.75 - 2.5)
03/19/2014 HPL-ED2014 V2.13 EN 3 / 12
Flexible mm2 1 x (0.75 - 2.5)2 x (0.75 - 2.5)
Flexible with ferrule mm2 1 x (0.75 - 1.5)2 x (0.75 - 1.5)
Solid or stranded AWG 18 - 14Tool
Stripping length mm 10Screwdriver blade width mm 3.5
MainconductingpathsRated impulse withstand voltage Uimp V
AC8000
Overvoltage category/pollution degree III/3Rated insulation voltage Ui V
AC690
Rated operational voltage Ue VAC
690
Safe isolation to EN 61140 between coil and contacts V
AC440
between the contacts VAC
440
Making capacity (p.f. to IEC/EN 60947) Up to 690
VA 910
Breaking capacity 220 V 230 V A 650380 V 400 V A 650500 V A 650660 V 690 V A 370
Short-circuit rating Short-circuit protection maximum fuse
Type “2” coordination 400 V gG/gL
500 VA 125
690 V gG/gL690 V
A 80
Type “1” coordination 400 V gG/gL
500 VA 250
690 V gG/gL690 V
A 100
ACAC-1
Rated operational current Conventional free air thermal current, 3 pole, 50 - 60 Hz
Open at 40 °C Ith =Ie A 98at 50 °C Ith =Ie A 88at 55 °C Ith =Ie A 83at 60 °C Ith =Ie A 80
enclosed Ith A 72Conventional free air thermal current, 1 pole
open Ith A 200enclosed Ith A 180
AC-3 Rated operational current
Open, 3-pole: 50 – 60 Hz 220 V 230 V Ie A 65240 V Ie A 65380 V 400 V Ie A 65
03/19/2014 HPL-ED2014 V2.13 EN 4 / 12
415 V Ie A 65440V Ie A 65500 V Ie A 65660 V 690 V Ie A 37
Motor rating P kWh 220 V 230 V P kW 20240V P kW 22380 V 400 V P kW 30415 V P kW 39440 V P kW 41500 V P kW 47660 V 690 V P kW 35
AC-4 Open, 3-pole: 50 – 60 Hz
220 V 230 V Ie A 25240 V Ie A 25380 V 400 V Ie A 25415 V Ie A 25440 V Ie A 25500 V Ie A 25660 V 690 V Ie A 20
Motor rating P kWh 220 V 230 V P kW 7240 V P kW 7.5380 V 400 V P kW 12415 V P kW 13440 V P kW 14500 V P kW 16660 V 690 V P kW 17
DCRated operational current, open
DC-1 60 V Ie A 72110 V Ie A 72220 V Ie A 65440 V Ie A 2.9
DC-3 60 V Ie A 72110 V Ie A 72220 V Ie A 35440 V Ie A 0.6
DC-5 60 V Ie A 72110 V Ie A 72220 V Ie A 35440 V Ie A 0.6
Currentheatloss3-pole at Ith W 28.8Current heat loss at Ie to AC-3/400 V W 19Impedance per pole mΩ 1.5
MagnetsystemsVoltage tolerance x Uc
AC operated Pick-up x Uc 0.8 - 1.1Drop-out voltage AC operated Drop-out x Uc 0.3 - 0.6
03/19/2014 HPL-ED2014 V2.13 EN 5 / 12
DC operated Pick-up x Uc 0.7 - 1.2Notes at least smoothed two-phase bridge rectifier or three-phase rectifierDC operated Drop-out x Uc 0.15 - 0.6
Power consumption of the coil in a cold state and 1.0 x Uc 50 Hz Pick-up VA 14950 Hz Sealing VA 1650 Hz Sealing W 4.360 Hz Pick-up VA 17860 Hz Sealing VA 1960 Hz Sealing W 5.350/60 Hz Pick-up VA 168
15450/60 Hz Sealing VA 22
1450/60 Hz Sealing W 5.3
4.3DC operated Pick-up W 24DC operated Sealing W 0.5
Duty factor %DF
100
Switching times at 100 % Uc (approximate values) Main contacts
AC operated Closing delay ms 12 - 18Opening delay ms 8 - 13
DC operated ms Closing delay ms 54Opening delay ms 24
Arcing time ms 10Lifespan, mechanical; Coil 50/60 Hz x
106Mechanical lifespan at 50 Hz approx. 30% lower than under “Technicaldata, general”
Electromagneticcompatibility(EMC)Emitted interference to EN 60947-1Interference immunity to EN 60947-1
TechnicaldataETIM5.0Low-voltage industrial components (EG000017) / Magnet contactor, AC-switching (EC000066)Electric engineering, automation, process control engineering / Low-voltage switch technology / Contactor (LV) / Power contactor, AC switching (ecl@ss8-27-37-10-03[AAB718011])Rated control supply voltage Us at AC50HZ
V 220 - 220
Rated control supply voltage Us at AC60HZ
V 240 - 240
Rated control supply voltage Us at DC V 0 - 0Voltage type for actuating ACRated operation current Ie at AC-1, 400V
A 98
Rated operation current Ie at AC-3, 400V
A 65
Rated operation power at AC-3, 400 V kW 30Rated operation current Ie at AC-4, 400V
A 25
Rated operation power Ie at AC-4, 400V
kW 12
Modular version NoNumber of auxiliary contacts asnormally open contact
0
Number of auxiliary contacts asnormally closed contact
0
Connection type main current circuit Screw connectionNumber of normally closed contacts asmain contact
on the side: 2 x DILM1000-XHI(V)11-SI; surface mounting: 1 x DILM150-XHIA11on the side: 2 x DILM1000-XHI(V)11-SA; surface mounting: 1 x DILM150-XHI (2 pole)on the side: 1 x DILM1000-XHI(V)11-SI; surface mounting: 1 x DILM150-XHIA22on the side: 1 x DILM1000-XHI(V)11-SA; surface mounting: 1 x DILM150-XHI (4 pole)
Characteristic curves
03/19/2014 HPL-ED2014 V2.13 EN 8 / 12
Squirrel-cage motorOperating characteristicsStarting:from restStopping:after attaining full running speedElectrical characteristicsMake: up to 6 x rated motor currentBreak: up to 1 x rated motor currentUtilization category100 % AC-3Typical applicationsCompressorsLiftsMixersPumpsEscalatorsAgitatorsFansConveyor beltsCentrifugesHinged flapsBucket-elevatorsAir conditioning systemGeneral drives in manufacturing and processing machines
03/19/2014 HPL-ED2014 V2.13 EN 9 / 12
Extreme switching dutySquirrel-cage motorOperating characteristicsInching, plugging, reversingElectrical characteristicsMake: up to 6 x rated motor currentBreak: up to 6 x rated motor currentUtilization category100 % AC-4Typical applicationsPrinting pressesWire-drawing machinesCentrifugesSpecial drives for manufacturing and processing machines