The Strong-Bolt® 2 wedge anchor is the next-generation solution for cracked and uncracked concrete. Following rigorous testing according to ICC-ES acceptance criteria, the Strong-Bolt 2 anchor received classification as a Category 1 anchor, the highest attainable anchor category for performance in cracked concrete under static and seismic loading. Available in stainless steel, it is code-listed by ICC-ES under the 2009 IBC requirements for post-installed anchors in cracked and uncracked concrete.
FEATURES:• Category1anchorclassification: The Strong-Bolt 2 anchor received classification
as a Category 1 anchor, which is established by performance in reliability tests in accordance with AC193 and ACI355.2 test criteria. Category 1 is the highest attainable anchor category for reliability.
• Tri-segmentedclip: Each segment adjusts independently, increasing follow-up expansion should the hole increase in size as a result of a crack
• Dualembossmentsoneachclipsegment: Enables clip to undercut into the concrete thereby increasing follow-up expansion should a crack occur
• The3⁄8"anchorsolutionapprovedfor31⁄4"concretethickness: The Strong-Bolt 2 anchor can be installed in cracked concrete with a minimum thickness of 3 ¼", including concrete-over-metal decking
• High-strengthalloycliponcarbon-steelanchors: This special alloy clip offers improved performance
• Standard(ANSI)fractionalanchor: Fits most fixtures and installs with common drill bit sizes and tools
• Type316stainless-steelcliponstainlesssteelanchors: In addition to superior corrosion resistance, a stainless-steel clip offers “memory” that contributes to the anchor’s performance if the hole increases in size because of a crack
MATERiAl: Carbon-steel stud with special alloy clip; stainless-steel stud with stainless-steel clip
FINISH: Zinc-plated (carbon steel)
CODES: ICC-ES ESR-3037 (carbon and stainless steel in concrete); IAPMO ES ER-240 (carbon steel in CMU); City of Los Angeles RR25891; Underwriters Laboratories File Ex3605; Factory Mutual 3043442; Florida – Pending
TEST CRiTERiA:The Strong-Bolt 2 wedge anchor has been tested in accordance with the ICC-ES Acceptance Criteria for Mechanical Anchors in Concrete Elements (AC 193) and ACI 355.2 for the following:• Static tension and shear loading in cracked and uncracked concrete
• Seismic and wind loading in cracked and uncracked concrete
• Performance in cracked concrete
• Performance in lightweight concrete over metal deck
iNSTAllATiON: •DonotuseanimpactwrenchtosetortightentheStrong-Bolt2anchor. Caution: Oversized holes in the base material will make it difficult to set the anchor and will reduce the anchor's load capacity.
•Drillaholeinthebasematerialusingacarbidedrillbitthesamediameterasthe nominaldiameteroftheanchortobeinstalled.Drilltheholetothespecified embedment depth and blow it clean using compressed air. Overhead installations need not be blown clean. Alternatively, drill the hole deep enough to accommodate minimum hole depth and dust from drilling.
•Assembletheanchorwithnutandwashersothatthetopofthenutisflush with the top of the anchor. Place the anchor in the fixture and drive into the hole until washer and nut are tight against the fixture.
•Tightentotherequiredinstallationtorque.
DESiGN EXMPlE: See pages 233–234
LengthIdentificationHeadMarksonStrong-Bolt®2WedgeAnchors(correspondstolengthofanchor–inches)Mark Units A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Strong‑Bolt® 2 Wedge Anchor for Cracked and Uncracked Concrete
Mechanical Anchors
CarbonSteel-ZincPlated1
ComponentMaterials
AnchorBody Nut Washer Clip
Carbon Steel
Carbon Steel
ASTM A 563, Grade A
Carbon Steel
ASTM F844
Carbon Steel ASTM A 568
1. Zinc meets ASTM B 633, Class SC 1 (Fe / Zn 5), Type III.
StainlessSteel
ComponentMaterials
AnchorBody Nut Washer Clip
Type 316 Stainless Steel
Type 316 Stainless Steel
Type 316 Stainless Steel
Type 316 Stainless Steel
MaterialSpecifications
1. TheinformationpresentedinthistableistobeusedinconjunctionwiththedesigncriteriaofACI318AppendixD.2. The clearance must comply with applicable code requirements for the connected element.3. For the 2006 IBC, do replaces da.4. For the 2003 IBC, fut replaces futa.
Strong-Bolt® 2AnchorProductData
Size(in.)
CarbonSteelModelNo.
316StainlessSteel
ModelNo.
DrillBitDia.(in.)
ThreadLength(in.)
Quantity
Box Carton
3⁄8 x 2 3⁄4 STB2-37234 STB2-372346SS 3⁄8 1 5⁄16 50 2503⁄8 x 3 STB2-37300 STB2-373006SS 3⁄8 1 9⁄16 50 2503⁄8 x 3 1⁄2 STB2-37312 STB2-373126SS 3⁄8 2 1⁄16 50 2503⁄8 x 3 3⁄4 STB2-37334 STB2-373346SS 3⁄8 2 5⁄16 50 2503⁄8 x 5 STB2-37500 STB2-375006SS 3⁄8 3 9⁄16 50 2003⁄8 x 7 STB2-37700 STB2-377006SS 3⁄8 5 9⁄16 50 2001⁄2 x 3 3⁄4 STB2-50334 STB2-503346SS 1⁄2 2 1⁄16 25 1251⁄2 x 4 1⁄4 STB2-50414 STB2-504146SS 1⁄2 2 9⁄16 25 1001⁄2 x 4 3⁄4 STB2-50434 STB2-504346SS 1⁄2 3 1⁄16 25 1001⁄2 x 5 1⁄2 STB2-50512 STB2-505126SS 1⁄2 3 13⁄16 25 1001⁄2 x 7 STB2-50700 STB2-507006SS 1⁄2 5 5⁄16 25 1001⁄2 x 8 1⁄2 STB2-50812 STB2-508126SS 1⁄2 6 25 501⁄2 x 10 STB2-50100 STB2-501006SS 1⁄2 6 25 505⁄8 x 4 1⁄2 STB2-62412 STB2-624126SS 5⁄8 2 7⁄16 20 805⁄8 x 5 STB2-62500 STB2-625006SS 5⁄8 2 15⁄16 20 805⁄8 x 6 STB2-62600 STB2-626006SS 5⁄8 3 15⁄16 20 805⁄8 x 7 STB2-62700 STB2-627006SS 5⁄8 4 15⁄16 20 805⁄8 x 8 1⁄2 STB2-62812 STB2-628126SS 5⁄8 6 20 405⁄8 x 10 STB2-62100 STB2-621006SS 5⁄8 6 10 203⁄4 x 5 1⁄2 STB2-75512 STB2-755126SS 3⁄4 3 3⁄16 10 403⁄4 x 6 1⁄4 STB2-75614 STB2-756146SS 3⁄4 3 15⁄16 10 403⁄4 x 7 STB2-75700 STB2-757006SS 3⁄4 4 11⁄16 10 403⁄4 x 8 1⁄2 STB2-75812 STB2-758126SS 3⁄4 6 10 203⁄4 x 10 STB2-75100 STB2-751006SS 3⁄4 6 10 20
1. TheinformationpresentedinthistableistobeusedinconjunctionwiththedesigncriteriaofACI318AppendixD.2. The clearance must comply with applicable code requirements for the connected element.3. For the 2006 IBC, do replaces da.4. For the 2003 IBC, fut replaces futa.
Simpson Strong-Tie ® Anchoring and Fastening Systems for Concrete and Masonry
1. TheinformationpresentedinthistablemustbeusedinconjunctionwiththedesigncriteriaofACI318AppendixD,exceptasmodifiedbelow.2. The tabulated value of ϕsa applies when the load combinations of Section 1605.2.1 of the IBC, or ACI 318 Section 9.2 are used. If the
load combinations of ACI 318 Appendix C are used, the appropriate value of ϕsamustbedeterminedinaccordancewithACI318D.4.5.Strong-Bolt®2anchorsareductilesteelelementsasdefinedinACI318D.1.
3. The tabulated value of ϕcb applies when both the load combinations of Section 1605.2.1 of the IBC, or ACI 318 Section 9.2 are used and the requirementsofACI318SectionD.4.4(c)forConditionBaremet.ConditionBapplieswheresupplementaryreinforcementisnotprovided.For installations where complying supplementary reinforcement can be verified, the ϕcbfactorsdescribedinACI318D.4.4forConditionAareallowed.IftheloadcombinationsofACI318Section9.2areusedandtherequirementsofACI318SectionD.4.4forConditionAaremet,theappropriate value of ϕcbmustbedeterminedinaccordancewithACI318D.4.4(c).IftheloadcombinationsofACI318AppendixCareused,theappropriate value of ϕcbmustbedeterminedinaccordancewithACI318D.4.5(c).
4. N/A (Not Applicable) denotes that pullout resistance does not need to be considered. 5. The characteristic pull-out strength for greater concrete compressive strengths shall be increased by multiplying the tabular value by
(f'c / 2,500 psi)0.5.6. The tabulated value of ϕp or ϕeq applies when the load combinations of Section 1605.2.1 of the IBC, or ACI 318 Section 9.2 are used and the
requirementsofACI318D.4.4(c)forConditionBaremet.IftheloadcombinationsofACI318AppendixCareused,appropriatevalueofϕ must bedeterminedinaccordancewithACI318SectionD.4.5(c).
7. For the 2003 IBC, Ψ3 replaces Ψc,N.8. Forsand-lightweightconcrete,inlieuofACI318SectionD.3.4,modifythevalueofconcretebreakoutstrength,Np,cr, Np,uncr and Neq by 0.6.
All-lightweight concrete is beyond the scope of this table.
See page 13 for an explanation of the load table icons
*
Simpson Strong-Tie ® Anchoring and Fastening Systems for Concrete and MasonryC-
1. TheinformationpresentedinthistablemustbeusedinconjunctionwiththedesigncriteriaofACI318AppendixD,exceptasmodifiedbelow.2. The tabulated value of ϕsa applies when the load combinations of Section 1605.2.1 of the IBC, or ACI 318 Section 9.2 are used. If the load
combinations of ACI 318 Appendix C are used, the appropriate value of ϕsamustbedeterminedinaccordancewithACI318D.4.5.Strong-Bolt® 2 anchorsareductilesteelelementsasdefinedinACI318D.1.
3. The tabulated value of ϕcb applies when both the load combinations of Section 1605.2.1 of the IBC, or ACI 318 Section 9.2 are used and the requirementsofACI318SectionD.4.4(c)forConditionBaremet.ConditionBapplieswheresupplementaryreinforcementisnotprovided. For installations where complying supplementary reinforcement can be verified, the ϕcbfactorsdescribedinACI318D.4.4forConditionAareallowed.IftheloadcombinationsofACI318Section9.2areusedandtherequirementsofACI318SectionD.4.4forConditionAaremet,theappropriatevalueof ϕcbmustbedeterminedinaccordancewithACI318D.4.4(c).IftheloadcombinationsofACI318AppendixCareused,theappropriatevalueofϕcb mustbedeterminedinaccordancewithACI318D.4.5(c).
4. N/A (Not Applicable) denotes that pullout resistance does not need to be considered. 5. The characteristic pull-out strength for greater concrete compressive strengths shall be increased by multiplying the tabular value by (f'c / 2,500 psi)0.5.6. The characteristic pull-out strength for greater concrete compressive strengths shall be increased by multiplying the tabular value by (f'c / 2,500 psi)0.3. 7. The characteristic pull-out strength for greater concrete compressive strengths shall be increased by multiplying the tabular value by (f'c / 2,500 psi)0.4.8. The tabulated value of ϕp or ϕeq applies when the load combinations of Section 1605.2.1 of the IBC, or ACI 318 Section 9.2 are used and the
requirementsofACI318D.4.4(c)forConditionBaremet.IftheloadcombinationsofACI318AppendixCareused,appropriatevalueofϕ must be determinedinaccordancewithACI318SectionD.4.5(c).
9. For the 2003 IBC, ψ3 replaces ψc,N.10. Forsand-lightweightconcrete,inlieuofACI318SectionD.3.4,modifythevalueofconcretebreakoutstrength,Np,cr, Np,uncr and Neq by 0.6.
All-lightweight concrete is beyond the scope of this table.
See page 13 for an explanation of the load table icons
*
Simpson Strong-Tie ® Anchoring and Fastening Systems for Concrete and Masonry
1. TheinformationpresentedinthistablemustbeusedinconjunctionwiththedesigncriteriaofACI318AppendixD,exceptasmodifiedbelow.2. The tabulated value of ϕsa applies when the load combinations of Section 1605.2.1 of the IBC, or ACI 318 Section 9.2 are used and the
3. The tabulated value of ϕcb applies when both the load combinations of Section 1605.2.1 of the IBC, or ACI 318 Section 9.2 are used and the requirementsofACI318SectionD.4.4(c)forConditionBaremet.ConditionBapplieswheresupplementaryreinforcementisnotprovided. For installations where complying supplementary reinforcement can be verified, the ϕcbfactorsdescribedinACI318SectionD.4.4forConditionAareallowed.IftheloadcombinationsofACI318Section9.2areusedandtherequirementsofACI318SectionD.4.4forConditionAare met, the appropriate value of ϕcbmustbedeterminedinaccordancewithACI318SectionD.4.4(c).IftheloadcombinationsofACI318Appendix C are used, the appropriate value of ϕcbmustbedeterminedinaccordancewithACI318SectionD.4.5(c).
4. The tabulated value of ϕcpapplieswhenboththeloadcombinationsofACI318Section9.2areusedandtherequirementsofACI318D.4.4(c)for Condition B are met. If the load combinations of ACI 318 Appendix C are used, the appropriate value of ϕcp must be determined in accordancewithACI318D.4.5(c).
5. For the 2006 IBC, do replaces da.6. Forsand-lightweightconcrete,inlieuofACI318SectionD.3.4,modifythevalueofconcretebreakoutstrengthby0.6.All-lightweightconcrete
is beyond the scope of this table.
See page 13 for an explanation of the load table icons
*
Simpson Strong-Tie ® Anchoring and Fastening Systems for Concrete and MasonryC-
1. TheinformationpresentedinthistablemustbeusedinconjunctionwiththedesigncriteriaofACI318AppendixD,exceptasmodifiedbelow.2. The tabulated value of ϕsa applies when the load combinations of Section 1605.2.1 of the IBC, or ACI 318 Section 9.2 are used and the
3. The tabulated value of ϕcb applies when both the load combinations of Section 1605.2.1 of the IBC, or ACI 318 Section 9.2 are used and the requirementsofACI318SectionD.4.4(c)forConditionBaremet.ConditionBapplieswheresupplementaryreinforcementisnotprovided. For installations where complying supplementary reinforcement can be verified, the ϕcbfactorsdescribedinACI318SectionD.4.4forConditionAareallowed.IftheloadcombinationsofACI318Section9.2areusedandtherequirementsofACI318SectionD.4.4forConditionAare met, the appropriate value of ϕcbmustbedeterminedinaccordancewithACI318SectionD.4.4(c).IftheloadcombinationsofACI318Appendix C are used, the appropriate value of ϕcbmustbedeterminedinaccordancewithACI318SectionD.4.5(c).
4. The tabulated value of ϕcpapplieswhenboththeloadcombinationsofACI318Section9.2areusedandtherequirementsofACI318D.4.4(c)for Condition B are met. If the load combinations of ACI 318 Appendix C are used, the appropriate value of ϕcp must be determined in accordancewithACI318D.4.5(c).
5. For the 2006 IBC, do replaces da.6. Forsand-lightweightconcrete,inlieuofACI318SectionD.3.4,modifythevalueofconcretebreakoutstrengthby0.6.All-lightweightconcrete
Pullout Strength, concrete on metal deck (uncracked)3 Np,deck,uncr lb 1,5808 3,9508 2,4757 2,6607 2,4707 5,0007 4,2759 1,9908 2,5607
Pullout Strength, concrete on metal deck (seismic)5 Np,deck,eq lb 1,2308 2,3458 1,9907 2,5507 1,7509 4,0209 3,0307 1,5508 2,0557
Steel Strength in Shear, concrete on metal deck4 Vsa,deck lb 2,285 3,085 3,430 4,680 3,235 5,430 6,135 3,085 5,955
Steel Strength in Shear, concrete on metal deck (seismic)5 Vsa,deck.eq lb 2,285 3,085 2,400 3,275 3,235 5,430 5,520 3,085 4,170
1. The information presented in this table must be used in conjunction with the design criteriaofACI318AppendixD,exceptasmodifiedbelow.
2. Profile steel deck must comply with the configuration in the figure below, and have a minimum base-steel thickness of 0.035 inch [20 gauge]. Steel must comply with ASTM A 653/A 653M SS Grade 33 with minimum yield strength of 33,000 psi. Concrete compressive strength shall be 3,000 psi minimum.
3. For anchors installed in the soffit of sand-lightweight or normal-weight concrete over metaldeckfloorandroofassemblies,calculationoftheconcretebreakoutstrengthmay be omitted.
4. InaccordancewithACI318SectionD.5.3.2,thenominalpulloutstrengthincrackedconcrete for anchors installed in the soffit of sand-lightweight or normal-weight concreteovermetaldeckfloorandroodassembliesNp,deck,cr shall be substituted for Np,cr. Where analysis indicates no cracking at service loads, the normal pullout
strength in uncracked concrete Np,deck,uncr shall be substituted for Np,uncr. For seismic loads, Np,deck,eq shall be substituted for Np.
5. InaccordancewithACI318SectionD.6.1.2(c),theshearstrengthforanchorsinstalledinthesoffitofsand-lightweightornormal-weightconcreteovermetaldeckfloorandrood assemblies Vsa,deck shall be substituted for Vsa. For seismic loads, Vsa,deck,eq shall be substituted for Vsa.
6. Theminimumanchorspacingalongtheflutemustbethegreaterof3.0hef or 1.5 times theflutewidth.
7. The characteristic pull-out strength for greater concrete compressive strengths shall be increased by multiplying the tabular value by (f'c / 3,000 psi)0.5.
8. Concrete shall be normal-weight or structural sand-lightweight concrete having a minimum specified compressive strength, f'c, of 3,000 psi.
9. Minimum distance to edge of panel is 2hef.
1. The information presented in this table must be used in conjunction with the design criteriaofACI318AppendixD,exceptasmodifiedbelow.
2. Profile steel deck must comply with the configuration in the figure below, and have a minimum base-steel thickness of 0.035 inch [20 gauge]. Steel must comply with ASTM A 653/A 653M SS Grade 33 with minimum yield strength of 33,000 psi. Concrete compressive strength shall be 3,000 psi minimum.
3. For anchors installed in the soffit of sand-lightweight or normal-weight concrete over metaldeckfloorandroofassemblies,calculationoftheconcretebreakoutstrengthmay be omitted.
4. InaccordancewithACI318SectionD.5.3.2,thenominalpulloutstrengthincrackedconcrete for anchors installed in the soffit of sand-lightweight or normal-weight concreteovermetaldeckfloorandroodassembliesNp,deck,cr shall be substituted for Np,cr. Where analysis indicates no cracking at service loads, the normal pullout strength in uncracked concrete Np,deck,uncr shall be substituted for Np,uncr. For seismic loads, Np,deck,eq shall be substituted for Np.
5. InaccordancewithACI318SectionD.6.1.2(c),theshearstrengthforanchorsinstalledinthesoffitofsand-lightweightornormal-weightconcreteovermetaldeckfloorandrood assemblies Vsa,deck shall be substituted for Vsa. For seismic loads, Vsa, deck,eq shall be substituted for Vsa.
6. Theminimumanchorspacingalongtheflutemustbethegreaterof3.0hef or 1.5 times theflutewidth.
7. The characteristic pull-out strength for greater concrete compressive strengths shall be increased by multiplying the tabular value by (f'c / 3,000 psi)0.5.
8. The characteristic pull-out strength for greater concrete compressive strengths shall be increased by multiplying the tabular value by (f'c / 3,000 psi)0.3.
9. The characteristic pull-out strength for greater concrete compressive strengths shall be increased by multiplying the tabular value by (f'c / 3,000 psi)0.4.
10. Concrete shall be normal-weight or structural sand-lightweight concrete having a minimum specified compressive strength, f'c, of 3,000 psi.
11. Minimum distance to edge of panel is 2hef.
* See page 13 for an explanation of the load table icons
*See page 13 for an explanation of the load table icons
*
*
Simpson Strong-Tie ® Anchoring and Fastening Systems for Concrete and MasonryC-
1. The tabulated allowable loads are based on a safety factor of 5.0 for installation under the IBC and IRC.
2. Listed loads may be applied to installations on the face of the CMU wall at least 1 1⁄4 inch away from headjoints.
3. Values for 8-inch wide concrete masonry units (CMU) with a minimum specified compressive strength of masonry, f'm, at 28 days is 1500 psi.
4. Embedment depth is measured from the outside face of the concrete masonry unit.5. Tension and shear loads may be combined using the parabolic interaction equation (n = 5/3).6. Refer to allowable load adjustment factors for edge distance and spacing on page 105.
1. The tabulated allowable loads are based on a safety factor of 5.0 for installation under the IBC and IRC. 2. Values for 8-inch wide concrete masonry units (CMU) with a minimum specified compressive strength of masonry,
f'm, at 28 days is 1500 psi.3. Tension and shear loads may be combined using the parabolic interaction equation (n = 5/3).4. Refer to allowable load adjustment factors for edge distance and spacing on page 105.
LoadAdjustmentFactorsforCarbon-SteelStrong-Bolt®2AnchorsinFace-of-WallInstallationin8"Grout-FilledCMU:EdgeDistanceandSpacing,TensionandShearLoadsHowtousethesecharts:1. The following tables are for reduced edge distance and spacing.2. Locate the anchor size to be used for either a tension and/or shear load application.3. Locate the embedment (E) at which the anchor is to be installed.4. Located the edge distance (Cact) or spacing (Sact) at which the anchor is to
be installed.
5. The load adjustment factor (fc or fs) is the intersection of the row and column.6. Multiply the allowable load by the applicable load adjustment factor.7. Reduction factors for multiple edges or spacings are multiplied together.
Howtousethesecharts:1. The following tables are for reduced edge distance and spacing.2. Locate the anchor size to be used for either a tension and/or shear load application.3. Locate the embedment (E) at which the anchor is to be installed.4. Located the edge distance (Cact) or spacing (Sact) at which the anchor is to
be installed.
5. The load adjustment factor (fc or fs) is the intersection of the row and column.6. Multiply the allowable load by the applicable load adjustment factor.7. Reduction factors for multiple edges or spacings are multiplied together.
* See page 13 for an explanation of the load table icons
*
*
* See page 13 for an explanation of the load table icons
*
*
* See page 13 for an explanation of the load table icons
*
* See page 13 for an explanation of the load table icons
*
* See page 13 for an explanation of the load table icons
*
* *
Simpson Strong-Tie ® Anchoring and Fastening Systems for Concrete and MasonryC-