www.ge.com/energy BuyLog ® Catalog Publications and Reference: See Section 22 for a complete list of additional product-related publications 20-1 Capacitors, Arresters and Harmonic Filters Rev. 1/08 Prices and data subject to change without notice Section 20 Line/Load Reactors—up to 600V......................................................20-2 Line/Load Reactors—Three-phase Reactors ..............................20-4 Matrix Series D Harmonic Filters .....................................................20-6 Protective Capacitors for AC Rotating Machines...................20-11 Fixed Motor and Pump Capacitors ...............................................20-13 Fixed Low Voltage Power Factor Correction Capacitors ............................................................................................20-15 Fixed Low Voltage Power Factor Correction with Harmonic Filter Equipment .................................................20-24 Automatic Fast-Switching LV Power Factor Correction Capacitors .......................................................20-26 Automatic LV Power Factor Correction Capacitors ..............20-30 Automatic LV Power Factor Correction Capacitors and Harmonic Filter Equipment .........................20-33 Active Harmonic Filter .......................................................................20-35 Fixed MV Power Factor Correction Capacitors .......................20-37 High Voltage Capacitor Units, Single- and Three-Phase ................................................................................20-40 High Voltage Pole-Mounted, Open Stack-Rack and Metal Enclosed Equipment ..................................................20-44 Capacitor Oil Switches........................................................................20-46 OEM High Energy Surge Protectors..............................................20-47 TRANQUELL ® ‚ Motor Surge Protectors— Motor and Generator Surge Protection Equipment ..........20-49 Secondary Surge Arresters and Protective Capacitors Series 9L15F .........................................................................................20-50 HV Station Arresters—Polymer and Porcelain.........................20-51 HV Intermediate Arresters—Polymer ...........................................20-59 Station and Intermediate Arresters—Outline Drawings .....20-63 Station and Intermediate Class Arrestors—Accessories ....20-64 Distribution and Riser Pole Arresters ...........................................20-65 Internet Web Site: www.ge.com/energy For more information on these products, see our Internet Web Site or order publications listed below. Order From: GE Attn: Distribution Services 1601 GE Road Bloomington, IL 61704 Phone: 309-664-1513 (Dial Comm 8*325-4513) Fax: 309-662-9660 (Dial Comm 8*325-4511) Reference Publications Capacitors GEP-974G, DEA-226 Motor and Pump Capacitors, 240 and 480 Volts GEP-974G, DEA-226 Fixed–Low Voltage Power Factor Correction Capacitors, 240, 480 and 600 Volts GEP-974G, DEA-226 Automatically Switched, LV Power Factor Correction Capacitors, 240, 480 and 600 Volts GEP-974G, DEA-226 Automatically Switched Harmonic Filters, 240, 480 and 600 Volts DEA-298 GEMATIC ® Quick Response GEP-974G, DEA-222, DEA-226 Medium Voltage 2400-4800 Volts, Type HWT DEA-216 High Voltage Single-Phase Capacitors, 2400-21,600 Volts DEA-213, DEA-214 High Voltage Pole Top and Open Stack Rack Equipment DEA-224 Protective Capacitors for AC Rotating Machines Arresters: TVSS GED-7060A TRANQUELL ® Secondary Surge Arresters and Protective Capacitor FETA-100A Product Selection and Application Guide Harmonic Filters GEH-7256 Matrix D Harmonic Filter DET-376 GEMACTIVE Harmonic Filter FETR-100 AC Line/Load Reactors
68
Embed
Capacitors, Arresters and Harmonic Filters Section 20elmechanics.com/documents/pdf/232/18L0015WH.pdf · Capacitors, Arresters and Harmonic Filters Section 20 Line/Load Reactors Up
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-1
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20
Line/Load Reactors—up to 600V......................................................20-2Line/Load Reactors—Three-phase Reactors ..............................20-4Matrix Series D Harmonic Filters .....................................................20-6Protective Capacitors for AC Rotating Machines...................20-11Fixed Motor and Pump Capacitors...............................................20-13Fixed Low Voltage Power Factor Correction
Capacitors ............................................................................................20-15Fixed Low Voltage Power Factor Correction
with Harmonic Filter Equipment.................................................20-24Automatic Fast-Switching LV Power
Factor Correction Capacitors.......................................................20-26Automatic LV Power Factor Correction Capacitors ..............20-30Automatic LV Power Factor Correction
Capacitors and Harmonic Filter Equipment .........................20-33Active Harmonic Filter .......................................................................20-35Fixed MV Power Factor Correction Capacitors.......................20-37High Voltage Capacitor Units, Single-
and Three-Phase ................................................................................20-40High Voltage Pole-Mounted, Open Stack-Rack
and Metal Enclosed Equipment ..................................................20-44Capacitor Oil Switches........................................................................20-46OEM High Energy Surge Protectors..............................................20-47TRANQUELL®‚ Motor Surge Protectors—
Motor and Generator Surge Protection Equipment ..........20-49Secondary Surge Arresters and Protective Capacitors
Series 9L15F .........................................................................................20-50HV Station Arresters—Polymer and Porcelain.........................20-51HV Intermediate Arresters—Polymer...........................................20-59Station and Intermediate Arresters—Outline Drawings .....20-63Station and Intermediate Class Arrestors—Accessories ....20-64Distribution and Riser Pole Arresters...........................................20-65
Internet Web Site: www.ge.com/energyFor more information on these products, see our Internet WebSite or order publications listed below.
Order From:GEAttn: Distribution Services1601 GE RoadBloomington, IL 61704Phone: 309-664-1513 (Dial Comm 8*325-4513)Fax: 309-662-9660 (Dial Comm 8*325-4511)
Reference PublicationsCapacitorsGEP-974G, DEA-226 Motor and Pump Capacitors,
240 and 480 VoltsGEP-974G, DEA-226 Fixed–Low Voltage Power Factor Correction
Capacitors, 240, 480 and 600 VoltsGEP-974G, DEA-226 Automatically Switched, LV Power Factor
Arresters and Protective CapacitorFETA-100A Product Selection and
Application Guide
Harmonic FiltersGEH-7256 Matrix D Harmonic FilterDET-376 GEMACTIVE Harmonic FilterFETR-100 AC Line/Load Reactors
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-2
Capacitors, Arresters and Harmonic Filters Section 20Line/Load ReactorsUp to 600V
Cabinet Product Number GO-52
List PriceW
Wgt (lbs.)H D
NEMA 1Enclosure Style Type
37GCAB8 $146.00 CAB-8 Wall Mount 8 8 6 7
13.22 13 13.09 31
17 24 18.38 45
17.54 31 20.90 180
37GCAB13V $240.00 CAB-13V Floor
37GCAB17V $650.00 CAB-17V Floor
37GCAB26C $1564.00 CAB-26C Floor
Outline DimensionsExact terminal configuration may be different than shown. For exactterminal configuration contact factory for outline drawing.
Motor ProtectionReactors help to protect motors from the high peak voltages andfast rise times (dv/dt) which can be experienced in IGBT inverter applications when the distance between the inverter and motor is long.
Harmonic ReductionBecause all standard GE Line/Load reactors are compensated forharmonics (current and frequency), they are extremely effectiveat reducing the amount of harmonics which are produced by a drive/inverter. Use 5% impedance, harmonic compensatedreactors for best reaction of harmonic distortion.
Voltage Spike ProtectionA 3% impedance reactor is very effective at protecting against damage to or nuisance tripping of AC voltage source inverters,due to voltage spikes.
Voltage spikes on the AC power lines cause elevation of the DCBus voltage which may cause the inverter to “trip-off” and indi-cate an over-voltage protection condition. Use reactors to absorbthese line spikes and offer protection to the rectifiers and DC Buscapacitors while minimizing nuisance tripping of the inverter.
Typical Harmonic Distortion of PWM Inverter Without Reactor
With 5% Impedance Reactor
Agency Approvals—GE line reactors are UL recognized.—All UL approvals are for USA and Canada.—UL-506 File #E191687 (1 amp-1200 amps)—UL-508 File #E191686 (1 amp-1200 amps)—All higher currents offer UL recognized insulation systems
and construction.—CE Marked
NEMA 1 CabinetsAll GE Line/Load Reactors are available as either open type or in a NEMA Type 1 general purpose enclosure. To order a reactormounted in a cabinet simply change the second to last digit ofthe product number from “0” to “1”. Example 37G 00802 becomes37G 00812.
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-3
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
*For maximum continuous current ratings refer to Specifications on next page.
For Input or Output of Adjustable Speed Drive/Inverter Systems*For higher or lower current ratings, consult factory.*For other voltages or frequencies, consult factory. Single phase reactors are also available, consult factory for proper selection.
This table is suitable for selection of both input and output reactors because their harmonic compensation and IGBT protection allow them to be used in either application. Specific current and inductance ratings are indicated on next page. Consult factory for any special applications (higher current, motor rating different than controller rating, etc.)Select GE Line/Load reactors based upon motor horsepower, (or kilowatts) and voltage. Verify that the motor full load ampere rating is within the fundamental current rating of the reactor, and the drive/inverter rating is within the maximum continuous rating of the reactor(See next page).
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-4
Capacitors, Arresters and Harmonic Filters Section 20
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-6
Capacitors, Arresters and Harmonic Filters Section 20
Typical ApplicationsUse Matrix Harmonic filters to minimize harmonic current distor-tion in these and other 6-pulse rectifier applications:
—Fans and Pumps—Water Treatment Facilities—HVAC Systems—AC or DC Motor Drives—Rectifier type welders—Induction Heating Equipment—UPS Equipment—Elevators
Matrix Filter enables most AC drive systems to comply with the voltage and current distortion limits outlined in IEEE 519. A completeharmonic analysis and product selection tool is available on the internet. Go to geelectrical.com and select Products, selectCapacitors, choose Matrix Harmonic Filter and then select EnergySavings Calculator and Harmonic Estimator.
Matrix Harmonic Filters are multi-stage low pass filters speciallyconfigured to avoid the attraction of harmonics from othersources on a shared power system. Matrix filters will not causepower system resonance. However, the configuration of the filterrequires that only drives or equivalent loads be loaded on theoutput of a Matrix harmonic filter. One filter can be used withmultiple drives. However, if there is a drive bypass circuit, theremust be one filter per drive and the filter and drive combinationmust be bypassed.
Matrix Harmonic Filters are available in a NEMA 1, NEMA 3R or as a modular design preassembled onto panels for subsequentassembly into customer supplied cabinet.
Product Specifications—Input Voltage 480 Volts +/– 10%—Ambient Temperature:
—Storage – 40°C to 90°C—Operating – 40°C to 40°C
—Altitude: 1000 meters maximum—UL approved – File E191686 for U.S. and Canada
Minimum System Requirements to Achieve Performance Levels—Source Impedance: 1.5% minimum to 5% maximum—System voltage: 480 volts (line to line) +/– 10%—Frequency: 60 Hz +/– .75 Hz—Balanced Line Voltage: within 1%—Background Voltage Distortion: 0% THVD
Matrix Series D Harmonic FiltersMatrix Harmonic filters provide broadband reduction of harmonics.Matrix Harmonic Filters not only offer better performance overother broad band filtering and 18-pulse harmonic reduction tech-niques, they are also suitable for a wider range of applications.Matrix Harmonic Filters can be installed in either variable or constant torque drive applications and can be applied on eitherdiode or SCR rectifiers. For any application other than variabletorque applications, it is suggested that you contact the factoryfor filter selection.
The Matrix D Filters typically achieve 5% THID at full load andguarantee worst case current distortion at any load between 0%and 100%, will be 8% THID or less at the filter input terminals. TheMatrix D Series is typically used in place of applications requiringharmonic mitigation associated with 12- or 18-pulse rectifiers.The chart below compares the performance of Matrix D Filters to 18-pulse rectifiers in real world applications, which include linevoltage unbalance of 1% to 3% and loading conditions from 0%to 100%.
Matrix D Filter performs better than 18-pulse in normal operating conditions.
Matrix D vs. 18-pulse
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-7
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
ApplicationsSelect Matrix filters based on the horsepower (or kilowatt) rating for the adjustable speeddrive or the combined currrent rating of all motors to be connected to the load side ofthe filter. For constant torque, DC drive or other applications consult factory for proper filter selection.
Source ImpedanceIf the source impedance is less than 1.5% impedance, it is required that an input reactorof at least 1.5% impedance be added in order to have guaranteed performance level.For best value and performance it is recommended that a 3% line reactor be usedwhenever the source impedance is less than 1.5%.
Matrix Series D Harmonic Filters
General Purpose Enclosure Style
480 Volts, 60 HzNEMA 1 & NEMA 2 List Price Wt. NEMA 3R List Price Wt.
Amps HP Open Panel GO-52A (Lbs.) HMR Size (in.) Size (in.)
6 3 37GMDP0006D $921.00 22 11.3"H X 6"W X 6.2"D 4.8"H x 4.8"W x 7.3"D8 5 37GMDP0008D $957.00 24 11.3"H X 6"W X 6.3"D 4.8"H x 4.8"W x 7.3"D11 7.5 37GMDP0011D $1005.00 29 12.4"H x 7.2"W x 5.7"D 4.8"H x 4.8"W x 8.2"D14 10 37GMDP0014D $1051.00 35 12.4"H x 7.3"W x 6.3"D 4.8"H x 4.8"W x 8.2"D21 15 37GMDP0021D $1263.00 46 15.8"H x 9"W x 6.5"D 5.6"H x 5.6"W x 7.3"D27 20 37GMDP0027D $1353.00 61 15.8"H x 9"W x 7"D 5.6"H x 5.6"W x 8.2"D34 25 37GMDP0034D $1586.00 72 15.8"H x 9"W x 7.5"D 5.6"H x 5.6"W x 8.7"D44 30 37GMDP0044D $1721.00 84 15.8"H x 9"W x 8"D 5.6"H x 5.6"W x 7.3"D52 40 37GMDP0052D $2113.00 125 16.5"H x 12.3"W x 9.6"D 5.6"H x 5.6"W x 7.3"D66 50 37GMDP0066D $2450.00 154 16.5"H x 12.3"W x 10.7"D 8"H x 7.3"W x 12"D83 60 37GMDP0083D $2785.00 176 16.5"H x 12.3"W x 11.3"D 8"H x 7.3"W x 12"D103 75 37GMDP0103D $2951.00 180 16.5"H x 12.3"W x 11"D 8"H x 7.3"W x 12"D128 100 37GMDP0128D $3726.00 217 23"H x 15.3"W x 11.3"D 12"H x 7.3"W x 12"D165 125 37GMDP0165D $4126.00 273 23"H x 15.3"W x 11.5"D 12"H x 7.3"W x 12"D208 150 37GMDP0208D $4650.00 292 23"H x 15.3"W x 12"D 15"H x 7.3"W x 12"D240 200 37GMDP0240D $4726.00 298 23"H x 15.3"W x 12.4"D 15"H x 7.3"W x 12"D
320 250 37GMDP0320D $7054.00 464 35.5"H x 18"W x 20.2"D15"H x 7.3"W x 12"D8"H x 7.3"W x 12"D
403 300 37GMDP0403D $8401.00 508 35.5"H x 18"W x 22.5"D12"H x 7.3"W x 12"D15"H x 7.3"W x 12"D
482 400 37GMDP0482D $9068.00 602 35.5"H x 18"W x 23"D15"H x 7.3"W x 12"D15"H x 7.3"W x 12"D12"H x 8.1"W x 12"D
636 500 37GMDP0636D $11942.00 873 35.5"H x 24"W x 23.5"D 15"H x 7.3"W x 12"D15"H x 7.3"W x 12"D15"H x 7.3"W x 12"D
786 600 37GMDP0786D $13410.00 1082 35.5"H x 24"W x 24"D15"H x 7.3"W x 12"D15"H x 7.3"W x 12"D5.6"H x 5.6"W x 7.3"D
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-8
Capacitors, Arresters and Harmonic Filters Section 20Matrix Series D Harmonic FiltersOutlines and Dimensions
FRONT VIEWRIGHT SIDE VIEW
SPLASH GUARD
17.00REF.
7.00
24.00
9.31
12.54
14.75.41 X .88 SLOT (4) PLACES
23.00 WITH OPTIONALNEMA 3R WEATHERSHIELDS
17.89
.41 X .88 SLOT (4) PLACES
7.00
24.00REF.
31.00
14.31FRONT VIEW
17.54
17.75RIGHT SIDE VIEW
SPLASH GUARD
26.00 WITH OPTIONALNEMA 3R WEATHERSHIELDS
20.90
CAB-12C, 6-44 Amps
CAB-17C, 52-103 Amps
Figure 1 6–44 Amps
Figure 2 52–103 Amps
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-9
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20Matrix Series D Harmonic FiltersOutlines and Dimensions
21.75
30.00 WITH OPTIONALNEMA 3R WEATHERSHIELDS KIT
26.55
23.31FRONT VIEW
40.00REF.
47.00
RIGHT SIDE VIEW
7.00
24.90
SPLASH GUARD
.41 X .88 SLOT (4) PLACES
.41 X .88 SLOT (4) PLACES
FRONT VIEW
SPLASH GUARD
RIGHT SIDE VIEW
26.55
72.00
65.00REF.
7.00
21.75
34.00 WITH OPTIONALNEMA 3R WEATHERSHIELDS
24.90
23.31
CAB-26C, 128-240 Amps
CAB-26D, 320-482 Amps
Figure 3 128–240 Amps
Figure 4 320–482 Amps
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-10
Capacitors, Arresters and Harmonic Filters Section 20Matrix Series D Harmonic FiltersOutlines and Dimensions
82.00REF.
27.73 REF.27.31
30.55 31.35
40.00 WITH OPTIONALNEMA 3R WEATHERSHIELDS
CAB-30D, 636-786 Amps
Figure 5 636–786 Amps
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-11
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20Protective Capacitors for AC Rotating Machines Surge Protection for AC Generators, Synchronous Condensers and Large Motors
Protective capacitors offer surge protection for AC generators, synchronous condensersand large motors.
Dielektrol® is the GE non-PCB power capacitor dielectric system, developed to providean environmentally acceptable product with superior performance and reliability.
Protective capacitors contain a film dielectric and hermetically sealed bushings, which permit mounting of capacitors in an upright position or on the side. GE Surge Capacitors protect the winding insulation by reducing the steepness of wave fronts applied to or reflected within the machine windings.
Features and Benefits—Surge protection for AC Generators, synchronous condensers and large motors —Time proven GE HAZY film foil dielectric system—Dielektrol® Non-PCB insulating fluid—Provides Turn-to-Turn insulation protection by reducing steepness of wave fronts
applied to or reflected within the machine—Used in combination with TRANQUELL® station arresters for optimum protection—Protective capacitors contain a film dielectric and hermetically sealed bushings,
which permit mounting of capacitors in an upright position or on the side.—Altitude: 0 to 18,000 feet
*18L0004WH and 18L0005WH are rated for DC Applications
Product Number50/60 HZ
MaximumVoltage
rms Volts L-L
VoltageRating
rms Volts L-L
Approx. NetWeightMicrofarads
per PolePoles
per UnitList Price, 2.4-24kV
GO-412
13800 15180 18L0051WH $1325.00 1 0.5 49 22.3
Protective Capacitors
Dielektrol® Non-PCB Dielectric Protective Capacitors with Internal Discharge Resistors—Indoor or Outdoor Mounting
For other mounting arrangements contact the factory. 2400 and 4160 volt designs are identical and use the same product number. All units are provided with CSA labels.Units are not intended for upside down mounting except for product numbers 18L0060WH, 18L0061WH, and 18L0062WH.For up-to-date Capacitor Outline Drawings go to the web at www.ge-energy.com/ecatalog/html/index
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-12
Capacitors, Arresters and Harmonic Filters Section 20Protective Capacitors for AC Rotating MachinesSurge Protection for AC Generators, Synchronous Condensers and Large Motors
Protective Capacitors for AC Rotating Machines Guide for Superseded ModelsPresentModel
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-13
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20
DescriptionThese Type GEM™ capacitors are designed primarily for the motor requirements of oilfield and other pumping installations. Their application, however, may be extended toother motor applications installed indoor or outdoor. Type GEM™ OFW capacitors feature multiple cells which are assembled in parallel in a NEMA 3 enclosure. Eachcapacitor cell features the patented GE Pressure Sensitive Interrupter (PSI) that protectsagainst cell rupture. The metallized polypropylene film dielectric system provides an instantaneous self-healing action and greatly reduced energy losses.
Discharge resistors are included to reduce voltage to 50 volts or less within one minuteof de-energization. A 4 ft., 4-conductor flexible cable is provided for easy installation.
Type GEM™ capacitors offer high reliability and long life. They are suitable for operationover a temperature range of –40°C to +46°C. GEM™ also features Dielektrol® impregnantwhich is a biodegradable Class IIIB combustible fluid.
Note: To determine kVAR at 208V, multiply kVAR at 240V by .75.
kVAR
Dimensions (See Fig. 1)
Cable Size
List PriceEach,
GO-410Product Number
A B
240 Volts
480 Volts
Approx. Weight
Fixed Motor and Pump Capacitors (Type GEM™ OFW)Outdoor Weatherproof1-15 kVAR 240 Volts1-30 kVAR 480 VoltsThree-phase Delta, 60 Hertz
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-14
Capacitors, Arresters and Harmonic Filters Section 20Fixed Motor and Pump Capacitors (Type GEM™ OFW)
Figure 1
Dimensions
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-15
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20
Description
Type GEM™ Capacitors feature multiple cells which are assembled in parallel in an enclosure suitable for both indoor and outdoor applications (NEMA 12 and NEMA 3).Each capacitor cell features the patented GE Pressure Sensitive Interrupter (PSI) that pro-tects against cell rupture. The metallized polypropylene film dielectric system providesan instantaneous self-healing action and greatly reduced energy losses. GEM™ capaci-tors include discharge resistors to reduce voltage to 50 volts or less within one minute ofde-energization. GEM™ also features Dielektrol® impregnant which is a biodegradableClass IIIB combustible fluid.
GEM™ capacitors offer high reliability and long life. They are suitable for operation overa temperature range of –40°C to +46°.
The GEM™ assemblies are UL Listed and CSA labeled.
Line Fuses/Blown Fuse LightsTo be specified by customer. Order by appropriate basic product number plus suffix for a complete product number.
NOTE: NEC Article 460-8B requires capacitors to have overcurrent protection in allungrounded conductors—except if connected on the load side of a motor overload protective device.
MountingGEM™ 65L800 series can be mounted upright on any level surface, such as a floor, topof a motor control center, or directly to any wall with brackets provided.
GEM™ 65L900 series equipments can also be mounted upright on any level surface. An adapter kit is required for wall mounting. Order the wall mounting kit by productnumber 186C323600005, List Price $85.00, GO-410.
Line Connection and Cable EntranceLine connection and cable entrance on Figure 1 equipments must be made through theright end panel. For all other equipment figures the entrance may be made througheither end panel (after first punching out the appropriate size hole).
Replacement Fuses
NOTE: Replacement EDT/EWT Equipmentsincluding 55L series capacitors are available on request. Please contact thefactory. (For New Equipments use the 65L Series.)
Volts 3-ph1 kVAR
240 1-5 30 MIDGET 147A781600030 $11.00
240 6-15 100 T 147A781600028 $24.00
240 17.5-40 200 T 147A781600029 $24.00
480 1-12.5 30 MIDGET 147A781600030 $11.00
480 15-32.5 100 T 147A781600028 $24.00
480 35-100 200 T 147A781600029 $24.00
600 1-15 30 MIDGET 147A781600026 $11.00
600 17.5-40 100 T 147A781600028 $24.00
600 42.5-60 200 T 147A781600029 $24.00
GO-410List Price
Note: Obsolete fuses 147A781600024 and 147A781600025 used in 65L3___, 65L6___,and 37F6___ assemblies have been replaced by fuse kit 308A318700001, List Price $48.00, GO-410. 1Refer to factory for single-phase fuses.
Unit Rating
Fuse Amps Fuse Class Product Number
Typical Type GEM™, cover removed
Fixed Low Voltage Power Factor Correction CapacitorsEnclosed Indoor Dustproof NEMA 12 and Outdoor Weatherproof NEMA 3Single Phase or 3-Phase1.0-500 kVAR, 60 Hertz240, 480, 600 Volts
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-16
Capacitors, Arresters and Harmonic Filters Section 20
1 See Note on page 20-15 referring to NEC Article 460-8B.
3
3
3
3
Fixed Low Voltage Power Factor Correction CapacitorsEnclosed Indoor Dustproof NEMA 12 and Outdoor Weatherproof NEMA 3 Single Phase or 3-Phase 1.0-500 kVAR, 60 Hertz 240, 480, 600 Volts
EXAMPLE: 240V, 3-phase, 25 kVAR, with 3 fuses and 3 blown fuse lights:Product Number: 65L815TQ2, Price: $676.00Note: To determine kVAR at 208V, multiply kVAR at 240V by .75.Consult factory for additional Single-phase designs.
See page 20-22 for outline diagrams and dimensions.
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-17
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20
42.5-550 kVAR, 240 Volts
Fixed Low Voltage Power Factor Correction CapacitorsEnclosed Indoor Dustproof NEMA 12 and Outdoor Weatherproof NEMA 3 Single Phase or 3-Phase 1.0-500 kVAR, 60 Hertz 240, 480, 600 Volts
1 See Note on page 20-15 referring to NEC Article 460-8B.Consult factory for additional Single-phase designs.
Suffix GO-410List Price
GO-410List Price
GO-410List Price
GO-410List Price
GO-410List Price
GO-410List Price
Suffix Suffix Suffix Suffix Suffix Lb s K g
No Fuses1 3 Fuses1 3 Fuses, 3 Lights1Fig. No.
(See page 20-23)
Approx.Weight
240 Volt, 1-phase
No Fuses Fuses Fuses & Lights
kVARBasic
Product No.
240 Volt, 3-phase Delta
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-18
Capacitors, Arresters and Harmonic Filters Section 20
1.0-100 kVAR, 480 Volts
Fixed Low Voltage Power Factor Correction CapacitorsEnclosed Indoor Dustproof NEMA 12 and Outdoor Weatherproof NEMA 3Single Phase or 3 - Phase1.0-500 kVAR, 60 Hertz240, 480, 600 Volts
Suffix Suffix Suffix Suffix Suffix Suffix Lb s K g
1 See Note on page 20-15 referring to NEC Article 460-8B.
kVARBasic
Product No.
480 Volt, 3-phase Delta 480 Volt, 1-phase
No Fuses1 3 Fuses1 3 Fuses, 3 Lights1 No Fuses Fuses Fuses & Lights Fig. No.(See page
20-22)GO-410List Price
GO-410List Price
GO-410List Price
GO-410List Price
GO-410List Price
GO-410List Price
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-19
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20
110-500 kVAR, 480 Volts
Fixed Low Voltage Power Factor Correction CapacitorsEnclosed Indoor Dustproof NEMA 12 and Outdoor Weatherproof NEMA 3Single Phase or 3 - Phase1.0-500 kVAR, 60 Hertz240, 480, 600 Volts
Suffix Suffix Suffix Suffix Suffix Suffix Lb s K g
1 See Note on page 20-15 referring to NEC Article 460-8B.
Fig. No.(See page
20-23)
Approx.Weight
No Fuses1 3 Fuses1 3 Fuses, 3 Lights1 No Fuses Fuses Fuses & Lights
kVARBasic
Product No.
480 Volt, 3-phase Delta 480 Volt, 1-phase
GO-410List Price
GO-410List Price
GO-410List Price
GO-410List Price
GO-410List Price
GO-410List Price
EXAMPLE: 480V, 3-phase, 50 kVAR, with 3 fuses no lights:Product Number: 65L825TC1, Price: $547.00
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-20
Capacitors, Arresters and Harmonic Filters Section 20
See Note on page 20-15 referring to NEC Article 460-8B.1
GO-410List Price
GO-410List Price
GO-410List Price
Fixed Low Voltage Power Factor Correction CapacitorsEnclosed Indoor Dustproof NEMA 12 and Outdoor Weatherproof NEMA 3 Single Phase or 3-Phase 1.0-500 kVAR, 60 Hertz 240, 480, 600 Volts
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-21
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20
65-500 kVAR, 600 Volts
Fixed Low Voltage Power Factor Correction CapacitorsEnclosed Indoor Dustproof NEMA 12 and Outdoor Weatherproof NEMA 3 Single Phase or 3-Phase 1.0-500 kVAR, 60 Hertz 240, 480, 600 Volts
1See Note on page 20-15 referring to NEC Article 460-8B.
Suffix GO-410List Price
GO-410List Price
GO-410List Price
Suffix Suffix Lbs Kg
Approx.WeightFig. No.
(See page 20-23)kVAR Basic Product No.
600 Volt, 3-phase Wye
No Fuses1 3 Fuses1 3 Fuses, 3 Lights1
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-22
Capacitors, Arresters and Harmonic Filters Section 20
Dimensions
Fixed Low Voltage Power Factor Correction CapacitorsEnclosed Indoor Dustproof NEMA 12 and Outdoor Weatherproof NEMA 3Single Phase or 3-Phase1.0-500 kVAR, 60 Hertz240, 480, 600 Volts
Fig. 1. 65L8___ Fig. 2. 65L8
Fig. 3. 65L8___
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-23
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20
Dimensions
Fixed Low Voltage Power Factor Correction CapacitorsEnclosed Indoor Dustproof NEMA 12 and Outdoor Weatherproof NEMA 3Single Phase or 3 - Phase1.0-500 kVAR, 60 Hertz240, 480, 600 Volts
Fig. 4. 65L9___ Fig. 5. 65L9___ Fig. 8. All 65L9___ units
Fig. 6. 65L9___ Fig. 7. 65L9___
Front View Side View
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-24
Capacitors, Arresters and Harmonic Filters Section 20
ApplicationThe proliferation of electronic equipment used to improve efficiencies and provide more reliable performance causes har-monics on power systems. Equipment such as variable speed ACand DC drives, uninterruptible power supplies, switching powersupplies and other solid state controls or devices inject non-linearcomponents into what was a linear system. The application ofpower factor correction capacitor systems can create unwantedincreases in harmonic voltage and current unless the capacitorsare properly applied with reactors, in series with the capacitor, tosuppress harmful harmonics.
GE’s line of fixed, harmonically suppressed capacitors permits theinstallation of power factor correction capacitors on systems withnonlinear components. The GEMTRAP system can be tuned to anydesired frequency but is normally tuned to the 4.7th harmonic.
DesignThe installation of this system is application specific. Contact the GE Sales office or the factory to ensure that the proper combina-tion of capacitors and reactors is used. Misapplication may resultwithout proper guidance.
Engineering Specifications Fixed Power Factor Capacitor Equipment
Applicable Standards—NEMA, IEEE/ANSI, NEC
Ratings—240V, 25 to 50 kVAR; 3 ph—480 V, 25 to 200 kVAR; 3 ph—600 V; 25 to 200 kVAR; 3 ph
Capacitor Cell—Industrial Rated Capacitor cells
Fixed Low Voltage Power Factor Correction with Harmonic Filter EquipmentMetal-Enclosed (GEMTRAP)
Equipment Construction—Enclosure and wiring hood:
—Indoor/outdoor gasketed heavy gauge steel. Finished with azinc rich primer and an ANSI #70 enamel overcoat. Louveredpanels around reactors for protection and cooling.
—Mounting:—Floor mounting.
—Capacitor Fuses:—UL recognized, designed specifically for capacitor applica-
tions. Rated 600 VAC, 200kAIC. Fast acting and currentlimiting; allows clearing action of capacitors while protectingfrom catastrophic failures. Three phase fusing standard.
—Aluminum Connecting Bus for Parallel Cells
—Input Connections:—Listed Cu/Al Mechanical wire connectors, sized for kVAR
requirements, mounted on top of bus for easy access.
—Harmonic Reactor
Options—Blown fuse lights—Consult factory for larger kVAR requirements—Consult factory for custom applications and designs
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-25
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20Fixed Low Voltage Power Factor Correction with Harmonic Filter EquipmentMetal-Enclosed (GEMTRAP)Three-phase, 60Hz240, 480, 600 VoltsNEMA 1 Enclosure
Normally tuned for the 4.7th HarmonicCan be tuned to any desired frequency.
Note: Do not apply Harmonic Filters without a detailed analysis of the power system.
System Analysis RequirementsPrimary VoltsTransformer: L - L kVASecondary VoltsTransformer: kVATransformer impedance %Fundamental Freq. HzTotal System Load KWPower Factor:
Existing: %Desired %
Include One-Line diagram, if availableHarmonic Analysis: Voltage/Current Spectrum
Outline Dimensions (inches)
Fig. List Price, GO-410 Suffix List Price, GO-410
240 25 38FH1025D333F 1 $4100.00 L $4260.00 195 (88)
240 35 38FH2035D333F 2 $7500.00 L $7660.00 341 (155)
240 40 38FH2040D333F 2 $7600.00 L $7760.00 346 (157)
240 45 38FH2045D333F 2 $7700.00 L $7860.00 351 (160)
240 50 38FH2050D333F 2 $7800.00 L $7960.00 356 (162)
480 25 38FH1025F333F 1 $3750.00 L $3910.00 159 (72)
480 30 38FH1030F333F 1 $3150.00 L $3310.00 191 (87)
480 40 38FH1040F333F 1 $3200.00 L $3360.00 197 (90)
480 50 38FH1050F333F 1 $3250.00 L $3410.00 202 (92)
480 75 38FH1075F333F 1 $4125.00 L $4285.00 235 (107)
480 80 38FH1080F333F 1 $4000.00 L $4160.00 263 (120)
480 100 38FH1100F333F 1 $4500.00 L $4660.00 279 (127)
480 120 38FH2120F333F 2 $7800.00 L $7960.00 424 (195)
480 125 38FH2125F333F 2 $6875.00 L $7035.00 447 (203)
480 140 38FH2140F333F 2 $7700.00 L $7860.00 500 (227)
480 150 38FH2150F333F 2 $8250.00 L $8410.00 514 (234)
480 175 38FH2175F333F 2 $8750.00 L $8910.00 524 (238)
480 200 38FH2200F333F 2 $8400.00 L $8560.00 568 (258)
600 25 38FH1025H333F 1 $3750.00 L $3910.00 159 (72)
600 30 38FH1030H333F 1 $3150.00 L $3310.00 191 (87)
600 40 38FH1040H333F 1 $3200.00 L $3360.00 196 (89)
600 50 38FH1050H333F 1 $3250.00 L $3410.00 196 (89)
600 75 38FH1075H333F 1 $4125.00 L $4285.00 245 (111)
600 80 38FH1080H333F 1 $4000.00 L $4160.00 248 (113)
600 100 38FH1100H333F 1 $4500.00 L $4660.00 271 (123)
600 120 38FH2120H333F 2 $7800.00 L $7960.00 484 (220)
600 125 38FH2125H333F 2 $6875.00 L $7035.00 487 (221)
600 140 38FH2140H333F 2 $7700.00 L $7860.00 495 (225)
600 150 38FH2150H333F 2 $8250.00 L $8410.00 500 (227)
600 175 38FH2175H333F 2 $8750.00 L $8910.00 526 (239)
600 200 38FH2200H333F 2 $8400.00 L $8560.00 552 (251)
Apprx. Wt. Lbs. (kg)
Caps with ReactorsIncl (3) Fuses With Lights
Volts kVAR Basic Product No.
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-26
Capacitors, Arresters and Harmonic Filters Section 20Automatic Fast-Switching LV Power Factor Correction CapacitorsGEMATIC® Quick Response
Fast Response, Transient-Free Reactive Power Compensation Systems—Ultra Fast Response (UFR): A real-time, transient-free system
used to compensate extremely rapid loads within one cycle(typically 5-16 mSec).
—Fast Response (FR): A fast, transient-free system, used to compensate any load within 3-4 seconds.
Advantages—Ultra Fast Response (UFR) and Fast Response (FR):
—Transient-free capacitor group switching, using electronicswitching elements
—Prevent damage to sensitive electronic equipment—Saves energy—Harmonic filtration—Accurate power factor control, even in the presence of
harmonics—Dramatically increases the life expectancy of switching
elements and capacitors—Considerably lower temperature rise of capacitors and
inductors due to unique scan feature—Built-in three phase network analyzer, measuring all network
parameters including harmonics—Unique self-testing and comprehensive reporting feature—Power IQ
—Ultra Fast Response (UFR) (in addition to the above):
—Cycle-by-cycle reactive power compensation (total acquisitiontime of 5-16 mSec)
—Prevents voltage drop and flickering—Used for Real Time applications, such as spot welding and
motor start-up—Enhances capacity of local generator systems, such as diesel
and windmill generators—Combination of one to three single-phase systems available
for unbalanced loads
Types Available—Basic Systems: Include iron core reactors to limit the inrush
current with either:—Detuned Systems: Include iron core reactors that detune the
network to prevent resonance and absorb up to 50% of the5th harmonic, or
—Tuned Systems: Individually designed to absorb the 5th and7th harmonics
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-27
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20Automatic Fast-Switching LV Power FactorCorrection CapacitorsGEMATIC® Quick Response
Controller SpecificationsPower Supply 115/230V, 50/60 HzLCD Display Size 94 x 76 mmLCD Display Resolution Graphic 160 x 128 pixelsLCD Display Type FSTN, LED backlightFrequency 45 to 65 HzPower Consumption 10 VAOperating Temperature -20° to +55°C9 Analog Channels 3 current channels for mains load
2 current channels for Equalizer cabinet4 voltage channels
Communications RS485/422 communications portProtocol ELCOM, Modbus/RTUAlarm Voltage free N.O./N.C. relay, max 2A @ 250 VacProtection Class IP 40Dimensions 144 x 144 x 138 mmWeight 1.4kgStorage Temperature -25° to 70°CElectromagnetic Compatibility EN50081-2, EN50082-2, EN55011,
Parameter Phases Loads 1 2 3 4Frequency Common Mains • • • •Phase Current L1, L2, L3 Mains, Load, Cap. • • • •Neutral Current Neutral Mains • • • •Phase to Phase Current L1-2, L2-3, L3-1 Mains, Load • • • •Phase Voltage L1, L2, L3 Mains • • • •Neutral Voltage Neutral Mains • • • •Phase to Phase Voltage L1-2, L2-3, L3-1 Mains • • • •Active Power (kW) L1, L2, L3, Total Mains • • • •Reactive Power (kVAr) L1, L2, L3, Total Mains, Load, Cap. • • • •Apparent Power (kVA) L1, L2, L3, Total Mains, Load, Cap. • • • •Power Factor L1, L2, L3, Total Mains, Load, Cap. • • • •Time of use (TOU) — in, out, net, total:
Active Energy (kWh) Total Mains • • •Reactive Energy (kVARh) Total Mains • • •
THD at Phase Current L1, L2, L3 Mains, Load, Cap. • • •THD at Neutral Current Neutral Mains • • •THD at Phase to Phase Current L1-2, L2-3, L3-1 Mains, Load • • •THD at Phase Voltage L1, L2, L3 Mains • • •THD at Neutral Voltage Neutral Mains • • •THD at Phase to Phase Voltage L1-2, L2-3, L3-1 Mains • • •Harmonics of Phase Current L1, L2, L3 Mains, Load, Cap. • •Harmonics of Neutral Current Neutral Mains • •Harmonics of Ph. to Ph. Current L1-2, L2-3, L3-1 Mains, Load • •Harmonics of Phase Voltage L1, L2, L3 Mains • •Harmonics of Neutral Voltage Neutral Mains • •Harmonics of Ph. to Ph. Voltage L1-2, L2-3, L3-1 Mains • •Waveforms of Phase Current L1, L2, L3 Mains, Load, Cap. • •Waveforms of Neutral Current Neutral Mains • •Waveforms of Ph. to Ph. Current L1-2, L2-3, L3-1 Mains • •Waveforms of Phase Voltage L1, L2, L3 Mains • •Waveforms of Neutral Voltage Neutral Mains • •Waveforms of Ph. to Ph. Voltage L1-2, L2-3, L3-1 Mains • •System Log • • • •Event Log •Data Log (future) •
Typical Screens
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-28
Capacitors, Arresters and Harmonic Filters Section 20Automatic Fast-Switching LV Power FactorCorrection CapacitorsGEMATIC® Quick Response
Capacitor/Reactor Module
Iron Core Limiting Capacitors
Iron Core Tuned or Detuned Reactor Capacitors
Switching Module
Power IQ Measurement and Analysis Software
This software displays the system status as well as the measurement results on numer-ous screens running under Windows. All network parameters, including harmonics up tothe 63rd, can be recorded at preselected intervals. The duration of the recording is onlylimited to the size of the computer’s hard disk. The software can be set to record databased on selected triggers of various network parameters, such as voltage sags and/orcurrent spikes. The system records before and after the trigger event. The software hasintranet and internet support.
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-29
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20Automatic Fast-Switching LV Power FactorCorrection CapacitorsGEMATIC® Quick Response
Features—Design
—Steel sheet cabinet
—Enclosure Finish—Epoxy powder coated, in gray (RAL 7032)—Internal parts rust proof aluzinc
—Rated Voltage—400V/50 Hz and 480V/60 Hz—Other voltage values are available upon request
—Output rating—Refer to table—Other output ratings are available upon request
—Capacitors—Low loss, self-healing, IEC 831-1/2
—Ambient Temperature— +40°C max short time— +35°C average in 24 hours— +20°C annual average— -10°C low limit
GEMATIC® Quick Response – Fast Response (3-4 sec.)Output per Cabinet Dimensions
Output (kVAR) Step (kVAR) W x D x HProduct Number 480V/60 Hz 480V/60 Hz Ratio (mm) (in)
38FE3156F315F 156 31 1:2:2 1400 x 600 x 2100 55 x 24 x 8338FE3187F385F 187 37.5 1:2:2 1400 x 600 x 2100 55 x 24 x 8338FE3219F315F 219 31 1:2:4 1400 x 600 x 2100 55 x 24 x 8338FE3250F505F 250 50 1:2:2 1400 x 600 x 2100 55 x 24 x 8338FE3262F385F 262 37.5 1:2:4 1400 x 600 x 2100 55 x 24 x 8338FE3312F635F 312 62.5 1:2:2 1400 x 600 x 2100 55 x 24 x 8338FE3375F755F 375 75 1:2:2 1400 x 600 x 2100 55 x 24 x 8338FE3437F635F 437 62.5 1:2:4 1400 x 600 x 2100 55 x 24 x 8338FE3450FF05F 450 150 1:1:1 1400 x 600 x 2100 55 x 24 x 8338FE4525F755F 525 75 1:2:2 1600 x 600 x 2100 63 x 24 x 8338FE4600FF05F 600 150 1:1:1 1600 x 600 x 2100 63 x 24 x 8338FE6600FA05F 600 100 1:1:1 2200 x 600 x 2100 87 x 24 x 8338FE6687F635F 687 62.5 1:2:2 2200 x 600 x 2100 87 x 24 x 8338FE6750FC55F 750 125 1:1:1 2200 x 600 x 2100 87 x 24 x 8338FE6825F755F 825 75 1:2:2 2200 x 600 x 2100 87 x 24 x 8338FE6900FF05F 900 150 1:1:1 2200 x 600 x 2100 87 x 24 x 8338FE9B25FC55F 1125 125 1:1:1 3000 x 600 x 2100 118 x 24 x 8338FE9D50FF05F 1350 150 1:1:1 3000 x 600 x 2100 118 x 24 x 8338FECF00FC55F 1500 125 1:1:1 3800 x 600 x 2100 150 x 24 x 8338FECI00FF05F 1800 150 1:1:1 3800 x 600 x 2100 150 x 24 x 83
Standard Balanced Systems for 480V/60 Hz Networks—Systems with inrush limiting reactors—Detuned systems with tuning frequency of 245 Hz (4.08th
Harmonic at 480Vac/60 Hz) up to 100kVAR per group at400V/50 Hz
—Tuned systems with tuning frequency of 282 Hz (4.7th Harmonic at 480Vac/60 Hz)
Non-Standard Systems (550V-1000V 50/60 Hz or 100V-240V 50/60 Hz)—With circuit breaker or load breaker—With or without busbar connection—Single cabinet—Dual door single cabinet—Mechanical structure and dimensions of larger systems are
available upon request
Option PackagesF ReactorsG Lights and ReactorsW Lights, Breaker and Reactors
For pricing, contact One-Stop or Factory.
GEMATIC® Quick Response Ultra Fast Response (UFR) (5-16 mSec)requires special application for selection and sizing. Contact fac-tory for application assistance.
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-30
Capacitors, Arresters and Harmonic Filters Section 20
DescriptionGEMATIC® multi-step power factor control equipment automati-cally maintains desired power factor level, adjusting to systemload requirements in selected kVAR steps. The solid-state controlresponds to a current signal from the optional current trans-former and to a voltage signal from a potential transformerincluded in the equipment.
GEMATIC® equipments feature capacitors with a metallized dielec-tric system providing a self-healing action and reduced energylosses. The biodegradable impregnant is a class IIIB combustiblefluid. Discharge resistors reduce the voltage to 50 volts or lesswithin one minute of de-energization. The capacitor cells are 3phase and are designed for 110% of rated voltage, 135% of ratedcurrent, and, 135% of rated kVAR.
The power factor controller requires a CT signal for operation. TheCT primary should be sized for the total phase current to be com-pensated (capacitor current and load current). Typically, the totalphase current should be 50% to 80% of the CT primary rating. TheCT secondary is rated 5A. The CT is connected to one phase of theequipment and the factory installed PT is connected across theother two phases.
Automatic LV Power Factor Correction CapacitorsType GEMATIC® Compact and GEMATIC® SelectThree-phase, 60 Hertz240, 480, 600 Volts
GEMATIC® equipment includes:—Solid-state multi-step power factory controller with digital
display and indication of loss of kVAR or blown fuse—Three phase self-healing metallized capacitors—Stage contactors—Potential transformer—Plated copper bus—Three fuses for each stage—Modular construction easily uprated—UL and C-UL Listed
Automatic LV Power Factor Correction CapacitorsType GEMATIC® Compact and GEMATIC® SelectThree Phase, 60 Hertz240, 480, 600 Volts
GEMATIC® Compact 480/600 volts
GEMATIC® Compact 240 volts
GEMATIC® Select 240 voltsExample of GEMATIC® Select Product Number. 300kVAR, 480V, with Lights, Breaker and copper bus, 37FC6300F505R0.
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-32
Capacitors, Arresters and Harmonic Filters Section 20
Suffix Option
L Indicating Lights
BreakerB
R Lights & Breaker
Ratio Product Number GO-410List Price
Multitap w/ Ratio
XT0-69752-0105G $350.00800/1200/1500/2000/
2200/2500/3000 : 5
4000 : 5 XT0-69752-0011G $400.00
Automatic LV Power Factor Correction CapacitorsType GEMATIC® Compact and GEMATIC® SelectThree Phase, 60 Hertz240, 480, 600 Volts
For 600 volts, replace second “F” in the basic product number with an “H”. (e.g.37FC3100F255 becomes 37FC3100H255).
For NEMA 12 enclosure, replace “C” in the basic product number with “O”, Price Adder, $750.00, GO-410 (e.g., 37FC8400F505 becomes 37FO8400F505). For bottomentry last digit of Product Number changes from “5” to “6” (e.g., 37FC8400F505 becomes37FC8400F506).
Option Packages
Note: Add only one suffix letter to the end of product numbers
For breakers add the following code for standard breaker optionCurrent Rating kAIC Rating Code for Standard Breaker Option
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-33
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20
Type GEMATIC® CustomThe GEMATIC® Custom offers power factor correction with theflexibility of including harmonic filter reactors initially or addingthem later if they are required.
Many of today’s power systems require modern solutions topower factor correction. The rapid increase in variable speeddrive use and other solid state devices has resulted in severeharmonic loads on power systems. GE has 10 years experience in preventing the occurrence of non-sinusoidal resonance.Successful integration in tuned L-C networks solves the problemof parallel resonance.
GEMATIC® Custom automatic power factor correction systemswith 3-phase harmonic suppression reactors are applicationspecific. Accordingly, each installation requires specificinformation to aid GE application engineers in designing eachsystem to meet your requirements. This information shouldinclude, but not be limited to, kVAR requirements, transformer sizeand impedance, kVAsc of the transformer, and a harmonic profileof your system. Load characteristic at the time of the survey andworst case should also be included.
The GEMATIC® Custom systems may be configured for the addition of harmonic suppression reactors in the future to meetthe imminent needs of your system. This reduces initialinvestment and provides a ready made retrofit package. Thissystem provides total flexibility in achieving maximum automaticpower factor correction. Please contact the local GE sales officeor the GE factory for any assistance with your particular powerfactor correction and harmonic suppression needs.
Automatic LV Power Factor Correction Capacitors and Harmonic Filter Equipment
Applicable Standards—NEMA, IEEE/ANSI, NEC
GEMATIC® Custom Optional Features—Outdoor NEMA 3R enclosure—100 kAIC bus bracing—Main breaker—Iron core reactors—Blown fuse indicating lights
GEMATIC® Custom includes—Solid-state multi-step power factor controller with digital
display and indication of loss of kVAR or blown fuse—Three phase self-healing metallized capacitors—Stage contactors—Three fuses for each stage—Potential transformer—Plated copper bus, 75 kAIC bracing —NEMA 1 enclosure—UL and cUL listed
Ratings—240 V; up to 300 kVAR—480 V and 600 V; up to 1500 kVAR—For larger kVAR ratings, contact factory
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-34
Capacitors, Arresters and Harmonic Filters Section 20Automatic LV Power Factor Correction Capacitors and Harmonic Filter EquipmentOutline Dimensions (inches)
Optional Features: R—Outdoor NEMA 3R Enclosure (Change prefix 38FP to 38FR)
1Price includes cabinet adder for breaker. 2Enclosure width increases by one section with breaker.For ratings not listed consult factory.Add breaker code suffix shown on page 20-32 GEMATIC compact and select.For reverse entry last digit of Product Number changes from "5" to "7."
For bottom entry "5" changes to "6" and "7" changes to "8." Bottom entry may change equipment width. Consult factory or e-catalog for dimension and pricing of bottom entry.
Options—List Price GO-410, Each
Total kVAR
ProductNumber
kVAR/Step
Basic List Price,
GO-410Enclosure Width
(# of Sections)
GEMATIC® CustomThree-phase, 60 Hz NEMA 1 or 3REnclosure supplied with or without reactors tuned to the 4.7th Harmonic.Option Suffix
Lights LBreaker BReactors FLights and Breaker RLights and Reactors GLights, Breaker, and Reactors WBreaker and Reactors K
Section Dimensions A B
NEMA 1 25” 35”NEMA 3R 24 36
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-35
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20
GE GEMACTIVE Active Harmonic Filter—Dynamic current injection for harmonic cancellation and
power factor correction—Reduces harmonics for IEEE 519 (1992) standard compliance—Decreases harmonic related overheating of cables, switchgear
and transformers—Reduces downtime caused by nuisance thermal tripping of
protective devices—Increases electrical network reliability and reduces operating costs—Compensates each phase independently—UL and CSA approved—Parallel connection allows for easy retrofit and installation
of multiple units for large networks—Filters to the 50th harmonic—Filters entire network or specific loads depending on
installation point—Response to load fluctuations begins in 40 microseconds with
8 milliseconds for full response to step load changes—IGBT based power electronic technology—50, 100 and 300A models for 208 to 480V, 50/60 Hz three-
phase networks
GE GEMACTIVE reduces problematic harmonic levels and providesinstantaneous power factor correction. Cost savings result fromreduced downtime and maintenance. In addition, over-sizing of distribution equipment to provide for harmonics and poor power factor can be avoided. GE GEMACTIVE dynamically corrects powerquality by providing: Active Harmonic Filtration, ResonancePrevention, Power Factor Correction and Dynamic VARCompensation.
Active Harmonic Filter
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-36
Capacitors, Arresters and Harmonic Filters Section 20
Dynamic VAR Compensation by GEMACTIVELarge inductive inrush currents typically cause voltage sags thatresult in reduced productivity, poor process quality and possibledowntime due to undervoltage tripping of devices.
GEMACTIVE is able to inject peak current at two and a half timesits rms current rating for one cycle. For many applications thislevel of compensation eliminates visible flicker and improves voltage regulation resulting in better productivity and quality.
GEMACTIVE SizingA harmonic study is not required to select the size of the GEMACTIVE installation. This is because when GEMACTIVE isinstalled it becomes a lower impedance path for harmonics than the existing power supply. For sizing, please contact GE. To expedite the product selection process, please have a singleline diagram and/or details of the application including sizes of transformers, non-linear and linear loads, and any existing filtersand capacitors.
Active Harmonic Filter
Fig. 1: Non-linear current waveform with poor power factor
Fig. 2: Corrected Current waveform with improved power factor and reduced harmonic content after Active Harmonic Filter Installation
Fig. 3: Inrush Current without Active Harmonic Filter
Fig. 4: Inrush Current with Active Harmonic Filter
Active Filter Three-phase 60/50HzCurrent Enclosure 240/480V List PriceRating Type Product Number GO-410B
50 NEMA 1 37GA050FG $21500.00Chassis 37GA050FC $19950.00
100 NEMA 1 37GA100FG $31800.00Chassis 37GA100FC $30100.00
300 NEMA 1 37GA300FG $63600.00Chassis 37GA300FC $60450.00
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-37
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20
ApplicationType HWT equipments are suitable for use on indoor or outdoor primary circuits where small amounts of kVAR are required. Theymay be installed at load centers or directly at the terminals of2300 and 4000 volt motors. Permissible ambient temperaturesare –40° to +45°C. Discharge resistors in each capacitor reducethe voltage to 50 volts or less within 5 minutes of de-energization.
Type HWT equipments contain less than three gallons of flamma-ble liquid in a single container and therefore do not requireinstallation in a vault to meet the NEC.
Line TerminalsSolderless connectors are provided on each phase:
Assembly Connector Size
One unit #10 - #4
Two unit #14 - 1/0
Three unit #6 - 250 kcmil
Fixed MV Power Factor Correction CapacitorsEnclosed Indoor Dustproof and Outdoor Weatherproof25-900 kVAR, 60 Hz2400, 4160, 4800 Volts1.0-200 kVAR, 240 Volt
FusesProtection is provided by 50,000 ampere interrupting capacity current limiting fuses. A pop-up button on the fuse gives visual indication of a blown fuse. GE recommends the use of three fusesfor the most complete protection against terminal-to-terminaland terminal-to-ground failures on grounded systems. Two fusesare sufficient to provide protection against terminal-to-terminalfailures on ungrounded systems.
Blown Fuse LightsBlown fuse lights provide a positive external indication of an operated fuse. A glowing light makes inspection of capacitorseasy, effective, and safe. A 120 VAC source must be suppliedexternally. When ordered with this option, the HWT assembly is supplied with one light per capacitor.
For higher voltage designs, contact factory or consult e-catalog.
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-38
Capacitors, Arresters and Harmonic Filters Section 20Fixed MV Power Factor Correction Capacitors
Complete Assemblies Including Terminal Box, Fuses and Mounting Frame
1When replacing rack mounted RS or US unit with WS unit, ask for bracket adapters. Order two 251A639700051 and two 115A189300009 at NO CHARGE.2Top and Bottom fuse adapters needed, one each per fuse: Order Product No. 308A390100001 $17.60 List, GO-410A.
This is a kit that contains one top and one bottom adapter. For units tested and labeled per CSA Standard, add 037 suffix.
List Price GO-410A2400 volts 4160 volts 4800 volts
Fixed MV Power Factor Correction CapacitorsEnclosed Indoor Dustproof and Outdoor Weatherproof25-900 kVAR, 60 Hz2400, 4160, 4800 Volt
DimensionsHWT Assemblies Including Terminal Box, 2 Fuses Per Unit and Mounting Frame
Fig. 1 Fig. 2 Fig. 3
Fig. 4 Fig. 5 Fig. 6
Replacement Capacitor Units1 and Fuses2
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-40
Capacitors, Arresters and Harmonic Filters Section 20
Film/Foil Dielektrol® is the GE non-PCB low loss power capacitor dielectric system, developed to provide lower operating costs andgreatly enhanced fuse coordination for the prevention of case ruptures. The Dielektrol® insulating liquid is a Class IIIB combustible fluid.
—These capacitors are designed to meet ANSI Std 18—Units for special applications (i.e. system harmonics) or other non-standard capacitors, contact Product Department or visit
www.ge.com/energy—CSA labeling available upon request
High Voltage Capacitor Units, Single and Three-PhaseStandard Duty(Film/Foil Designs w/Dielektrol®)50-600 kVAR, 60 Hertz2400-24,940 Volts
Single Phase Standard Ratings and Product Numbers1
50 kVAR 100 kVAR 150 kVAR 200 kVAR
Voltage BIL 1 Bushing 2 Bushing 1 Bushing 2 Bushing 1 Bushing 2 Bushing 1 Bushing 2 Bushing
1Larger kVAR units, extra creep options and other voltages are available. Consult factory for product numbers and pricing.
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-41
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20High Voltage Capacitor Units, Single- and Three-PhaseHeavy DutyFilm/Foil Designs w/Dielektrol®)50-600 kVAR, 60 Hertz2400-24,940 Volts
GE Heavy Duty all-film capacitors are designed, manufactured, and tested to meet the requirements of all applicable ANSI/IEEE,NEMA, and IEC standards. In addition they are designed to exceed the requirements of these standards in terms of continuous rmsand peak overvoltage withstand capabilities. They are good for 125% continuous rms overvoltage capability and 135% peak over -voltage capability. These capacitors are suitable for industrial power systems that have higher voltages or harmonic loads. CSALabeling available upon request and 50 HZ designs also available upon request.
GE Heavy Duty 125% Continuous Overvoltage Capability Product Numbers50 KVAR 100 KVAR 150KVAR 200KVAR
Voltage BIL 1 Bushing 2 Bushing 1 Bushing 2 Bushing 1 Bushing 2 Bushing 1 Bushing 2 Bushing
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-42
Capacitors, Arresters and Harmonic Filters Section 20High Voltage Capacitor Units, Single- and Three-Phase
For up to date Capacitor Outline Drawings go to the web:—Go to http://www.ge-energy.com/ecatalog/html/index—Select Capacitors and input voltage, kVAR, and number of
bushings—Click search to bring up matches —Select the appropriate match by clicking on the product
number; this will pull up information on the capacitor with theopportunity to select additional resources where an outlinedrawing can be selected
Single-Phase Unit PricesList Price Each, GO 411 Standard BIL
Standard Duty Heavy Duty15,000 Volts 15,000 Volts andand Below 2770 Above Below Except 2400 & 2770 Above
kVar Bushing Except 2770 Volts Volt Units 15,000 Volts 2400 & 2770 Volts Volt Units 15,000 Volts
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-43
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20
Pole Mounted Racks Factory Assembled—Welded
Field Assembly—Bolted1
Bird Caps/Wildlife Protectors
Description Product Number GO-411BList Price
Capacitor Bird Caps with Sleeve 614A507000101 $8.00
Total Capacity # of Units BIL Product Number GO-411BList Price
3 95 39F0083004 $200.00
3 125 39F0083015 $220.00
6 95 39F0086010 $225.00
6 125 39F0086011 $245.00
1Field assembly racks are for fixed applications only and will not support the addition of switches.
Total Unit Capacity
Product Number
ProductNumberGO-411B
List PriceGO-411BList Price
3 33F10AA002 $345.00 33F24AA004 $365.00
6 33F10BA002 $390.00 33F26BA004 $410.00
9 33F10CA002 $435.00 33F26CA004 $455.00
12 33F10DA002 $480.00 33F26DA004 $500.00
95kV-BIL 125kV-BIL
Fuse Holders
Flipper Springs
HV Fuses and Fuse Links
Drawing Number Application GO-411BList Price
248A695400001 Upright $8.00
248A695400002 Edgemount $8.00
Drawing Number EEI-NEMA GO-411BList Price
115A162000078 8T $10.50
115A162000079 10T $10.50
115A162000080 12T $10.50
115A162000063 15T $10.50
115A162000081 20T $10.50
115A162000035 25T $10.50
115A162000053 30T $10.50
115A162000036 40T $10.50
115A162000043 50K $10.50
115A162000024 65K $10.50
115A162000059 80K $18.50
115A162000025 100K $18.50
Current Interrupting
31F2807001 15 50 3600 amp. Sym $34.00
31F2808001 23 25 3600/1800 amp. Sym $36.00
115A161500041 8 100 7400 amp. Sym $128.00
115A161500049 25 50 1800 amp. Sym $162.00
Rating
kVProduct Number GO-411BList Price
Three Phase Cantilever Mount UnitsThese three-phase capacitor units use the same technology as our single-phase unitsand when mounted directly to a pole offer a convenient single piece alternative to amulti-unit pole mount rack.
High Voltage Capacitor Units, Single- and Three-PhaseThree-Phase Units and Accessories
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-44
Capacitors, Arresters and Harmonic Filters Section 20
Pole Mounted Equipment DescriptionThese equipments are pre-wired, factory assembled, and shipped ready for pole installa-tion with single-phase units. Racks are of welded structural aluminum and are suitablefor mounting switches and junction box and cable assembly. Lightning arresters and/orpotential transformers can also be mounted.
Required Data for Pole-Type Quotation:The following questions must be answered before contacting the factory for a quotation.
1. Total kVAR? ________2. Line-to-line (system) voltage? ________3. Line-to-neutral voltage? ________4. Bank connection — Delta, Grounded Wye, or Floating Wye? ________5. Fixed or switched? _________
(check one)a. Fixed expandable (switches later) _________b. Fixed nonexpandable (no switches later) ________c. Switch type (vacuum or oil) ________
6. Number of capacitor bushings (1 or 2)? ______ BIL (Basic Insulation Level) ____7. Options (specify):
a. Current transformerb. Potential transformerc. Lightning arrestersd. Switching controls (example: voltage, current, kVAR, time controls)e. Other. Please specify __________________________________________________
Open Stack-Rack Equipment DescriptionThis application is most popular for large blocks of three-phase Kilovar. Capacitor unitsand individual fuses are installed in welded aluminum racks, either upright or edge-mount. Racks are shipped ready for field installation with base and inter-rack insulators,substructure, interconnecting bus wire and other accessories for a three-phase equipment. Harmonic filter banks are available. Submit complete specifications including harmonic currents and voltages.
Required Data for Stack-Rack Quotation:The following questions must be answered before contacting the factory for a quotation.
1. Total kVAR? ________2. Line-to-line (system) voltage? ________3. Bank connection — Floating Wye, Grounded Wye, Delta, or Double Wye1? ______4. Fixed or switched2? ________
a. If switched, how many steps? _________________b. If switched, how many kVAR per step? ________________
5. Is substructure required (8 ft. standard)? ________6. Space limitations (if any). Please specify____________________________________7. Options (specify):
a. Current transformerb. Potential transformerc. Ground switch (phase, neutral, both)d. Other. Please specify __________________________________________________
8. When optional apparatus is requested, state the available short circuit currentfor proper sizing of the options.
1Three-phase, 60 Hertz is assumed. Specify if different.2If switched:
a. Supply specification on switch requested.b. Advise if any parallel banks and ratings.
Typical in-line pole-type equipment ,single-phase units
Upright stack-rack equipment
Edgemount stack-rack equipment
High Voltage Pole-Mounted, Open Stack-Rack and Metal Enclosed EquipmentPole-type Equipment Metal Enclosed150-3600 kVAR, 60 Hertz 2.4 through 38kVOpen Stack-rack Banks 150 kVAR and above1200 kVAR and above, 60 Hertz
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-45
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20
These power factor correction equipments are metal enclosed for indoor and outdoorinstallations. These banks can be located on a distribution feeder as a small padmountor at the workstation site. Banks are shipped ready for installation. Banks can be provid-ed with the following options: oil or vacuum switching, automatic control and protection,stainless steel housing, custom colors, key mechnical or electrical interlocks, capacitorremoval device, NEMA 1, 3R, 4, 4X or 12 enclosures.
Required Data for Metal Enclosed Quotation:The following questions must be answered before contacting the factory for a quotation.
1.Total kVAR? ________
2.Line-to-line (system) voltage? ________
3. Bank connection - Floating Wye, Grounded Wye, Delta, or Double Wye ?________When in doubt Floating Wye is typically the best choice to avoid fault protection issues
4. Fixed or switched? ___________a. If switched do you want automatic control? ________b. If switched, how many steps? ________c. If switched, how many kVAR per step? ________
5.Space or access limitations (if any). Please specify ________
6.Type of Enclosure (Indoor or Outdoor; is Stainless Steel required)
7. Options (specify):Incoming Air Disconnect ________Main Incoming fuses (capacitors will be individually fused as standard practice) ___________Ground switch (phase, neutral, both) ________Power factor Controller (see 4a above) ________Key Interlocks ________Blown fuse Detection System ________Control Power Transformer ________Arresters - Distribution, Intermediate or Station class ________Incoming Breaker ________Power Quality Meter ________Overload protection (Yes or No) ________Overvoltage protection (Yes or No) ________Relay requirememts (class, type, brand, other please specify) ________Other. Please specify _________________________________________
8. When optional apparatus is requested, state the available short circuit current for proper sizing of the options. ___________________________________
9. Harmonic Filter Bank (Yes or No) ________If yes, tuning point (5th, 7th, 11th, ...) ________
High Voltage Pole-Mounted, Open Stack-Rack and Metal Enclosed EquipmentMetal Enclosed Capacitor Banks 2.4 thru 38KV
Metal Enclosed Cabinet
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-46
Capacitors, Arresters and Harmonic Filters Section 20
ApplicationSingle-pole, remote-control, outdoor oil switch is a completelyself-contained, motor-operated, nonautomatic device. Application is the switching of line or station capacitor banks.
Oil Switches—Motor Operated1
Number Rating Product List Price Weightof Poles Number GO-411A Lb Kg
1 Disconnect plug for receptacle, Model No. 9F90AAW027 $51.002 Bushing Caps, Model No. 115A168500591 $15.00
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-47
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20
This HESP design is intended for mounting in OEM equipment orin an existing enclosure to offer protection against internally andexternally generated surges. UL-1449, Second Edition RecognizedComponent designed and tested according to ANSI/IEEE C62.41and C62.45.
FeaturesEnergy Capability Options: This high energy capability option permits survivability in demanding environments and a lower clamping level for better protection.
High Surge Current Capability: The 76mm HESP protective ele-ments are designed and tested at 100kA per mode.
Parallel or Series Connection: Unfused protectors are suitablefor series connection in circuits rated up to 100 amps continuous,and T-connection (parallel) with no limitation on continuous loadcurrent.
The ability to connect the units in the series configuration offersoptimum protection. This connection keeps lead length inductivevoltage to a minimum and provides the lowest protective levelsfor each rating.
Dependable Protection: The unique zinc oxide "valve" elementinside each arrester gives you improved overvoltage protection.These tough elements are designed so that they can handlesurge after surge without trouble, breakdown, or repairs. YourTRANQUELL® arrester’s protective ability will remain unchangedthroughout its service life.
OEM High Energy Surge Protectors9L10K Series120-600 Volt Ratings
Common Mode Protection Option: In addition to normal mode protection (L-L and L-N), HESP offers common mode protection (L-G and N-G) for 3-phase wye and single-phase 1 or 2 poledevices. This optional protection is recommended for devicesremotely located from the system neutral to ground bond.
9L10K Series is direct replacement for superseded 9L10M Series.
Selection and RatingsNominal Voltage Max. Continuous 1 second Diagram Energy Rating UL-1449, Second Edition Suppressed Voltage
and Configuration Operating Voltage Temporary Overvoltage Figure (Joules Rating (SVR) with 6 leads Product List Price(Volts, rms) (Volts, rms) (Volts, rms) page 20-48 per Phase) L-N N-G2 L-G2,3 L-L Number1 GO-57
1Add $70.00 list for optional Common Mode Protection and change the product numbers as follows: for single-phase devices substitute 2 in the 8th position of the product number. For 3-phase WYE devices substitute 4 in the 8th position of the product number.
2N-G and L-G values for WYE product numbers are only applicable to those units with the optional common mode protection.3For service entry applications where the neutral and ground are bonded, the L-G rating is equivalent to the L-N rating.4Units indicated are not UL approved.
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-48
Capacitors, Arresters and Harmonic Filters Section 20
OEM High Energy Surge Protectors9L10K Series120 – 600 Volt Ratings
4-terminal device shownDimensions (in/mm)
Fig. 1 Single Phase 2 or 3 Wire
Series ConnectionMax. Continuous Current:
100A/Phase
“T” ConnectionMax. Continuous Current:
Unlimited
Fig. 2 Single Phase 3 or 4 Wire
Fig. 3 Three Phase Wye Ungrounded
Fig. 4 Three Phase Wye/4 or 5 Wire/GND Neutral
Fig. 5 Three Phase Delta/Ungrounded
Fig. 6 Three Delta/One Phase Grounded
Connection Diagrams
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-49
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20TRANQUELL® Motor Surge ProtectorMotor and Generator Surge Protection EquipmentThree-Phase, 60 Hz2400 through 24,000 Volt RatingsNEMA 12/3R Enclosure
Selection Table
Voltage Rating rms Volts (L-L)
Product No. Product No. Delta & Ungrounded
Neutral SystemsGrounded
Neutral SystemsList Price Each,
GO-412AArrester
Rating kV rmsArrester
MCOV kV rms
Capacitor Microfarads per Pole μF
Dimension "D" (side view) Weight lbs
2400 38F2401 — $8426.00 3 2.55 0.5 23" 300
4160 38F2402 — $8469.00 6.0 5.1 0.5 23" 300
— — 38F2403 $8426.00 3 2.55 0.5 23" 300
4800 38F2404 — $9457.00 6 5.1 0.5 23" 300
6900 38F2405 — $9929.00 9.0 7.65 0.5 23" 300
7200 38F2406 — $8646.00 9 7.65 0.5 23" 300
13200 38F2407 — $9669.00 18 15.3 0.25 23" 300
— — 38F2408 $9523.00 10 8.4 0.25 23" 300
13800 38F2409 — $9669.00 18 15.3 0.25 23" 300
— — 38F2410 $9531.00 12 10.2 0.25 23" 300
24000 38F2411 — $11553.00 27 22.0 0.125 36" 350
— — 38F2412 $11283.00 21 17.0 0.125 36" 350
Contact factory for other ratings.
DescriptionTRANQUELL® MOTOR SURGE PROTECTOR provides surge protec-tion for AC rotating machines including motors and generators.They are typically applied directly at the motor terminals and con-sist of GE TRANQUELL® Station Class arresters connected inparallel with GE Dielektrol® Protective Capacitor(s). The arrestersprotect the major insulation to ground by limiting the amplitudeof applied impulse waves or reflections within the machine wind-ings, while the protective capacitor(s) reduce the steepness ofwave fronts. Studies indicate that this dual protection approachresults in significant reduction of lightning stresses imposed onrotating machines and contribute to increased security againstfailures and downtime costs. Enclosure is suitable for indoor andoutdoor applications.
How to Select1. Determine the nominal system voltage and connection at the
equipment being protected (Line-to-Line voltage, delta or wye,grounded or ungrounded).
2. Select product number (column 2 or 3) based on the line to linevoltage (column 1).
Dimensions: (inches)
Front Side
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-50
Capacitors, Arresters and Harmonic Filters Section 20
Assures Service ContinuityThe GE TRANQUELL® secondary arrester is specifically designed to protect utility, agricultural, and industrial installations and equip-ment in the 120-650 volt range from overvoltages caused bylightning discharges. It is available for both single- and three-phase application.
Applications that provide ideal installations for this arrester are:—Exposed secondary circuits—Watt hour meters—Station auxiliary equipment and circuits—Motors and control circuits—Distribution transformer secondaries
Dependable ProtectionThe unique metal oxide element inside each TRANQUELL® arrestergives you improved overvoltage protection. These tough elementsare designed so that they can handle surge after surge withouttrouble, breakdown, or repairs. Your arrester’s protective abilitywill remain unchanged throughout its service life.
TRANQUELL® Secondary Surge Arresters and Protective Capacitors120-650 VacSeries 9L15F
Figure 1 TRANQUELL® Arrester
FusingTo minimize the possibility of violent rupture in the unlikely eventof electrical failure of the arrester, current limiting fuses are rec-ommended for all applications above 120 volts. A fuse must beinstalled in series with each pole of the arrester (i.e. each blackwire). See Fuse Selection table below. The GEH-4982C instructionbook shipped with each arrester also includes fusing guidelines.
Secondary Arresters – Indoor or Outdoor MountingUL and CSA Listed - For Knockout or Bracket Mounting
Circuit Max. PermissibleVoltage Line-to-Ground No. of Net Weight Product List Price
Rating rms Voltage rms Poles (lbs/Kg) Number1 GO-58
Non-PCB Secondary Protective Capacitors– Indoor or Outdoor Mounting
Circuit Max. PermissibleVoltage Line-to-Ground No. of Net Weight Product List Price
Rating rms Voltage rms Poles (lbs/Kg) Number1 GO-58
0-650 650 3 4.00/1.8 9L18BBB301 $152.00
1Quantity break pricing applies; consult factory or your GE sales representative.
Secondary Surge Arrester Protective CharacteristicsDischarge Voltage kV Crest Discharge Energy
(8 x 20 Microsecond Current Wave) Capabilities Handling1.5 kA 5.0 kA 10.0 kA 20.0 kA 8 x 20 microsecond Capability
2.2 2.6 2.9 3.5 20,000 amp 900 joulesper pole
Fuse Selection – For 9L15E Series (above 120V)Arrester Maximum Fuse Location Lightning Impulse2,3 Rating 4
A Long Branch Circuit more than 20m from
200A30 A; 600 V
Service Entrance U.L. Class T
with wires #14-10200,000 A Interrupt
B Major Feeders and Short Branch Circuits 3 kA
30 A; 600 V
less than 20m from 8x20 μsU.L. Class T
Service Entrance200,000 A Interrupt
C Outside and 10 kA30 A; 600 V
Service Entrance 4x10 μsU.L. Class T
200,000 A Interrupt
Figure 2 Protective Capacitor 5
2Maximum impulse expected as described in ANSI/IEEE C62.41 for systems withmedium exposure to surges. Arresters have been design tested to impulses ashigh as 20 kA, 8x20μs.
3Design tests for secondary arresters as required by ANSI/IEEE standards are limitedto a maximum of 10 kA, 4x10μs impulses.
4UL Class CC (Midget) 30 A fuses are also satisfactory for locations A and B.5Secondary capacitor is a 3-pole device that can be applied with 1- and 2-pole arresters
by connecting the corresponding black leads and tying off the unused leads.
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-51
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20TRANQUELL® Station ArrestersPolymer and Porcelain High-VoltageIndoor and Outdoor Service
Product DescriptionTRANQUELL® XE porcelain and XEP polymer station arresters provide both excellent protective characteristics and temporaryovervoltage capability. Gapless construction results in a designwhich is simple, reliable and economical while offering excellentfault current capability to meet the most demanding service con-ditions. The GE arrester is based on the field-proven metal oxidedisks known for maintaining stable characteristics. Stationarresters are designed and manufactured in accordance with thelatest revision of ANSI/IEEE C62.11. TRANQUELL® Polymer Station ArresterPorcelain and Polymer Arresters (Station Class)for both Indoor and Outdoor Mounting (2.7-612 kVrms)
Normally Used on System Voltage Class (L-L)Maximum1 High Impedance2 Product Number
Continuous Grounded, Product Number (Gray Porcelain)4 (Gray Silicone)4 Product Number (Gray Polymer)4
Arrester Voltage Capability Ungrounded (Delta) Solidly Grounded Metal Top Porcelain Top Metal Top 4-hole NEMA Pad Eyebolt Terminal Rating (L-N) kVrms or Temporarily Neutral System for Indoor or for Indoor or for Indoor or List Price for Indoor or Outdoor for Indoor or Outdoor List PricekVrms Porc Poly Ungrounded Circuits kVrms Outdoor Mounting Cubicle Mounting Outdoor Mounting GO-53/54 Upright Mounting Upright Mounting3 GO-53/54
108 84 115 138 9L11SXA108S - $4727.00 9L11XPA108S 9L11XPB108S $3199.00108 88 115 138 9L11ZTA108S - 9L11HMA108S $4727.00 - - --120 98 115 138/161 9L11ZTA120S - 9L11HMA120S $4973.00 9L11XPA120S 9L11XPB120S $3454.00132 106 138 161 9L11ZTA132S - 9L11HMA132S $5519.00 9L11XPA132S 9L11XPB132S $3784.00144 115 138/161 161 9L11ZTA144S - 9L11HMA144S $6071.00 9L11XPA144S 9L11XPB144S $3988.00168 131 161 - 9L11ZTA168S - 9L11HMA168S $7197.00 9L11XPA168S 9L11XPB168S $5729.00172 140 - 230 9L11ZTA172S - 9L11HMA172S $7734.00 9L11XPA172S 9L11XPB172S $5550.00180 144 - 230 9L11ZTA180S - 9L11HMA180S $8012.00 9L11XPA180S 9L11XPB180S $6025.00192 152 - 230 9L11ZTA192S - 9L11HMA192S $8364.00 9L11XPA192S 9L11XPB192S $6285.00228 180 230 - 9L11ZTA228S - $9154.00 9L11XPA228S 9L11XPB228S $6862.00240 194 230 - 9L11ZTA240S - $10179.00 - - --258 209 For Nominal 345 kV Systems 9L11ZTA258S - 9L11HMA258S $10903.00 - - --264 212 For Nominal 345 kV Systems 9L11ZTA264S - 9L11HMA264S $11195.00 - - --276 220 For Nominal 345 kV Systems 9L11ZTA276S - 9L11HMA276S $11836.00 - - --288 234 For Nominal 345 kV Systems 9L11ZTA288S - $13363.00 - - --294 237 For Nominal 345 kV Systems 9L11ZTA294S - $14225.00 - - --300 243 For Nominal 345 kV Systems 9L11ZTA300S - $14717.00 - - --312 245 For Nominal 345 kV Systems 9L11ZTA312S - 9L11HMA312S $15829.00 - - --300 243 For Nominal 400 kV Systems 9L11ZTA300S - $14717.00 - - --312 245 For Nominal 400 kV Systems 9L11ZTA312S - $15829.00 - - --336 264 For Nominal 400 kV Systems 9L11ZTA336S - $17505.00 - - --360 288 For Nominal 400 kV Systems 9L11ZTA360S - $19774.00 - - --396 318 For Nominal 400 kV Systems 9L11ZTA396S - 9L11HMA396S $28182.00 - - --420 335 For Nominal 400 kV Systems 9L11ZTA420S - 9L11HMA420S $30261.00 - - --396 318 For Nominal 500 kV Systems 9L16GNS396S - $44241.00 - - --420 335 For Nominal 500 kV Systems 9L16GNS420S - $46471.00 - - --444 353 For Nominal 500 kV Systems 9L16GNS444S - $48466.00 - - --588 470 For Nominal 765 kV Systems 9L16GNS588S - $79664.00 - - --612 485 For Nominal 765 kV Systems 9L16GNS612S - $84433.00 - - --
1TRANQUELL® Arresters are designed to be operated at voltages equal to or less than their continuous capability as stated in column 2.2Application of specified rating is permissible for ungrounded or resistance grounded systems where a single phase ground may be tolerated for
a substantial period of time not to exceed the arrester's overvoltage capability.3For underhung (or upside down) mounting, with eyebolt terminal on the bottom, change letter B of the product number to E.4Special Ratings available on request.
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-52
Capacitors, Arresters and Harmonic Filters Section 20
Porcelain, Metal Top Station Arrester Dimensions, Leakage Distances, Mounting Clearances and WeightsMounting Clearance1
Product "X" Overall Height Leakage Dist Phase to Phase Phase To Ground WeightNumber MCOV (kV) in mm in mm in mm in mm lb kg
TRANQUELL® Station ArrestersPorcelain High-VoltageIndoor and Outdoor Service
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-54
Capacitors, Arresters and Harmonic Filters Section 20TRANQUELL® Station ArrestersPorcelain High-VoltageIndoor and Outdoor Service
Porcelain Station Arrester – Protective CharacteristicsProduct Rated Voltage MCOV 0.5μsec 10kA Max Switching Surge Max 8/20 Maximum Discharge Voltage
1Based on 500A surge of 45μs time to crest through 88kV MCOV, 1kA surge of 45μs time to crest for 98kV≤MCOV≤194kV, and 2kA surge of 45μs time to crest for MCOVgreater than 194kV.
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-55
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20
9L11ZGBO##S Series Rated Voltage 3-27kV
9L11ZGAO##S Series Rated Voltage 3-48kV
9L11ZTA###S Series Rated Voltage 54-120kV
9L11ZTA###S Series Rated Voltage 132-168kV
9L11ZTA###S Series Rated Voltage 172-228kV
9L11ZTA###S Series Rated Voltage 240-312kV
TRANQUELL® Station ArrestersPorcelain High-VoltageIndoor and Outdoor Service
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-56
Capacitors, Arresters and Harmonic Filters Section 20
Polymer Station Arrester – Protective Characteristics 9L11XPAxxxS and 9L11XPBxxxS
500A Switching Insulation Withstand
Rated 0.5μsec, Surge Min Wet DryVoltage MCOV 10kA Max. Max IR 8/20μs Maximum Discharge Voltage - kVcrest Creep Strike 1.2x50μs 10 sec 1 min(kVrms) (kVrms) IR (kVcrest) (kVcrest) 1.5kA 3kA 5kA 10kA 20kA 40kA in mm in mm (kV crest) (kVrms) (kVrms)
TRANQUELL® Station ArrestersPolymer High-VoltageIndoor and Outdoor Service
Polymer Station Arrester – Weights and DimensionsProduct Number Mounting Clearance1
4-hole NEMA Single Eyebolt Rated Voltage MCOV Overall Height2 Center Line to Center Line WeightPad Line Terminal Line Terminal (kVrms) (kVrms) in mm Center Line (in.) to Ground (in.) Lbs. kg
1Center line to center line is equivalent to phase-to-phase; center line to ground is equivalent to phase-to-ground. These are recommended minimum clearances only and as such are not intended to take precedence over existing construction codes or specifications.
2Overall height of 9L11XPB0**S arresters is determined by subtracting 0.63 in or 15.9 mm from listed overall height.
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-57
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20TRANQUELL® Station Arresters
Silicone Station Arresters Protective CharacteristicsMaximum Switching
Maximum 0.5μs Surge Protective LevelRated Discharge At Classifying
Product Voltage MCOV Voltage1 Current Levels kV2 Maximum Discharge Voltage Using an 8/20 Current Wave-kVNumber kVrms kVrms kV kV 1.5kA 3kA 5kA 10kA 20kA 40kA
1 Maximum discharge voltage for an impulse current wave which produces a voltage wave cresting in 0.5 μs. Discharge Currents are 10kA for 42-353 kV MCOV. This can beused for coordination where front-of-wave sparkover formerly was used.
2 Discharge voltages are based on a 500A surge of 45 μs time to crest through 88kV MCOV and a 1000A surge of 45 μs to crest through 180 kV MCOV and 2000A through245 kV MCOV.
3 Minimum clearances are based on arrester protective levels and should be increased when necessary to meet local requirements for spacing of energized equipment.
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-58
Capacitors, Arresters and Harmonic Filters Section 20TRANQUELL® Station ArrestersPolymer High-VoltageIndoor and Outdoor Service
Polymer Arresters (Station Class)for both Indoor and Outdoor Mounting (2.7-72 kVrms)9L11XPMxxxS , 9L11XPNxxxS, and 9L11XPTxxxSPressure Relief Capability: 40 kA rms Energy Handling Capability: 6.0kJ/kV mCOVCantilever Strength: 4,000 inch-pounds, rated ultimate cantilever moment
Product Number (Gray Polymer)
Arrester Maximum Continuous 4-hole NEMA Pad for Eyebolt Terminal forRating Voltage Capability Indoor or Outdoor Indoor or Outdoor List Price Indoor or cubicle List PricekVrms (L-N) kVrms Upright Mounting Upright Mounting GO-53/54 Terminal Mounting GO-53/54
For weight, dimensional and other technical information, please visit the Arresters section of www.ge.com/energy
19L11XPNxxxS & 9L11XPMxxxS, the electrical characteristics in this table are applicable to these catalog numbers.Outline drawings can be downloaded from the GE Arrester, E-Catalog on the web.
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-59
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20
Product DescriptionTRANQUELL® XEP polymer intermediate arresters provide bothexcellent protective characteristics and temporary overvoltagecapability. Gapless construction results in a design which issimple, reliable, and economical while offering excellent faultcurrent capability to meet the most demanding service conditions.The GE TRANQUELL® arrester is based on the field-proven metaloxide disks known for maintaining stable characteristics.TRANQUELL® intermediate arresters are designed andmanufactured in accordance with the latest revision of ANSI/IEEEC62.11 and IEC 99-4.
Polymer Arresters (Intermediate-Class)for both Indoor and Outdoor Mounting (3-144 kVrms)
Normally Used on System Voltage Class (L-L) Product Number (Gray Polymer)
Arrester Maximum Continuous High Impedance Grounded, Solidly Grounded 4-hole NEMA Pad Eyebolt TerminalRating Operating Voltage Capability1 Ungrounded (Delta), or Neutral Systems for Indoor or Outdoor for Indoor or Outdoor List PricekVrms (L-N) kVrms temporarily ungrounded circuits kVrms Upright Mounting Upright Mounting2 GO-50
1TRANQUELL® Arresters are designed to be operated at voltages equal to or less than their continuous capability as stated in column 2.2For underhung or upside down mounting with eyebolt terminal on the bottom change the letter B of the catalog number to E.3Application of specified rating is permissible for ungrounded or resistance grounded systems where a single phase ground may be
tolerated for a substantial period of time not to exceed the TRANQUELL® arresters overvoltage capability.
TRANQUELL® Intermediate ArrestersPolymer High VoltageIndoor and Outdoor Service
9L12PPA Polymer
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-60
Capacitors, Arresters and Harmonic Filters Section 20
Polymer Intermediate Arrester Weights and DimensionsProduct Number Mounting Clearance1
4-hole NEMA Pad Single Eyebolt Rated Voltage MCOV "X" Height Phase to Phase Phase to Ground Weight
Line Terminal Line Terminal (kVrms) (kVrms) inches mm (in) (mm) (in) (mm) lb kg
1These clearances are recommended minimum clearances only and as such are not intended to take precedence over existing construction codes or specifications.Placement of the units should be such that they do not physically touch each other.
Polymer Intermediate Arrester Protective Characteristics 9L12PPAxxxS and 9L12PPBxxxSInsulation Withstand
Rated 0.5μsec, 500A Switching Min Wet DryVoltage MCOV 10kA Max. IR Surge Max IR 8/20μs Maximum Discharge Voltage - kVcrest Creep Strike 1.2x50μs 10 sec 1 min (kVrms) (kVrms) (kVcrest) (kVcrest) 1.5kA 3kA 5kA 10kA 20kA 40kA in mm in mm (kV crest) (kVrms) (kVrms)
TRANQUELL® Intermediate ArrestersPolymer High VoltageIndoor and Outdoor Service
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-61
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20
Polymer Arresters (Intermediate Class)for both Indoor and Outdoor Mounting (2.7-72 kVrms)9L12PPMxxxS and 9L12PPTxxxSPressure Relief Capability: 16.1 kA rms Energy Handling Capability: 3.6kJ/kV mCOVCantilever Strength: 3,000 inch-pounds, rated ultimate cantilever moment
Product Number (Gray Polymer)Arrester Rating Maximum Continuous Voltage Eyebolt Terminal for Indoor or List Price Indoor or cubicle List Price
For weight, dimensional and other technical information, please visit the Arresters section of www.ge.com/energy
19L12PPMxxxs, the electrical characteristics in this table are applicable to these product numbers. Outline drawings can be downloaded from http://www.ge-energy.com/ecatalog/html/index
TRANQUELL® Intermediate ArrestersPolymer High VoltageIndoor and Outdoor Service
Dimensions and Mounting Minimum Mounting
Product Ratings "X" Leakage Spacing on Center (In.) NetNumber Voltage kV rms MCOV Dimension (In.) Distance (In.) Ph-Ph Ph-Grd Weight (Lbs.)
*9L12PPMxxxs, the electrical characteristics in this table are applicable to these catalog numbers.Outline drawings can be downloaded from http://www.ge-energy.com/ecatalog/html/index
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-62
Capacitors, Arresters and Harmonic Filters Section 20TRANQUELL® Intermediate ArrestersPolymer High VoltageIndoor and Outdoor Service
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-63
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20TRANQUELL® Station and Intermediate ArrestersOutline Drawings
Fig. 1 – Polymer Station Arrester – 9L11XPAxxxS3kV through 96kV
Fig. 3 – Polymer Station Arrester – 9L11XPBxxxS3kV through 7kV
Fig. 5 – Polymer Intermediate Arrester – 9L12PPAxxxS90kV through 144kV
Fig. 2 – Polymer Station Arrester – 9L11XPAxxxS108kV through 228kV
Fig. 4 – Polymer Intermediate Arrester – 9L12PPAxxxS3kV through 72kV
Fig. 6 – Polymer Intermediate Arrester – 9L12PPBxxxS3kV through 72kV
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-64
Capacitors, Arresters and Harmonic Filters Section 20
Discharge Counters, Insulating Bases and BracketsWeight List Price
Description lbs kgs Product Number GO-76A
Discharge Counter 6.6 3.0 9L26FBE005E $1155.00Discharge Counter with leakage current ammeter
7.7 3.5 9L26FBE012E $1449.00
Description -3 included, 1 for each foot of the arrester
Insulating Base for Polymer Intermediate arresters and
5 2.27 9L11LGW804S $180.00Porcelain Station arresters 3-48kV rated voltageInsulating Base for Polymer Station arrester
5 2.27 9L11LGW805S $200.00
Insulating Base for Porcelain Station arrester 47 21.4 9L11LGW807E $483.00(54-360 kV rated voltage)Insulating Base for Porcelain EHV arresters (>360kV)
47 21.4 9L16AAW110S $525.00
Distribution, Intermediate and Station Arrester – ApplicationArrester Rated Housing Arrester Max. Current for Energy
Voltage (kV rms) Type Type Energy Rating (Amps) (kJ/kV of MCOV)
3-36 kV PolymerHeavy Duty Distribution
450 1.8
3-36 kV Polymer Riser Pole 650 2.23.0 - 144 kV Polymer Intermediate 650 63.0 - 144 kV Polymer Station 1000 93.0 - 48 kV Porcelain Station 1000 954 - 360 kV Porcelain Station 1500 13
396 - 612 kV Porcelain Station 2400 17
Station and Intermediate Class ArrestersAccessoriesTerminals and Mounting Brackets
The energy capability for GE Surge Arresters is defined basedupon Switching Surges, 2 milliseconds, transmission line discharges,with multiple discharges over a one-minute period and with cur-rent amplitudes that are no greater than listed below. Based uponthis definition GE arresters have an energy capability as follows:
To provide assurance that all disks used in GE arresters have thiscapability, we perform a Low Current Long Duration Strength Teston 100% of our disks applying the above energies. We apply twogroups of three shots per group. Each shot is a square wave,which is 2 milliseconds wide. We allow 15 to 20 seconds betweenshots, three are applied within 60 seconds, and we allow the diskto cool between the two groups of three shots. This is followed bythree shots of a half sine wave, which is 14 milliseconds wide with15 to 20 seconds between shots. These tests weed out any weakdisks and provide assurance that the disks used in the final prod-uct are indeed capable of withstanding the energy claimed.
GE arresters exceed the requirements of Seismic Zone 2 and haveCantilever Strengths and fault current capabilities as follows:
Details of Discharge Counter, Models 9L26FBE005E and 9L26FBE012E (Dimensions in mm)
Distribution, Intermediate and Station Arrester – ApplicationArrester Rated Ultimate Maximum Working Fault Current
Rated Voltage Housing Arrester Cantilever Strength Cantilever Strength Capability(kV rms) Type Type in-lbs N-m in-lbs N-m (kA sym)
3 - 36 kV Polymer Normal Duty Distribution 1,500 169 600 68 103 - 36 kV Polymer Heavy Duty Distribution 3,000 339 1,200 136 203 - 36 kV Polymer Riser Pole 4,000 452 1,600 181 20
GE arresters are manufactured in an ISO 9002 certified facility (File #A3803, issued January 19, 1995).
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-65
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20Distribution and Riser Pole Arresters9L20 Polymer Distribution9L27 Polymer Riser Pole0-12,000 ft. Altitude
Product DescriptionThe GE TRANQUELL® distribution and riser pole polymer line of surge arrester products provide excellent protective characteristics,temporary overvoltage capability, and switching surge energywithstand to power systems of voltages less than 46 kV rms. GE polymer arresters are ideally suited for application in bothindoor and outdoor situations. They are designed and manufacturedin accordance with the latest revision of ANSI/IEEE C62.11 and IEC 99-4.
TRANQUELL® distribution arrester, rated 10 kV, with disconnector)
Application Guide – Nominal System Suggested Arrester Rating
4 Wire 3 Wire Delta or WYE1
Line-to-Line Multi-Grounded Low Impedance High ImpedanceVoltage Neutral System Ground or Ungrounded
3-36 kV rms Polymer Heavy Duty Distribution Arresters 9L20Note: kV rating fills positions 9 and 10 (**) of product numberProduct Insulating Bird X-Arm Xformer 18" Line Ground List Price GO-55Number Bracket Disconnect Cap Bracket Bracket Lead Strap 3kV 6kV 9kV 10kV 12kV 15kV 18kV 21kV 24kV 27kV 30kV 36kV
9L20AXX0**AHS X X X $109.00 $111.00 $125.00 $129.00 $144.00 $167.00 $179.00 $223.00 $238.00 $260.00 $288.00 $315.009L20AXX4**AHS X X X X $111.00 $113.00 $127.00 $132.00 $146.00 $169.00 $181.00 $225.00 $240.00 $263.00 $290.00 $317.009L20AXA4**AHS X X X X X $113.00 $115.00 $129.00 $134.00 $148.00 $171.00 $184.00 $227.00 $242.00 $265.00 $292.00 $319.009L20AXA0**AHS X X X X $111.00 $113.00 $127.00 $132.00 $146.00 $169.00 $181.00 $225.00 $240.00 $263.00 $290.00 $317.009L20AXX0**XHS X X $98.00 $100.00 $115.00 $119.00 $134.00 $156.00 $169.00 $213.00 $227.00 $250.00 $277.00 $304.009L20AXX4**XHS X X X $100.00 $100.00 $117.00 $121.00 $136.00 $159.00 $171.00 $215.00 $229.00 $252.00 $279.00 $306.009L20AXA4**XHS X X X X $102.00 $104.00 $119.00 $123.00 $138.00 $161.00 $173.00 $217.00 $231.00 $254.00 $281.00 $308.009L20AXA0**XHS X X X $100.00 $102.00 $117.00 $121.00 $136.00 $159.00 $171.00 $215.00 $229.00 $252.00 $279.00 $306.009L20AXX0**BHS X X X $109.00 $111.00 $125.00 $129.00 $144.00 $167.00 $179.00 $217.00 $231.00 $254.00 $281.00 $310.009L20AXX4**BHS X X X X $111.00 $113.00 $127.00 $132.00 $146.00 $169.00 $171.00 $175.00 $219.00 $233.00 $256.00 $283.009L20AHA4**BHS X X X X X X $109.00 $111.00 $125.00 $129.009L20AHX4**BHS X X X X X $107.00 $109.00 $123.00 $127.009L20AHX0**BHS X X X X $104.00 $107.00 $121.00 $125.009L20AFA4**BHS X X X X X X $144.00 $167.00 $179.00 $223.00 $238.00 $260.00 $288.00 $315.009L20AFX4**BHS X X X X X $142.00 $165.00 $177.00 $221.00 $236.00 $258.00 $285.00 $312.009L20AFX0**BHS X X X X $140.00 $163.00 $175.00 $219.00 $233.00 $256.00 $283.00 $310.009L20BXX0**XHS X $86.00 $88.00 $102.00 $107.00 $121.00 $144.00 $156.00 $200.00 $215.00 $238.00 $265.00 $292.009L20FXX0**XHS $73.00 $75.00 $90.00 $94.00 $109.00 $132.00 $144.00 $188.00 $202.00 $225.00 $252.00 $279.00
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-66
Capacitors, Arresters and Harmonic Filters Section 20
Heavy Duty Distribution Arresters 9L20 – Protective CharacteristicsRating 0.5 μsec 10kA Switching
Voltage MCOV Max. IrR Surge 8/20 Maximum Discharge Voltage (kV) Crest
Distribution and Riser Pole Arresters9L20 Polymer Distribution9L27 Polymer Riser Pole0-12,000 ft. Altitude
Heavy Duty Distribution Arresters 9L20 – Insulation and Physical CharacteristicsMin Power Mounting
Rating Min 1.2 x 50μs Frequency (kV rms) Clearance "x" Center Line Center Line WeightsVoltage MCOV Creep Strike Withstand Dry Wet Overall Height to Center Line to Ground (unit only)kV rms kV rms in mm in mm (kV Crest) (1 sec) (10 sec) in mm in mm in mm lbs kgs
9L27HXX**XHS X X X $104.00 $111.00 $117.00 $123.00 $148.00 $173.00 $184.00 $227.00 $248.00 $248.00 $281.00 $354.00
9L27HXX**AHS X X X X $113.00 $119.00 $125.00 $132.00 $156.00 $181.00 $192.00 $236.00 $256.00 $256.00 $290.00 $362.00
www.ge.com/energy BuyLog® Catalog
Publications and Reference: See Section 22 for a complete list of additional product-related publications
20-67
Capacitors, Arresters and Harmonic Filters
Rev. 1/08Prices and data subject to change without notice
Section 20
Riser Pole Arresters 9L27 – Insulation and Physical CharacteristicsMin Power Mounting
Rating Min 1.2 x 50μs Frequency (kV rms) Clearance "x" Center Line Center Line WeightsVoltage MCOV Creep Strike Withstand Dry Wet Overall Height to Center Line to Ground (unit only)kV rms kV rms in mm in mm (kV Crest) (1 sec) (10 sec) in mm in mm in mm lbs kgs
For more product information, go to www.ge.com/energy, click on “Products and Services” and then “Products.”For up-to-date outline drawings, go to http://www.ge-energy.com/ecatalog/html/index
www.ge.com/energy Rev. 1/08Prices and data subject to change without notice
BuyLog® Catalog20-68
Capacitors, Arresters and Harmonic Filters Section 20